Measure Server delta- T using AUDIT- BUDDY

Size: px
Start display at page:

Download "Measure Server delta- T using AUDIT- BUDDY"

Transcription

1 Measure Server delta- T using AUDIT- BUDDY The ideal tool to facilitate data driven airflow management Executive Summary : In many of today s data centers, a significant amount of cold air is wasted because it bypasses the server, or hot air recirculates back into the cold aisle. The extent of this problem can be determined by comparing the delta- T (temperature differential) at the CRAC unit and delta- T at the server; the higher the difference, the more significant the cooling inefficiency. In the past, measurement of the server delta- T has proven difficult. Now users can place two AUDIT- BUDDY systems (one in the hot aisle and one in the cold aisle) to track changes in delta- T at a given server over an extended period of time and assess the degree of recirculation or bypass airflow present. This simple portable tool yields a metric to indicate cooling efficiency at the rack level. 202 Worcester Street, Unit 5, North Grafton, MA info@purkaylabs.com

2 Introduction An efficient data center requires an effective cooling and airflow management system. The modern forced air cooled data center is designed to maximize the passage of cold air through the server. In reality, a fair amount of cold air bypasses the servers completely or recirculates with hot air, leading to poor efficiency and un- necessarily higher electricity usage. The problem has become more difficult with the addition of high- energy consuming blade servers and rapid changes in an active facility. It is possible to assess the cooling efficiency by comparing the server delta- T with the HVAC delta- T at the CRAC units. In the past, it was difficult to measure the server delta- T. Now, users can place two AUDIT- BUDDY systems in the hot and cold aisle and to track the changes in delta- T at a given server over an extended period of time. The information gathered, when compared to the HVAC delta- T, can be used to assess the degree of recirculation or bypass airflow and address the cooling (in)efficiency. Data Center Cooling The data center cooling model has changed significantly over the years. Previously, the cooling objective was to cool the whole data center at a uniform temperature, around 68 F. 1 Now, the aim is to direct cooling to servers and not overcool portions of the room that don t need to be cooled. 2 The basic premise is by separating the hot and cold aisles the cold supply air goes to the server intakes and allow hot server exhaust to go directly to the cooling unit return air. 3 This allows data centers to maintain a specific inlet temperature designated by the equipment manufacturer s specifications, while keeping cooling costs low. (See Diagram 1: Airflow Distribution- Underfloor) Diagram 1: Underfloor Airflow Distribution 1 Lucian Lipinsky de Orlov Lowering Data Center Cooling Costs with Airflow Modeling and Perforated raised- floor tiles 27 April 2009 at data- center- cooling- costs- with- airflow- modeling- and- perforated- raised- floor- tiles 2 Arthur Cole and Wally Phelps Simple Steps to a Greener Data Center 25 November 2008 at steps- to- a- greener- data- center/?cs= Ibid. Page 1

3 Unfortunately, a fair amount of cold air is wasted. The biggest and most common problem is that the cold air supply air bypasses the server rack and mixes with the warm return air without cooling the server. Another associated problem occurs when the hot air from the server exhaust recirculates back into the cold aisle instead of returning to the CRAC unit. (See Diagram 2: Bypass & Recirculation Airflow). Both these factors contribute significantly to a poor PUE number and the CRAC units are forced to work harder to compensate for the cold air inefficiency, raising the cost of cooling. Diagram 2: Bypass & Recirculation Airflow The immediate inclination is to add additional cooling units or crank up the CRAC and overcool the facility to address the temperature variation at the rack. This mistakenly assumes that inlet server temperature is too hot or too cold because there is not enough cold air being supplied or that the air is not cold enough. Instead, the fundamental issue is that the cold air is not reaching the server efficiently, and instead is being lost or wasted through bypass or recirculation airflow. 4 Data Center Managers must improve their airflow management in order to improve cooling conditions. This means identifying and eliminating the airflow waste to ensure that the majority of cold air supplied to the data center produces effective cooling at the server. 5 4 Vali Sorell Airflow Management Strategies for Efficient Data Center Cooling March 2009 at flow- management- strategies- for- efficient- data- center- cooling 5 Vali Sorell Airflow Management Strategies for Efficient Data Center Cooling March 2009 at flow- management- strategies- for- efficient- data- center- cooling Page 2

