Northwestern University Information Technology Building Infrastructure Requirements for Communication Facilities ( January 2010)

Size: px
Start display at page:

Download "Northwestern University Information Technology Building Infrastructure Requirements for Communication Facilities ( January 2010)"

Transcription

1 Northwestern University Information Technology Building Infrastructure Requirements for Communication Facilities ( January 2010) I. Introduction This document presents the current Northwestern University standards for communications wiring. They are intended for use in locations where Students, Staff and Faculty are located. These proprietary specifications are provided to in planning spaces, budgeting for communications infrastructure, and as the technical description suitable for use in Requests for Proposal. These specifications used in conjunction with published current TIA standards, present a communications wiring system, which will anticipate technological developments over the next several years. As technology changes, this document will be reviewed annually so as to remain the most current and effective information available. Any aspects of communications wiring, which are not sufficiently addressed in this document, shall be brought to the attention of Northwestern University Information Technology. Steps will be taken to remedy omissions in a timely manner. II. General Communications Cabling NUIT shall provide specific location and placement for all Communications Cabling. 1. Any penetration of rated construction shall not change the rating of the construction system. 2. Space planners and designers should plan for the inclusion of one standard communications outlet for every 75 net square feet. Erring on high side has proven beneficial to the University. 3. Intra building communications cabling shall be provided, connecting the building Intermediate Distribution Frame (IDF), located in the Main Building Telecommunications Room to the outlets servicing the communications equipment located throughout the building. The intra building cabling system includes the building IDF, the house cables (HSE) which are also known as the riser cables, the local house cables (LHSE) which interconnect Telecommunications Rooms or terminals, and the wiring between any of the above locations to the communications outlets which is known as station or horizontal wiring. 4. Underground entry. The building point of entry for underground communication cables shall be located in a room of at least 100 square feet located on the lower or basement

2 floor of the building. Incoming communications cables shall be terminated in this room according to the type of cable and the appropriate communication/electrical standards and codes. a. Underground fiber optic cables shall be Corning ALTOS (dryblock) cable. Fiber optic entrance cable will be terminated in a rack mounted Corning CCH 04U fiber optic distribution panel. Each building shall have a minimum of 48 strands of singlemode fiber terminating on LC connectors. A green stranded #12 AWG will follow all Fiber Optic paths for the entire length of the cable. NUIT will determine the actual required fiber optic count based on the intended use and square footage of the building. b. Underground Copper Cables will be installed in the Building Telecommunications Room on Standard 110 blocks attached to the fireproof plywood backboard. A minimum of 100 pair PE 89 cable is required for any building. NUIT Telecom & Network Services will consult with the FM Project Manager concerning exact cable sizes and origination and termination for the new cable. c. Entrance Pathway shall be installed for all new facilities and in cases where the entrance room is being relocated. A minimum of 3 trade size, schedule 40 4 ducts shall be installed. The actual number installed during the constructuion ahall be the actual number necessary (minimum 1 for copper and 1 for fiber) plus 1 duct for growth. Entrance path conduits shall be adjoined to the conduit system in the immediate area of the facility. 5. Riser system. The building entry point shall be aligned vertically under the individual floor Telecommunications Rooms wherever possible in order to provide a cable riser system that will enable easy access to each floor. Riser conduit or sleeves must be a minimum of 4" in diameter, and there must be one empty spare sleeve between each floor of a building at the time of building turnover for future expansion. If the horizontal station runs from the Telecommunications Room to the individual outlet exceed 290 cable feet, a second basement IDF and riser system is necessary. If the second riser is employed, there must be a minimum of one 4" conduit installed between the two IDFs and one 12" cable tray system interconnecting the Telecommunications Rooms on each floor. In buildings with more than one Telecommunications Room per floor, Northwestern University Information Technology Telecommunications shall specify which room outlets will be served from which Telecommunications Room. The default shall be the nearest Telecommunications room.. 6. Fiber optic riser cables. Fiber optic riser cables shall be installed in all new and renovated buildings. Page: 2 Northwestern University Information Technology issued: JULY 2009

3 a. The fiber optic cable shall be a minimum of 24 strands of Corning singlemode fiber are installed to each floor's Telecommunications Room from the Building Telecommunications Room. All fiber installed are Corning Cable Systems "MIC" p/n 024E for riser and indoor use. NUIT will determine the actual required fiber optic count based on the square footage and use of the area served by the floor telecommunications room. b. All fiber optic underground and riser cables shall be terminated at the Main Building Telecommunications Room utilizing Corning CCH 04U fiber optic patching panel with LC connectors for singlemode fiber. c. The fiber optic house cable system shall be terminated at the Telecommunications Room with a Corning CCH 04P enclosure. The CCH 04P enclosure shall be equipped with an appropriate number of CCH CP24 A9 connector panels. 7. Recycling of Abandoned Cable. Unused, undocumented and otherwise abandoned cables, SHALL be removed and recycled prior to the completion of the project. NUIT Telecom & Network Services is available to assist in the identification of these cables. Certification of removal and recycling can be obtained at no charge by coordinating with DuPont Abandoned Cable FUELOAD ( ). The definition of Abandoned Cable is contained in NEC 2002 Articles: 640, 645, 725, 760, 770, 800, 810, 820 and 830. Further definition is contained in NFPA 75, NFPA 76 and NFPA 90A. III. IV VoIP preparation. Voice communications for all new buildings, and renovated spaces that NUIT has upgraded and deemed by publication VoIP ready, shall only receive VoIP services. A minimum of one jack in each work space shall be prepared for VoIP voice communications. This preparation consists of a POE (power over Ethernet) port activation for each instance. Newly established or relocated telecommunications rooms shall be equipped with a sufficiently sized Uninterrupted Power Supply (UPS) including batteries for a two hour emergency run time. NUIT TNS (Field Operations) shall assist in the sizing and specification of this device. Telecommunications Rooms The Telecommunications Room located on each floor of a building is the transition point between the vertical and the horizontal communications cable distribution pathways. Each Telecommunications Room must be capable of housing equipment including active network electronic components, uninterruptable power supply and batteries, copper, coaxial and fiber optic terminations as well as associated cross connection wiring. Telecommunications Room space must be determined as early as possible in the design of new and renovated buildings. Telecommunications Rooms must be dedicated to the Page: 3 Northwestern University Information Technology issued: JULY 2009

