IMPROVING ENERGY PERFORMANCE OF ARMY DINING FACILITIES

Size: px
Start display at page:

Download "IMPROVING ENERGY PERFORMANCE OF ARMY DINING FACILITIES"

Transcription

1 IMPROVING ENERGY PERFORMANCE OF ARMY DINING FACILITIES Michael Deru, Ph.D. National Renewable Energy Lab Alexander Zhivov, Ph.D and Dale Herron Engineer Research and Development Center Donald Fisher Fisher Nickel, Inc Vernon Smith Architectural Energy Corporation

2 Table of Contents Introduction...3 Approach...4 Existing Army Dining Facilities, Their Systems, Equipment and Issues...4 Army Dining Facilities Description...5 Locations...6 Energy Modeling...6 Air Tightness and Infiltration...8 Envelope...9 Lighting...9 HVAC...10 Ventilation and Outside Air...10 Results...11 Energy Conservation Measures Total Energy Savings with Recommended Technology Sets...19 Summary and Discussion...21 Acknowledgement...21 References List of Figures and Tables Figures Page 1 Sketch of a Proposed Army Dining Facility Proposed DFAC floor plan from the Army Thermal zoning for the DFAC energy model Rendering of the energy simulation model for the DFAC Daily process load electricity consumption profiles Daily process load gas consumption profiles Daily total process load consumption profiles of electricity and gas Energy use by end use for the baseline building Energy use by end use for regulated loads in the baseline building Annual energy savings for each ECM Various canopy hoods for cooking equipment (source, ASHRAE Standard 154) Example best-design practices within exhaust system design and specifications

3 Tables 1 Building Zones and Internal Loads (IP units) Building Zones and Internal Loads (SI units) Climate Zones and Cities used for Simulations Building Model Parameters Process Loads Baseline Building Model Outside Air Requirements Baseline Exhaust Hood Air Flows Energy Budgets by Climate Zone Energy Conservation Measures Envelope Conservation Measures Building Lighting Power Efficient Building Model Outside Air Requirements Energy Efficient Exhaust Hood Air Flows HVAC systems Annual Energy Savings for Individual ECMs (kbtu/ft 2 ) Annual Energy Savings for Individual ECMs 1000Btu/ft 2 (MJ/m 2 ) Final Energy Efficient Design Solutions without Process Loads Final Energy Efficient Design Solutions with Process Loads Summary of ECMs in Final Models (grey shading indicates not recommended or investigate on a case by case basis) Page Introduction Section 109 of the Energy Policy Act of 2005 (EPAct 2005) states that, for new federal facilities, the buildings be designed to achieve energy consumption levels that are at least 30 percent below the levels established in the version of the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) Standard or the International Energy Conservation Code, as appropriate (U.S. Congress 2005). The energy efficient designs must be life cycle cost effective; however, the term cost effective is not defined in the law; it is left up to each federal agency to define. The U.S. Department of Energy (DOE) issued additional guidance in the Federal Register (NARA 2006), which states that savings calculations should not include the plug loads and implies that the savings shall be determined through energy cost savings. The U.S. Army decided it would use site energy for the HVAC, lighting, and hot water loads to determine the energy savings. 3

4 The U.S. Army constructs buildings across the country and the Office of the Assistant Chief of Staff of the Installations Management and the U.S. Army Corps of Engineers (HQUSACE) worked to streamline the process of meeting the energy savings requirements. The U.S. Army Corps of Engineers (USACE) worked in collaboration with the National Renewable Energy Laboratory (NREL), and the ASHRAE Military Technology Group (MTG) to develop baseline and target energy budgets and design guides with a prescriptive path for achieving energy savings of 30% or more over the baseline. The project covers eight building types over all U.S. climate zones: basic training barracks, unaccompanied enlisted personal housing, battalion headquarters, tactical equipment maintenance facilities, dining facilities (DFAC), child development centers, Army reserve centers, and company operations. This paper focuses on DFAC; however, the process for developing all the design guides is similar. The concept for these design guides was adapted from the Advanced Energy Design Guides (AEDGs) from ASHRAE (2008). Each AEDG was developed for a specific building type and provides recommendation tables for each of the eight major climate zones and a how-to section on implementing the recommendations. The AEDGs do not provide baseline and target energy budgets, which are used by the Army in its requests for proposals. Approach A representative model of the DFAC building was developed based on the information provided by the USACE Norfolk District the DFAC Center of Standardization. Baseline and target energy budgets were developed and energy savings using different sets of technologies were analyzed. Energy conservation technology candidates were selected based on previous energy design guide work (FSTC 2004a) and input from commercial kitchen consultants, who have experience with military kitchens. All energy simulations for the DFAC were carried out with EnergyPlus version 2.1 (DOE 2008). NREL is part of the EnergyPlus development team and has developed additional programs that work with EnergyPlus. These programs work together to create input files, manage the numerous simulations, provide optimization, and post-process the results. The optimization engine, called Opt-E-Plus, is used to help optimize building designs based on energy performance, energy cost performance, or life cycle cost performance. A baseline building energy model was created from the representative DFAC model meeting the minimum requirements of ASHRAE Standard following Appendix G (ASHRAE 2004a). We followed Appendix G with two exceptions, which were approved by DOE. For this project analysis we used site energy based on the Army decision, and developed baseline and target energy budgets without plug or process loads as our metric for savings following EPAct 2005 guidance from DOE. Finally, Standard does not contain requirements to building air leakage and infiltration levels. For the DFAC, we defined a baseline air leakage rate and an energy efficient leakage rate and included this factor in our energy efficiency analysis. Existing Army Dining Facilities, Their Systems, Equipment and Issues Existing Army dining facilities were not designed with energy and water efficiency as a primary objective. While minimizing construction costs have always been a goal within facility design, specifying lower-first-cost equipment that is inherently energy inefficient has been a reality with the design of Army dining facilities. Although the focus has changed within the context of the 2005 Energy Policy Act, it is not possible to economically transform existing facilities into Energy Star models of institutional food service. It is still practical, however, to implement such low-cost energy conservation measures as lowflow prerinse spray valves in the dishroom, or high-efficiency motors for evaporator fans in walk-in coolers as energy efficiency transformation is approached on a step-by-step basis. Since dining facilities are among the buildings on Army installations that use the most energy, comprehensive audits 4

5 should be initiated in existing dining facilities to address the many available no-cost, low-cost, and investment grade retrofits of ventilation, lighting, and automation systems, and equipment replacement opportunities. It is imperative that energy efficient options (e.g., Energy Star-qualified for applicable equipment categories including fryers, steamers, holding cabinets, ice machines, reach-in refrigerators and freezers) be considered when existing equipment is changed out (EPA 2008). Where Energy Star categories do not exist, FEMP-recommended or California-rebate-qualified equipment should be considered (FEMP 2008, FSTC 2008b). Army Dining Facilities Description The Army has developed standard designs for their dining facilities ranging in size from 251 to 500, 501 to 800, 801 to 1300, and 2600 meals based on the number of meals served in a single meal time. Most of the building elements scale with the size of the building. However, the kitchen is nearly the same size across all models to fit a standard set of food preparation equipment. The basic design is a single story building with spaces for food preparation, serving, dining, dishwashing, take-out food area, employee break area, storage, and utilities. The design must facilitate feeding the maximum number of meals in an hour and a half. Much of the short-order cooking is accomplished in the serving area on broilers or griddles, range tops, and in ovens. Several ventilation hoods are required to service the cooking equipment. In addition to the cooking equipment, there is a walk-in cooler and a walk-in freezer and several reach-in refrigerators and other ancillary equipment typically found in commercial foodservice. Figure 1 shows a sketch of a proposed dining facility. A dining facility serving between 801 and 1300 meals was selected for our study this is a medium sized building and the one most often constructed. The proposed floor plan from the Army shown in Figure 2 has an area of 25,609 ft 2 (2,379 m 2 ). The building is occupied 7 days a week from 3 a.m. to 8 p.m. Tables 16-1 and 16-2 list the zones and thermal loading. Table 1. Building Zones and Internal Loads (IP units). Zone Area (ft 2 ) Volume (ft 3 ) People Lights (W/ft 2 ) Electric Equipment (W/ft 2 ) Gas Equipment (W) Dining 7,981 95, Storage/Receiving 2,622 31, Dish wash 1,120 13, Kitchen 2,763 33, ,000 Servery 4,277 51, ,000 Entry/Circulation 3,290 39, Carryout 1,044 12, ,000 Office 1,444 17, Utility 1,053 12, Total 25, , ,486 W 246,824 W 93,000 W Table 2. Building Zones and Internal Loads (SI units). Zone Area (ft 2 ) Volume (ft 3 ) People Lights (W/ft 2 ) Electric Equipment (W/ft 2 ) Gas Equipment (W) Dining 741 2, Storage/Receiving Dishwashing Kitchen ,000 Servery 397 1, ,000 Entry/Circulation 306 1, Carryout ,000 5

6 Zone Area (ft 2 ) Volume (ft 3 ) People Lights (W/ft 2 ) Office Utility Electric Equipment (W/ft 2 ) Gas Equipment (W) Total 2,378 8, , ,824 93,000 W Locations Fifteen locations were selected to represent 15 climate zones in the United States based on TMY2 weather files. The locations were selected as representative cities for the climate zones by the Pacific Northwest National Laboratory (Briggs et al. 2003). We selected Colorado Springs for climate zone 5B instead of Boise, ID to more closely align with the installations at Fort Carson, CO. Table 3 lists the 15 climate zones and the cities used to represent the climate zones. Table 3. Climate Zones and Cities used for Simulations. Climate Zone City HDD Base 65ºF (18ºC) CDD Base 50ºF (10ºC) 1A Miami, FL 200 (111) 9474 (5263) 2A Houston, TX 1599 (888) 6876 (3820) 2B Phoenix, AZ 1350 (750) 8425 (4681) 3A Memphis, TN 3082 (1712) 5467 (3037) 3B El Paso, TX 2708 (1504) 5488 (3049) 3C San Francisco, CA 3016 (1676) 2883 (1602) 4A Baltimore, MD 4707 (2615) 3709 (2061) 4B Albuquerque, NM 4425 (2458) 3908 (2171) 4C Seattle, WA 4908 (2727) 1823 (1013) 5A Chicago, IL 6536 (3631) 2941 (1634) 5B Colorado Springs, CO 6415 (3564) 2312 (1284) 6A Burlington, VT 7771 (4317) 2228 (1238) 6B Helena, MT 7699 (4277) 1841 (1023) 7A Duluth, MN 9818 (5454) 1536 (853) 8A Fairbanks, AK (7744) 1040 (578) Energy Modeling The energy simulations were completed using EnergyPlus version 2.1 (DOE 2008). All simulations were completed with the NREL analysis platform based around Opt-E-Plus that manages EnergyPlus simulations. This section describes the modeling assumptions used in the baseline and energy efficient models. Figure 3 shows the thermal model of the DFAC used for this study, a one story, 25,593 ft 2 (2,378 m 2 ) building. Figure 4 shows the rendered view of the energy simulation model. The skylights in the servery and dining zones are used for daylighting in the energy efficient models. The skylights must be included in the baseline building as well according to Standard Appendix G modeling rules. The skylights and daylighting did not provide energy savings in Fairbanks and are not included in the energy models for this location. Table 4 lists the building model parameters. There were some issues with modeling this building in EnergyPlus, which introduced some errors and required some changes in the model inputs. There are several hours of unmet heating loads from a bug in EnergyPlus control algorithms that lead to temperatures dropping about 1ºF (0.6ºC) below the 6