4 Determining Airflow Waste & Cooling Efficiency through the delta- T ratio The Data Center Manager must first measure the temperatures at both the CRAC unit and at the server. Data Center Managers can then quantify the amount of airflow waste by comparing the server delta- T (at the server rack) with the HVAC delta- T (at the CRAC unit). The server delta- T (ΔT Server ) is difference between inlet and outlet temperature of a server. HVAC delta- T (ΔT HVAC ) is the difference between the supply air and the return air. If the ΔT HVAC is the same or similar to the ΔT Server, then cooling is efficient. This means that there is little to no change in temperatures between the CRAC unit and the Server, and all or the majority of the cold air supply is reaching the server. If the ΔT HVAC is greater than the ΔT Server, then there is bypass air circulation. This means that some of the cold air is returning to the CRAC unit without cooling the server. The greater the difference, the more cold air is bypassing the server, and the data center is being over cooled unnecessarily. If the ΔT HVAC is less than the ΔT Server, then there is recirculation airflow present. This means that hot air from the server exhaust recirculates back into the cold aisle instead of returning to the CRAC unit. The greater the difference, more likely there is not enough HVAC airflow reaching the server and there is high chance of hotspots. Cooling Pattern Cooling Condition Result ΔT HVAC = ΔT Server Efficient Cooling Cold air reaches server with no or minimal waste ΔT HVAC > ΔT Server Bypass Airflow Cold air not reaching server; overcooling ΔT HVAC < ΔT Server Recirculation Airflow Server exhaust mixing with cold air A simple metric to characterize cooling efficiency is to compare the ratio of ΔT HVAC to ΔT Server or the delta- T rati ( T RATIO ). The T RATIO is defined as: delta- T ratio ( T RATIO ) = Server delta- T (ΔT Server ) : [Outlet Temperature Inlet Temperature] HVAC delta- T (ΔT HVAC ) : [Return Temperature Supply Temperature] With this formula, Data Center Managers can determine the extent of bypass or recirculation airflow. Implication Corrective Action Table 1 delta- T Ratio (ΔT RATIO ) for Rack Below to 1.2 Above 1.2 Bypass Dominates Low Entering Temperatures, Excessive HVAC usage Better containment required for safe operation of servers. Normal Operating Conditions Strive for 1.0 Recirculation Dominates too little HVAC airflow, high entering temperatures Consider blanking panels and other corrective actions. Page 3

5 The Problem of Measuring ΔT Server While ΔT RATIO is a simple and effective way to gauge cooling efficiency, measuring the ΔT RATIO is not common practice in the modern data center. The reason is that it is far easier to measure the ΔT HVAC at the CRAC unit, than measure the ΔT Server at the server rack. CRAC units are supplied with temperature sensors and controls at the return and supply. Busy Data Center Managers can easily make adjustments, and supply colder air to the racks without any extra measurements. But, as mentioned previously, colder air does not compensate for cooling inefficiencies due to bypass or recirculation airflow. If anything, overcooling gives a false sense of reliability, which leaving the server open to hot spots and server failures. Measurement of ΔT Server is extremely important, but difficult to ascertain. The temperature at these multiple server, rack and aisle locations will vary greatly at any given point. Data Center Managers measuring the ΔT Server cannot just hold a thermometer at the inlet and outlet of the server and get an accurate measurement of ΔT Server. Data Center Managers have to take three factors into account when measuring ΔT Server. (1) Rack Height: Every server rack contains multiple servers, and the temperature will vary greatly across the server profile. One simply has to look at a CFD model or thermal contour map to see that the inlet temperature at the front of the rack will vary from the top to the bottom. One must measure delta- T at different heights to account for variance across the server profile. (2) Aisle Composition: In the same vein as the individual server rack, there will be temperature variation from rack to rack across an aisle. The inlet temperature at one end of an aisle will not necessarily be the same as inlet temperature at the other end. This is further complicated by the mix of old servers and high- energy blade servers. One must measure delta- T at different racks to account for variations across an aisle. (3) Time: The IT load varies throughout the day in an active data center. The IT load in a financial services firm may be much higher during the day during trading hours than at night. As a result the delta- T will change over time in a dynamic environment due to server loading, cooling algorithms, and airflow variance. One must measure delta- T over a long period of time (24 hours) to account for load variations. Traditional methods of measurement such as BAS or DCIM are inadequate to measure ΔT Server because none monitor the inlet and outlet at multiple rack heights simultaneously, or measure over a long period of time. Hand held devices are good for spot measurements only and completely miss the time variance aspect. IR guns are simply not accurate enough. 6 6 For more information, please Purkay Labs Introducing AUDIT- BUDDY : Monitoring Temperature and Humidity for Greater Data Center Efficiency at Page 4

