1 UNITED AIRLINES DENVER INTERNATIONAL AIRPORT May 2014 CHELSEA FLIGHT KITCHEN FACILITY ASSESSMENT By JBT AEROTECH 1

2 Table of Contents 1. Introduction / General 2. Facility Exterior / Structural / Roof 3. Facility Interior 4. Fire Protection (Central) / Boiler Systems 5. Plumbing Systems 6. Mechanical and Refrigeration Systems 7. Electrical and Lighting Systems 8. Miscellaneous / Building Automation & Control Systems 9. Repair / Replacement / Life Cycle Analysis 10. Conclusions 2

3 Introduction The enclosed assessment provides a high level, non-intrusive, observation of the operating condition, reliability and asset value of the facility and systems for the United Airlines Chelsea Flight Kitchen facility at the Denver International Airport. The assessment and analysis is based on an onsite review performed on April 28, 2014 and involved a through walk-through of the facility and discussions with onsite personnel responsible for the routine maintenance of the facility. For those systems listed in the Table of Contents above, the assessment also provides general statements, with pictures for each system, regarding the information listed below: - Overall condition/appearance (i.e., good, average, poor) - Current operability (i.e., operable, non-operable) - Mandatory and/or critical repairs required - Missing and/or disassembled system components and/or sub-components - Probable operational reliability absent capital investment - Near-term capital renewal or rehabilitation requirements Matrices are provided at the end of the report that identify specific systems and components and provide design life expectancies and as is remaining life estimates as well as estimated costs required for specific system and/or component repair or replacement. The assessment also provides an estimate of the cost of a new similar facility based on current average new construction costs in the Denver area. The lease agreement provided by United Airlines makes reference to maintaining and making repairs and replacements to equipment that has an expected life of greater than (12) years. All of the equipment and assets reviewed in this report generally have life expectancies exceeding (12) years. It should be noted that some level of preventive maintenance has evidently been performed on the systems assessed within the Chelsea facility but work order or written PM documentation was not reviewed. As such, it is difficult to assess the level or frequency of that maintenance activity. However, it was noted that the maintenance crew at Chelsea uses a maintenance management program and supports that program with subcontractors who typically perform annual and required maintenance functions that are outside the resource capabilities of the existing crew. The assessment is based solely on visual and non-destructive analysis and on discussions with maintenance personnel and subcontractors who have had previous maintenance and/or repair responsibility for the equipment and/or assets. 3

4 A good program of preventive maintenance should be adhered to and is intended to prevent (or mitigate) system or equipment failure and includes recommended inspections, repairs, cleaning, painting, and adjustments. Compliance with lubrication procedures is particularly important. While local conditions will determine to some degree the exact details of a good preventive maintenance program, a comprehensive maintenance program should always be in place. This assessment includes analysis on building infrastructure, mechanical, electrical, plumbing and associated equipment, refrigeration and ice making equipment and some pieces of kitchen equipment. The assessment makes no analysis or reference to code compliance and assumes that all systems and equipment were code compliant upon initial construction and that any initial and/or subsequent code compliance or regulatory issues have been addressed by the owner and/or subtenant. General The Chelsea facility was constructed in 1994 and consists of a 65,000 sq. ft. flight kitchen facility including delivery and receiving truck docks and administrative space as well as paved ramp for truck circulation and parking. The facility is in fair condition overall with average wear and deficiencies for a facility constructed twenty years ago. The exterior of the facility is in fair condition and benefits from a recent roof replacement. The interior is also in fair condition but also shows the wear of 20 years of use. Most of the equipment and systems within the facility are in fair condition but also show their age and 20 years of use even though the operation incorporates a relatively robust maintenance program. The facility has incurred structural damage over numerous years due to expansive soils in the area around the airport. These are evident in numerous areas in and around the facility and are particularly noted in Exterior and Interior sections of this document. The situation is exacerbated by runoff from the berm adjacent the runway/taxiway area causing water to infiltrate the building under heavy rains. 4

5 Building Exterior Facility Exterior and Signage - Cracked tile and leaching of minerals - Damage/deterioration of signage on front and side of facility - Tile/grout replacement - Potential crack in wall system behind tile - Sign repair/replacement may or may not be warranted depending upon facility swap 5

6 Exterior Facility Entrance walkway and stairs - Cracks in concrete around railing - Deterioration of concrete on vertical stairs - Settling of concrete partition for planter - Saw-cut and dowel-in new (high PSI) concrete with reinforced rebar and anti-skid plates 6

7 Parking Lot Parking lot issues - Cracks in concrete - Cracks around trench drain systems - Faded parking lot paint striping near vehicle spots - Rod & fill cracked areas with sealant -or- - Saw-cut and replace damaged areas - Restripe parking lot 7

8 Entrance Soffit Entrance soffit - Water damage from roof membrane leak - ¼ opening in cap strip sealant - Repair soffit and associated damage (paint to match) - Remove and reseal cap strip sealant 8

9 Exterior Fence/Gate View of exterior fence and gate. - Bent/damaged rolling gate - Missing top horizontal support bar on fence - Lower tension wire lacks tension - Install replacement horizontal support and associated hardware - Re-tension fence and lower tension wires - Rear Entrance/Exit gate inoperative 9

10 Facility Interior / Structural Interior cinderblock wall and exterior loading dock wall - Cracked cinderblock wall from expansive soils and facility settling - Cracked concrete at loading dock wall - Fill cracks with anchor cement - As concrete begins to fail, saw cut, dowel, and rebar and form replacement areas Certain areas of structural damage in the facility may require structural engineering analysis and repairs that are in excess of those listed above. 10

11 Interior Wall / Floor Joint Damage Electrical Room Boiler / Electrical Room - Cracks in cinderblock wall of electrical room - Expansive soil issues and settling of facility has widened expansion joints and caused sealant failures Investment required: (Parts and labor) - Align and seal cracks - Remove existing expansion joints/ sealant and reseal Certain areas of structural damage in the facility may require structural engineering analysis and repairs that are in excess of those listed above. 11

12 Roof System Roof Membrane EPDM roof membrane replaced in Uneven surfaces allowing ponding of water and will lead to premature roof failure - Membrane heat bond not secured in all areas (some lifting/bubbles) - Pads becoming unsecured around the perimeter - Un-bonded wear mat - Some lightning rods missing and cable detached Investment required: - Request bonding for lifting areas (may be under warranty) - Lifting pads should be re-secured to EPDM membrane - Ponding issues should be addressed - Routine maintenance should be performed on the roof to remove wind-blown articles, roof area related repair and construction debris, etc. - Re-secure un-bonded wear mats - Replace missing lightning protection rods - Secure cabling 12

13 Interior - General Interior Walls and Floors - Interior walls are generally in good condition and indicate recent rework and paint - Floors are generally in good condition although high traffic areas show wear and are in need of replacement - This is evident in the carpeted areas of the administration offices as well as in tiled areas of the restrooms - Replace areas of worn carpeting in office areas and worn floor tiles in restroom/other areas 13

14 Interior / Ceilings Ceiling tiles and grid - Delaminating surface due to age/humidity - Bent ceiling tile grid (settling and wind drafts from open doors) - Ceilings in office areas are generally in good condition - Ceiling tiles with food grade membranes can be cleaned by hand or replaced - Deformed ceiling tile grid should be replaced 14