7 setpoint. This problem occurs in zones with high outside air and in cold climates. The result is a slightly lower heating energy than what it should be, which was assumed to be small and was ignored in this study. The bug is known to the EnergyPlus development team and may be fixed in a future release of EnergyPlus. Another issue was undersizing of cooling coils in hot climates. This was corrected by increasing the zone sizing factor for the kitchens in Houston, Phoenix, and El Paso. One final issue concerns the outside air for zones with exhaust fans and transfer air, which is discussed further in the section on ventilation. Table 4. Building Model Parameters. Building Component Baseline Building Model Efficient Building Model Area 25,593 ft 2 (2,378 m 2 ) Same as baseline Floors 1 Same as baseline Aspect ratio 4.4 Same as baseline Fenestration type Standard See Tables and Wall construction Steel frame Steel frame Wall insulation Standard steel frame See Tables and Roof construction Flat built up roof Flat built up roof Roof insulation Standard equal to the insulation entirely See Tables and above deck Roof albedo 0.3 Same as baseline Infiltration 0.4 cfm/ft 0.3 in w.g. (2.0 L/s m 75 Pa) 0.25 cfm/ft 2 at 0.3 in w.g. (1.25 L/s/m 2 at 75 Pa) Temp setpoints 70ºF (21ºC) heating; 75ºF (24ºC) cooling set back/up Same as baseline to 55ºF (13ºC) heating; 91ºF (33ºC) cooling Kitchen: 80ºF (27ºC) cooling - set up to 91ºF (33ºC) HVAC PSZ with DX-AC (3.05 COP) and gas furnace (0.8 Et); See Table 15 DHW Natural gas boiler (0.8 Et) Natural gas boiler (0.94 Et) Plug and Process Loads Several assumptions have to be made to include the plug and process loads in the energy models. The process loads for a commercial kitchen are large and have a significant impact on the HVAC and overall building energy use. The 2007 DOE Buildings Energy Data Book estimates that the cooking and refrigeration loads in a typical Food Service building is approximately 45% of the total energy use (DOE 2007). The process loads associated with food preparation, serving, and cleaning for this model were estimated by foodservice industry consultants. Kitchen appliances for both the baseline building and the energy efficient building were all selected to be either ENERGY STAR-qualified, FEMPrecommended, or qualified for California utilities Rebate Program (EPA 2008, FEMP 2008, FSTC 2008b). USACE Norfolk District provided with the layout of the kitchen, the equipment specification sheets, a 21-day menu, and the number of meals served per day. The cooking energy for each piece of equipment was estimated for each space based on the menus and aggregated schedules were created for each space including warm-up and idle times. Figures 16-5, 16-6, and 16-7 show (and Table 5 lists) the total electricity and gas process loads by zone. Service hot water (SHW) use in the food preparation and dish washing areas is considered a process load and is removed from the energy savings calculations. It was assumed that 95% of the building SHW use is for food preparation and washing (see Table 5). The remaining 5% is for hand washing in the restrooms and hand washing stations in the entry and is included in the energy savings calculations. 7

8 Air Tightness and Infiltration Infiltration is a difficult parameter to obtain good data on. Every building has different air leakage and the infiltration varies with operation of the building and ambient conditions. There was a proposed addendum to Standard , which includes an air tightness standard. This document proposes that one approach to meeting the standard would be to perform a pressurization test to show that the building leakage does not exceed 0.4 cfm/ft 2 at 0.3 in w.g. (2 L/s/m 2 at 75 Pa). This air tightness level provides a number that can be used for the energy simulations and was assumed to be the leakage rate for the baseline building models in this analysis. 8

9 Zone Peak Elec. (kw) Table 5. Process Loads. Electric (kwh/day) Dining Dishwashing Peak Gas 1000Btu (MJ) Gas 1000Btu/day (MJ/day) Kitchen (193) 1,989 (2,099) Servery (50) 394 (416) Bake shop (60) 620 (654) Carryout (50) 422 (445) Service Hot Water gal/day (L/day) Total 2,075 3,425 (3,614) 5,740 (21,728) Based on input from building air tightness experts, the U.S. Army has proposed in their new construction regulations that the leakage rate must not exceed 0.25 cfm/ft 2 at 0.3 in w.g. (1.25 L/s/m 2 at 75 Pa), which was assumed for the energy efficient building models in this study. Several assumptions still have to be made to go from these leakage rates to the simple infiltration model in the building energy simulation. The infiltration at these leakage rates and pressures were calculated based on the above grade envelope area (exterior walls and roof) of the building then converted to a pressure of 0.02 in w.g. (5 Pa) assuming a flow coefficient of It was assumed that the average pressure difference across the building envelope is 0.02 in w.g. (5 Pa). Tables 16-6 and lists the infiltration values. Infiltration is often assumed to go to zero when buildings are pressurized. This assumption is usually made because there is a lack of evidence to know what really happens and lack of knowledge of how to model it in an energy simulation. We have assumed that the uncontrolled infiltration is reduced to 10% of the value calculated at 5 Pa when the building ventilation system is running. When the ventilation system is off (no outside air), the infiltration is modeled at the full leakage rate calculated at 5 Pa. Infiltration is modeled at constant air changes per hour. Wind pressure and temperature differentials across the building envelope drive the infiltration and these driving forces vary throughout the year; however, we are not modeling these variations in the simulation models. We are assuming that a constant air changes per hour (ACH) models the average effects over the year and in different locations. This is a gross assumption, but one that is necessary without moving to more complicated flow network simulations. Envelope The baseline building envelope features are modeled as steel frame wall construction, roof insulation entirely above deck, and door and fenestration types from ASHRAE Standard The door, window, and skylight sizes and distribution are exactly the same in all building models. Skylights are included at 4% of the roof area in the servery and dining zones for daylighting. Skylights are not included near the exterior walls in the dining zone because adequate daylight can be harvested from the exterior windows. Skylights are not included in the models for Fairbanks because the latitude and cold climate reduce their effectiveness in saving energy. Lighting Tables and 16-2 list the interior lighting power densities (LPD) for the baseline and the energy efficient model for each space. 9

10 HVAC The baseline HVAC system from Standard Appendix G is the system 3 package single zone air conditioning (PTAC) system for each zone. The systems were auto-sized by EnergyPlus for each simulation with a 1.2 sizing factor. The kitchen had over 300 hours of the cooling temperature setpoint not met in Houston, Phoenix, and El Paso. A sizing factor of 2.0 was used for the kitchen in these locations to ensure that the number of hours that the cooling setpoints were met did not exceed 300 as required by Standard Appendix G. Ventilation and Outside Air The outside air requirements for each zone are determined by meeting the highest of the Standard (ASHRAE 2004c) outside air requirements and the make-up air requirements for the food preparation exhaust hoods. Table 6 lists the building infiltration, ventilation, and outside air requirements for the baseline building. The maximum outside air for the servery in the last column is slightly greater than the maximum exhaust hood flow minus the transfer air because the hourly operation of the individual hood flows and the transfer air cause the peak air flows to occur at different times. Some of the make-up air for the servery exhaust hoods comes from the dining and entry/circulation areas. The transfer air from the entry/circulation is very small and was not included in the energy simulations. A small amount of make-up air for the kitchen comes from the adjacent storage area; however, this transfer air is small and was not included in the simulations. The transfer air is the same for all models; therefore, no credit is taken in the energy efficient models for transfer air. Table 6. Baseline Building Model Outside Air Requirements Ventilation cfm (L/s) Maximum Outside Air cfm (L/s) Zone Infiltration cfm (L/s) Transfer Air cfm (L/s) Exhaust Hood cfm (L/s) Dining 768 (362) 5,187 (2,448) -4,496 (2,122) 5,187 (2,448) Storage/Receiving 248 (117) 315 (149) 315 (149) Dishwashing 77 (36) 784 (370) 750 (354) 750 (354) Kitchen 190 (90) 1,934 (913) 13,250 (6,253) 13,250 (6,253) Servery 294 (139) 1,145 (540) 4,496 (2,122) 17,075 (8,058) 12,900 (6,088) Entry/Circulation 294 (139) 372 (176) 372 (176) Carryout 131 (62) 93 (44) 2,100 (991) 2,100 (991) Office 157 (74) 117 (55) 117 (55) Utility 132 (62) 63 (30) 63 (30) There is very little guidance for modeling kitchen exhaust hood systems for energy savings calculations. The only guidance in is in Section 6.5.7, which requires that at least 50% of the make-up air for hoods larger than 5000 cfm be provided by uncooled and heated to no more than 60ºF. The Code of Federal Regulations Volume 71, Number 232 states that kitchen ventilation systems are to be included as part of the HVAC system for energy savings calculations (NARA 2006). With the lack of specific guidance on what the baseline exhaust system should be, we used the typical design for the Army dining facility as the baseline. This design incorporates some improvements in layout and hood design from previous designs. Establishing the baseline is very important because the exhaust hoods and the make-up air requirements constitute a large portion of the energy consumption in the building. There are 10 exhaust hoods for food preparation and one for the dish washer in this dining facility model. Table 7 lists the exhaust hoods and the characteristics for the baseline model. The baseline flow rates, fan pressure, and fan power were taken from the manufacturers equipment cut sheets for the model building used for this study. There was no cut sheet for the double island hood in the kitchen. It was assumed that this hood was 53 ft (16.2 m), counting both sides, and had a flow of 250 cfm/linear 10