6 Given these challenges rack height, aisle composition, time Data Center Managers have mostly chosen to ignore or approximate server delta- T values. The only practical solution is to use two AUDIT- BUDDY systems to measure the inlet and outlet air temperature at the server. AUDIT- BUDDY is a stand- alone temperature and humidity monitor that measures true air quality in Data Centers. Each system consists of three temperature and humidity (TH1) Modules and an adjustable carbon fiber rod. The design permits facility managers to measure inlet air temperature at three different heights (up to 84-48U). AUDIT- BUDDY is battery powered and weights 5.5lbs so it can measure multiple servers, and then be moved across an aisle to measure be moved across multiple racks. The weighted triangular base allows the AUDIT- BUDDY to be placed as close as 1 inch away from the server rack, allowing the patent pending fan design to draw in air and quickly adjust to the thermal ambient. Measuring ΔT Server with AUDIT- BUDDY To measure delta- T across a rack, place one AUDIT- BUDDY in the Cold Aisle side and the other on the Hot Aisle side (See Figure 1). The TH1 Modules may be placed at any height on the adjustable Carbon Figure 1 Measuring ΔT Server with AUDIT- BUDDY Fiber Rod. This allows for measurement of three different servers on the rack at the same time. The placement of the TH1 Modules should be as shown with the TH1 Module as close to the server inlet and exhaust as possible. Figure 2 illustrates a close up for measurement of a particular server. The design of the AUDIT- BUDDY system allows the TH1 Module to be as close as 1 from the server. Page 5

7 Figure 2 Close- up of Measurement of one Server Once the Modules are positioned, both TH1 Modules should be set to collect data using LongScan mode with a sample rate of 1 minute. The sampling duration is dependent on the test interval. For example, if the desire is to track the delta- T performance through a work day of 9 hours, set the collection period to 12 hours or higher. After the data collection is completed, the data is transferred from the TH1 Modules using a USB stick directly to the PC or MAC Excel Program. Analysis of Data Purkay Labs offers the delta- T Excel Macro along with the delta- T package. This Macro runs both on a PC or Mac computers running Excel 2010 or higher. Starting the Macro is achieved simply by clicking the Start button. Figure 3 Start Button for delta- T Macro Once the Macro is enabled, the program asks the user to identify the data collected by the two TH1 Modules. The data is stored in the USB in a special compressed format and the files are identified as.pkl files. The file name reflects the time when the data collection was started and is named automatically based on when the Data collection was started in a PMDDHHMM format. For example, if measurement for the Inlet TH1 Module in the middle position was started at July 12 at 7:45PM, the file name will be M PKL. Page 6

8 The program will ask the user to identify both files. It does not matter which file is identified first. The program determines which files represents the inlet and outlet readings automatically. The program lines up the measurements even though the TH1 Module units may have been started slightly different times. The ΔT Server information is calculated and presented automatically. The program, as an option, allows the user to input the Operator and Specific Server Name, before allowing the user to save the information in a.csv file. Figure 4 Delta- T Macro Output Page 7

9 Figure 5 Delta- T, Inlet, and Outlet Plot over time The Macro Utility also allows the user to generate a Plot of the ΔT Server over time (Figure 5) to be exported to a.gif or.png file. The trend plot allows for one to synchronize wide variance of ΔT Server with specific server loads. This information would be useful in either tuning the server load via virtualization or changing the cooling strategy around that particular server. For example, a higher ΔT Server at certain parts of the day would indicate perhaps the airflow is not uniform when the server is drawing lot more IT Load. This would be an indicator that corrective action may be necessary for that specific server. The Macro Utility also allows for integrating six Module Data into one report to report to the user the overall summary of Bypass or Recirculation airflow present in the rack by calculating an aggregate T- RATIO for the particular rack where the measurements were conducted. Towards a more Energy Efficient Data Center AUDIT- BUDDY Delta- T Package gives the Data Center Manager an economical tool to measure T Server in a facility in simple, inexpensive manner. One can get the T Server of three servers averaged over a period of operation without requiring any additional infrastructure additions, permanent or temporary installs in the cabinet or learning a new software tool. Once the average T Server is gathered, one can get the T- RATIO for the Data Center by looking at the T HVAC. The Manager now has an idea of how efficient the cooling air flow is and the degree of over cooling Page 8