4 communications function. Because of the sensitive nature of communications equipment that is housed in these areas, shared use of Telecommunications Rooms, is not allowed. 1. In the planning of Telecommunications Room space, each shall have three walls covered with 3/4" fire retardant plywood (painted white), a minimum of two Panduit #CMR19X84 communications racks mounted 36" from the wall, equipped with 12" cable raceway both across the racks to the riser sleeve wall and to the cable entrance/egress for the room. Both sides of each rack installed, shall have Panduit part # WMPVHDF45E (6") vertical wire managers attached. NUIT shall approve the design and execution of all Telecommunications rooms. 1. A single Telecommunications Room may serve three or more floors of a typical building providing the following parameters and factors are met: a. The size of the Telecommunications Room is at least 100 square feet. b. The dead weight floor loading exceeds 150 pounds per square foot. c. There is adequate 24 X 365 cooling and ventilation. Typically, 17,000 btu s per hour will be introduced into the space and must be kept at in a temperature range of 70 o 78 o f.non condensing. d. No telecommunications cable length being served from the room is in excess of 290 feet. e. The Telecommunications Room is located near the core (center) of the building f. The Telecommunications room is located and accessible from a public hallway. If the building has only a basement and up to three additional floors with a total area less than 15,000 square feet, and the furthest outlet is less than 290 cable feet from the Building Telecommunications Room, then the building Telecommunications Room may be used as the communication room for the entire building. NUIT TNS is available to consult with building designers to collapse Building Backbone infrastructure wherever possible. 3. Based upon the planning figure of one workstation / standard communications outlet per 75 sq. ft., the general rule for sizing individual Telecommunications Rooms is: a. Floor area under 5,000 sq. ft. Telecommunications Room size 10' by 8' b. Floor area up to 10,000 sq. ft. Telecommunications Room size 10' by 10' c. Floor area under 15,000 sq. ft. Telecommunications Room size 10' by 16' The dimensions of the Telecommunications Room may be adjusted within practical limits. No single dimension shall be reduced to less than eight feet. Thus, a 10' by 11' Telecommunications Room could be revised to 8' by 14'. Page: 4 Northwestern University Information Technology issued: JULY 2009

5 In no circumstance, shall a Telecommunications Room be smaller than 6' X 8'. Copper Riser Cable termination points located in the Telecommunications Rooms will be mounted on the plywood backboards using Standard 110 style hardware. 110 termination blocks will be mounted in vertical columns. If more than four blocks are required, a second column will be started. Metal or plastic rings or posts will be provided as an aid to the installation of jumper wire. Fiber optic terminations will be attached to installed Panduit frames as required. Fiber will be terminated on Corning CCH04U hardware, using CCH CP24 A9 panels and LC compatible connectors for singlemode fiber. Coaxial Cable terminations and connections will be dressed to the plywood backboard. 5. Lighting in each Telecommunications Room must be a minimum of 60 foot candles measured 3' above the finished floor and mounted as strip lights along the long walls at an 8 minimum above the finished floor. A false ceiling shall not be installed. 6. The access door to each Telecommunications Room must be a minimum of 36" wide and 84" high, without doorsill and hinged to open outward or slide side to side. The door must be equipped with a Marlok electronic key locking device coded to NUIT space. 7. All floors, walls and ceiling surfaces must be treated to eliminate dust. Finishes shall be White to enhance room lighting. Each Telecommunications room shall be equipped with a minimum of one 20A 110v circuit, equipped with one quad outlet, one L5 20 R twistlock, and one 208v L6 30 R twistlock. When possible all circuits shall be on a generator fed EM circuit. These power outlets shall be placed at 18 a.f.f. and located just behind the equipment rack. Nominal convenience outlets should be distributed throughout the room. Access shall be made available to the main building ground bus bar. 8. In Buildings where water flow Fire protection is required, Sprinkler heads must be equipped with wire cages in order to prevent accidental operation. Water charged Sprinkler heads shall not have a trip rating less than 210 o F 9. A positive air pressure shall be maintained in the Telecommunications Room, when active electronics are present, consideration must be given to providing a sufficient number of air changes to dissipate heat generated in the Telecommunications Room and maintain temperatures equal to adjacent office areas. Temperature and Humidity ranges shall not exceed a range of +70 o through +78 o F non condensing Typically, 17,000 btu s per hour will be introduced into the space. Page: 5 Northwestern University Information Technology issued: JULY 2009

6 10. Based on square footage of the closet and number of network ports to be served from a communications room, NUIT shall provide an estimate of the actual heat load based on building programming documents.. Page: 6 Northwestern University Information Technology issued: JULY 2009

7 Page: 7 Northwestern University Information Technology issued: JULY 2009

8 Telecommunications room Rack Layout RS 1 Corning CCH 04U Corning CCH 04U (as necessary) 12 Owner Provided Equipment Owner Provided Equipment 24 Panduit WMPVHCF45E Panduit WMPVHCF45E Owner Provided Equipment Owner Provided Equipment Owner Provided Equipment Owner Provided Equipment Panduit WMPVHCF45E Owner Provided Equipment Owner Provided Equipment 36 Owner Provided Equipment Area Left Blank 46 Panduit CMR19X84 Panduit CMR19X84 Page: 8 Northwestern University Information Technology issued: JULY 2009

9 V Fiber Optics Each new building is required to have a minimum of 48 strands 8.3/125 Singlemode fiber, Corning Altos/Freedm p/n 024RS A20 entering the Building Telecommunications Room. The beginning of this entrance fiber run is from the next regional routing and switching site on Campus. Telecom and Network Services will provide information on the exact location of any particular site as well as known cable routing. On the inside of each building, a minimum of 24 strands of Corning Singlemode p/n 048E Fiber Optic cable are installed to each floor s Telecommunications Room from the Building Telecommunications room. This riser cable is Corning MIC riser rated 24 strand part number 024E When multiple Telecommunications Rooms are used on a floor, a minimum of 24 strands of singlemode tie each Telecommunications Room together. NUIT TNS will define all fiber counts and placement during the design phase of all projects All single mode fiber is terminated on LC compatible connectors. In the Telecommunications Room system Fiber distribution id achieved using Corning Cable Systems "CCH 04U" housings mounted on the equipment side of the floor mounted racks. Single mode terminations will be completed on CCH CP24 A9 panels Inner duct (aka ENT pipe) is NOT used inside of buildings at Northwestern University. Testing Each strand of fiber must be tested both with a Power Meter and with an OTDR. All test equipment must have been certified in the past 12 months. Attenuation losses from the chart below are considered acceptable performance standards. All tests will be conducted in the modes described below. Single mode 8.3/125 Each connector.4db 1300nm light.51db / km 1550nm light.4db / km for runs under 500 feet a 1.3 db 1550nm is acceptable Testing shall be completed with both a certified power meter operating at the specified frequencies and a certified OTDR. OTDR traces shall be conducted from both directions. The data will be organized for presentation as follows: Name:Strand 1 from A to B, then immediately following: Strand 1 from B to A. Page: 9 Northwestern University Information Technology issued: JULY 2009

10 A test document will be devised in Microsoft Excel in the following format: Location A Location B Strand Loss@1300nm Loss@1550nm Length of Cable Size of Cable Cable tests will only be accepted on CD s or DVD s professionally and permanently labeled with the project name, test area covered, test date and contractor name. Certification of the test devices shall accompany all test results Labeling Refer to Section VIII. Specifications Refer to Corning Cable Systems specification for all additional fiber information. VI. Communications Outlet Graphics A minimum of one Northwestern University Standard Communications Outlet or Service Jack shall be installed at each client workstation or office. This outlet consists of three high speed module inserts (currently denoted by yellow color). This configuration is always installed in a two gang faceplate allowing for additional modules. Depending on the actual needs of any individual space, faceplates may be purchased in the two gang configuration with two to ten openings for inserts. Each module represents a unique four pair cable from the outlet to the Telecommunications Room. Installation of multiple services on any four pair cable is prohibited. Symbol Jack on Wall JJJ The architectural symbol for this outlet is: To add two more jacks at the same place on the wall would be depicted as: Symbol 5 Jack on Wall JJJ JJ Page: 10 Northwestern University Information Technology issued: JULY 2009