15 Cafeteria Cafeteria window walls - Cracks in glass - Displacement of molding and trim at the base of the window - Water damage from past roof leaks - Settling door frame showing daylight in seal - Replace window glass - Repair and silicone trim in place - Replace water damaged material (patch and paint) - Shim door and add appropriate weather seal 15

16 Cafeteria Cafeteria serving line wall/floor - Wall is uneven and wavy due to expansive soils issue and settling of the building - Loose/lifting VCT - Vinyl wall siding is separating due to shifting/settling - Replace loose/bubbled VCT flooring - Re-secure joint over VCT sheets 16

17 Facility Maintenance Office Facility maintenance office window - Broken window pane - Replace broken window pane Facility maintenance office - Facility maintenance office is organized and house kept and indicates a relatively robust maintenance program 17

18 Fire Protection / Boiler Systems Emergency Diesel Engine Fire Pump and Fire Sprinkler systems appear to be in good condition and show up to date inspections. The two Cleaver Brooks natural gas boilers appear to be well maintained and show up to date inspections as well. 18

19 Boilers and Chemical Feed Boiler and chemical feed. - Sight-glass is leaking steam and should be replaced (spare on-hard) - Associated chemical quill piping showing corrosion - Steam leaks from valves apparent near heat exchanger - Associated piping needs to be reinsulated Investment required: - Replace sight glass - Replace chemical quill piping - Repair steam leaks and check steam distribution piping - Re-insulate associated piping 19 Eye bolts and chains in tunnel wall are a catch hazard for passengers and should be removed.

20 Water Softener Water Softener Systems / Brine Tank Culligan 200 Gallon Water Softener - Leaky control head assembly - Rusted resin tank - Sediment deposits in brine tank Investment required: - Recommend replacement of entire water softener unit - Recommend emptying and cleaning of brine tank on a quarterly or semiannual basis Eye bolts and chains in tunnel wall are a catch hazard for passengers and should be removed. 20

21 Gray Water Drains Boiler Room Drains. - Drain does not flow; suspected collapse of underground sanitary line (pump currently transferring water to another drain system). - Drain cover has been damaged and may be a trip hazard Investment required: - Pipe scope inspection to determine drain line integrity - Underground repair of drain - Replace and clean drain cover and surrounding areas Expansive soil issues may have caused sanitary drain line failure and may require pipe scope inspections and/or replacement of drain lines. Eye bolts and chains in tunnel wall are a catch hazard for passengers and should be removed. 21

22 Domestic Water Storage Tank Domestic Water Tank 1,000 Gallon A O Smith Tank - 1,000 gallon domestic water tank appears to be leaking (location unknown due to jacketing) Investment required: - Replace leaking domestic water storage tank Some general maintenance is required in and around the mechanical room. 22

23 Domestic Hot Water Hot water piping and heat exchangers - One heat exchanger replaced recently - Piping requires re-insulation - (1) heat exchanger is leaking (appears to be long-term) from the flange and will most likely require replacement Investment required: (Approx. parts and labor) - Re-insulate piping - Replace leaking heat exchanger Eye bolts and chains in tunnel wall are a catch hazard for passengers and should be removed. 23

24 Air Compressors Boiler Room Compressor (2) Champion 15hp - Oil leak on one compressor cylinder head - Unit is showing low oil Investment required: - Remove compressor head assembly and replace seals - Check and maintain oil levels 24

25 Rooftop Exhaust Fans Roof-mounted exhaust fans. - Numerous exhaust fans appeared to not be functioning. It was not known whether they were activated by equipment or were inoperative. - Hot Foods exhaust fans may allow grease and food to be spilled onto roof membrane - Test and replace inoperative exhaust fans - Add drip buckets to collect grease to prolong roof membrane life 25

26 HVAC & Coils Condenser and evaporator coils. - Condenser coils show weathering and hail damage - Evaporator coils have recently changed filters but require annual cleaning to maintain proper heat transfer - Outside air/economizer damper linkages are disconnected leading to inadequate ventilation and increased energy consumption - Utilize coil brush to open airflow - Add hail guards to coils - Implement an annual coil cleaning program using non-corrosive chemicals to prevent premature aluminum fatigue - Re-commission HVAC and controls systems and verify adequate outside air ventilation levels within the facility 26

27 HVAC and Coils View of HVAC heat sections - Gas valve is on but there are a few units that lack verifiable operation (potentially due to BAS issues) - Indications were that office areas were very cold in the winter and that frozen condensation existed on the windows at times - HVAC pans are rusted and holding water - Test and re-commission BAS and verify operation of heaters and associated economizer functions - Pans should be cleaned-out on a regular basis and treated with fungicide tablets annually. - Once rust starts on pans, they can be power-washed and/or beadblasted and coated with a rubberized coating to prevent further damage or be replaced 27

28 Refrigeration Equipment Refrigeration Equipment - Frozen compressor Ice Bin - Frozen refrigerant lines - Refrigerant line insulation is missing and/or damaged - Verify compressor block heater operation - Check refrigerant level and compressor pressure switch settings - Reinsulate refrigerant lines - Verify/correct inoperative evaporator fans 28

29 Refrigeration Equipment Thermal Images of compressors and refrigerant lines - Blast Chiller compressor is running excessively hot: 222*F (ideal temperature should not exceed 200*F) - Mechanical valve noise can be heard through compressor case via mechanic s stethoscope - Deterioration or missing insulation on refrigeration piping - Check oil, refrigerant charge and pressure switch settings on blast chiller compressor - Reinsulate associated refrigerant piping 29

30 Ice Plant & Ice Storage Bin Ice Plant Equipment Issues noted: - Ice plant equipment appeared to be maintained fairly well - Verify comprehensive routine maintenance program 30

31 Ice Plant & Ice Storage Bin Ice Plant Equipment - Lower bearing at ice surge bin is damaged/worn beyond limits - Frozen over evaporators in ice storage bin - Inoperative evaporator fans in ice storage - Replace ice surge bin bearing and hardware with food grade products (must be greased on a regular basis) - Verify operation of heat strips within ice storage bin - Replace/troubleshoot inoperative fans in ice storage bin evaporators 31

32 Blast Chiller View of Blast Chiller Evaporator Coils - Damage to coils from trays/carts - Corrosion damage to evaporator aluminum fins - Verify proper operation and refrigerant pressure - Clean coils with non-corrosive cleaner - Install impact protection to prevent future damage 32

33 Freezers/Coolers Evaporators in food storage area - Forklift damage to evaporator (unit appeared functional) - Verify drip pan drainage flow - Food preparation room coils showing aluminum corrosion and deterioration - Install forklift protection or remove storage racking near evaporator assemblies to prevent future damage - Monitor evaporator effectiveness and replace coils as necessary - Clean cold room evaporator coils o Refrain from using any corrosive cleaner on coils and rinse thoroughly after cleaning 33