10 present and what corrective actions are required Now the manager has the metric in hand to guide whether to raise the operating temperature of the facility or simply shut down some of the extra CRAC units, or do some simple air flow management with tiles. One can measure T- RATIO again after the changes have been made to decide whether the lever has been moved sufficiently or there are more efficiency opportunities to be realized. Given that almost every Data Center is overcooled because of different factors cited above, the AUDIT- BUDDY Delta T Package gives the Data Center Manager the metric through which one could implement a clear air flow management strategy, reduce operational expense without affecting the reliability of the data centers. This low hanging fruit can be realized quite easily using AUDIT- BUDDY Delta- T Package while reducing the carbon footprint of the Data Center. Summary AUDIT- BUDDY offers an economical way to measure ΔT Server throughout the Data Center taking in to account variations on the server load throughout the day. It is accurate, measures true air temperature and best of all is portable. It may be moved from rack to rack as the dynamics of the Data Center change. Powered by 3 AA alkaline batteries, AUDIT- BUDDY can be installed in minutes and requires little back- end management. It can be used on demand, and stored when not needed. The system imposes no demands on the existing infrastructure and may be deployed throughout the Data Center floor as required. This inexpensive tool will allow the Facility Engineer to manage the Data Center more efficiently and reduce Operational Expense by establishing better cooling strategies without putting the servers at risk. About Purkay Labs Founded in 2012, Purkay Labs specializes in temperature and humidity monitoring devices. Our flagship product AUDIT- BUDDY is a revolutionary standalone monitor that measures free air in the white space. Use this inexpensive tool to spot check air quality, measure non- BAS covered zones, prove SLA and generate real- time CFD. Make data- driven decisions with AUDIT- BUDDY to control energy costs and increase operational efficiency. Ideal for telecom closet, server room, colo and mission critical facilities. AUDIT- BUDDY is designed with the simplicity and portability in mind. We proudly provide personalized and knowledgeable customer service for our products. Additional information is available at or by at info@purkaylabs.com. Page 9

Introducing AUDIT-BUDDY

Introducing AUDIT-BUDDY Introducing AUDIT-BUDDY Optimize the Data Center with AUDIT-BUDDY Executive Summary Proper temperature and humidity for the inlet air into the servers is essential to efficient data center operation. Several

More information

Introducing AUDIT- BUDDY

Introducing AUDIT- BUDDY Introducing AUDIT- BUDDY Monitoring Temperature and Humidity for Greater Data Center Efficiency 202 Worcester Street, Unit 5, North Grafton, MA 01536 www.purkaylabs.com info@purkaylabs.com 1.774.261.4444

More information

How To Improve Energy Efficiency Through Raising Inlet Temperatures

How To Improve Energy Efficiency Through Raising Inlet Temperatures Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD

More information

Managing Data Centre Heat Issues

Managing Data Centre Heat Issues Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design

More information

Environmental Data Center Management and Monitoring

Environmental Data Center Management and Monitoring 2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

Data center upgrade proposal. (phase one)

Data center upgrade proposal. (phase one) Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The

More information

Improving Data Center Energy Efficiency Through Environmental Optimization

Improving Data Center Energy Efficiency Through Environmental Optimization Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

Benefits of Cold Aisle Containment During Cooling Failure

Benefits of Cold Aisle Containment During Cooling Failure Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business

More information

Great Lakes Data Room Case Study

Great Lakes Data Room Case Study Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200

More information

Airflow Simulation Solves Data Centre Cooling Problem

Airflow Simulation Solves Data Centre Cooling Problem Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length

More information

Data Centers: How Does It Affect My Building s Energy Use and What Can I Do?