11 Other applicable symbols are as follows: W Wall mounted telephone: (48" above finished floor) F Floor Mounted Service Outlet: C Ceiling Mounted Service Outlet Jack ID Labeling Designers of new and remodeled spaces shall designate each communications outlet on the construction documents with a unique number. Refer to section VIII for labeling details. Northwestern University adheres to a modified version of the TIA standard 606 for jack nomenclature. To achieve this with a reasonable amount of clarity, each Communications Outlet beginning at the entrance to a particular room and moving in a clockwise manner will be designated as follows: Room Number, Module number. So the first Standard Communications Outlet in room 101 is designated: 101 1, and The wall phone clockwise from that outlet is designated: And the next Standard Communications Outlet is designated: 101 5, and The identification of the type of wire being used is done through the color of the insert (yellow for Category 5E.) Each of the wires is always a four pair wire, therefore covering the issues in the 606 standard relating to the number of wire pairs. VII. Horizontal Wiring Systems, Devices, Testing and Part Numbers Coaxial Cabling At times, based on customer requests, coaxial cable for Cable TV may be installed as part of horizontal cabling. This wiring will be installed within the Panduit MiniCom jack system and Page: 11 Northwestern University Information Technology issued: JULY 2009

12 raceways detailed below. Further details concerning coaxial cable are found in the section IX labeled "RF Television (CATV) Distribution". Each office and/or workstation in a building is to be wired with a minimum of one Standard Communications Outlet. Laboratories and other large open areas shall be wired with a minimum of one Standard Communications Outlet for each workstation. Applicable city electrical codes and building codes must be followed for installation of all communication facilities. Care shall be taken to allow for adequate cabling facilities in areas of planned expansion. Adjustments may be made based upon the specific applications or use of a given space. The entire horizontal cabling system must exceed the TIA 568B wiring standards. Wireless Access Points New construction and major renovations must include ubiquitous wireless coverage. A request should be made early in the design process for NUIT engineers to access the space and the proposed usage to determine wireless requirements for the project. The contractor shall install, terminate and test a single wire Category 5E jack. This jack shall be located; 1) just above a suspended ceiling 2) in a shallow 2 gang junction box of a hard ceiling and designated by the architect with a C adjacent to the standard triangle depicting a communications outlet. NUIT will install the Wireless Access Point and activate the switch port. No Horizontal Communications Cable shall exceed 90 meters or 290 feet. At the current time, Optical Fiber Cables are NOT being installed as a standard part of horizontal cabling. 10 Gigabit per second Cabling Systems Recent advances in technology now allow copper cabling to perform at data speeds of 10 gigabits per second. These systems are commonly known as Category 6A systems. These systems are best installed for use in: Server Rooms and Research Cluster Computing Centers. These systems are best installed where all jack outlets are in patch panels both at the computing equipment and at the network equipment. Category 6A Cabling Systems shall be installed with the strictest conformance to ANSI/TIA 568 B.2 ad10 (Augmented Category 6) the minimum trade size conduit for use in these systems is 1 ¼ Nominal cable diameter is.295. It is important in a 6A system that the entire system is provided by a single manufacturer. NUIT has chosen Blue as the color code for Category 6A assemblies. Blue Belden part number 10GX32006 bonded pair Cable, Blue Belden AX Jacks and Black Belden AX RU Patch Panels shall be used in all Category 6A applications at Northwestern University. Cables shall be loosely bundled in groups of no more than 12 cables. Testing shall be in accordance with ANSI/TIA 568 B.2 ad10 specifications including alien crosstalk. A minimum of 5 cables will be tested for alien crosstalk from each bundle of cables. These tests shall be on the 5 longest length cables that are adjacent on the patch panel. The contractor may wish to use the following 3 tools in the installation: Connecting/Insertion Tool AX100749, Termination Station AX101852, and the Release Tool AX Page: 12 Northwestern University Information Technology issued: JULY 2009

13 1. Horizontal distribution of communication cables on each floor shall be supported in a minimum of 12" wide fully supported cable tray. This tray must originate from the individual floor Telecommunications Room and provide continuous support to all rooms on that floor. There must be a minimum of 12" clearance between all communication cable trays and any fluorescent light fixtures or other electrical ballasts. 2. Conduit shall be provided from the cable tray system to each communication outlet location. This conduit must be a minimum of 3/4" in diameter unless Category 6A cabling is used (see 10 Gigabit per second Cabling Systems, above). A maximum of two 90 degree bends are allowed in a conduit run before a pull box is required. Conduit bends must be no less than 6 inch radius of curvature. Up to three communication outlets may be served from a single conduit run providing the conduit meets the following sizing criteria: a. One outlet 3/4" minimum diameter b. Two outlets downstream 1 " minimum diameter c. Three outlets downstream 1 1/4" minimum diameter Standard Communication Outlet. Each communication outlet shall be equipped with an 11b electrical box. The 11b boxes must be installed oriented vertically 18" above the finished floor and fitted with double duplex plaster rings and an appropriate cover plate. Other mounting heights may be required for specific applications. In cases where Communications Facilities must be flush mounted in a floor, Thomas and Betts model 665 SC (UPC ) is recommended due to its superior space for bend radius. The Thomas and Betts 664 (UPC S ) are adequate for installations when only a single gang of communications and power is specified. The"KI" (Krueger Industries) power up device shall be used for Communications and Power in applications where Telecommunications is necessary in desktops. Panduit "Minicom" series CJ5E88GYL inserts will be installed in the Powerups. This product is NOT a definition of furniture products, but specifically, Telecommunication installations. 3. Station wiring is most generally PVC jacketed cable. Standard wiring to each communication outlet will be three 4 pair cables and a pull tape. The three service cables will be bright yellow jacketed, Category 5E, Belden DataTwist 350 part # 1700A 4 pair, 24 AWG. In situations where plenum cables are required, Belden DataTwist 350 part # 1701A 4 pair, 24 AWG. Standard communication outlets will be outfitted minimally with a Panduit two gang (double duplex) stainless steel faceplate p/n CFP4S 2G containing three yellow receptacles Panduit p/n CJ5E88GYL, and one blank module Panduit p/n CMBIW X. The three 4 pair cables will be terminated at the outlet jack and the patch panel in Page: 13 Northwestern University Information Technology issued: JULY 2009