34 Electrical Systems Electrical Room issues - Conduit abandoned/modified (should be removed or boxed and capped) - Numerous wall penetrations in multiple areas require fire stop caulking - Electrical panel schedules may have duplicate entries and lack definition on equipment served Investment required: - Box and/or cap unused conduit - Seal wall penetrations with fire stop - Update panel schedules/labels to reflect as-built service conditions and equipment served 34

35 Electrical Systems Electrical Room issues - Electrical systems were relatively clean and appeared to maintained well. Investment required: - Ensure annual electrical maintenance is performed on switchgear and electrical systems with routine IR scanning 35

36 Lighting Systems Lighting - It was noted that lights were on in unused rooms that and some T 12 fluorescent bulbs were still in use - Energy consumption is increased because of lights being on in unused rooms - It was also noted that a high number of metal halide fixtures are in use Investment required: - Replace T 12 bulbs with T 8 bulbs - Install occupancy sensors in low usage areas to reduce energy consumption - Investigate high efficiency T 5 and/or LED replacements for high bay lights 36

37 Miscellaneous - Warehouse Area Ceiling mounted heater unit. - Damaged heater housing remains mounted over warehouse storage area - Inoperative emergency exit light in warehouse area - Replace damaged gas-fired heater unit - Repair/replace emergency exit light 37

38 Miscellaneous - Dock View of warehouse roll-up/air doors. - Damaged Mars Air Door - Roll-up door drum spring failures - The fan appeared operational but headache bars should be installed to prevent further forklift damage - Replace spring in roll-up door drums 38

39 Miscellaneous - Fire Suppression View of fire hose cabinet and fire panel map. - Fire hoses have been removed and replaced with extinguishers - Supervisory alarms were noted on the fire panel - Replace fire extinguishers with hoses - Repair recently noted fire inspection discrepancies - Contact Fire Detection Suppression contractor to troubleshoot Supervisory Alarms 39

40 Kitchen / Hood Equipment - General Kitchen and Hood Equipment - Kitchen and hood equipment appeared to be maintained fairly well - Ensure annual maintenance and proper regulatory inspections 40

41 Building Automation / Controls Building Management System Controller - The control system is 2004 vintage Andover system that has not had any re-commissioning activity performed - Batteries past age limit noted - Functionality of HVAC Equipment is questionable as it has been reported that heat in some RTU(s) is not functional and the BMS is suspected - Replace batteries on BMS Controllers - Test & Re-commission equipment to verify functionality and check software routines for current building operation 41

42 Repair / Replacement / Life Cycle Analysis As indicated in this assessment, there are numerous repairs and/or equipment/system replacements that are recommended at the United Airlines Chelsea Flight Kitchen facility at the Denver International Airport. Infrastructure equipment and systems within the 20 year old facility indicate that they have generally received routine maintenance, occasional corrective repair and periodic replacement for certain critical systems. However and as indicated, there are various systems that require attention, repair and replacement in order for the facility to continue to function per intended design. The following is a listing of those repairs/replacements with approximate repair/replacement costs (as would be billed by subcontractors) using 2014 RS Means Maintenance and Repair Cost Data which includes labor and materials: Page Description Estimated Cost Replace cracked exterior tile $8,500 Repair stairs, handrail base, planter, and uneven walkway $25,500 Parking lot rod and fill cracks & restripe $24,000 Repair entrance soffit water damage $4,000 Reseal roof membrane cap strip w/ sealant $150 Fence/gate repairs $5,500 Fill cinderblock wall crack and paint wall $1,500 Repair electrical room cinderblock wall crack $1,250 Repair approximately 60' of expansion joint $1,150 Reseal EPDM membrane and wear mats $3,500 Replace missing lightning rods and secure cabling $850 Replace worn carpet in offide areas and floor tiles in restrooms $2,700 Ceiling tile and grid cleaning/replacement $4,500 Replace cafeteria window and adjust associated millwork $2,700 Repair water damage in cafeteria $5,500 Adjust doors and replace weather stripping $500 Replace lifting cafeteria VCT floor tiles $2,200 Replace facility maintenance office window $1,200 Replace boiler sight glass, leaking valves, and chemical quill piping $1,750 Replace 200 gallon water softener $34,000 Repair boiler room underground drain $14,000 Replace boiler room drain cover $150 Replace 1,000 gallon water storage tank $11,000 Replace heat exchanger $19,000 Reinsulate (2) heat exchangers and associated piping $1,200 Rebuild & reseal compressor head $3,600 Test and repair/replace inoperative exhaust fans on roof $8,500 Install grease collection bucket on hot foods exhaust fan $350 42

43 Clean/straighten condenser coils Clean HVAC coils Repair HVAC economizer linkages and test controls/draft motor Test gas valve for heater control and associate BAS controls Clean and coat HVAC drain pans (rust) Troubleshoot (2) frozen compressors (freezer and ice storage bin) $750 $4,500 $2,600 $3,400 $1,250 $3, Reinsulate associated refrigeration piping $1,600 Replace Blast Chiller compressor $7,200 Replace surge bin bearings and shaft $2,200 Replace storage bin evaporator fans (5) and verify defrost operation $900 Clean blast chiller coils and fabricate coil guard $3,500 Verify evaporator drip pan and patch as necessary $500 Clean cold room evaporator coils $3,500 Cap off unused electrical conduit $1,200 Fire seal associated penetrations into the electrical room $1,000 Record end-user equipment on electrical panel schedules $1,500 Replace ceiling mounted warehouse heater $3,700 Replace emergency light in warehouse $300 Replace (2) roll-up door barrell spring assembly ($1,100 per repair) $2,200 Replace (3) fire suppression hoses $1,300 Fire detection/suppression deficiency inspection repairs $3,400 Replace BAS Batteries $400 Recommission and test BAS functionality (HVAC, Parking lot lights, etc.) $13,000 Total Estimated Repair Costs $252,050 Replacement / Life Cycle The above listing represents recommended repairs and replacements for the facility to function per intended design for some period of time. As mentioned, a comprehensive maintenance program is required to sustain that functionality. However, as with all equipment and systems, those within the Chelsea facility have recommended life spans that depend upon various factors including operating environment, duty and schedules as well as the maintenance to which those items receive. Based on those criteria, the following represents a list of major equipment/systems at the Chelsea facility and design life spans and estimated remaining useful life for those items according current condition and current maintenance activity. The list includes estimated replacement costs (using RS Means cost data) that include labor and materials as well as subcontractor s O&P estimates: 43