Data Centers: How Does It Affect My Building s Energy Use and What Can I Do? Data Centers: How Does It Affect My Building s Energy Use and What Can I Do? 1 Thank you for attending today s session! Please let us know your name and/or location when you sign in We ask everyone to

More information

How To Improve Energy Efficiency In A Data Center

How To Improve Energy Efficiency In A Data Center Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

Reducing the Annual Cost of a Telecommunications Data Center

Reducing the Annual Cost of a Telecommunications Data Center Applied Math Modeling White Paper Reducing the Annual Cost of a Telecommunications Data Center By Paul Bemis and Liz Marshall, Applied Math Modeling Inc., Concord, NH March, 2011 Introduction The facilities

More information

Data Center Power Consumption

Data Center Power Consumption Data Center Power Consumption A new look at a growing problem Fact - Data center power density up 10x in the last 10 years 2.1 kw/rack (1992); 14 kw/rack (2007) Racks are not fully populated due to power/cooling

More information

Choosing Close-Coupled IT Cooling Solutions

Choosing Close-Coupled IT Cooling Solutions W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of

More information

Benefits of. Air Flow Management. Data Center

Benefits of. Air Flow Management. Data Center Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment

More information

Utilizing Temperature Monitoring to Increase Datacenter Cooling Efficiency

Utilizing Temperature Monitoring to Increase Datacenter Cooling Efficiency WHITE PAPER Utilizing Temperature Monitoring to Increase Datacenter Cooling Efficiency 20A Dunklee Road Bow, NH 03304 USA 2007. All rights reserved. Sensatronics is a registered trademark of. 1 Abstract

More information

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment

More information

How Row-based Data Center Cooling Works

How Row-based Data Center Cooling Works How Row-based Data Center Cooling Works White Paper 208 Revision 0 by Paul Lin and Victor Avelar Executive summary Row-based data center cooling is normally regarded as a cold air supply architecture that

More information

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.

More information

Using CFD for optimal thermal management and cooling design in data centers

Using CFD for optimal thermal management and cooling design in data centers www.siemens.com/datacenters Using CFD for optimal thermal management and cooling design in data centers Introduction As the power density of IT equipment within a rack increases and energy costs rise,

More information

Saving energy in the Brookhaven National Laboratory Computing Center: Cold aisle containment implementation and computational fluid dynamics modeling

Saving energy in the Brookhaven National Laboratory Computing Center: Cold aisle containment implementation and computational fluid dynamics modeling Saving energy in the Brookhaven National Laboratory Computing Center: Cold aisle containment implementation and computational fluid dynamics modeling Student Intern Earth and Environmental Engineering,

More information

Data Center Components Overview

Data Center Components Overview Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room

More information

How To Run A Data Center Efficiently

How To Run A Data Center Efficiently A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly

More information

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200

More information

Effect of Rack Server Population on Temperatures in Data Centers

Effect of Rack Server Population on Temperatures in Data Centers Effect of Rack Server Population on Temperatures in Data Centers Rajat Ghosh, Vikneshan Sundaralingam, Yogendra Joshi G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology, Atlanta,

More information

Using Simulation to Improve Data Center Efficiency

Using Simulation to Improve Data Center Efficiency A WHITE PAPER FROM FUTURE FACILITIES INCORPORATED Using Simulation to Improve Data Center Efficiency Cooling Path Management for maximizing cooling system efficiency without sacrificing equipment resilience

More information

Using Simulation to Improve Data Center Efficiency

Using Simulation to Improve Data Center Efficiency A WHITE PAPER FROM FUTURE FACILITIES INCORPORATED Using Simulation to Improve Data Center Efficiency Cooling Path Management for maximizing cooling system efficiency without sacrificing equipment resilience

More information

BRUNS-PAK Presents MARK S. EVANKO, Principal

BRUNS-PAK Presents MARK S. EVANKO, Principal BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations

More information

Server Room Thermal Assessment

Server Room Thermal Assessment PREPARED FOR CUSTOMER Server Room Thermal Assessment Analysis of Server Room COMMERCIAL IN CONFIDENCE MAY 2011 Contents 1 Document Information... 3 2 Executive Summary... 4 2.1 Recommendation Summary...