14 accordance with TIA 568A wiring standards. All Cables (yellow) will also follow TIA Category 5E as tested by Underwriters Laboratories. The Category 5E wire will be terminated on Panduit patch panels, part number CPPA 48FMWBL (48 port) Patch Panels shall be interpolated with Panduit horizontal cable management p/n CMPHF2. This cable will be terminated at the patch panel in accordance with Category 5E standards, configured as TIA 568A. Cables from the Communications Outlets to the Patch Panels shall be attached to the rear of the vertical cable management and the rear of the racks Wall telephones. For a wall phone, public safety phone, or pay phone, a single 1900 box with a simplex plaster ring shall be used. The 1900 box shall be mounted vertically 48" above the finished floor or as required by code. A 3/4" conduit shall connect the 1900 box to the cable tray system. A single, bright yellow jacketed, Category 5E, Belden DataTwist 350 part # 1700A 4 pair, 24 AWG cable will be installed and terminated on a flush mounted Panduit Stainless Steel RJ 45 wall telephone jack, part number 5WP5E. Public Telephone enclosures and booths are considered architectural, thus the specification, installation and maintenance of these devices is the responsibility of Northwestern University Facilities Management Design and Construction. Testing and Documentation Each Category 5E cable will be tested using an appropriate TIA Level 3, 250 MHz testing device. Headroom shall be above 4 db in all instances. Comprehensive reports for each cable at each communications outlet, detailing the results of all TIA Category 5E tests, Using Permanent Link Test mode at 250 MHz shall be submitted on completion and/or turnover of the project. No marginal (*PASS) will be accepted. All test results shall be presented in the native format of the testing device being used. E.g. *.flw for Fluke. Cable tests will only be accepted on CD s or DVD s professionally and permanently labeled with the project name, test area covered, test date and contractor name. A sample of required information follows: NAME OF CONTRACTOR Cable ID: RM207 1 Test Summary:PASS SITE: NWU JACOB CENTER 2ND FLR Headroom: 6.8 db Remote 36 45) Date / Time: 08/25/ :31:41am Test Limit: TIA Cat 5e Perm. Link OPERATOR: CHRIS PROKOP Cable Type: UTP 100 Ohm Cat 5e Software Version: DSP 4000 S/N: PM 006 NVP: 69.0% FAULT ANOMALY THRESHOLD: 15% DSP 4000SR S/N: PM 006 Shield Test: N/A Limits Version: 5.17 Wire Map: PASS Result RJ45 PIN: S RJ45 PIN: Length Prop. Delay Resistance Impedance Insertion Loss Delay Skew Anom. Result Freq. Limit Pair (ft) Limit ns Limit ns Limit ohms Limit ohms Limit (ft) (db) MHz (db) Page: 14 Northwestern University Information Technology issued: JULY 2009

15 Main Results Remote Results Worst Margin Worst Value Worst Margin Worst Value Margin Freq. Limit Margin Freq. Limit Margin Freq. Limit Margin Freq. Limit Pair (db) MHz (db) (db) MHz (db) (db) MHz (db) (db) MHz (db) RL PS NEXT PS ACR N NEXT ACR N ACR F PS ACR F Page: 15 Northwestern University Information Technology issued: JULY 2009

16 Underground coaxial distribution cables will be installed without splices or connectors unless otherwise specified. Sufficient cable shall be run into cable vaults, manholes, pedestals, etc., in order to allow splicing and further distribution at a future time. Coaxial cable ends shall be protected against water ingress by moisture sealing tape of heat shrink sealing caps. All coaxial cable splice locations shall be in buildings or other protected structures. Direct burial splices are not approved, and shall not be utilized VIII Labeling Explanation of terms: Telco room This term refers to the Telecommunications Room that all wires are consolidated to that service the individual rooms. Jack This term refers to the single receptacle that a customer used telecommunications device would be plugged into. Communications Outlet This term refers to the device that houses the cable and protects the jacks. Port This term refers to the equipment end of the jack, which is found in the Telecommunications Room on a patch panel. The port is on the other end of the cable where you would find the jack. Switch port This term refers to an individual receptacle found on the electronic switching equipment. Patch cord This term refers to the cord that connects the customer used telecommunications device to the jack, or the cord that connects the port to the switch port Fiber shelf This term refers to the housing that supports the fiber cables. Fiber panel This term refers to the group of receptacles that individual fiber strands connect to. Labeling of jacks at the Communications Outlet Each jack of a Communications Outlet will be individually labeled with three eighths of an inch tall label consisting of two lines of text of black ink on a white background. This label will be placed on the outlet as close to the jack as possible. The floor, room number, and the series number of that jack within the room will be printed on the first line. The floor and room number of the Telecommunications Room that serves that jack will be printed on the second Page: 16 Northwestern University Information Technology issued: JULY 2009

17 line. The length of the label is not to exceed 0.65, which is the width of a Panduit jack. Font size will be of such type as to allow two lines of text while preserving the 0.65 length. When data or voice circuits are to be installed, each jack used will be labeled with either the data circuit number or the telephone number just above the outlet ID label. This label will be of the same size and width as the ID label. Labeling of Emergency phone call boxes Emergency call boxes will be labeled with a three eights tall labels inside the call box behind the actual phone. The following information will be placed in the call box on individual labels: Call box number Phone number LEN Underground cable assignments On the top of the Telephone Housing (or the front, just above the phone set, for a column mount) the following will be placed on a ¾ label in four rows. Call Box Number, LEN, UG cable and Pair, and DN Labeling of ports Each port of a patch panel in a Telecommunications Room will be labeled with three eighths of an inch tall label consisting of one line of text of black ink on a white background. This line of text will document the floor, room number and series number of the jack that this port supports. The length of the label is not to exceed 0.65, which is the width of a Panduit jack. Font size will be of such type as to allow one line of text while preserving the 0.65 length. Labeling of patch cords Each end of the patch cord used in Telecommunications room will be labeled with three fourths of an inch wide label of black ink on a white background wrapped around the outer jacket. This label will be no less than one inch in length, and will consist of the data circuit ID (EDC/CDC), or the telephone number. Only patch cords that are used in Telecommunications rooms will be labeled. All other patch and line cords will remain blank. Outlet jack color designations Cable types presently in use at Northwestern University are made apparent by the different color jacks that are used both in outlets and in patch panels. Under no circumstances will different color inserts be used on the same cable. Jack color Wire type Yellow Category 5e Red Category 5 Black Category 4 or below Purple Category 5e voice (housing applications only) Blue Category 6A Page: 17 Northwestern University Information Technology issued: JULY 2009

18 Labeling of fiber shelves Fiber shelves will be labeled with the series number of that shelf within the same equipment rack or room if no rack exists. This label may be either three eights or one half of an inch in height. Labeling of fiber panels Fiber panels shall include labels to designate each fiber panel in use. This label may be either three eights or one half of an inch in height. Information on this label will be: Room number of far end of cable Equipment rack number of far end of cable Fiber shelf number of far end of cable Fiber panel designation of far end of cable Labeling of fiber patch cords Fiber patch cords will be labeled with a circuit identification number. This label will be threefourths of an inch tall with the circuit ID repeated over a one inch length of the label. This label is to be wrapped around the fiber patch cord in the same manner as a self laminated sticker would. Labeling of Telecommunications room switches Switches installed in Telco rooms will be labeled for identification purposes. This label may be either three eights or three fourths of an inch in height. Information on this label will be: IP address of switch Name of switch Card and port number of equipment that serves this switch This information will be included on each side of the switch with the exception of the rear where no label is required. Only the IP address is required for the front as lack of space limits restricts use of multiple labels. Labeling of equipment racks Floor and wall mounted equipment racks will be labeled for identification purposes. This label will be three fourths of an inch tall with a font type large enough so letters and numbers are clearly visible from a distance of at least six feet. Information on this label will be: room number of Telecommunications room and sequence number of equipment rack. Example: G = G166 is the room number of Telecommunications room,.01 is the equipment rack number. IX. University Housing Applications Horizontal Distribution System Each student room will be equipped with PANDUIT mini com jack components as described. Generally a single University Standard Outlet (refer to Chapter VII ) is adequate. At minimum Page: 18 Northwestern University Information Technology issued: JULY 2009