44 Equipment Design Life (Yrs) Remaining Life (Yrs) Replacement Cost ($) Boiler - Cleaver Brooks - CB $300,000 Boiler - Cleaver Brooks - CB $300,000 Air Compressor - Champion 15 HP 25 5 $15,000 Air Compressor - Champion 15 HP 25 5 $15,000 Air Handling Units - Trane CFM 15 5 $26,000 Air Handling Units - Trane CFM 15 5 $41,000 Air Handling Units - Trane CFM 15 5 $17,000 Air Handling Units - Trane CFM 15 5 $22,000 Air Handling Units - Trane CFM 15 5 $24,000 Air Handling Units - Trane CFM 15 5 $24,000 Makeup Air unit - Trane CFM 15 5 $26,000 Makeup Air unit - Trane CFM 15 5 $25,000 Makeup Air unit - Trane CFM 15 5 $25,000 Makeup Air unit - Trane CFM 15 5 $25,000 Makeup Air unit - Trane CFM 15 5 $19,000 Stean Unit Heaters - (8) Higher Capacity 15 3 $16,000 Roof Hood / Exhaust Fans (12) 20 3 $48,000 Steam Traps (29) 7 1 $9,000 Condensate Pumps (3) 15 3 $9,000 Roof Top Package Units (5) 20 5 $150,000 The above list primarily includes mechanical equipment since most of the equipment is original install and since very little replacement activity has occurred. Additionally, most of the electrical equipment and systems at Chelsea are in good condition and have design lives of 30 years and remaining lives exceeding 10 years. As such, electrical systems are not included in the current equipment/systems replacement listing. Conclusions The United Airlines Chelsea Flight Kitchen facility at the Denver International Airport is in Fair condition. Infrastructure equipment and systems within the 20 year old facility indicate that they have generally received routine maintenance, occasional corrective repair and periodic replacement for certain critical systems. As indicated, there are various systems that require attention, repair and replacement in order for the facility to continue to function per intended design. 44

45 In an effort to assist United Airlines with assigning a value to the facility, current Building Cost Guide data was assessed for US facilities and for facilities in the Denver area. While benchmark building cost data is scarce for Flight Kitchen Facilities, benchmark cost data does exist for warehouse, cold storage and office facilities in various parts of the country. A composite of these along with a geographic normalization factor can reasonably be used to estimate the value of a new flight kitchen facility of similar size in the Denver area. Benchmark building cost data for those facilities is as follows: Facility Cost ($)/Sq. Ft. - Warehouse $53/sq.ft. - Cold Storage $126/sq.ft. - Office $158/sq.ft. For the Chelsea facility, the following square footage estimates are used for usage and value calculations: Chelsea Cost ($) - Warehouse (~50%) (65,000sq.ft.)(0.5)($53/sq.ft.) = $1,722,500 - Cold Storage ( ~25%) (65,000sq.ft.)(.25)($126/sq.ft.) = $2,047,500 - Office (~25%) (65,000sq.ft.)(.25)($158/sq.ft.) = $2,567,500 Total $6,337,500 Based on those averages, new construction costs for a similar facility as the Chelsea Flight Kitchen facility in Denver should be in the range of $6.3 M or at a composite ~$97.5 / sq. ft. These estimates certainly depend on numerous variables including types and quantities of equipment, finishes and amenities. Any final valuation and estimate should be performed by a general contractor and should be based on basis of design and/or actual design documents. The list of recommended repairs and associated costs, the life cycle summary of existing Chelsea equipment and the construction cost comparison are provided to United Airlines to assist in valuation calculations as they prepare to transfer facilities between Chelsea and the LSG facility. This information is based, as indicated, on a visual, non-intrusive inspection of the equipment and systems and should be used in conjunction with other analysis to arrive at final facility valuations. 45

www.citiesinspection.com October 5, 2015 Dear Client,

www.citiesinspection.com October 5, 2015 Dear Client, www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.

More information

Building Condition Assessment Report

Building Condition Assessment Report Building Condition Assessment Report Asset C3c - Oak Terrace Cottage 121 Address Riverview Lands, 2601 Lougheed Highway, Coquitlam, BC. V5C 4J2 Construction Year Size (Gross Floor Area) 1920. 2,553 Sq.Ft.

More information

SECTION 00 0110 TABLE OF CONTENTS. H. 00 2115.01 - Proposed Material, Product or Equipment Substitution Request

SECTION 00 0110 TABLE OF CONTENTS. H. 00 2115.01 - Proposed Material, Product or Equipment Substitution Request SECTION 00 0110 PROCUREMENT AND CONTRACTING REQUIREMENTS 1.1 DIVISION 00 -- PROCUREMENT AND CONTRACTING REQUIREMENTS A. 00 0101 - Project Title Page B. 00 0105 - Certifications Page C. 00 0110 - Table

More information

Vision Home Inspection

Vision Home Inspection Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the

More information

SAMPLE SCHEDULE OF VALUES APPLICATION & CERTIFICATE FOR PAYMENT

SAMPLE SCHEDULE OF VALUES APPLICATION & CERTIFICATE FOR PAYMENT SAMPLE SCHEDULE OF S 1.00 General Conditions 1.01 Project Management 1.02 General Superintendent 1.03 Superintendents 1.04 Safety Engineer 1.05 Scheduling 1.06 Field Engineering 1.07 Bonds 1.08 Trailer

More information

Inspecting to a higher standard.

Inspecting to a higher standard. Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com rob@protec-inspections.com

More information

COMPREHENSIVE PROPERTY INSPECTIONS

COMPREHENSIVE PROPERTY INSPECTIONS COMPREHENSIVE PROPERTY INSPECTIONS Thank you for selecting CPI for your Deficiency Observation. A full home inspection was not performed on this property at the buyers request. This inspection is a limited

More information

Property Condition Assessment

Property Condition Assessment Property Condition Assessment Business, Wisconsin Inspection Date: 8/2009 Prepared For: Business Owner Report Number: TD999909 Prepared By: Shamrock Building Inspection Consultants LLC N29 W29951 Shel-Mar

More information

Building Condition Assessment Report

Building Condition Assessment Report C2 - Nurses Resident (aka Administration) Building Condition Assessment Report Asset Address Address Construction Year Size (Gross Floor Area) Asset Type Floors Above Ground Inspection Date C2 - Nurses

More information

Project Close Out Summary

Project Close Out Summary Project Close Out Summary 1. Final Cleaning and Inspection 2. Testing and Certification 3. Demonstration of Systems and Equipment 4. Inspections by Authorities Having Jurisdiction 5. O&M Manuals and As

More information

Facilities Maintenance Standards rev 9-1-2015

Facilities Maintenance Standards rev 9-1-2015 Facilities Maintenance Standards rev 9-1-2015 Purpose The purpose of these standards is to outline the minimum requirements for maintaining state owned facilities and infrastructures in a manner that will

More information

Schedule of Maintenance Fees

Schedule of Maintenance Fees Schedule of Maintenance Fees Effective July 1, 2015 It is the policy of the Housing Authority of Murray not to charge for NORMAL wear and tear. However, the Housing Authority reserves the right in every

More information

Report Index PROPERTY DESCRIPTION 1 ELECTRICAL SYSTEM 2 COMMON INTERIOR AREAS 3 INTERIOR ROOMS 6 KITCHEN 8 BATHROOMS 10

Report Index PROPERTY DESCRIPTION 1 ELECTRICAL SYSTEM 2 COMMON INTERIOR AREAS 3 INTERIOR ROOMS 6 KITCHEN 8 BATHROOMS 10 Report Index PROPERTY DESCRIPTION 1 ELECTRICAL SYSTEM 2 COMMON INTERIOR AREAS 3 INTERIOR ROOMS 6 KITCHEN 8 BATHROOMS 10 PROPERTY DESCRIPTION PROPERTY INSPECTED: INSPECTION ADDRESS: 4722 Baltimore Avenue