More information

Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems

Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems NER Data Corporation White Paper Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems Introduction Data centers are

More information

Introducing Computational Fluid Dynamics Virtual Facility 6SigmaDC

Introducing Computational Fluid Dynamics Virtual Facility 6SigmaDC IT Infrastructure Services Ltd Holborn Gate, 330 High Holborn, London, WC1V 7QT Telephone: +44 (0)20 7849 6848 Fax: +44 (0)20 7203 6701 Email: info@itisltd.co.uk www.itisltd.com Introducing Computational

More information

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

Managing Cooling Capacity & Redundancy In Data Centers Today

Managing Cooling Capacity & Redundancy In Data Centers Today Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw

More information

Data Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015

Data Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015 Data Center Cooling & Air Flow Management Arnold Murphy, CDCEP, CDCAP March 3, 2015 Strategic Clean Technology Inc Focus on improving cooling and air flow management to achieve energy cost savings and

More information

The New Data Center Cooling Paradigm The Tiered Approach

The New Data Center Cooling Paradigm The Tiered Approach Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,

More information

5 Reasons. Environment Sensors are used in all Modern Data Centers

5 Reasons. Environment Sensors are used in all Modern Data Centers 5 Reasons Environment Sensors are used in all Modern Data Centers TABLE OF CONTENTS 5 Reasons Environmental Sensors are used in all Modern Data Centers Save on Cooling by Confidently Raising Data Center

More information

Improve competiveness of IDC and enterprise data centers with DCIM

Improve competiveness of IDC and enterprise data centers with DCIM Improve competiveness of IDC and enterprise data centers with DCIM This paper studies the implementation of modern DCIM systems for data centers to improve operational competitiveness with ATEN's DCIM

More information

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue

More information

Prediction Is Better Than Cure CFD Simulation For Data Center Operation.

Prediction Is Better Than Cure CFD Simulation For Data Center Operation. Prediction Is Better Than Cure CFD Simulation For Data Center Operation. This paper was written to support/reflect a seminar presented at ASHRAE Winter meeting 2014, January 21 st, by, Future Facilities.

More information

An Introduction to Cold Aisle Containment Systems in the Data Centre

An Introduction to Cold Aisle Containment Systems in the Data Centre An Introduction to Cold Aisle Containment Systems in the Data Centre White Paper October 2010 By Zac Potts MEng Mechanical Engineer Sudlows October 2010 An Introduction to Cold Aisle Containment Systems

More information

HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE

HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE Best practices for airflow management and cooling optimisation AIRFLOW MANAGEMENT COLD AND HOT AISLE CONTAINMENT DC ASSESSMENT SERVICES Achieving true 24/7/365

More information

Greening Commercial Data Centres

Greening Commercial Data Centres Greening Commercial Data Centres Fresh air cooling giving a PUE of 1.2 in a colocation environment Greater efficiency and greater resilience Adjustable Overhead Supply allows variation in rack cooling

More information

Center Thermal Management Can Live Together

Center Thermal Management Can Live Together Network Management age e and Data Center Thermal Management Can Live Together Ian Seaton Chatsworth Products, Inc. Benefits of Hot Air Isolation 1. Eliminates reliance on thermostat 2. Eliminates hot spots

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical

More information

Energy Efficiency and Availability Management in Consolidated Data Centers

Energy Efficiency and Availability Management in Consolidated Data Centers Energy Efficiency and Availability Management in Consolidated Data Centers Abstract The Federal Data Center Consolidation Initiative (FDCCI) was driven by the recognition that growth in the number of Federal

More information

Thermal Optimisation in the Data Centre

Thermal Optimisation in the Data Centre Thermal Optimisation in the Data Centre Best Practices for achieving optimal cooling performance and significant energy savings in your data centre 1. Thermal analysis 2. Cold-Aisle-Containment 3. Seal

More information

Best Practices for Wire-free Environmental Monitoring in the Data Center

Best Practices for Wire-free Environmental Monitoring in the Data Center White Paper Best Practices for Wire-free Environmental Monitoring in the Data Center April 2012 Introduction Monitoring for environmental threats in the data center is not a new concept. Since the beginning

More information

Energy Performance Optimization of Server Room HVAC System

Energy Performance Optimization of Server Room HVAC System International Journal of Thermal Technologies E-ISSN 2277 4114 2 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Manoj Jadhav * and Pramod Chaudhari Department

More information

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack

More information

Data centers have been cooled for many years by delivering

Data centers have been cooled for many years by delivering The Increasing Challenge of Data Center Design and Management: Is CFD a Must? Mark Seymour, Christopher Aldham, Matthew Warner, Hassan Moezzi Future Facilities, San Jose, California, USA Mark Seymour,

More information

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling

More information

White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010

White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010 White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence

More information

Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers

Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 techsupport@chatsworth.com www.chatsworth.com All products