19 there must be one Category 5E jack for each student designated for the room plus 2 spare jacks. Stainless Steel faceplates and Blank inserts will be sized and used as necessary based on the capacity of the outlet. Each horizontal Service cable will be bright yellow jacketed, Category 5E, Belden DataTwist 350 part #1700A, 4 pair, 24 AWG cable will be installed to each CATEGORY 5E Jack module in the Service Outlet. Terminations for the data cable will be made on PANDUIT "mini com" TIA 568A equipment as specified below. The number of jacks to be installed in any student s room will equal the number of students living in that room, plus two additional Yellow Ethernet outlets. All jack modules will be wired in accordance with TIA specification 568A. No telecommunications cable may exceed 290 feet in length. Telecommunications cables will be terminated on PANDUIT CJ5E88G YL (jacks arranged and inserted PANDUIT CPPA 48FMWBL, 48 port patch panels. Patch Panels will be mounted on Panduit 19X.24 freestanding relay racks.) On the patch panel side, each jack will be marked with the Room Number and sequentially for each room a number 1,2,3,etc. Further details on labeling in section VIII. All Jacks will be tested and documented for category 5E compliance wire mapping and end to end distance with appropriate test equipment. The contractor will develop a form (both electronic and printed) in concert with NU IT Telecommunications for the presentation of the test data. The form shall identify the Room/Cable number, pair under test, technician, test date and results. Comments will be reserved for resolution to cables not passing the initial test. Jack identification numbers will equal the room number where the jack is located. Additionally all inserts will be identified with the use of a number: 1,2,3,etc. PANDUIT Parts Reference Description P/N RJ 45 Yellow Insert CJ5E88GYL 48 port Patch Panel CPPA 48FMWBL 2 Position Stainless Steel 1G Faceplate CFP2SS 4 Position Stainless Steel 1G Faceplate CFP4SS 6 Position Stainless Steel 1G Faceplate CFP6SS "F" type TV module Blank Module CMFBAIW CMBIW X 6 opening Surface Mount CBX6IW A Page: 19 Northwestern University Information Technology issued: JULY 2009

20 X. RF Television (CATV) Distribution This section applies to RF television distribution cabling within buildings only. See Section II.5 for specification of underground cabling for television distribution. This specification is not applicable to video or closed circuit TV distribution and shall not be applied to such installations. 1. Cable runs shall be laid out so that cable length from the TV tap to distribution point does not exceed 300 feet. Coaxial cable shall be Belden 1189A (Quad Shield RG 6). Cables shall be continuous runs from the distribution point to the TV tap. In line splicing is not acceptable. 2. Coaxial cable connectors shall be threaded, CATV grade types such as the following. Connectors that use compression rings, hex crimps, or tool less attachment means are not acceptable. Connectors designed to press on rather than threading on to F connectors are also not acceptable. The approved Connector is the Digicon 6Q 3. Wall taps shall be feed through (No Loss) type threaded to accept an "F" connector. Where the TV tap is to occupy the same panel and backbox as other telecommunications jacks, (Panduit) the TV tap shall utilize the same mounting system and standards as the other telecommunications jacks. 4. Splitters and Couplers a. Splitters shall be Regal "GRSxDGx" series. Design maximum frequency must be 1000 MHz or greater. Radiation shielding must be 110 db minimum. Where splitters are to be mounted on a flat surface, "vertical" version splitters shall be used (i.e. the output ports shall be perpendicular to the mounting surface). b. "T" type directional couplers shall be Regal RDCT10 series. Design maximum frequency must be 1000 MHz or greater. Radiation shielding must be 110 db minimum. c. "L" type directional couplers shall not be used. d. Directional multi taps shall not be used. 5. Terminators. Line termination resistors shall be Gilbert GTR59A. All unused ports, including test ports, shall be terminated with approved 75 ohm termination resistors. TV taps do not require termination. 6. Amplifiers. Northwestern University Information Technology Telecommunications will supply and install all amplifiers. Page: 20 Northwestern University Information Technology issued: JULY 2009

21 7. Other passive or active equipment. Equipment not specifically described in this specification may not be attached to the coaxial cable system without prior written permission from Northwestern University Information Technology Telecommunications. Vendors are required to submit technical literature and supporting comments to Northwestern University Information Technology Telecommunications prior to proposing such equipment. 8. Construction practices. a. All coaxial cable shall be installed according to the manufacturer's specifications. Appropriate care shall be taken to prevent crush or cut damage to the cable. Manufacturer specified bend radii shall be maintained. b. Cable preparation and connector application shall be done only with tools approved for use with the connector. All connections must be made wrench tight to prevent signal leakage and maintain efficiency. Connections must not be over tightened to the point of damaging the connector. XI. Applicable Standards and Practices ANSI/TIA C.0 Generic Telecommunications Cabling for Customer Premises (2009) ANSI/TIA C.1 Commercial Builing Telecommunications Cabling Standard (2009) ANSI/TIA 569A Commercial Building Standard for Telecommunications Pathways and Spaces ANSI/TIA 606 A Administration Standard for the Telecommunication Standard of Commercial Buildings TR 42.6 Labeling ANSI/TIA 607A Commercial Building Grounding and Bonding Requirements for Telecommunications ANSI/TIA TSB 95 Testing standards ANSI/TIA 568 B.2 ad10 Augmented Category 6 ANSI/TIA 942 Data Center Cabling Standard Page: 21 Northwestern University Information Technology issued: JULY 2009

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute

More information

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. 1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking

More information

Minimum Standards for Data/Voice Infrastructure in New Building Construction

Minimum Standards for Data/Voice Infrastructure in New Building Construction UNIVERSITY OF WATERLOO Minimum Standards for Data/Voice Infrastructure in New Building Construction 12/17/2012 Offices 1. Two Work Area Outlets (WAO) on opposite walls, each with 2 jacks 2. Each WAO shall

More information

ATTACHMENT F 050R6800016 - CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6

ATTACHMENT F 050R6800016 - CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6 050R6800016 CABLE AND WIRING SERVICES (Column A) (Column B) (Column C) (Column D) (Column E) (Column F) (Column G) (B+C+D+E)*F= G Item Description PER 100' RUN PER 150' RUN PER 200' RUN PER 300' RUN QUANTITY

More information

1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.

1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications. Issued 2005/06/01 Section 16743 Data System Page 1 of 7 PART 1 GENERAL 1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications..2 Data system equipment

More information

1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:

1. Furnish and install faceplate and modular jacks at each single gang outlet as described below: Washington University in St. Louis Building: Communication Specification: Research Voice/Network/Typical 1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:

More information

Building Telecommunications Infrastructure Requirements

Building Telecommunications Infrastructure Requirements Building Telecommunications Infrastructure Requirements This page identifies specific requirements for the design of telecommunications infrastructure for buildings at Clemson University. (Revised October,

More information

Network Design. Yiannos Mylonas

Network Design. Yiannos Mylonas Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which

More information

TCTC Cabling Specifications

TCTC Cabling Specifications TCTC Cabling Specifications Purpose: To provide a standard specification that will be used for all Tri County Technical College (TCTC) facilities requiring structured cabling installation. Product specifications,

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

SECTION 25110 TELECOMMUNICATION ROOMS

SECTION 25110 TELECOMMUNICATION ROOMS PART 1 - GENERAL 1.1 SUMMARY A. SCOPE SECTION 25110 TELECOMMUNICATION ROOMS 1. This section includes the minimum installation requirements for equipment and cabling infrastructure in Telecommunication

More information

UT Southwestern Medical Center Information Resources Cable Installation Standard

UT Southwestern Medical Center Information Resources Cable Installation Standard UT Southwestern Medical Center Information Resources Cable Installation Standard PART 1- GENERAL 1.01 SUMMARY A. Furnish and install wire, cable, devices, equipment, and accessories for a complete system

More information

IT&T Infrastructure Standards

IT&T Infrastructure Standards Technology Services IT&T Infrastructure Standards Version 1.5 17 th April 2015 Page 1 Table of contents 1 CHANGE HISTORY... 3 1.1 DOCUMENT HISTORY... 3 1.2 REVIEWERS... 3 1.3 APPROVALS... 3 2 INTRODUCTION...