11 foot (387 L/s/m) for a total flow of 13,250 cfm (6,253 L/s). The hood duty categories were determined based on Table 1 from the Kitchen Ventilation chapter in the ASHRAE HVAC Applications Handbook (ASHRAE 2007). The flow per unit length was determined from the flow and length specified in the manufacturers cut sheets and they agree with the minimum flow ranges specified in Table 2 of the Kitchen Ventilation chapter in the HVAC Applications Handbook. Table 7. Baseline Exhaust Hood Air Flows. Flow per Length cfm/ft (L/s/m) Zone Hood Duty Length ft (m) Flow cfm (L/s) Static Press. in w.g. (Pa) Fan Power (kw) Dishwashing Dishwasher Light 750 (354) Kitchen Double Island Medium 53.0 (16.2) 250 (387) 13,250 (6,253) 2 (426) Carryout Wall-Mounted Medium 8.5 (2.6) 247 (382) 2,100 (991) 2 (426) Servery Wall-Mounted Medium 5.5 (1.7) 350 (542) 1,925 (908) 2 (516) Single Island Medium 7.0 (2.1) 300 (465) 2,100 (991) 2 (426) Single Island Heavy 5.0 (1.5) 350 (542) 1,750 (826) 2 (426) Single Island Medium 7.0 (2.1) 300 (465) 2,100 (991) 2 (426) Single Island Medium 7.0 (2.1) 300 (465) 2,100 (991) 2 (426) Medium 7.0 (2.1) 300 (465) 2,100 (991) 2 (426) Wall-Mounted hood over fryer Wall-Mounted Medium 9.0 (2.7) 250 (387) 2,250 (1,062) 1 (298) Bake shop Light 11.0 (3.4) 250 (387) 2,750 (1,298) 1 (292) Servery Total 17,075 (8,058) Building Total 32,425 (15,303) Total Fan Eff. There are two limitations in EnergyPlus version 2.1 that forced a workaround for the exhaust fans and make-up air. Exhaust fans are only controlled with an on off schedule and cannot have a fractional schedule, which makes it impossible to model the various fans in the servery turning on and off at different times. In addition, EnergyPlus does not account for the transfer air from the dining zone when calculating the outside air requirements. EnergyPlus determines the outside air as the maximum of the exhaust fan flow rate and the minimum outside air schedule times the peak outside air flow rate without consideration of the transfer air. The outside air requirements for the servery goes up and down as the various exhaust fans and the transfer air turn on and off on different schedules. To get around this problem, the hourly energy use of the exhaust fans was calculated in a spreadsheet then entered in the EnergyPlus model as an external load to the zones. The outside air requirements were entered with an hourly schedule. The exhaust fan energy was then moved from the external load to the fan energy with post-processing. Results The annual energy use intensity for each climate as simulated by EnergyPlus forms the baseline energy budget. The target energy budget is 70% of these baseline values. Table 8 lists the site energy use intensities (EUI) with and without plug and process loads for the baseline and target energy budgets for each climate zone. Figure 8 shows breakouts of the energy consumption by end use. 11

12 Climate Zone City Table 8. Energy Budgets by Climate Zone. Baseline kbtu/ft 2 (MJ/m 2 ) With Process Loads Target kbtu/ft 2 (MJ/m 2 ) Without Process Loads Baseline kbtu/ft 2 (MJ/m 2 ) Target kbtu/ft 2 (MJ/m 2 ) 1A Miami, FL 355 (1,229) 249 (862) 153 (530) 107 (370) 2A Houston, TX 363 (1,256) 254 (879) 154 (533) 108 (374) 2B Phoenix, AZ 348 (1,205) 244 (845) 143 (495) 100 (346) 3A Memphis, TN 375 (1,298) 263 (910) 161 (557) 113 (391) 3B El Paso, TX 355 (1,229) 248 (858) 143 (495) 100 (346) 3C San Francisco, CA 331 (1,146) 232 (803) 112 (388) 78 (270) 4A Baltimore, MD 402 (1,391) 282 (976) 182 (630) 127 (440) 4B Albuquerque, NM 368 (1,274) 258 (893) 149 (516) 104 (360) 4C Seattle, WA 372 (1,288) 260 (900) 149 (516) 104 (360) 5A Chicago, IL 433 (1,499) 303 (1,049) 209 (723) 146 (505) 5B Colorado Springs, CO 393 (1,360) 275 (952) 168 (581) 117 (405) 6A Burlington, VT 464 (1,606) 325 (1,125) 236 (817) 165 (571) 6B Helena, MT 435 (1,506) 304 (1,052) 206 (713) 144 (498) 7A Duluth, MN 508 (1,758) 356 (1,232) 273 (945) 191 (661) 8A Fairbanks, AK 630 (2,181) 441 (1,526) 388 (1,343) 271 (938) Energy Conservation Measures Tables and show the annual energy savings intensity for each of the ECMs. The energy savings across all the ECMs in the final building are not additive because of the interactions between all of the building systems. The lighting and envelope ECMs were modeled separately and in combination to determine the best combinations by climate zone. Table 9. Energy Conservation Measures. ECM Description Envelope air tightness Improved building air leakage to 0.25 cfm/ft 2 at 0.3 in w.g. (1.25 L/s/m 2 at 75 Pa) Envelope insulation Used 30% Small Office Advanced Energy Design Guide insulation Envelope fenestration Used 30% Small Office Advanced Energy Design Guide windows Cool Roof Increased solar reflectance to 0.65 Improved lighting design Reduced lighting power densities Daylighting Added daylighting controls to the dining, servery, carryout, and office Ventilation hood end panels Added partial end panels on the kitchen hood and all wall-mounted hoods in the servery, bake shop, and carryout areas Eliminate single-island hoods Replaced single-island hoods with wall-mounted hoods in servery DCV ventilation hoods Added DCV to the hoods in the servery, carryout, and kitchen High efficiency HVAC Increased the efficiency of all HVAC and water heating equipment Low-flow pre-rinse nozzles Added low-flow pre-rinse nozzles 1.2 gpm (0.076 L/s) Envelope Air Tightness. Based on input from building air tightness experts, the U.S. Army has proposed in their new construction regulations that the leakage rate must not exceed 0.25 cfm/ft 2 at 0.3 in w.g. (1.25 L/s/m 2 at 75 Pa), which was assumed for the energy efficient building models in this study. The energy savings for this ECM are small in all climates except for climate zones 6 and 8 where the savings reaches 6%. Improved Envelope. Tables lists the recommended building envelope insulation levels and fenestration for the energy efficient building. The opaque envelope insulation recommendations follow Standard for climate zones 1 through 2B and the ASHRAE Small Office 30% Advanced 12

13 Energy Design Guide (AEDG) (ASHRAE 2004b) for the other climate zones. The recommended fenestration follow Standard for climate zones 1 through 3C and follow the Small Office 30% AEDG for climate zones 4 through 8. The opaque envelope ECM shows very little savings in climate zone 3 and significant energy savings in the cold climates. This difference in windows shows negative energy savings in climate zone 1A because of the higher solar heat gain in the AEDG windows. A high roof solar reflectance was modeled as a separate case. The baseline roof solar reflectance was 0.3 and the cool roof solar reflectance was This ECM shows small energy savings for climate zones 1, 2, and 4B and a very small savings in 3A. There is negative energy savings in the other climate zones. The energy use in this building is driven by the requirements to treat the make-up air; therefore, this ECM has a small impact compared to other building types. 13

14 Table 10. Envelope Conservation Measures Item Component(1) Climate Zones Roof Assembly Max U-value U U U U U U U U Walls Floors Over Unconditioned Space Slab-on-Grade Doors Insulation Entirely R-15ci R-15ci R-20ci R-20ci R-20ci R-25ci R-25ci R-25ci Above Deck Attic and Other R-19 R-19 R-30 R-30 R-30 R-38 R-38 R-38 Solar Reflectance (2) Assembly Max U-value U U U U U U U U Mass R-6.5ci R-6.5ci R-10 R-13 R-13 R-13 R-13 R R-3.0ci Steel Framed R-13 R-13 R-13 + R-3.8ci Wood Framed and Other R-13 + R-7.5ci R-13 R-13 R-13 R-13 + R-3.8ci R-13 + R-7.5ci R-13 + R-3.8ci R-13 + R-7.5ci R-13 + R-3.8ci R-13 + R-7.5ci R-13 + R-3.8ci R-13 + R-18.8ci R-13 + R-19.5ci Assembly Max U-value U U U U U U U U Mass R-6.3ci R-6.3ci R-10.4ci. R-10.4ci. R-16.7ci. R-25.1ci. R-25.1ci. R-25.1ci. Steel Joists R-13 R-13 R-13 R-13 R-19 R-30 R-30 R-30 Wood Framed and R-13 R-13 R-13 R-13 R-19 R-30 R-30 R-30 Others Assembly Max F-value; F ; F ; F ; F ; F ; F ; F ; F ; Unheated NR (3) NR (3) NR (3) R-15.0 for R-15.0 for R-20.0 for R-20.0 for R-20.0 for 24 in. 24 in. 24 in. 24 in. 48 in. Assembly Max F-value; F-1.020; F-1.020; F ; F ; F-0.688; F-0.688; F-0.671; F-0.671; Heated R-7.5 for R-7.5 for R-15.0 for R-20 for R-20.0 for R-20.0 for R-25.0 for R-25.0 for 12 in 12 in 24 in. 24 in. 48 in 48 in 48 in 48 in Swinging U-0.70 U-0.70 U-0.70 U-0.50 U-0.50 U-0.50 U-0.50 U-0.50 Non-swinging U-1.45 U-1.45 U-1.45 U-0.50 U-0.50 U-0.50 U-0.50 U-0.50 Air Tightness (4) Max Leakage at ±75Pa Blower Test Pressures Vertical Glazing Window to Wall Ratio (WWR) 0.25 cfm/ft cfm/ft cfm/ft cfm/ft cfm/ft cfm/ft cfm/ft cfm/ft 2 < 20% < 20% < 20% < 20% < 20% < 20% < 20% < 20% Thermal U-1.22 U-1.22 U-0.57 U-0.42 U-0.42 U-0.42 U-0.33 U-0.33 transmittance (Assembly Maximum) Solar heat gain coefficient (SHGC) NR (3) NR (3) South Overhangs NR (3) NR (3) NR (3) NR (3) NR (3) NR (3) NR (3) NR (3) Skylights (Dining and Servery) Percent Roof Area 4% 4% 4% 4% 4% 4% 4% None Thermal transmittance (Assembly Maximum) U-1.36 U-1.36 U-0.69 U-0.69 U-0.69 U-0.69 U-0.69 NR (3) Solar heat gain NR (3) coefficient (SHGC) 14