More information

Re Engineering to a "Green" Data Center, with Measurable ROI

Re Engineering to a Green Data Center, with Measurable ROI Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

How to Build a Data Centre Cooling Budget. Ian Cathcart

How to Build a Data Centre Cooling Budget. Ian Cathcart How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options

More information

Colocation and Cloud Hosting Solutions. Build a strong and efficient physical infrastructure that delivers service reliability and profitability

Colocation and Cloud Hosting Solutions. Build a strong and efficient physical infrastructure that delivers service reliability and profitability Colocation and Cloud Hosting Solutions Build a strong and efficient physical infrastructure that delivers service reliability and profitability 2 Dependability and Deployment Speed that Improves Your Bottom

More information

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015 I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 8, Loughborough University, 29 th June 2015 Topics to be considered 1. Progress on project tasks 2. Development of data centre test facility

More information

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room

More information

Recovering Stranded Capacity in the Data Center. Greg Bell Driving e-research Across the Pacific `09 Sydney: 11/13/09

Recovering Stranded Capacity in the Data Center. Greg Bell Driving e-research Across the Pacific `09 Sydney: 11/13/09 Recovering Stranded Capacity in the Data Center Greg Bell Driving e-research Across the Pacific `09 Sydney: 11/13/09 2 Recovering Stranded Data Center Capacity most data centers are overcooled & inefficient

More information

DataCenter 2020: first results for energy-optimization at existing data centers

DataCenter 2020: first results for energy-optimization at existing data centers DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction

More information

Improving Rack Cooling Performance Using Airflow Management Blanking Panels

Improving Rack Cooling Performance Using Airflow Management Blanking Panels Improving Rack Cooling Performance Using Airflow Management Blanking Panels White Paper 44 Revision 4 by Neil Rasmussen > Executive summary Unused vertical space in open frame racks and rack enclosures

More information

Rack Hygiene. Data Center White Paper. Executive Summary

Rack Hygiene. Data Center White Paper. Executive Summary Data Center White Paper Rack Hygiene April 14, 2011 Ed Eacueo Data Center Manager Executive Summary This paper describes the concept of Rack Hygiene, which positions the rack as an airflow management device,

More information

Rack Blanking Panels To Fill or Not to Fill

Rack Blanking Panels To Fill or Not to Fill Rack Blanking Panels To Fill or Not to Fill A Dell Technical White Paper Dell Data Center Infrastructure David L. Moss Joyce F. Ruff Learn more at Dell.com/PowerEdge/Rack THIS WHITE PAPER IS FOR INFORMATIONAL

More information

The Benefits of Supply Air Temperature Control in the Data Centre

The Benefits of Supply Air Temperature Control in the Data Centre Executive Summary: Controlling the temperature in a data centre is critical to achieving maximum uptime and efficiency, but is it being controlled in the correct place? Whilst data centre layouts have

More information

Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential

Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential TECHNICAL REPORT Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. +1.888.982.7800 upsite.com

More information

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no

More information

Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs

Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs WHITE PAPER Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs By Lars Strong, P.E., Upsite Technologies, Inc. 505.798.000 upsite.com Reducing Room-Level

More information

Data Center Cooling. 1-800-693-0351 www.dpstele.com. A guide from: Your partners in UPS Monitoring Systems

Data Center Cooling. 1-800-693-0351 www.dpstele.com. A guide from: Your partners in UPS Monitoring Systems Data Center Cooling A guide from: Your partners in UPS Monitoring Systems The air in your server room, especially nearest the processors in your equipment, will rise to dangerous temperatures quickly if

More information

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

Raising Inlet Temperatures in the Data Centre

Raising Inlet Temperatures in the Data Centre Raising Inlet Temperatures in the Data Centre White paper of a round table debate by industry experts on this key topic. Hosted by Keysource with participants including the Uptime Institute. Sophistication

More information

Improving Rack Cooling Performance Using Airflow Management Blanking Panels

Improving Rack Cooling Performance Using Airflow Management Blanking Panels Improving Rack Cooling Performance Using Airflow Management Blanking Panels By Neil Rasmussen White Paper #44 Revision 3 Executive Summary Unused vertical space in open frame racks and rack enclosures

More information

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich

More information

FNT EXPERT PAPER. // Data Center Efficiency AUTHOR. Using CFD to Optimize Cooling in Design and Operation. www.fntsoftware.com