More information

SODA SPRINGS JOINT SCHOOL DISTRICT NO. 150 RECOMMENDED REPAIRS, REPLACEMENT, AND ADDITIONS OPINIONS OF PROBABLE COST

SODA SPRINGS JOINT SCHOOL DISTRICT NO. 150 RECOMMENDED REPAIRS, REPLACEMENT, AND ADDITIONS OPINIONS OF PROBABLE COST SODA SPRINGS JOINT SCHOOL DISTRICT NO. 150 RECOMMENDED REPAIRS, REPLACEMENT, AND ADDITIONS OPINIONS OF PROBABLE COST SODA SPRINGS HIGH SCHOOL REPAIRS AND UPGRADES SITE Construction Estimate = $100,000

More information

BUNKER HILL ELEMENTARY SCHOOL

BUNKER HILL ELEMENTARY SCHOOL INITIAL YEAR BUILT 1970 BUILDING AREA 98,200 SF CURRENT PROGRAM CAPACITY 332 ENROLLMENT 2008 387 WARD 5 PROPOSED PROGRAM CAPACITY 750 Site Plan BUNKER HILL - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION

More information

DRAPER ELEMENTARY SCHOOL

DRAPER ELEMENTARY SCHOOL INITIAL YEAR BUILT 1953 BUILDING AREA 54,000 SF CURRENT PROGRAM CAPACITY 250 ENROLLMENT 2008 84 WARD 8 PROPOSED PROGRAM CAPACITY 325 Site Plan DRAPER - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-5

More information

Mechanical, Plumbing, and Fire Protection Conditions

Mechanical, Plumbing, and Fire Protection Conditions Mechanical, Plumbing, and Fire Protection Conditions Mechanical Conditions The mechanical systems within the building consist of a combination of the original 1926 systems and renovations that occurred

More information

MTA UNIVERSAL STATION PEDESTRIAN BRIDGE Los Angeles, CA. Project Manual and Specification 100% PE SUBMITTAL TABLE OF CONTENTS

MTA UNIVERSAL STATION PEDESTRIAN BRIDGE Los Angeles, CA. Project Manual and Specification 100% PE SUBMITTAL TABLE OF CONTENTS Los Angeles, CA Project Manual and Specification DIVISION 1 GENERAL CONDITIONS 01 01 10 STATEMENT OF WORK 01 11 00 SUMMARY OF THE WORK 01 14 05 METRO (OWNER) - DIRECTED STOPPAGES 01 20 00 PRICE AND PAYMENT

More information

PEPPER VINER HOMES WARRANTY GUIDELINES

PEPPER VINER HOMES WARRANTY GUIDELINES PEPPER VINER HOMES WARRANTY GUIDELINES All non-emergency warranty and customer service requests MUST be made in writing. This provides you with documentation and allows Pepper Viner to operate efficiently.

More information

Hamilton-Wentworth Catholic District School Board Event Listing By Ascending Event Year

Hamilton-Wentworth Catholic District School Board Event Listing By Ascending Event Year Hamilton-Wentworth Catholic District School Board Event Listing By Ascending Event Year Printed On: 2003/04/03 St Patrick CES, 7932 Study [03.3-050 Plumbing Piping Systems] Study condition, remaining service

More information

May 5, 2010. Client Client Address. Re: Inspection Address, Chicago, Illinois. Dear Mr. Client,

May 5, 2010. Client Client Address. Re: Inspection Address, Chicago, Illinois. Dear Mr. Client, PROPERTY INSPECTION PROFESSIONALS May 5, 2010 Client Client Address Re: Inspection Address, Chicago, Illinois Dear Mr. Client, On May 4, 2010, Tomacor completed a property inspection of the above referenced

More information

164,491 SF Food Production Facility Situated on 10 Acres Available in

164,491 SF Food Production Facility Situated on 10 Acres Available in 164,491 SF Food Production Facility Situated on 10 Acres Available in Buffalo, New York CONSTRUCTION Acid resistant brick and coated floors in the production area with drains; clear ceiling heights from

More information

Preventative Maintenance

Preventative Maintenance Preventative Maintenance Safety Committee To have a preventative maintenance plan, you should have a Safety Committee. Designate persons involved with day to day operations and grounds control. Use your

More information

Table of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities

Table of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities Division 1 Requirements Design and Construction Quality Campus Master Plans Texas Tech University System Operating and Building Maintenance Project Administration Historically Underutilized Business (HUB)

More information

Self-Home Inspection Checklist

Self-Home Inspection Checklist To be used as a first home visit for note taking. Visit www.homeinspectiondirect.com for more tips and information about buying a home and hiring a home inspector. This form in no way replaces a professional

More information

MURCH ELEMENTARY SCHOOL

MURCH ELEMENTARY SCHOOL INITIAL YEAR BUILT 1929 BUILDING AREA 47,700 SF CURRENT PROGRAM CAPACITY 479 ENROLLMENT 2008 491 WARD 3 PROPOSED PROGRAM CAPACITY 500 Site Plan MURCH - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-5

More information

Facility Summary. Facility Condition Summary. Seattle School District David T. Denny International Infrastructure. Facility Components

Facility Summary. Facility Condition Summary. Seattle School District David T. Denny International Infrastructure. Facility Components Infrastructure Facility Condition Summary Weighted Avg Condition Score Facility Components Systems Surveyor/ Date Done Comments G Sitework.9 Site Improvements Parking Pedestrian Paving Site Development

More information

SECTION 11 78 13 MORTUARY REFRIGERATORS

SECTION 11 78 13 MORTUARY REFRIGERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

Home Management Checklist: Spring

Home Management Checklist: Spring Home Management Checklist: Spring HVAC System Attic Plumbing and Electrical Service air conditioning unit (Ventilation inspected as part of service call). Ensure gutters are discharging water away from

More information

HAMILTON SCHOOL. 1401 Brentwood Parkway, N.E., Washington, DC INITIAL YEAR BUILT 1968 BUILDING AREA

HAMILTON SCHOOL. 1401 Brentwood Parkway, N.E., Washington, DC INITIAL YEAR BUILT 1968 BUILDING AREA INITIAL YEAR BUILT 1968 BUILDING AREA 187,700 SF CURRENT PROGRAM CAPACITY N/A ENROLLMENT 2008 129 WARD 5 PROPOSED PROGRAM CAPACITY N/A Site Plan HAMILTON - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION

More information

How To Get A Building Permit In Florida

How To Get A Building Permit In Florida MIAMI-DADE COUNTY BUILDING DEPARTMENT PERMIT EXEMPTIONS Please note that the exemptions listed in this section are from Florida Building Code requirements only. Other State and County regulatory departments

More information

Building Description Project Description Estimated Cost Notes Total Deferred

Building Description Project Description Estimated Cost Notes Total Deferred Building Description Project Description Estimated Cost Notes Total Deferred Athletic Fields & Grounds Baseball dugouts 125,000 Surface level/inground? Relamp Baseball field 16,000 Relamp Softball field

More information

Restaurant & café guide

Restaurant & café guide 'Helping our customers stay in business by reducing risk' NZI Risk Solutions TM About NZI Risk Solutions NZI has extensive experience in providing expert risk management advice to help our commercial customers