15 Improved Lighting Design and Daylighting. Table 11 lists the interior lighting power densities (LPD) for the baseline and the energy efficient model for each space. The final column in this table lists the space type from Standard 90.1 Table Daylighting controls were modeled in the servery and the dining area as an energy conservation measure with a minimum illuminance level of 30 fc (300 lux). Table 15 lists the energy savings by location for reduced LPD and for reduced LPD with daylighting. The energy savings are best for the warmer climates. The energy performance in Fairbanks was better without the skylights; therefore there are no skylights and no daylighting in the final energy efficient model for Fairbanks. Occupancy sensors were not included in the simulations because the actual occupancy patterns for the spaces were unknown during this analysis. However, they should be included in all zones that are unoccupied for more than 20% of the building occupied period (3 a.m. to 8 p.m.). Zones that are possible candidates for occupancy sensors include restrooms, office, employee break room, utility rooms, janitor s closets, and storage rooms. Table 11. Building Lighting Power. Baseline Efficient Model Zone W/ft 2 (W/m 2 ) W W/ft 2 (W/m 2 ) W Space Type Dining 0.9 (9.68) 7, (8.61) 6,383 Dining area Storage/Receiving 0.8 (8.61) 2, (8.61) 2,098 Active Storage Dishwashing 1.2 (12.91) 1, (10.76) 1,120 Food Preparation Kitchen 1.2 (12.91) 3, (11.84) 3,039 Food Preparation Servery 1.2 (12.91) 5, (10.76) 4,276 Food Preparation Entry/Circulation 1.3 (13.99) 4, (10.76) 3,290 Lobby Carryout 1.2 (12.91) 1, (10.76) 1,044 Food Preparation Office 1.1 (11.84) 1, (9.68) 1,300 Office Utility 1.5 (16.14) 1, (10.76) 1,053 Elec/Mech Total 27,759 23,596 Ventilation. Table 12 lists the building infiltration, ventilation, and outside air requirements for the final energy efficient model. Three ECMs were applied to the exhaust hoods: addition of end panels, replacement of single island hoods with wall-mounted or back-shelf hoods, and application of demand controlled ventilation (DCV). Table 13 lists the characteristics of the exhaust hoods with all the ECMs applied. The first ECM was to add partial or full end panels to the kitchen hood and all wall-mounted hoods in the servery and carryout zones. It was assumed that this ECM would reduce the flow requirements for all affected hoods to the low end of the minimum flow range in Table 2 of the Kitchen Ventilation chapter in the ASHRAE HVAC Applications Handbook (ASHRAE 2007). The second ECM was to replace the single island hoods in the servery with wall-mounted, canopy hoods by adding full back and partial side walls. The back walls can be transparent to allow visibility from the serving line. The final ECM was to include DCV, which reduces the exhaust flow between heavy cooking periods. It was assumed that the exhaust flow was reduced by half between the heavy cooking periods. A schedule for the DCV operation was derived from analysis of the cooking loads. Actual savings from DCV may vary depending on the effectiveness of the DCV controller and the amount of off peak cooking time. Another ECM that affects the transfer air from the dining zone is the reduced infiltration from a tighter building, which affects the make-up air requirements in the servery. Tables 16-6 and show the infiltration and the transfer air from the dining zone. The reduced infiltration leaves more of the ventilation air in the dining zone available to be transferred to the servery. The maximum outside air requirement in Tables 16-6 and for the servery is higher than the servery exhaust minus the dining transfer air. Each of the exhaust hoods in the servery and the dining transfer air operate on different schedules. The maximum outside air requirement in the servery occurs in the morning when some of the exhaust fans are on and before the dining outside air system is turned 15

16 on. Zone Table 12. Efficient Building Model Outside Air Requirements. Infiltration cfm (L/s) Ventilation cfm (L/s) Transfer Air cfm (L/s) Exhaust Hood cfm (L/s) Maximum Outside Air cfm (L/s) Dining 480 (227) 5,187 (2,448) -4,755 (2,244) 5,187 (2,448) Storage/Receiving 155 (73) 315 (149) 315 (149) Dishwashing 48 (23) 784 (370) 750 (354) 750 (354) Kitchen 119 (56) 1,934 (913) 10,600 (5,003) 10,600 (5,003) Servery 184 (87) 1,145 (540) 4,755 (2,244) 11,400 (5,380) 7,875 (3,717) Entry/Circulation 184 (87) 372 (176) 372 (176) Carryout 82 (39) 93 (44) 1,700 (802) 1,700 (802) Office 98 (46) 117 (55) 117 (55) Utility 82 (39) 63 (30) 63 (30) Zone Hood Duty Table 13. Energy Efficient Exhaust Hood Air Flows. Length ft (m) Flow per Length cfm/ft (L/s/m) Dishwashing Dishwasher Light 750 (354) Flow cfm (L/s) Static Press. in w.g. (Pa) Fan Power (kw) Kitchen Double Island Medium 53.0 (16.2) 200 (310) 10,600 (5,003) 1.20 (298) Carryout Wall-Mounted Medium 8.5 (2.6) 200 (310) 1,700 (802) 1.22 (304) Servery Wall-Mounted Medium 5.5 (1.7) 200 (310) 1,100 (519) 0.85 (211) Wall-Mounted Medium 7.0 (2.1) 200 (310) 1,400 (661) 0.90 (223) Wall-Mounted Heavy 5.0 (1.5) 250 (387) 1,250 (590) 1.00 (249) Wall-Mounted Medium 7.0 (2.1) 200 (310) 1,400 (661) 0.90 (223) Wall-Mounted Medium 7.0 (2.1) 200 (310) 1,400 (661) 0.90 (223) Wall-Mounted hood Medium 7.0 (2.1) 200 (310) 1,400 (661) 0.90 (223) over fryer Wall-Mounted Medium 9.0 (2.7) 200 (310) 1,800 (850) 0.84 (209) Bake shop Light 11.0 (3.4) 150 (232) 1,650 (779) 0.52 (129) Servery Total 11,400 (5,380) Building Total 23,700 (11,185) Total Fan Eff. Figure 10 shows (and Table 16 lists) the energy savings from reducing the hood exhaust rates. The savings are higher in the colder climates because of the large temperature difference between the outside air and the zone air temperatures. Installing end panels provides the largest energy savings for climate zones 7 and 8. Replacing the single island hoods with wall-mounted hoods showed small savings in the warm climates and larger savings in the cold climates. Including DCV on the hoods also shows small savings in the warm climates and significant savings in the cold climates. If the singleisland hoods are not replaced, this ECM will have a larger effect in all climates. The savings associated with this ECM strongly depend on the number of hours with reduced flow and the reduction in flow. Further analysis should be completed if the operating conditions are different than those assumed in this study. The design exhaust rate for kitchen ventilation systems depends on the hood style along with subtle construction features and enhancements (e.g., return flanges along the inside edge of the hood, integral side skirts). Wall-mounted canopy hoods, island (single or double) canopy hoods, and proximity (backshelf, pass-over, or eyebrow) hoods all have different capture areas and are mounted at different heights and horizontal positions relative to the cooking equipment (Figure 11). Generally, for the identical (thermal plume) challenge, a single-island canopy hood requires more exhaust than a wallmounted canopy hood, and a wall-mounted canopy hood requires more exhaust than a proximity 16

17 (backshelf) hood. The performance of a double-island canopy tends to emulate the performance of two back-to-back wall-canopy hoods, although the lack of a physical barrier between the two hood sections makes the configuration more susceptible to cross drafts. Where applicable, the following best-design practices should be incorporated within the exhaust system design and specifications to ensure that capture and containment performance of the hood is satisfactorily at the reduced exhaust rate: 1. Incorporate partial side panels or end walls (Figure 12a and 16-12b). 2. Maximize overhang and minimize clearance between appliance and rear wall (Figure 12c and 16-12d). 3. Position heavy duty equipment (e.g., broilers) in middle of the hood and light duty (e.g., ovens, kettles) at the end of the cook line. 4. Specify wall-mounted canopy hoods instead of single-island canopies. 5. Specify back-shelf (i.e., proximity hoods) over short-order equipment such as griddles and fryers. 6. introduce low-velocity makeup air near hoods (e.g., no 4-way diffusers in kitchens). 7. Maximize transfer air. 8. Incorporate demand ventilation controls High Efficiency HVAC. Three HVAC systems were modeled as improvements to the baseline system: high efficiency PTAC, packaged variable air volume (VAV) with an air cooled chiller, and a packaged VAV with a water cooled chiller. All three improved systems showed similar performance. The high efficiency PTAC was included in the final models. Table 14 lists the four HVAC systems parameters. This ECM shows significant energy savings in all climates. For climate zones 1 through 3 and 4B, it is the single highest saving ECM. Parameter Size range 1000Btu/h (kw) (39 70) Table 14. HVAC systems. Baseline PTAC High Eff. PTAC PVAV Air Cooled Chiller (39 70) EER COP COP w/o supply fan N/A N/A Total fan efficiency Heating source Gas furnace Gas furnace Gas boiler Gas boiler Heating efficiency Pump efficiency N/A N/A SHW gas boiler efficiency PVAV Water Cooled Chiller Service Hot Water. Service hot water use is 15% to 20% of the total building energy consumption. The SHW use in the food preparation and dish wash areas is a process load and not included in the energy savings calculations. However, a 94% efficient boiler was included in the final energy efficient design model. Another ECM for saving hot water is to install low flow prerinse nozzles with a flow rate of 1.2 gpm (0.076 L/s). This ECM was not included in the final model because the SHW for washing is considered a process load. 17