FNT EXPERT PAPER. // Data Center Efficiency AUTHOR. Using CFD to Optimize Cooling in Design and Operation. www.fntsoftware.com FNT EXPERT PAPER AUTHOR Oliver Lindner Head of Business Line DCIM FNT GmbH // Data Center Efficiency Using CFD to Optimize Cooling in Design and Operation Energy is the biggest cost factor with the highest

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Best Practices for Wire-free Environmental Monitoring in the Data Center

Best Practices for Wire-free Environmental Monitoring in the Data Center White Paper 11800 Ridge Parkway Broomfiled, CO 80021 1-800-638-2638 http://www.42u.com sales@42u.com Best Practices for Wire-free Environmental Monitoring in the Data Center Introduction Monitoring for

More information

Cheat Sheets to Data Center Infrastructure Management

Cheat Sheets to Data Center Infrastructure Management ^ Business-wise, Future-drivenTM Cheat Sheets to Data Center Infrastructure Management The Brands You Trust. Table of Contents Introduction...3 How DCIM helps operations...4 How DCIM helps planning...5

More information

Data Center Energy Consumption

Data Center Energy Consumption Data Center Energy Consumption The digital revolution is here, and data is taking over. Human existence is being condensed, chronicled, and calculated, one bit at a time, in our servers and tapes. From

More information

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,

More information

Speaker: John Peterson Time: April 4, 2014, 9:45-10:45 a.m. Venue: Crystal 1-2. Data Center Design and Commissioning

Speaker: John Peterson Time: April 4, 2014, 9:45-10:45 a.m. Venue: Crystal 1-2. Data Center Design and Commissioning Speaker: John Peterson Time: April 4, 2014, 9:45-10:45 a.m. Venue: Crystal 1-2 Data Center Design and Commissioning High enterprise relevancy for addressing space, power, and cooling, as well as costs

More information

Energy Management Services

Energy Management Services February, 2012 Energy Management Services Data centers & IT environments are often critical to today s businesses, directly affecting operations and profitability. General & Mechanical Services has the

More information

HPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.)

HPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.) HPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.) Felipe Visbal / March 27, 2013 HPPR Data Center Technologies Team Services Data Centers: Thermal Assessments

More information

APC APPLICATION NOTE #92

APC APPLICATION NOTE #92 #92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center

More information

Statement Of Work. Data Center Power and Cooling Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary

Statement Of Work. Data Center Power and Cooling Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary Statement Of Work Professional Services Data Center Power and Cooling Assessment Data Center Power and Cooling Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features

More information

Unified Physical Infrastructure (UPI) Strategies for Thermal Management

Unified Physical Infrastructure (UPI) Strategies for Thermal Management Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting

More information

How High Temperature Data Centers and Intel Technologies Decrease Operating Costs

How High Temperature Data Centers and Intel Technologies Decrease Operating Costs Intel Intelligent Management How High Temperature Data Centers and Intel Technologies Decrease Operating Costs and cooling savings through the use of Intel s Platforms and Intelligent Management features

More information

Specialty Environment Design Mission Critical Facilities

Specialty Environment Design Mission Critical Facilities Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,

More information

FAC 2.1: Data Center Cooling Simulation. Jacob Harris, Application Engineer Yue Ma, Senior Product Manager

FAC 2.1: Data Center Cooling Simulation. Jacob Harris, Application Engineer Yue Ma, Senior Product Manager FAC 2.1: Data Center Cooling Simulation Jacob Harris, Application Engineer Yue Ma, Senior Product Manager FAC 2.1: Data Center Cooling Simulation Computational Fluid Dynamics (CFD) can be used to numerically

More information

Office of the Government Chief Information Officer. Green Data Centre Practices

Office of the Government Chief Information Officer. Green Data Centre Practices Office of the Government Chief Information Officer Green Data Centre Practices Version : 2.0 April 2013 The Government of the Hong Kong Special Administrative Region The contents of this document remain

More information

Data Center Energy Profiler Questions Checklist

Data Center Energy Profiler Questions Checklist Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space

More information

DOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers

DOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers DOE FEMP First Thursday Seminar Achieving Energy Efficient Data Centers with New ASHRAE Thermal Guidelines Learner Guide Core Competency Areas Addressed in the Training Energy/Sustainability Managers and

More information

Reducing Data Center Energy Consumption

Reducing Data Center Energy Consumption Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate

More information