More information

TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012

TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012 TIA 569 Standards Update Pathways & Spaces Ignacio Diaz, RCDD April 25, 2012 The purpose of this Standard is to standardize specific pathway and space design and construction practices in support of telecommunications

More information

Specifications for Communication Cabling Distribution Systems

Specifications for Communication Cabling Distribution Systems Washington University in St. Louis Specifications for Communication Cabling Distribution Systems General Overview Listed below are the separate sub-systems of Washington University s structured cabling

More information

Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011)

Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011) Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011) A. Objectives The Information Technology (IT) Department of Embry-Riddle Aeronautical University (ERAU) seeks to establish a standards-based

More information

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit

More information

ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard.

ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard. WIRING STANDARD INTRODUCTION This standard defines a telecommunications wiring system for North Dakota State Agencies, offices or buildings that will support a multi-product environment. The purpose of

More information

Specifying an IT Cabling System

Specifying an IT Cabling System Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your

More information

TrueAlarm Fire Alarm Systems

TrueAlarm Fire Alarm Systems TrueAlarm Systems UL, ULC, CSFM Listed; FM Approved* Network Annunciators; es Features Provides a dedicated local area network (LAN) for connection of a TrueSite workstation server to remote clients: es

More information

1 Campus Cabling Systems Introduction

1 Campus Cabling Systems Introduction 1 Campus Cabling Systems Introduction This document represents the campus cable and infrastructure standards adopted and supported by the XXXX. All new construction and renovation should conform to these

More information

TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS. University of Chicago IT Services Infrastructure Services October 2011

TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS. University of Chicago IT Services Infrastructure Services October 2011 TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS IT Services Infrastructure Services October 2011 Table of Contents 1 Introduction... 4 1.1 Planning and Design... 4 1.2.1 Roles and Responsibilities...

More information

ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers

ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers Jonathan Jew jew@j-and-m.com J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center working group Co-chair BICSI data centers standards

More information

SECTION 16715 TELECOMMUNICATIONS ACCEPTANCE TESTING

SECTION 16715 TELECOMMUNICATIONS ACCEPTANCE TESTING PART 1 - GENERAL 1.1 SECTION INCLUDES A. Testing Publications and Standards B. Inspection and testing procedures for copper and fiber optic cable, RF CATV / MATV systems, and the antenna systems. C. Documentation

More information

Category 6 Solutions. 4. Category 6 Solutions. 09/08 400836IN TrueNet Structured Cabling. Introduction... 4.2. Cable... 4.3. Patch Panels... 4.

Category 6 Solutions. 4. Category 6 Solutions. 09/08 400836IN TrueNet Structured Cabling. Introduction... 4.2. Cable... 4.3. Patch Panels... 4. Category 6 Solutions Introduction... 4.2 Cable... 4.3 Patch Panels... 4.4 Modules... 4.6 Patch Cords... 4.12 Outlets... 4.16 Faceplates...4.18 4. 1 Search Category 6 Solutions Introduction ADC KRONE s

More information

Panduit 28 AWG Patch Cords Installation Guideline

Panduit 28 AWG Patch Cords Installation Guideline Panduit 28 AWG Installation Guideline Introduction Panduit is a leading supplier of Structured Cabling Systems and Unified Physical Infrastructure. Panduit solutions enable the physical infrastructure

More information

ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers

ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers Jonathan Jew jew@j-and and-m.com J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center committee Co-chair BICSI data centers

More information

ADC Structured Cabling Solutions

ADC Structured Cabling Solutions ADC Structured Cabling Solutions The highest performing cross-connect system in the world HighBand Wall Mount Patching Solution Reliable, secure and cost effective ADC s HighBand cross connect solution

More information

a. Design or design review of Voice, Data, and Wireless systems b. Copper cable manufacturer selection for new buildings and large scale renovations.

a. Design or design review of Voice, Data, and Wireless systems b. Copper cable manufacturer selection for new buildings and large scale renovations. 5.18 Voice and Data Distribution 5.18.1 General Introduction 1. This standards document is to be used for any projects on the University of Calgary campus that involves the voice and data distribution

More information

The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration

The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration Bill Charuk, SR Product Manager, Data Center Solutions Introduction With the advent of data centers in communication infrastructure, various

More information

Intelligent Cable Management Systems

Intelligent Cable Management Systems Intelligent Cable Management Systems Bringing Practical Application Karen Pearson - Leviton Why Cable Management Matters Performance Cooling and air-handling Maintenance ANSI/TIA 569* Telecommunication

More information

TELECOMMUNICATIONS NETWORK STANDARDS AND GUIDELINES FOR THE NEW ADMINISTRATION BULDING

TELECOMMUNICATIONS NETWORK STANDARDS AND GUIDELINES FOR THE NEW ADMINISTRATION BULDING TELECOMMUNICATIONS NETWORK STANDARDS AND GUIDELINES FOR THE NEW ADMINISTRATION BULDING October 1998 Table of Contents SECTION I: New Construction Programming 1.0 New Construction 1.1 Design Elements..................................

More information

SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines

SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines This document contains critical information regarding the installation of a certified SYSTIMAX SCS that meets or exceeds performance

More information

Pretium Connector Housings

Pretium Connector Housings Pretium Connector Housings A LANscape Pretium Solutions Product Applications Main cross connect, intermediate cross connects and telecommunications rooms Rack or equipment cabinet installations Data center

More information

Structured Cabling Statement of Work

Structured Cabling Statement of Work Structured Cabling Statement of Work Multiple Locations June 15, 2010 Page 1 A. GENERAL a. San Joaquin County (referred to as Owner ) is requesting proposals for a new structured cabling infrastructure

More information

Cable Installation Project

Cable Installation Project Cable Installation Project 1. Intent. It is the intent of the U.S. Court of Appeals to install Category 6 (CAT6) data cabling in the Robert F. Peckham Federal Building and United States Courthouse, 280

More information

DESIGN GUIDELINES. Local Area Network

DESIGN GUIDELINES. Local Area Network DESIGN GUIDELINES Local Area Network The total oversight and management responsibilities for information assurance (IA) and protection of DoDEA s critical infrastructure fall under the purview of the DoDEA

More information

University of North Carolina at Charlotte Design and Construction Manual Section 3, Annex K, 49er Card Systems ANNEX K 49ER CARD SYSTEMS

University of North Carolina at Charlotte Design and Construction Manual Section 3, Annex K, 49er Card Systems ANNEX K 49ER CARD SYSTEMS ANNEX K 49ER CARD SYSTEMS UNC CHARLOTTE 49ER CARD SYSTEM INSTALLATION AND CONTRACTOR REQUIREMENT SCOPE OF WORK: The following information pertains to the installation and contractor requirements to install