18 Table 15. Annual Energy Savings for Individual ECMs (kbtu/ft 2 ) CZ City Envelope Air Tightness AEDG 30% SO Opaque Envelope 1A Miami, FL 0.4 (1.4) 0.0 (0.0) -0.6 (-2.1) 0.5 (1.7) 4.2 (14.5) 9.1 (31.5) 2A Houston, TX 1.1 (3.8) 0.0 (0.0) 0.6 (2.1) 0.5 (1.7) 3.5 (12.1) 8.7 (30.1) 2B Phoenix, AZ 0.7 (2.4) 0.0 (0.0) 0.4 (1.4) 1.1 (3.8) 3.5 (12.1) 8.4 (29.1) 3A Memphis, TN 1.5 (5.2) 0.9 (3.1) 0.3 (1.0) 0.1 (0.3) 3.0 (10.4) 7.7 (26.7) 3B El Paso, TX 0.8 (2.8) 1.0 (3.5) 0.3 (1.0) -0.2 (-0.7) 3.4 (11.8) 8.4 (29.1) 3C San Francisco, CA 1.1 (3.8) 1.3 (4.5) 0.9 (3.1) -0.5 (-1.7) 2.4 (8.3) 6.7 (23.2) 4A Baltimore, MD 2.0 (6.9) 2.3 (8.0) 0.6 (2.1) -0.2 (-0.7) 2.4 (8.3) 6.3 (21.8) 4B Albuquerque, NM 1.3 (4.5) 2.2 (7.6) 0.3 (1.0) 0.4 (1.4) 2.5 (8.7) 6.8 (23.5) 4C Seattle, WA 2.0 (6.9) 2.5 (8.7) 0.5 (1.7) -0.3 (-1.0) 1.8 (6.2) 4.7 (16.3) 5A Chicago, IL 2.6 (9.0) 2.1 (7.3) 0.9 (3.1) -0.4 (-1.4) 1.9 (6.6) 5.3 (18.3) 5B Colo. Springs, CO 2.0 (6.9) 2.2 (7.6) 0.7 (2.4) -0.6 (-2.1) 2.1 (7.3) 5.7 (19.7) 6A Burlington, VT 3.2 (11.1) 2.6 (9.0) 1.2 (4.2) -0.8 (-2.8) 1.7 (5.9) 4.8 (16.6) 6B Helena, MT 3.0 (10.4) 3.1 (10.7) 1.2 (4.2) -0.6 (-2.1) 1.6 (5.5) 4.3 (14.9) 7A Duluth, MN 4.0 (13.8) 2.7 (9.3) 2.2 (7.6) -1.1 (-3.8) 1.4 (4.8) 3.7 (12.8) 8A Fairbanks, AK 5.9 (20.4) 7.2 (24.9) 1.7 (5.9) -0.5 (-1.7) 1.2 (4.2) 2.2 (7.6) AEDG 30% SO Fenestration Cool Roof Reduced LPD Reduced LPD Daylighting CZ City Table 16. Annual Energy Savings for Individual ECMs 1000Btu/ft 2 (MJ/m 2 ) End Panels on all Hoods Replace Single Island Hoods in Servery DCV Hoods in Servery & Carryout on top of End Panels and Single Island 1A Miami, FL 7.2 (24.9) 2.4 (8.3) 1.8 (6.2) 0.6 (2.1) 2.4 (8.3) 40.0 (138.5) 2.7 (9.3) 2A Houston, TX 10.3 (35.7) 3.9 (13.5) 1.3 (4.5) 3.5 (12.1) 4.8 (16.6) 35.0 (121.1) 3.0 (10.4) 2B Phoenix, AZ 8.7 (30.1) 2.8 (9.7) 0.4 (1.4) 3.4 (11.8) 3.8 (13.2) 34.0 (117.7) 2.9 (10.0) 3A Memphis, TN 18.1 (62.6) 5.9 (20.4) 1.4 (4.8) 6.8 (23.5) 8.3 (28.7) 31.0 (107.3) 3.3 (11.4) 3B El Paso, TX 11.0 (38.1) 3.4 (11.8) -0.3 (-1.0) 4.6 (15.9) 4.3 (14.9) 32.0 (110.8) 3.2 (11.1) 3C San Francisco, CA 15.0 (51.9) 3.7 (12.8) -0.5 (-1.7) 6.7 (23.2) 6.2 (21.5) 19.0 (65.8) 3.4 (11.8) 4A Baltimore, MD 25.8 (89.3) 8.9 (30.8) 2.9 (10.0) 10.8 (37.4) 13.6 (47.1) 30.0 (103.8) 3.6 (12.5) 4B Albuquerque, NM 18.6 (64.4) 6.1 (21.1) 1.3 (4.5) 8.4 (29.1) 9.7 (33.6) 27.0 (93.5) 3.5 (12.1) 4C Seattle, WA 24.8 (85.8) 8.0 (27.7) 1.3 (4.5) 10.9 (37.7) 12.2 (42.2) 21.0 (72.7) 3.6 (12.5) 5A Chicago, IL 32.4 (112.1) 11.5 (39.8) 4.8 (16.6) 13.8 (47.8) 18.7 (64.7) 31.0 (107.3) 3.7 (12.8) 5B Colo. Springs, CO 24.2 (83.8) 8.2 (28.4) 2.6 (9.0) 11.5 (39.8) 14.1 (48.8) 28.0 (96.9) 3.8 (13.2) 6A Burlington, VT 38.7 (134.0) 13.8 (47.8) 7.0 (24.2) 16.9 (58.5) 23.9 (82.7) 32.0 (110.8) 3.9 (13.5) 6B Helena, MT 34.2 (118.4) 12.1 (41.9) 5.5 (19.0) 15.7 (54.3) 21.2 (73.4) 28.0 (96.9) 3.9 (13.5) 7A Duluth, MN 47.8 (165.4) 17.3 (59.9) 9.5 (32.9) 21.1 (73.0) 30.6 (105.9) 34.0 (117.7) 4.2 (14.5) 8A Fairbanks, AK 69.7 (241.3) 25.5 (88.3) 17.3 (59.9) 30.4 (105.2) 47.7 (165.1) 45.0 (155.8) 4.6 (15.9) DCV Kitchen Hoods on top of End Panels First two hood ECMs plus DCV on all Hoods High Eff. HVAC Low-Flow Nozzles 18

19 Total Energy Savings with Recommended Technology Sets The energy savings for the final energy efficient solutions are shown with and without the plug and process loads in Tables and The energy savings ranges from 35% to 48%. Table 19 lists the combinations of best performing solutions for each climate zone. Table 17. Final Energy Efficient Design Solutions without Process Loads Final Energy Efficient CZ City Baseline 1000Btu/ft 2 (MJ/m 2 ) Solution 1000Btu/ft 2 (MJ/m 2 ) Energy Savings 1A Miami, FL 153 (530) 100 (346) 35% 2A Houston, TX 154 (533) 97 (336) 37% 2B Phoenix, AZ 143 (495) 90 (312) 37% 3A Memphis, TN 161 (557) 92 (318) 43% 3B El Paso, TX 143 (495) 82 (284) 42% 3C San Francisco, CA 112 (388) 60 (208) 46% 4A Baltimore, MD 182 (630) 99 (343) 46% 4B Albuquerque, NM 149 (516) 80 (277) 46% 4C Seattle, WA 149 (516) 77 (267) 48% 5A Chicago, IL 209 (723) 112 (388) 46% 5B Colorado Springs, CO 168 (581) 88 (305) 48% 6A Burlington, VT 236 (817) 124 (429) 47% 6B Helena, MT 206 (713) 107 (370) 48% 7A Duluth, MN 273 (945) 142 (492) 48% 8A Fairbanks, AK 388 (1,343) 203 (703) 48% Table 18. Final Energy Efficient Design Solutions with Process Loads Final Energy Efficient CZ City Baseline 1000Btu/ft 2 (MJ/m 2 ) Solution 1000Btu/ft 2 (MJ/m 2 ) Energy Savings 1A Miami, FL 355 (1,229) 295 (1,021) 17% 2A Houston, TX 363 (1,256) 297 (1,028) 18% 2B Phoenix, AZ 348 (1,205) 287 (993) 17% 3A Memphis, TN 375 (1,298) 297 (1,028) 21% 3B El Paso, TX 355 (1,229) 286 (990) 19% 3C San Francisco, CA 331 (1,146) 269 (931) 19% 4A Baltimore, MD 402 (1,391) 309 (1,070) 23% 4B Albuquerque, NM 368 (1,274) 290 (1,004) 21% 4C Seattle, WA 372 (1,288) 290 (1,004) 22% 5A Chicago, IL 433 (1,499) 326 (1,128) 25% 5B Colorado Springs, CO 393 (1,360) 303 (1,049) 23% 6A Burlington, VT 464 (1,606) 341 (1,180) 26% 6B Helena, MT 435 (1,506) 324 (1,121) 25% 7A Duluth, MN 508 (1,758) 365 (1,263) 28% 8A Fairbanks, AK 630 (2,181) 432 (1,495) 31% 19

20 Table 19. Summary of ECMs in Final Models (grey shading indicates not recommended or investigate on a case by case basis) Zone City Envelope Air Tightness AEDG 30% SO Insulation AEDG 30% SO Fenestration Skylights Cool Roof Reduced LPD Daylighting Hood End Panels Replace Single Island Hoods Servery DCV Hoods Kitchen DCV Hoods High Eff. HVAC 1A 2A Miami, FL Houston, TX 2B Phoenix, AZ 3A Memphis, TN 3B El Paso, TX 3C San Francisco, CA 4A Baltimore, MD 4B Albuquerque, NM 4C Seattle, WA 5A Chicago, IL 5B Colo. Springs, CO 6A Burlington, VT 6B Helena, MT 7A Duluth, MN 8A Fairbanks, AK Energy savings associated with effectively reducing the average kitchen exhaust ventilation rate (and the associated makeup air requirements) represent a very significant set of ECMs for Army dining facilities. Installing partial end panels or skirts on all wall-canopy hoods in the kitchen and servery shows significant energy savings in all climate zones, especially the cold climates. Similarly, replacing single-island canopy hoods with wall-mounted canopy hoods (or proximity style back-shelf hoods on short-order cooklines) generates significant savings in the cold climates. Overlaying demand controlled ventilation on all ventilation hoods in the kitchen saves energy in all climate zones, particularly the hot and cold climates. Applied to the servery hoods, there are cases where the reduction in average ventilation rate did not generate savings in the mild climate zones. Effectively, all three kitchen ventilation ECMs facilitate a reduction in the average exhaust and makeup air flow rates and generate significant energy savings. In moderate climate zones, the benefits of reduced makeup air heating and cooling may be offset by the economizer effect of having higher exhaust rates during extended shoulder seasons. Installing high efficiency HVAC (PTAC, 12.0 EER (3.52 COP); 0.9 E t gas heater; 0.94 E t gas boiler Vs PTAC, 9.7 EER (2.84 COP); 0.8 E t gas heater; 0.8 E t gas boiler) in the baseline case per the ASHRAE Standard requirements shows significant energy savings in all climates. It shows the highest savings for climate zones 1 through 3 and 4B. Installing Low-Flow Pre-Rinse Nozzles, 1.2 gpm, in each of the storage and receiving, dish wash, and kitchen zones is very easy to implement and shows energy savings in all climates. 20

ENERGY DESIGN GUIDES FOR ARMY BARRACKS

ENERGY DESIGN GUIDES FOR ARMY BARRACKS ENERGY DESIGN GUIDES FOR ARMY BARRACKS Introduction Section 109 of the Energy Policy Act of 2005 (EPAct 2005) states that, for new federal facilities, the buildings be designed to achieve energy consumption

More information

ENERGY EFFICIENCY/RENEWABLE ENERGY (EERE) PROJECTS IN TEXAS PUBLIC SCHOOLS

ENERGY EFFICIENCY/RENEWABLE ENERGY (EERE) PROJECTS IN TEXAS PUBLIC SCHOOLS ENERGY EFFICIENCY/RENEWABLE ENERGY (EERE) PROJECTS IN TEXAS PUBLIC SCHOOLS N Jeff S. Haberl, Ph.D., P.E Zi Liu, Ph.D. Hyojin Kim Jaya Mukhopadhyay Sunglok Do Bahman Yazdani, P.E. Charles Culp, Ph.D., P.E.

More information

BUILDING ENVELOPE. Alexander Zhivov, Ph.D., Dale Herron, and Richard Liesen, Ph.D. USACE Engineer Research and Development Center

BUILDING ENVELOPE. Alexander Zhivov, Ph.D., Dale Herron, and Richard Liesen, Ph.D. USACE Engineer Research and Development Center BUILDING ENVELOPE Specifications Alexander Zhivov, Ph.D., Dale Herron, and Richard Liesen, Ph.D. USACE Engineer Research and Development Center The building envelope performs various tasks, which includes

More information

ACHIEVING ENERGY EFFICIENCY AND IMPROVING INDOOR AIR QUALITY IN ARMY MAINTENANCE FACILITIES (TEMF)

ACHIEVING ENERGY EFFICIENCY AND IMPROVING INDOOR AIR QUALITY IN ARMY MAINTENANCE FACILITIES (TEMF) ACHIEVING ENERGY EFFICIENCY AND IMPROVING INDOOR AIR QUALITY IN ARMY MAINTENANCE FACILITIES (TEMF) Alexander Zhivov, Ph.D., Dale Herron and Richard Liesen, Ph.D. USACE Engineer Research and Development

More information

HVAC. Kitchen Exhaust. rooftop equipment! let s drop on a few exhaust fans! it doesn t get easier!