More information

Inspection Report. Dream Home Inspections. www.timinspects.com. 415 Second Ave. Frisco CO 80443-1789 (970) 368-2668

Inspection Report. Dream Home Inspections. www.timinspects.com. 415 Second Ave. Frisco CO 80443-1789 (970) 368-2668 Inspection Report Property Address: 123 Dream Home Way Frisco, CO 80443 Prepared for: Inspector: Tim Nixon Tim Nixon Inspection date: 3/28/2014 1 of 9 General Information Property Information Address:

More information

NYC Department of Education Building Condition Assessment Survey 2014-2015 BROADWAY EDUCATION CAMPUS - MANHATTAN, 26 BROADWAY, MANHATTAN, NY, 10004

NYC Department of Education Building Condition Assessment Survey 2014-2015 BROADWAY EDUCATION CAMPUS - MANHATTAN, 26 BROADWAY, MANHATTAN, NY, 10004 School: InspectionId Asset Data Inspection Type Building Assessment Survey 204-205 BROADWAY EDUCATION CAMPUS - MANHATTAN, 26 BROADWAY, MANHATTAN, NY, 0004 Time In Last Edited 255 MECHANICAL 205-05-8 09:00AM

More information

Facility Assessment Report, Montgomery Independent School District

Facility Assessment Report, Montgomery Independent School District THE LEARNING CENTER CAMPUS DATA THE LEARNING CENTER 700 Dr. Martin Luther King Jr. Drive, Montgomery TX 77356 Year Built 1958 Approx. Total Square Footage Grades Served Current Enrollment 22,050 n/a n/a

More information

How To Check For A Deficiency

How To Check For A Deficiency UPCS in Pictures The following pictures are not all inclusive nor does it cover every deficiency. The pictures, however are some of the most commonly cited deficiencies on REAC inspections. Erosion The

More information

Roof Inspection. Summary Report

Roof Inspection. Summary Report www.real-estate-inspections.com Roof Inspection Summary Report Subject Property Prepared for: File Number: Client in Detroit 05-15-RF-004 Inspector: Craig Milliken, PE # 32779 CPM Real Estate Inspections,

More information

Guide to Care and Maintenance

Guide to Care and Maintenance Village of Mount Prospect Guide to Care and Maintenance of Your Apartment Sponsored ed by: y: Village of Mount Prospect Envir nvironmental Health Division with the assistance of The Concerened ened Owners

More information

Inspecton Report. Property Address:

Inspecton Report. Property Address: Inspecton Report Provided by: National Home Inspections Inspector: Bob Smith 456 S Main Denver, CO 46312 (645) 423-3242 bob@nationalhomeinspections.com www.nationalhomeservices.com Property Address: 873

More information

Element D Services Plumbing

Element D Services Plumbing PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL

More information

Nominal Life Expectancy for Building Components

Nominal Life Expectancy for Building Components Nominal Life Expectancy for Building Components Building System Page A. HVAC 2 B. Elevator/Escalator 6 C. Plumbing 7 D. Roofing 8 E. Electrical 10 F. Fire/Life/Safety/Security System 11 G. Interior Finishes

More information

Board Seminar Facilities. School Year 2012-2013. Submitted by Joseph L. Lisa-Director of Facilities

Board Seminar Facilities. School Year 2012-2013. Submitted by Joseph L. Lisa-Director of Facilities Board Seminar Facilities School Year 2012-2013 Submitted by Joseph L. Lisa-Director of Facilities High School Installed new fence for Pre-K activities by weight room. Installed new rails and side walks

More information

Roof Inspection. Summary Report

Roof Inspection. Summary Report Phone: (561) 866 9956 www.real-estate-inspections.com Roof Inspection Summary Report Subject Property File Number: 05-15-RF-002 Inspector: Craig Milliken, PE CPM Real Estate Inspections, Inc. Date of Inspection:

More information

ORANGE UNIFIED SCHOOL DISTRICT SCHOOL FACILITIES MASTER PLAN NEEDS ASSESSMENT

ORANGE UNIFIED SCHOOL DISTRICT SCHOOL FACILITIES MASTER PLAN NEEDS ASSESSMENT 1. SAFETY, HEALTH, CODE 1.1 Structural Requirements, Seismic Stability 1.1.1 Primary Structure 1.1.2 Ceilings 1.1.3 Cabinets, Equipment 1.1.4 Portables 1.2 Fire / Life Safety 1.2.1 Corridor, Separation

More information

RESPONSIBILITY FOR REPAIRS AND MAINTENANCE FAIR FUNDING: April 2002

RESPONSIBILITY FOR REPAIRS AND MAINTENANCE FAIR FUNDING: April 2002 RESPONSIBILITY FOR REPAIRS AND MAINTENANCE FAIR FUNDING: April 2002 INDEX New Build Flat and Pitched Roofs Rainwater Goods Porches to Existing Buildings / Covered Links etc, Between Buildings Floors /

More information

SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY

SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY Construction Criteria The unit costs for (Wet) space types are based on the construction quality and design features in the following table. This

More information

Presentation to Senate Select Committee on Government Facilities: Deferred Maintenance for State Supported Living Centers and State Hospitals

Presentation to Senate Select Committee on Government Facilities: Deferred Maintenance for State Supported Living Centers and State Hospitals Presentation to Senate Select Committee on Government Facilities: Deferred Maintenance for State Supported Living Centers and State Hospitals Les Butler Associate Commissioner for Business and Regional

More information

DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS

DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 MINORITY AND WOMEN S BUSINESS ENTERPRISE PARTICIPATION

More information

CONSERVATION MAINTENANCE WORKSHEET Universal Checklist

CONSERVATION MAINTENANCE WORKSHEET Universal Checklist 3.1 SITE 1 Concrete curbs Check for cracks, spalling, growth from joints X 2 Stone curbs Check for cracks, spalling, growth from joints X 3 Concrete walkways Look for uneven surfaces, ponding, growth from

More information

Name Of Occupancy Date. Yes No Describe

Name Of Occupancy Date. Yes No Describe FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address

More information

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C. CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front

More information

later damage - Loss ControL

later damage - Loss ControL later damage - Loss ControL axisinsurance.ca Table of Contents EXECUTIVE SUMMARY... 1 FACILITY SYSTEMS WATER DAMAGE... 2 Frozen Pipes.....................................................................................