More information

DEPARTMENTAL REGULATION

DEPARTMENTAL REGULATION U.S. DEPARTMENT OF AGRICULTURE WASHINGTON, D.C. 20250 DEPARTMENTAL REGULATION SUBJECT: Service Center Technology Modernization Project (SCTMP) Wiring/Cabling Specifications for Service Center Agencies

More information

HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP)

HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP) Cable Specification Category 5e CMP HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP) This cable specification complies with the electrical transmission

More information

STRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011

STRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011 STRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011 Project Ref. Project Name Project Manager Date issued... Consultant/Contractor... 1 CONTENTS 1000 GENERAL OVERVIEW

More information

The Telecommunications Closet and Building Services

The Telecommunications Closet and Building Services APPENDIX G Telecommunications Building & Network Standards 1. Expectations...2 2. Definitions...2 3. Contractor Requirements...2 4. Design Elements...3 4.1. Spaces...3 4.1.1. Building Service Entrance...3

More information

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation Data Center Pre-terminated Patch Panel System Patch Panels Plug & Play Installation 10G + Gigabit Patch Cords Bundled + Labeled Cabling Systems Simplified Our Mission At Cablesys, our mission is to simplify

More information

SECTION 16750 VOICE AND DATA COMMUNICATION CABLING

SECTION 16750 VOICE AND DATA COMMUNICATION CABLING SECTION 16750 VOICE AND DATA COMMUNICATION CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Store drawing set and general provisions of the Contract, including General and Supplementary Conditions and

More information

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property 2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical

More information

FTE Cabling Best Practices Author: Todd Bill, RCDD/NTS

FTE Cabling Best Practices Author: Todd Bill, RCDD/NTS FTE Cabling Best Practices Author: Todd Bill, RCDD/NTS Document ID: WP-07-01-ENG Original Issue Date: May 2007 Version: 1.0 FTE Cabling Best Practices 1 Table of Contents Introduction and Applicable Standards...3

More information

InstaPATCH Cu Cabling Solutions for Data Centers

InstaPATCH Cu Cabling Solutions for Data Centers SYSTIMAX Solutions InstaPATCH Cu Cabling Solutions for Data Centers Design Guidelines August 2008 www.commscope.com Contents Overview 1 Instapatch Cu Solution Specification 2 Harness Assembly Design 3

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Inspections and observations by the Owner do not relieve the A/E of contract responsibilities. B. Chain of command 1. The DPS Project Manager is

More information

Standards. www.nordx.com 5 ANSI/TIA/EIA-569-A (CSA T530)

Standards. www.nordx.com 5 ANSI/TIA/EIA-569-A (CSA T530) The primary focus of this standard is to provide design specifications and guidance for all building facilities relating to telecommunications cabling systems and components. This standard identifies and

More information

SECTION 16750. TELECOMMUNICATIONS SYSTEM (Cat 6)

SECTION 16750. TELECOMMUNICATIONS SYSTEM (Cat 6) SECTION 16750 TELECOMMUNICATIONS SYSTEM (Cat 6) PART 1 - GENERAL 1.01 REQUIREMENTS A. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements, apply

More information

SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY

SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY SECTION 28 05 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections, apply

More information

Network Telecommunications Design Standards Last Updated June 2013. Youngstown State University

Network Telecommunications Design Standards Last Updated June 2013. Youngstown State University 1 Network Telecommunications & Security Youngstown State University One University Plaza Youngstown, OH 44555 Network Telecommunications Design Standards Last Updated June 2013 Youngstown State University

More information

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval. Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's

More information

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to

More information

BIX Cross-Connect System Distribution Connectors, Multiplying Connectors and Modular Jack Connectors

BIX Cross-Connect System Distribution Connectors, Multiplying Connectors and Modular Jack Connectors C O M M E R C I A L N E T W O R K I N G C O P P E R 15.13 Distribution Connectors, Multiplying Connectors and Modular Jack Connectors A0393146 QCBIX1A4 Connector BIX Distribution Connector The BIX Distribution

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat

More information

BRIDGEWATER COLLEGE HERITAGE HALL RENOVATIONS 12057.00

BRIDGEWATER COLLEGE HERITAGE HALL RENOVATIONS 12057.00 SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING PART 1 - GENERAL 1.1 OVERVIEW A. This section provides the necessary guidelines to install service entrance cables to buildings and information for the

More information

The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects

The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects White Paper /7/0 Executive Summary Now that the TIA/EIA-568-B.- Category 6 Copper Cabling

More information

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12 SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications

More information

FIBER OPTIC CABLE PLANT DOCUMENTATION

FIBER OPTIC CABLE PLANT DOCUMENTATION C H A P T E R 13 FIBER OPTIC CABLE PLANT DOCUMENTATION JIM HAYES Documenting the fiber optic cable plant is a necessary part of the design and installation process for the fiber optic network. Documenting

More information

AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions

AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions TABLE OF CONTENTS TABLE OF CONTENTS... 2 INTRODUCTION... 3 CABLING

More information

4 Installation Requirements

4 Installation Requirements 4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming

More information

CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements

CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements 16600 Underground Electrical Duct Bank This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications

More information

Telecommunications Systems Narrative Page 1 The Engineering Enterprise

Telecommunications Systems Narrative Page 1 The Engineering Enterprise I. TELECOMMUNICATIONS GENERAL REQUIREMENTS A. The project consists of a renovation to the historic Clinical Sciences building, originally built in 1933. The existing building has a total area of 105,000

More information

SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.

SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical

More information

March 2007. 27 08 00 Commissioning of Communications. See Appendix E3. 27 08 00-1

March 2007. 27 08 00 Commissioning of Communications. See Appendix E3. 27 08 00-1 March 2007 27 08 00 Commissioning of Communications See Appendix E3. 27 08 00-1 27 11 00 Communications Equipment Room Fittings 1.0 General TELEPHONE RISERS: A. All copper telephone riser cables must be

More information

Fiber Plant Design Considerations for Active DAS Mike Brownson VP DAS Technical Solutions Hutton Communications

Fiber Plant Design Considerations for Active DAS Mike Brownson VP DAS Technical Solutions Hutton Communications Fiber Plant Design Considerations for Active DAS Mike Brownson VP DAS Technical Solutions Hutton Communications Topics! Understanding Fiber Types! Powering your Remotes via Composite Fiber! Fiber Design

More information

TIA-942 Data Centre Standards Overview WHITE PAPER

TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and

More information

800 Communications Circuits

800 Communications Circuits ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that

More information

Reliable, Consistent, Quality

Reliable, Consistent, Quality Reliable, Consistent, Quality 1-877-320-3143 www.fibertronics.com Reliable, Consistent, Quality Welcome To Fibertronics Inc. Reliability, consistency, and quality is what we put behind every Fiber optic

More information

TELUS Residential Service Conduit Requirements for Stand Alone Homes and Duplexes in Fibre Only Communities

TELUS Residential Service Conduit Requirements for Stand Alone Homes and Duplexes in Fibre Only Communities 1 TELUS Residential Service Conduit Requirements for Stand Alone Homes and Duplexes in Fibre Only Communities Beginning in January 2010 TELUS began designing new subdivisions within the Top 48 population

More information

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection. DIVISION 16 ELECTRICAL Section 16740 Telephone System PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Gigabit Passive Optical Networks