HVAC. Kitchen Exhaust. rooftop equipment! let s drop on a few exhaust fans! it doesn t get easier! HVAC & Kitchen Exhaust The Heart of Restaurant HVAC rooftop equipment! let s drop on a few exhaust fans! it doesn t get easier! 1 CKV Design: Just not that easy! There is no piece of equipment in the commercial

More information

Energy Performance Comparison of Heating and Air Conditioning Systems for Multifamily Residential Buildings

Energy Performance Comparison of Heating and Air Conditioning Systems for Multifamily Residential Buildings Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2010 Energy Performance Comparison of Heating and Air Conditioning Systems for Multifamily

More information

Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls

Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls PCA R&D Serial No. 415 Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls by John Gajda and Martha VanGeem 000 Portland Cement Association KEYWORDS Concrete,

More information

ENERGY STAR Certified Homes, Version 3 Cost & Savings Estimates

ENERGY STAR Certified Homes, Version 3 Cost & Savings Estimates November 1, 2013 Contents ENERGY STAR Certified Homes, Version 3 Section 1: Executive Summary... 3 Section 2: Detailed Incremental Cost Estimates... 6 Section 3: Incremental Cost & Savings of the Thermal

More information

Energy Savings in High-Rise Buildings Using High-Reflective Coatings

Energy Savings in High-Rise Buildings Using High-Reflective Coatings Energy Savings in High-Rise Buildings Using High-Reflective Coatings Executive Summary: Nevertheless, the simulation analyses showed that when designing a building for low energy consumption, even in cold

More information

2011 Energy Efficiency Expo!

2011 Energy Efficiency Expo! Welcome to the 2011 Energy Efficiency Expo! Thank you to our session sponsors! Comparison Between the 2009 and 2012 International Energy Conservation Code What s coming when the new commercial energy code

More information

Development of Design Guidance for K-12 Schools from 30% to 50% Energy Savings

Development of Design Guidance for K-12 Schools from 30% to 50% Energy Savings National Renewable Energy Laboratory Innovation for Our Energy Future A national laboratory of the U.S. Department of Energy Office of Energy Efficiency & Renewable Energy Development of Design Guidance

More information

Air Side Economizers and Energy Recovery - Improvements and New Regulations. Richard Lord 09-20-2012

Air Side Economizers and Energy Recovery - Improvements and New Regulations. Richard Lord 09-20-2012 Air Side Economizers and Energy Recovery - Improvements and New Regulations Richard Lord 09-20-2012 Introduction For commercial buildings the use of outside air for cooling and ventilation is an important

More information

Table 1: Prescriptive Envelope Requirements: Residential WOOD FRAME WALL R-VALUE MASS WALL R-VALUE CEILING R-VALUE

Table 1: Prescriptive Envelope Requirements: Residential WOOD FRAME WALL R-VALUE MASS WALL R-VALUE CEILING R-VALUE June 24, 2011 North Carolina Has a New Energy Conservation Code! By R. Christopher Mathis Executive Summary On Friday, June 24, 2011, Governor Beverly Perdue signed SB 708 into law and, with it, approved

More information

2009 Seattle Energy Code Impacts: See below for a recap of Changes in Envelope performance from 2006 to 2009

2009 Seattle Energy Code Impacts: See below for a recap of Changes in Envelope performance from 2006 to 2009 2009 Seattle Energy Code Impacts: Building Envelope Impacts: Below is a Summary of Changes that impact building envelope construction planned for 624 Yale. There are several modifications are required

More information

2009 IECC Update. Scope. Content. International Energy Conservation Code

2009 IECC Update. Scope. Content. International Energy Conservation Code 2009 IECC Update International Energy Conservation Code Scope The code applies to both residential and commercial buildings. In the code, the United States is divided into eight climate zones which are

More information

Energy Efficiency Analysis for a Multi-Story Commercial Office Building. (LG Multi V Water II Heat Recovery VRF System)

Energy Efficiency Analysis for a Multi-Story Commercial Office Building. (LG Multi V Water II Heat Recovery VRF System) Energy Efficiency Analysis for a Multi-Story Commercial Office Building (LG Multi V Water II Heat VRF System) Commercial Air-Conditioning Engineering Study VRF-ES-BL-001-US 011M05 Executive Summary Contents

More information

Comparing Energy Savings of Different VAV Systems

Comparing Energy Savings of Different VAV Systems Comparing Energy Savings of Different VAV Systems Prepared By: Martyn Dodd mart@energysoft.com EnergySoft LLC 1025 5th Street, Suite A Novato, CA 94945 415-897-6400 www.energysoft.com Last Modified: March

More information

Selecting Energy Efficient New Windows in Arizona

Selecting Energy Efficient New Windows in Arizona Selecting Energy Efficient New Windows in Arizona www.efficientwindows.org January 016 ENERGY STAR Zones 1. Meet the Energy Code & Look for the ENERGY STAR Windows must comply with your local energy code.

More information

By Donald Fisher, P.Eng., Associate Member ASHRAE

By Donald Fisher, P.Eng., Associate Member ASHRAE By Donald Fisher, P.Eng., Associate Member ASHRAE Decisions to purchase a commercial kitchen ventilation (CKV) system often are based on rule-of-thumb estimates using a $/cfm index (i.e., annual energy

More information

EnergyPro Building Energy Analysis. Assisted Living Building

EnergyPro Building Energy Analysis. Assisted Living Building EnergyPro Building Energy Analysis Assisted Living Building EnergyPro Building Energy Analysis for an assisted living building Project Scope The purpose of the EnergyPro energy model was to evaluate the

More information

Energy Efficiency Analysis for a Multi-Story Commercial Office Building. (LG Multi V III Heat Recovery VRF System)

Energy Efficiency Analysis for a Multi-Story Commercial Office Building. (LG Multi V III Heat Recovery VRF System) Energy Efficiency Analysis for a Multi-Story Commercial Office Building (LG Multi V III Heat Recovery VRF System) Commercial Air-Conditioning Engineering Study VRF-ES-BK-011-US 011L18 Executive Summary

More information

Selecting Energy Efficient Replacement Windows in Nevada

Selecting Energy Efficient Replacement Windows in Nevada Selecting Energy Efficient Replacement Windows in Nevada www.efficientwindows.org January 06 STAR Zones. Meet the Energy Code & Look for the STAR Windows must comply with your local energy code. Windows

More information

Selecting Energy Efficient New Windows in Georgia

Selecting Energy Efficient New Windows in Georgia Selecting Energy Efficient New Windows in Georgia www.efficientwindows.org January 016 ENERGY STAR Zones 1. Meet the Energy Code & Look for the ENERGY STAR Windows must comply with your local energy code.

More information

Energy Assessment Questionnaire www.energyprofiletool.com/xcel

Energy Assessment Questionnaire www.energyprofiletool.com/xcel Energy Assessment Questionnaire Energy Assessment Questionnaire Page 2 of 11 Xcel Customer No.: First Name: Last Name: Company Name: Address: City State: Zip: Phone: Email Address: You may send me information

More information

Case Studies: Infrared Heating in Industrial Applications

Case Studies: Infrared Heating in Industrial Applications Case Studies: Infrared Heating in Industrial Applications Chao Chen, Puget Sound Energy ABSTRACT Puget Sound Energy (PSE) is a utility which serves more than one million electric customers and over 700,000

More information

24.301.161 INCORPORATION BY REFERENCE OF INTERNATIONAL. (1) The Department of Labor and Industry adopts and incorporates by

24.301.161 INCORPORATION BY REFERENCE OF INTERNATIONAL. (1) The Department of Labor and Industry adopts and incorporates by 24.301.161 INCORPORATION BY REFERENCE OF INTERNATIONAL ENERGY CONSERVATION CODE (1) The Department of Labor and Industry adopts and incorporates by reference the International Code Council's International

More information

VAV Laboratory Room Airflow The Lowdown on Turndown

VAV Laboratory Room Airflow The Lowdown on Turndown Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally

More information

Energy Savings for Occupancy- Based Control (OBC) of Variable- Air-Volume (VAV) Systems

Energy Savings for Occupancy- Based Control (OBC) of Variable- Air-Volume (VAV) Systems PNNL- 22072 Prepared for the U.S. Department of Energy under Contract DE-AC05-76RL01830 Energy Savings for Occupancy- Based Control (OBC) of Variable- Air-Volume (VAV) Systems J Zhang RG Lutes G Liu MR

More information

ENERGY EFFICIENCY ENERGY EFFICIENCY: Saving Dollars While Clearing the Air

ENERGY EFFICIENCY ENERGY EFFICIENCY: Saving Dollars While Clearing the Air : Saving Dollars While Clearing the Air After labor and food, energy is the largest controllable cost in a restaurant s operation. And energy is a great place to start in becoming a green restaurant because

More information

CITY PLAN REVIEW AND INSPECTION. Lisa Fleming Brown, CPM

CITY PLAN REVIEW AND INSPECTION. Lisa Fleming Brown, CPM CITY PLAN REVIEW AND INSPECTION Lisa Fleming Brown, CPM Houston Commercial Energy Conservation Code (2011) A choice of 2009 IECC or ASHRAE 90.1-2007 with amendments. Effective September 2, 2011. Complete

More information

THE ROOFPOINT ENERGY AND CARBON CALCULATOR A NEW MODELING TOOL FOR ROOFING PROFESSIONALS

THE ROOFPOINT ENERGY AND CARBON CALCULATOR A NEW MODELING TOOL FOR ROOFING PROFESSIONALS THE ROOFPOINT ENERGY AND CARBON CALCULATOR A NEW MODELING TOOL FOR ROOFING PROFESSIONALS James L. Hoff, VP of Research Center for Environmental Innovation in Roofing Tools and Models Tools require models

More information

ANSI/ASHRAE Standard 140-2004 Building Thermal Envelope and Fabric Load Tests

ANSI/ASHRAE Standard 140-2004 Building Thermal Envelope and Fabric Load Tests ANSI/ASHRAE Standard 140-2004 Building Thermal Envelope and Fabric Load Tests DesignBuilder Version 1.2.0 (incorporating EnergyPlus version 1.3.0) - June 2006 1.0 Purpose The ANSI/ASHRAE Standard 140-2004

More information

Integrating Kitchen Exhaust Systems with Building HVAC

Integrating Kitchen Exhaust Systems with Building HVAC Design Guide 3 Improving Commercial Kitchen Ventilation System Performance Integrating Kitchen Exhaust Systems with Building HVAC This design guide provides information that may help achieve optimum performance

More information

Energy Savings with Window Retrofits

Energy Savings with Window Retrofits Center for Energy and Environment Energy Savings with Window Retrofits Presentation to Energy Design Conference & Expo Duluth, MN February 25, 2014 Agenda v Background v Introduction: What are window retrofits?