More information

How To Plan A Building

How To Plan A Building State of Nevada Department of Administration Purchasing Division Las Vegas Purchasing Warehouse Facility Condition Analysis LAS VEGAS PURCHASING WAREHOUSE 1054 South Commerce Street Las Vegas, Nevada Site

More information

Simplify. Homeownership

Simplify. Homeownership Simplify Homeownership Home Pulse An Innovative Program To Maintain Your Home. The Home Pulse Preventive Maintenance Plan will keep your home looking great, dramatically slow the deterioration process

More information

29 Broadway- 14 th Fl Tel: 212.888.8334 New York NY 10006 Fax: 212.419.1939. Due Diligence Report. New York, New York

29 Broadway- 14 th Fl Tel: 212.888.8334 New York NY 10006 Fax: 212.419.1939. Due Diligence Report. New York, New York Due Diligence Report New York, New York Prepared for Mr. On February 8, 2010 P a g e 1 Table of Contents PAGE 3.. GENERAL INFORMATION PAGE 4 FILINGS PERMITS AND ENCUMBRANCES PAGE 6. CORE AND SHELL PAGE

More information

Sub-Bid Contractor Update Statement. Tab A - Invitation for Bids. Tab B - Instructions to Bidders

Sub-Bid Contractor Update Statement. Tab A - Invitation for Bids. Tab B - Instructions to Bidders INTRODUCTORY INFORMATION TABLE OF CONTENTS 00 0101 PROJECT TITLE PAGE PROCUREMENT REQUIREMENTS (PROJECT MANUAL) Tab A - Invitation for Bids Tab B - Instructions to Bidders Tab C Bid Form for General Bids

More information

UNIVERSITY OF CALIFORNIA, SAN DIEGO

UNIVERSITY OF CALIFORNIA, SAN DIEGO UNIVERSITY OF CALIFORNIA, SAN DIEGO UCSD BERKELEY DAVIS IRVINE LOS ANGELES MERCED RIVERSIDE SAN DIEGO SAN FRANCISCO SANTA BARBARA SANTA CRUZ UNIVERSITY CENTERS - 0076 PHONE: (858) 822-4987 9500 GILMAN

More information

Commercial Roof Management

Commercial Roof Management Disclaimer: This material is designed and intended for general informational purposes only, and is not intended, nor shall it be construed or relied upon, as specific legal advice. Roof damage is a leading

More information

Home Maintenance Checklist

Home Maintenance Checklist Regular maintenance keeps your home functioning efficiently and safely and helps protect its value. We're happy to offer this checklist of ongoing and seasonal maintenance steps to help you safeguard your

More information

KIEWIT CM/GC Enabling/Utilities

KIEWIT CM/GC Enabling/Utilities South Terminal Redevelopment Program KIEWIT CM/GC Enabling/Utilities Contract Value $50 million M/WBE Goal 20 percent Contact John Todd, LEED AP Project Manager 303.930.9046 john.todd@kiewit.com General

More information

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to

More information

PROPERTY INSPECTION REPORT

PROPERTY INSPECTION REPORT (850) 297-1998 1716 Monticello Dr Tallahassee, Florida 32303 PROPERTY INSPECTION REPORT THIS INSPECTION IS A DETAILED LISTING OF AREAS VISUALLY INSPECTED AT:, Tallahassee FL Client Tallahassee, FL 32304

More information

COST OF WORK FORM. Abbreviations: ea = each, LF = linear feet, SF = square feet, HSF = square feet of living area (including garage conversion space)

COST OF WORK FORM. Abbreviations: ea = each, LF = linear feet, SF = square feet, HSF = square feet of living area (including garage conversion space) COST OF WORK FORM All costs shown are estimates using base grade materials, taxes, and labor. For houses where a higher quality is indicated, the costs should be increased for work requiring upgraded materials.

More information

Jagger Enterprises, Inc. dba Buckeye Home Inspections 17204 Dorchester Drive Cleveland OH 44119-1302 (216) 486-4663 Fax (216) 486-9922

Jagger Enterprises, Inc. dba Buckeye Home Inspections 17204 Dorchester Drive Cleveland OH 44119-1302 (216) 486-4663 Fax (216) 486-9922 Jagger Enterprises, Inc. dba Buckeye Home Inspections 17204 Dorchester Drive Cleveland OH 44119-1302 (216) 486-4663 Fax (216) 486-9922 November 09, 2002 Name deleted, Esq. address deleted Your client:

More information

Terms of Reference Air Handling Unit (HVAC System) Cleaning

Terms of Reference Air Handling Unit (HVAC System) Cleaning Terms of Reference Air Handling Unit (HVAC System) Cleaning Introduction General cleaning of the air handling units is currently undertaken by the Mechanical Division staff composing of 3 personnel. Cleaning

More information

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for

More information

Report for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000

Report for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000 Report for Dick and Jane Homeowner 1234 Lovers Lane, Houston, Texas 77000 March 17, 2004 I NI NP R Inspection Item I. STRUCTURAL SYSTEMS o o o A. Foundations (If all crawl space areas are not inspected,

More information

Acumen Enterprises, Inc.

Acumen Enterprises, Inc. Hourly rates Discount w/o Rebate Electrician $78.00 10% $70.20 $70.73 HVAC Technician $78.00 10% $70.20 $70.73 Insulator $42.00 10% $37.80 $38.08 Sheet Metal Worker $74.00 10% $66.60 $67.10 Plumber/Pipefitter

More information

ADDENDUM NO. 1 TO THE BIDDING DOCUMENTS. HVAC SERVICE AND MAINTENANCE Saint Clair County MidAmerica Saint Louis Airport.

ADDENDUM NO. 1 TO THE BIDDING DOCUMENTS. HVAC SERVICE AND MAINTENANCE Saint Clair County MidAmerica Saint Louis Airport. ADDENDUM NO. 1 TO THE BIDDING DOCUMENTS DATE: May 6, 2016 HVAC SERVICE AND MAINTENANCE Saint Clair County MidAmerica Saint Louis Airport BIDS CLOSE: May 12, 2016, at 2:30 p.m., Local Time TO ALL BIDDERS

More information

Attachment J-C18.1. HVAC Work Instructions

Attachment J-C18.1. HVAC Work Instructions . RFP: Attachment J-C18.1 HVAC Work Instructions NNC13ZFD017J SOW Item No. Title Page C18-02 Control Air Systems Annual PM 2 C18-03 Split System AC Indoor Section Annual PM 3 C18-04 Condensing Unit Semi-Annual

More information

Inspection Report Atlanta Strip Mall Commercial Building Property Address:

Inspection Report Atlanta Strip Mall Commercial Building Property Address: Page 1 of 25 Inspection Report Atlanta Strip Mall Property Address: Smyrna GA 30082 Page 2 of 25 South East Building Consultants Ray Thoroman Serving the entire State of Georgia 6 678-410-3005 Page 3 of

More information

School Construction Authority Architecture & Engineering

School Construction Authority Architecture & Engineering SCOPING GUIDELINES 1.0 GENERAL GUIDELINES 2.0 BUILDING ENVELOPE SCOPING GUIDELINES 3.0 CATEGORIES AND COMPONENTS: The Flood Elimination/Below Grade Capital Category may include some or all of the following

More information

Commercial Roof Inspection Form

Commercial Roof Inspection Form Inspection Date: Inspector: Building Information Building ID: No.: Used For: Year Roof Applied: Building Description: Permanent Temporary Building Type: Retail Industrial Residential Building Name: Building

More information

MY HOME IN A HOUSING BLOCK A GUIDE FOR RESIDENTS

MY HOME IN A HOUSING BLOCK A GUIDE FOR RESIDENTS MY HOME IN A HOUSING BLOCK A GUIDE FOR RESIDENTS -KESKUSTA One half of Finns live in housing blocks, which is a safe and comfortable way to live. Welcome a board! Buildings and the Finnish climate There

More information

A. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project.

A. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project. DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 08 02 PART 1 GENERAL 1.01 AUTHORITY (CxA) A. The Commissioning Authority (CxA) has been contracted or will be contracted directly

More information

17,280 square feet Overview:

17,280 square feet Overview: CENTRAL OFFICE Located at 167 Boston Post Road, East Lyme, Connecticut, the Central Office was built in 1916 as the original Flanders Elementary School and remains connected to the current school. The

More information

#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist

#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist #506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist Case #: Date: Project Name: Site Address: Application Submittal Building permit applications and plans can be submitted to the

More information

How to Prevent Liquid Damage Property Losses

How to Prevent Liquid Damage Property Losses 1. The leading cause of property losses is from liquid damage. A review of Zurich North America claims data highlights the problem. 2. Water damage originates from a number of sources: Domestic water lines

More information

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Table Z. Troubleshooting Chart for Air Conditioners. Cause Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause

More information

City of Oviedo Commercial Shell Building Permit Application Guidelines

City of Oviedo Commercial Shell Building Permit Application Guidelines City of Oviedo Commercial Shell Building Permit Application Guidelines All permit application packages must be complete prior to acceptance. A complete application package shall include the following:

More information

NEOGARD. Preventive Maintenance Manual

NEOGARD. Preventive Maintenance Manual NEOGARD Preventive Maintenance Manual Fluid-Applied Roof Coating Systems December 2014 Notes NEOGARD luid-applied roof coating systems are designed to be long lasting, monolithic membranes which provide

More information

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

INVOICE. DATE: May 11, 2005. DESCRIPTION Inspection and report on a property located at OF SERVICES: Perfect Street, Sarasota, Fl.

INVOICE. DATE: May 11, 2005. DESCRIPTION Inspection and report on a property located at OF SERVICES: Perfect Street, Sarasota, Fl. INVOICE DATE: May 11, 2005 CLIENT: The Buyer DESCRIPTION Inspection and report on a property located at OF SERVICES: Perfect Street, Sarasota, Fl. TOTAL FEE: $ See Schedule Tom Villani Hallmark Inspection

More information

PLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW

PLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW PRELIMINARY BUILDING REVIEW two sets of the following: Architectural/engineering design development drawings indicating size of the building,

More information

ADDENDUM NO. 1. DATE: February 10, 2015 INVITATION FOR BID: IFB K150015033 1801 Commerce Road Renovations Project DATED: February 9, 2015

ADDENDUM NO. 1. DATE: February 10, 2015 INVITATION FOR BID: IFB K150015033 1801 Commerce Road Renovations Project DATED: February 9, 2015 ADDENDUM NO. 1 DATE: February 10, 2015 INVITATION FOR BID: IFB K150015033 1801 Commerce Road Renovations Project DATED: February 9, 2015 RECEIPT DATE: March 17, 2015 at 2:30 p.m. OPENING DATE: March 18,

More information

Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com

Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Portland Area PO Box 665 West Linn, OR 97068 Ph: (503) 650-6957 Salem Area 5434 River Rd. N; #192 Keizer, OR 97303 Ph: (503) 362-5809

More information

U.S. Department of Housing and Urban Development Office of Public and Indian Housing. A Good Place to Live!

U.S. Department of Housing and Urban Development Office of Public and Indian Housing. A Good Place to Live! U.S. Department of Housing and Urban Development Office of Public and Indian Housing A Good Place to Live! Introduction Having a good place to live is important. Through your Public Housing Agency (or

More information

48. AQUARIUM. Aquarium. Classification: Cluster: Location: Close to junction of Inselrhue and Loiter Way, Belle Isle. Total Area: No.

48. AQUARIUM. Aquarium. Classification: Cluster: Location: Close to junction of Inselrhue and Loiter Way, Belle Isle. Total Area: No. Classification: Cluster: Location: Total Area: No. of Stories Aquarium Acreage Owned: Acquired: 1904 Most Recent Improvements: THE AQUARIUM Close to junction of Inselrhue and Loiter Way, Belle Isle Two

More information

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may

More information

PREVENTING GROUNDWATER POLLUTION: SECONDARY CONTAINMENT

PREVENTING GROUNDWATER POLLUTION: SECONDARY CONTAINMENT PREVENTING GROUNDWATER POLLUTION: SECONDARY CONTAINMENT PREVENTING GROUNDWATER POLLUTION IS EVERYONE S JOB! Even if our drinking water comes from rivers, lakes, or reservoirs, we need to be mindful of

More information

Preventive Maintenance. State Energy Assessment Workshop By: DTE Energy Partnership & Services

Preventive Maintenance. State Energy Assessment Workshop By: DTE Energy Partnership & Services Preventive Maintenance State Energy Assessment Workshop By: DTE Energy Partnership & Services Do you know? World wide research has shown that one of the reasons causing 80% of the accidents is deficient

More information

costs and billing Facilities Services State-Funded and Billable Services Centrally Funded Services for State Supported Spaces Billable Services

costs and billing Facilities Services State-Funded and Billable Services Centrally Funded Services for State Supported Spaces Billable Services Facilities Services State-Funded and Facilities Services receives funding to provide maintenance in eligible state-supported areas. State-supported areas, equipment, and facilities are those that are utilized

More information

PLP - TERMS AND CONDITIONS

PLP - TERMS AND CONDITIONS PLP - TERMS AND CONDITIONS 2014-2015 Philadelphia Gas Works Residential Parts & Labor Plan Contract This Residential Parts & Labor Plan Contract (this Plan ) is available to customers of the Philadelphia

More information

Number Northern Arizona University Facility Services Section Page. Effective April 1, 2011

Number Northern Arizona University Facility Services Section Page. Effective April 1, 2011 Facility Services Section Page Recharge Services, Maintenance and Construction PURPOSE 1 of 6 The purpose of this policy is to set forth standards for chargeable services for maintenance and construction

More information

Inspection Item COMMENTS

Inspection Item COMMENTS APPENDIX 9 AFFORDABLE HOUSING PROGRAM INSPECTION CHECKLIST Participating Jurisdiction: Homeowner Name: Assisted Property Address: Date of Physical Inspection of Property: Total Square Footage of Property:

More information

VOLUME V GUIDELINES FOR DESIGN CONSULTANT TABLE OF CONTENTS APPENDIX B: MASTER CONSTRUCTION SPECIFICATIONS AND PREPARATION GUIDE, DIVISIONS 0-10

VOLUME V GUIDELINES FOR DESIGN CONSULTANT TABLE OF CONTENTS APPENDIX B: MASTER CONSTRUCTION SPECIFICATIONS AND PREPARATION GUIDE, DIVISIONS 0-10 VOLUME V GUIDELINES FOR DESIGN CONSULTANT TABLE OF CONTENTS APPENDIX B: MASTER CONSTRUCTION SPECIFICATIONS AND PREPARATION GUIDE, DIVISIONS 0-10 SECTION B1: PREPARATION GUIDE B1.1 INTRODUCTION... B1-1

More information

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...

More information

Commercial Fire Inspections

Commercial Fire Inspections Commercial Fire Inspections Fire Department Inspection Requests and Procedures The following guidelines shall be used when calling for inspection requests: 1. All inspection requests shall be coordinated

More information