Gigabit Passive Optical Networks White Paper Gigabit Passive Optical Networks Passive Optical LAN Solutions (POLS) Theory, Design, and Installation Considerations Sean McCloud, RCDD Senior Applications Engineer, Leviton Network Solutions

More information

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE FOR TRAFFIC SIGNAL INTERCONNECT JANUARY 19, 2007

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE FOR TRAFFIC SIGNAL INTERCONNECT JANUARY 19, 2007 804.01 Description 804.02 General 804.03 Materials 804.04 Fan-Out Kit 804.05 Drop Cable 804.06 Fiber Optic Patch Cord 804.07 Termination Panel 804.08 Fusion Splice 804.09 Fiber Optic Connector 804.10 Splice

More information

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems

More information

NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS)

NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS) NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS) Revision date 28 th January 2014 The purpose of this document is to assist Building Refurbishment and

More information

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage: Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial

More information

B. PART 1 - GENERAL of SECTION 271300 BACKBONE COMMUNICATIONS CABLING shall also apply to this section.

B. PART 1 - GENERAL of SECTION 271300 BACKBONE COMMUNICATIONS CABLING shall also apply to this section. SECTION 271500 - HORIZONTAL UTP CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

HARTING Ethernet Cabling 8-poles Overview

HARTING Ethernet Cabling 8-poles Overview Ethernet Cabling 8-poles Overview RJ45 Connectors [on page 8] System cables [on page 12] Distribution modules and Outlets [on page 17] Connectors [on page 20] System cables [on page 26] Panel feed-throughs

More information

ANSI/TIA/EIA-606. Administration Standard for the Telecommunications Infrastructure of Commercial Buildings

ANSI/TIA/EIA-606. Administration Standard for the Telecommunications Infrastructure of Commercial Buildings ANSI/TIA/EIA-606 Administration Standard for the Telecommunications Infrastructure of Commercial Buildings Distributed by NDS INFORMATION- TELECOM SYSTEM --------------------------------------------- Head

More information

2301.1 Scope: Communications and Electronic Systems addressed in this section include:

2301.1 Scope: Communications and Electronic Systems addressed in this section include: Chapter 23 COMMUNICATIONS / ELECTRONIC SYSTEMS SECTION 2301 - GENERAL 2301.1 Scope: Communications and Electronic Systems addressed in this section include: 1. Fire Alarm System 2. Telecommunication and

More information

E Series. E Series. Category 6 and 5e. Features

E Series. E Series. Category 6 and 5e. Features E Series Category 6 and 5e CommScope, world leader in copper and fiber connectivity, offers the E Series product line as the ideal solution to all your infrastructure needs for safe and reliable data transmission.

More information

How To Set Up A Minipatch System For A Small Office Or Home Use

How To Set Up A Minipatch System For A Small Office Or Home Use Issue : 4 Wood Communications Networking Products Catalogue Small Office & Home Solution Small Office / Home Solution Min LAN Comms Cabinets - Multimedia Panel - Soho Ethernet Switches - Multiroom Audio/Video,

More information

Cat7/Class F New Installation Concept New infrastructure. Handbook

Cat7/Class F New Installation Concept New infrastructure. Handbook Cat7/Class F New Installation Concept New infrastructure Handbook contents 1 Introduction 3 2 What is the Cat7/Class F installation concept 3 3 Distribution centre 3 3.1 Patch Modules 3 4 How to handle

More information

Structured and Point to Point Network Cabling for Industrial Automation

Structured and Point to Point Network Cabling for Industrial Automation Structured and Point to Point Network Cabling for Industrial Automation Introduction Industrial automation systems are undergoing dramatic transformations that require businesses to adopt new strategies

More information

21 st Century Campus Network Responsibility Matrix 5/26/10

21 st Century Campus Network Responsibility Matrix 5/26/10 Definitions: DoIT Standards This column details the minimal configuration, which DoIT has defined in order to provide a campus-wide standard level of service. Departments may request services, which exceeds

More information

FITNESS FACILITY WIRING SPECIFICATIONS. NETPULSE Inc. 2331 3rd Street San Francisco, CA 94107 Phone: 415.643.0223

FITNESS FACILITY WIRING SPECIFICATIONS. NETPULSE Inc. 2331 3rd Street San Francisco, CA 94107 Phone: 415.643.0223 FITNESS FACILITY WIRING SPECIFICATIONS NETPULSE Inc. 2331 3rd Street San Francisco, CA 94107 Phone: 415.643.0223 CONTENTS: - Scope of work Summary - Equipment list - Technical specifications - Map of data

More information

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included

More information

Cabling Services (price per pull) Zone 1 Zone 2 Zone 3 Zone 4 Zone 5

Cabling Services (price per pull) Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 BryComm, LLC -SDD-1901 Cabling Services (per pull) - Labor Only STANDARD TIME The price per cable pull represents all labor to include fishing walls, running cable through modular furniture, terminating,

More information

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

ELECTRIC METERING COMMERCIAL & INDUSTRIAL ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS

More information

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 10 00 STRUCTURE CABLING TESTING

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 10 00 STRUCTURE CABLING TESTING RELATED SECTIONS: NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT Section 27 00 00 General Requirements Section 27 02 00 General Communication Requirements Section 27 05 26 Grounding and Bonding for Communications

More information

Table of Contents. Fiber Trunking 2. Copper Trunking 5. H-Series Enclosures 6. H-Series Mods/Adapter Panels 7. RSD Enclosures 8

Table of Contents. Fiber Trunking 2. Copper Trunking 5. H-Series Enclosures 6. H-Series Mods/Adapter Panels 7. RSD Enclosures 8 Data Center Guide 1 Our Philosophy As a leader in the enterprise cable industry since our inception over three decades ago, we can help you implement the solution that will work best for your cabling infrastructure,

More information

LOS ANGELES CITY COLLEGE Technology Design Standards

LOS ANGELES CITY COLLEGE Technology Design Standards LOS ANGELES CITY COLLEGE Technology Infrastructure Final January, 2007 Prepared for: Los Angeles City College Los Angeles City College TABLE OF CONTENTS Section Page INTRODUCTION 1 DESIGN STANDARDS FOR

More information

Accelerating Light. Copper Cabling Solutions. Category 6A

Accelerating Light. Copper Cabling Solutions. Category 6A Accelerating Light Copper Cabling Solutions Category 6A Category 6A Copper Cabling Solutions Fibernet designs and manufactures premium, high performance copper communication infrastructure and connectivity

More information

Electrical. This section applies to the design and installation of building power distribution systems.

Electrical. This section applies to the design and installation of building power distribution systems. Basis of Design This section applies to the design and installation of building power distribution systems. Design Criteria This section contains the architectural, structural and mechanical provisions

More information

Technical Specifications v5.6.14

Technical Specifications v5.6.14 Summer 14 Columbia University Information Technology [Author Name] Technical v5.6.14 [Type the abstract of the document here. The abstract is typically a short summary of the contents of the document.]

More information

Installation Manual For Support Call 01704 807114 or email info@hipentertainment.co.uk

Installation Manual For Support Call 01704 807114 or email info@hipentertainment.co.uk Installation Manual Hip Smart Hub (Standard BT and BT FTTP Sites) The Home Network Hub houses the Home Owner s Broadband Router and connects the hardwired network ports on that Router to three network

More information

Engineers Edge, LLC PDH & Professional Training

Engineers Edge, LLC PDH & Professional Training 510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Communication

More information