More information

Market Potential Study for Water Heater Demand Management

Market Potential Study for Water Heater Demand Management Market Potential Study for Water Heater Demand Management Rebecca Farrell Troutfetter, Frontier Associates LLC, Austin, TX INTRODUCTION Water heating represents between 13 and 17 percent of residential

More information

Home Energy Evaluation Report

Home Energy Evaluation Report Home Energy Evaluation Report Nate Begeman, 1550 Saint Francis Dr San Jose, CA 95125 Air Infiltration Current Air Leakage 2,852 Current Air Changes Per Hour 0.91 Recommended Air Changes Per Hour 0.35 Percent

More information

IECC Compliance Guide for Homes in Virginia

IECC Compliance Guide for Homes in Virginia IECC Compliance Guide for Homes in Virginia Amended Version of 2012 International Energy Conservation Code July 14, 2014 Climate Zone Since the entire state of Virginia falls in the IECC Climate Zone 4,

More information

Raising the Bar: A Comparison Study of Iowa s Current and Proposed Energy Code

Raising the Bar: A Comparison Study of Iowa s Current and Proposed Energy Code Raising the Bar: A Comparison Study of Iowa s Current and Proposed Energy Code Julia Gauthier, LEED AP BD+C Jeanne Huntsman, AIA, LEED Green Associate The Weidt Group Raising the Bar Special statements

More information

Building Energy Codes 101 October 23, 2013. Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance

Building Energy Codes 101 October 23, 2013. Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance Building Energy Codes 101 October 23, 2013 Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance OVERVIEW 1. Introduction 2. Energy Code Development 3. Adoption Process 4. Elements

More information

Smart School Symposium Heating Ventilation and Air Conditioning Session HVAC Products. Richard Lord

Smart School Symposium Heating Ventilation and Air Conditioning Session HVAC Products. Richard Lord Smart School Symposium Heating Ventilation and Air Conditioning Session HVAC Products Richard Lord Overview and Agenda My goal today is to give you quick an overview of the current status of HVAC products

More information

Impact of Infiltration on Heating and Cooling Loads in U.S. Office Buildings

Impact of Infiltration on Heating and Cooling Loads in U.S. Office Buildings Impact of Infiltration on Heating and Cooling Loads in U.S. Office Buildings 1 Steven J. Emmerich, 1 Andrew K. Persily, and 2 Timothy P. McDowell 1 Building and Fire Research Laboratory, National Institute

More information

Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects

Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects Makeup Air For Exhaust Systems In Tight Houses Tony Jellen Engineering Projects PA Housing & Land Development Conference February 23, 2012 Effects of Kitchen Ventilation on Residential Dwellings Anthony

More information

Pulling the Levers on Existing Buildings: A Simple Method for Calibrating Hourly Energy Models

Pulling the Levers on Existing Buildings: A Simple Method for Calibrating Hourly Energy Models 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, vol 116,part 2). For personal use only. Additional reproduction,

More information

Cost Estimation for Materials and Installation of Hot Water Piping Insulation

Cost Estimation for Materials and Installation of Hot Water Piping Insulation Cost Estimation for Materials and Installation of Hot Water Piping Insulation Prepared for Pacific Northwest National Laboratory Under Contract Number: 18O9O2 By Gary Klein, Managing Partner Affiliated

More information

DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL

DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL Brittany Hanam, MASc, EIT RDH Building Engineering Ltd. Vancouver, BC John Straube, PhD, P.Eng. Building Engineering Group, Civil

More information

Selecting Energy Efficient New Windows in Florida

Selecting Energy Efficient New Windows in Florida Selecting Energy Efficient New Windows in Florida www.efficientwindows.org January 06 Zones. Meet the Energy Code & Look for the Windows must comply with your local energy code. Windows that are certified

More information

INFORMED MECHANICAL DESIGN THROUGH TESTED AIR LEAKAGE RATES. Jeff Speert, AIA MAIBC LEED AP

INFORMED MECHANICAL DESIGN THROUGH TESTED AIR LEAKAGE RATES. Jeff Speert, AIA MAIBC LEED AP INFORMED MECHANICAL DESIGN THROUGH TESTED AIR LEAKAGE RATES Jeff Speert, AIA MAIBC LEED AP Background Move towards more energy efficient structures Collaborative approach promoted by LEED, 2030 Challenge,

More information

SECTION 11 78 13 MORTUARY REFRIGERATORS

SECTION 11 78 13 MORTUARY REFRIGERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

Residential HVAC System Sizing

Residential HVAC System Sizing Residential HVAC System Sizing William P. Goss University of Massachusetts, Amherst, Massachusetts, USA Corresponding email: goss@acad.umass.edu SUMMARY Heating, ventilating and air-conditioning (HVAC)

More information

Selecting Energy Efficient New Windows in Texas

Selecting Energy Efficient New Windows in Texas Selecting Energy Efficient New Windows in Texas www.efficientwindows.org January 06 Zones. Meet the Energy Code & Look for the Windows must comply with your local energy code. Windows that are certified

More information

Building Energy Analysis Report

Building Energy Analysis Report Building Energy Analysis Report Report Generated by Efilm, an EnergyPlus based program. Date: 6/8/2012 Project Information Title: Building Filmed in 2012 Address: City/State/Zip: New York, NY 10001 Analyst

More information

Analysis of HERS Index Scores for Recent Versions of the International Energy Conservation Code (IECC)

Analysis of HERS Index Scores for Recent Versions of the International Energy Conservation Code (IECC) Analysis of HERS Index Scores for Recent Versions of the International Energy Conservation Code (IECC) FSEC-CR-1941-13 Final Report January 11, 2013 Revised February 21, 2013 Submitted to Residential Energy

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning Load Calculation Criteria PART 1 - GENERAL 1.01 OVERVIEW A. This section includes requirements for calculating HVAC cooling and heating loads. B. Load calculations must be performed in accordance with

More information

Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer

Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code

More information

APPENDIX C FORMS 2010 FLORIDA BUILDING CODE ENERGY CONSERVATION C.1

APPENDIX C FORMS 2010 FLORIDA BUILDING CODE ENERGY CONSERVATION C.1 APPENDIX C FORMS 2010 FLORIDA BUILDING CODE ENERGY CONSERVATION C.1 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = The lower the Energy Performance Index, the more efficient

More information

Key energy-efficient features of your new home

Key energy-efficient features of your new home Key energy-efficient features of your new home Your thermal envelope The thermal envelope, or shell, of your home (walls, roof and floor) is designed to keep you dry and comfortable. It protects you from

More information

Load Calculation Spreadsheets Quick Answers Without Relying on Rules of Thumb

Load Calculation Spreadsheets Quick Answers Without Relying on Rules of Thumb This article was published in ASHRAE Journal, January 2012. Copyright 2012 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not

More information

BPC Green Builders. Green building for new and existing homes. Health Comfort Energy

BPC Green Builders. Green building for new and existing homes. Health Comfort Energy BPC Green Builders Green building for new and existing homes Health Comfort Energy Mechanical Systems Installed HVAC Systems Primary energy source large, roof mounted, solar thermal array (AET flat plate)

More information

METHODOLOGY FOR COMMERCIAL BUILDINGS THERMAL LOADS PREDICTIVE MODELS BASED ON SIMULATION PERFORMANCE

METHODOLOGY FOR COMMERCIAL BUILDINGS THERMAL LOADS PREDICTIVE MODELS BASED ON SIMULATION PERFORMANCE METHODOLOGY FOR COMMERCIAL BUILDINGS THERMAL LOADS PREDICTIVE MODELS BASED ON SIMULATION PERFORMANCE Dimitrios-Stavros Kapetanakis 1,2, Eleni Mangina 3 and Donal Finn 1,2 1 School of Mechanical & Materials

More information

Energy Savings Modeling and Inspection Guidelines for Commercial Building Federal Tax Deductions

Energy Savings Modeling and Inspection Guidelines for Commercial Building Federal Tax Deductions National Renewable Energy Laboratory Innovation for Our Energy Future A national laboratory of the U.S. Department of Energy Office of Energy Efficiency & Renewable Energy Energy Savings Modeling and Inspection

More information

Building Performance Evaluation Guide Version 1.7

Building Performance Evaluation Guide Version 1.7 Building Performance Evaluation Guide Version 1.7 Prepared by Center for Energy and Environment January 2014 Minnesota Sustainable Building 2030: Building Performance Evaluation Guide p 1 1. Schematic

More information

Mechanical Insulation. Hospitals and Schools

Mechanical Insulation. Hospitals and Schools Study on Mechanical Insulation in Hospitals and Schools March 1, 2011 Study Mechanical Insulation in Hospitals and Schools G. Christopher P. Crall, P.E. Ronald L. King Executive Summary Mechanical insulation

More information

Xcel Energy s Commercial Industrial Energy Efficiency Programs. Overview of Colorado Business Rebate Programs

Xcel Energy s Commercial Industrial Energy Efficiency Programs. Overview of Colorado Business Rebate Programs Xcel Energy s Commercial Industrial Energy Efficiency Programs Overview of Colorado Business Rebate Programs Trade Relation Managers Derek Shockley 303-294-2082 John.D.Shockley@XcelEnergy.com Commercial

More information

Energy Efficiency in Buildings

Energy Efficiency in Buildings Energy Efficiency in Buildings Supplemental Guide to SANS 10400-XA & SANS 204 V. 3.0 Registered to: The Drawing Studio Image: digitalart / FreeDigitalPhotos.net Report Date: 26 August 2014 Practice Name:

More information

Database of Low-e Storm Window Energy Performance across U.S. Climate Zones

Database of Low-e Storm Window Energy Performance across U.S. Climate Zones PNNL-22864, Rev.2 Database of Low-e Storm Window Energy Performance across U.S. Climate Zones September 2014 TD Culp KA Cort, Project Lead PNNL-22864, Rev.2 Database of Low-e Storm Window Energy Performance

More information

Selecting Energy Efficient New Windows in California

Selecting Energy Efficient New Windows in California Selecting Energy Efficient New Windows in California www.efficientwindows.org Janurary 016 Zones 1. Meet the Energy Code & Look for the Windows must comply with your local energy code. Windows that are

More information

Amplification of Notice 2006-52; Deduction for Energy Efficient Commercial Buildings

Amplification of Notice 2006-52; Deduction for Energy Efficient Commercial Buildings Internal Revenue Bulletin: 2008-14 April 7, 2008 Notice 2008-40 Amplification of Notice 2006-52; Deduction for Energy Efficient Commercial Buildings Table of Contents SECTION 1. PURPOSE SECTION 2. BACKGROUND

More information

Large Hospital 50% Energy Savings: Technical Support Document

Large Hospital 50% Energy Savings: Technical Support Document Large Hospital 50% Energy Savings: Technical Support Document Technical Report NREL/TP-550-47867 September 2010 Eric Bonnema, Daniel Studer, Andrew Parker, Shanti Pless, and Paul Torcellini Large Hospital

More information

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same

More information

Preserving Envelope Efficiency in Performance Based Code Compliance

Preserving Envelope Efficiency in Performance Based Code Compliance PNNL-24359 Preserving Envelope Efficiency in Performance Based Code Compliance BA Thornton GP Sullivan MI Rosenberg MC Baechler, Project Manager May 2015 PNNL-24359 Preserving Envelope Efficiency in Performance

More information

Optimizing Makeup Air

Optimizing Makeup Air Design Guide 2 Improving Commercial Kitchen Ventilation System Performance Optimizing Makeup Air This design guide provides information that will help achieve optimum performance and energy efficiency

More information

Differentiating Energy Modeling Software!

Differentiating Energy Modeling Software! Differentiating Energy Modeling Software! What works, what doesn t, and when it matters! A Boulder Green Building Guild brownbag presentation by! Adam Stenftenagel! Principal! Sustainably Built! Heat Movement

More information

Sensitivity of Forced Air Distribution System Efficiency to Climate, Duct Location, Air Leakage and Insulation

Sensitivity of Forced Air Distribution System Efficiency to Climate, Duct Location, Air Leakage and Insulation LBNL 43371 Sensitivity of Forced Air Distribution System Efficiency to Climate, Duct Location, Air Leakage and Insulation Iain S. Walker Energy Performance of Buildings Group Indoor Environment Department

More information

EarthCents (DSM) Program Summary

EarthCents (DSM) Program Summary EarthCents (DSM) Program Summary Renewable Energy EarthCents Programs Solar Water Heating This program is available to residential customers for the installation of a qualifying solar thermal water heater.

More information

NOTICE OF INCORPORATION United States Legal Document

NOTICE OF INCORPORATION United States Legal Document NOTICE OF INCORPORATION United States Legal Document All citizens and residents are hereby advised that this is a legally binding document duly incorporated by reference and that failure to comply with

More information

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating

More information

Introduction to Energy Codes & Green Building Programs

Introduction to Energy Codes & Green Building Programs Introduction to Energy Codes & Green Building Programs David Neiger B.S. Arch, LEED AP Homes, Certified HERS Rater Principal Populus Sustainable Design Consulting Why green homes? The Building Sector:

More information

Ventilation Retrofit Opportunities for Packaged HVAC

Ventilation Retrofit Opportunities for Packaged HVAC Ventilation Retrofit Opportunities for Packaged HVAC Reid Hart, PE National Energy Efficiency Technology Summit September 2012 PNNL-SA-90782 Acknowledgements Bonneville Power Administration City of Eugene

More information

Energy Efficiency Tips for Businesses

Energy Efficiency Tips for Businesses Energy Efficiency Tips for Businesses Top 10 Tips Lighting Tips Heating and Cooling Temperature Control Office Equipment Laundry Service Refrigeration Equipment Food Service Equipment Employee Involvement

More information

Energy Analysis for Window Films Applications in New and Existing Homes and Offices

Energy Analysis for Window Films Applications in New and Existing Homes and Offices Energy & Environmental Solutions Energy Analysis for Window Films Applications in New and Existing Homes and Offices PREPARED FOR: INTERNATIONAL WINDOW FILM ASSOCIATION P.O. BOX 3871 MARTINSVILLE, VA 24115-3871

More information

Commercial Energy Efficiency Program. Save money, reduce energy use and earn incentives. Save money, reduce energy use and qualify for incentives

Commercial Energy Efficiency Program. Save money, reduce energy use and earn incentives. Save money, reduce energy use and qualify for incentives Save money, reduce energy use and earn incentives by improving the energy efficiency of your business. Georgia Power s Commercial Energy Efficiency Program makes incorporating energy-efficient improvements

More information

CHAPTER 4 LOAD CALCULATIONS 4.1 CONTEXT

CHAPTER 4 LOAD CALCULATIONS 4.1 CONTEXT CHAPTER 4 LOAD CALCULATIONS 4.1 CONTEXT The accurate calculation of heating and cooling loads is essential to provide a sound bridge between fundamental building design decisions and an operating building.

More information

BECx& Building Airtightness. Presented by: Eric Amhaus Principal

BECx& Building Airtightness. Presented by: Eric Amhaus Principal BECx& Building Airtightness Presented by: Eric Amhaus Principal The Building Enclosure 2007 study: out of 17,000 construction defect claims, 69% result of moisture related defects in building enclosure

More information

Building Energy Systems. - HVAC: Heating, Distribution -

Building Energy Systems. - HVAC: Heating, Distribution - * Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center

More information

2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012

2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012 2012 Ontario Building Code Requirements for New Construction Bradford West Gwillimbury Building Division March 5, 2012 1 Ontario Building Code changes Applicable to permits applied for after December 31,

More information

Analysis of 2009 International Energy Conservation Code Requirements for Residential Buildings in Kansas City, Missouri

Analysis of 2009 International Energy Conservation Code Requirements for Residential Buildings in Kansas City, Missouri PNNL-20699 Prepared for the U.S. Department of Energy under Contract DE-AC05-76RL01830 Analysis of 2009 International Energy Conservation Code Requirements for Residential Buildings in Kansas City, Missouri

More information

APPENDIX C - Florida Energy Code Standard Reference Design Auto-Generation Tests

APPENDIX C - Florida Energy Code Standard Reference Design Auto-Generation Tests REM/Rate v15 Review 9/22/14 Purpose This document includes the results of limited testing and verification of the REM/Rate v15.0 software submitted as a simulation tool for demonstrating compliance with

More information

This notice sets forth interim guidance, pending the issuance of regulations,

This notice sets forth interim guidance, pending the issuance of regulations, Part III - Administrative, Procedural, and Miscellaneous Deduction for Energy Efficient Commercial Buildings Notice 2006-52 SECTION 1. PURPOSE This notice sets forth interim guidance, pending the issuance

More information

White paper on the comparative energy efficiency of zoned electric heaters Convectair, Inc. / Convectair-NMT Inc. September 2004

White paper on the comparative energy efficiency of zoned electric heaters Convectair, Inc. / Convectair-NMT Inc. September 2004 White paper on the comparative energy efficiency of zoned electric heaters Convectair, Inc. / Convectair-NMT Inc. September 2004 Contents : 1. Introduction 2. Fundamentals of heating 3. Temperature distribution

More information

Small Business Energy Efficiency and Specialty Equipment

Small Business Energy Efficiency and Specialty Equipment Small Business Energy Efficiency and Specialty Equipment Scott Schultz, LEED AP, CEM Energy Program Engineer, SAIC, an Ameren Illinois ActOnEnergy Partner August 28, 2013 Practical Items If you can't hear

More information

HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems

HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems Fundamental Principles of Environmentally Responsible, Energy Efficient Buildings 1. Energy efficiency is

More information

A Comparison of Energy, Economic and Environmental Benefits of Tinted Low-E Glasses

A Comparison of Energy, Economic and Environmental Benefits of Tinted Low-E Glasses A Comparison of Energy, Economic and Environmental Benefits of Tinted Low-E Glasses When measured against dual-pane tinted glass, the most commonly specified type of tinted glass, the study showed that

More information

ALBUQUERQUE PUBLIC SCHOOLS Facility Design & Construction / Maintenance & Operations

ALBUQUERQUE PUBLIC SCHOOLS Facility Design & Construction / Maintenance & Operations ALBUQUERQUE PUBLIC SCHOOLS Facility Design & Construction / Maintenance & Operations MECHANICAL SYSTEMS DESIGN STANDARDS Appendix A RECOMMENDED HVAC SYSTEMS BY TYPE OF SPACE Matt Higgins Valentin Lucero

More information

PERFORMANCE OF SIDE-BY-SIDE SOUTH TEXAS HOMES Isolating the Contribution of Spray Polyurethane Foam Insulation

PERFORMANCE OF SIDE-BY-SIDE SOUTH TEXAS HOMES Isolating the Contribution of Spray Polyurethane Foam Insulation PERFORMANCE OF SIDE-BY-SIDE SOUTH TEXAS HOMES Isolating the Contribution of Spray Polyurethane Foam Insulation INTRODUCTION As the use of spray polyurethane foam (SPF) insulation is increasing in both

More information

Energy and Energy Cost Savings Analysis of the 2015 IECC for Commercial Buildings

Energy and Energy Cost Savings Analysis of the 2015 IECC for Commercial Buildings PNNL-24269 Energy and Energy Cost Savings Analysis of the 2015 IECC for Commercial Buildings June 2015 J Zhang Y Xie R Athalye J Zhuge M Rosenberg R Hart B Liu PNNL-24269 Energy and Energy Cost Savings

More information

ENERGY SYSTEMS LABORATORY

ENERGY SYSTEMS LABORATORY ESL-TR-11-12-07 A COMPARISON OF BUILDING ENERGY CODE STRINGENCY: 2009 IECC VERSUS 2012 IECC FOR COMMERCIAL CONSTRUCTION IN TEXAS Jaya Mukhopadhyay Juan-Carlos Baltazar, Ph.D. Jeff S. Haberl, Ph.D., P.E.

More information

1/9/2013. Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability

1/9/2013. Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability 1/9/13 By Brett T. Fagan, P.E. Presented by Marie Horan, P.E. Building Diagnostics, Inc. Building Diagnostics Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability

More information

RULING OF THE MINISTER OF MUNICIPAL AFFAIRS AND HOUSING

RULING OF THE MINISTER OF MUNICIPAL AFFAIRS AND HOUSING BUILDING CODEACT, 1992 RULING OF THE MINISTER OF MUNICIPAL AFFAIRS AND HOUSING Pursuant to clause 29(l)(b) of the Building Code Act, 1992. as amended, the Director of the Building and Development Branch

More information

Existing Housing Stock

Existing Housing Stock 1 How Old and New Houses Use Energy Total Consumption per Household, 2001 120 100 2: RENOVATION - CONCORD, MA million per household 80 60 40 20 Space Heating Electric Air Conditioning Water Heating Refrigerators

More information

2015 IECC Commercial Requirements. Eric Makela, Britt/Makela Group

2015 IECC Commercial Requirements. Eric Makela, Britt/Makela Group 2015 IECC Commercial Requirements Eric Makela, Britt/Makela Group C402 Envelope C406.2 Eff. HVAC Performance C403 Mechanical C406.3 Reduced LPD Prescriptive C404 SWH Pick One C406.4 Digital Lighting Controls

More information