Standardized energy measurement concept for data centers and their infrastructures
|
|
|
- Blaise Beasley
- 9 years ago
- Views:
Transcription
1 Standardized energy measurement concept for data centers and their infrastructures Bigfoot Technology Version 05 / 30 June 2008 / English translation / 10 February 2009 Amstein + Walthert SA, Rue Pécolat 1, CP 1044, CH-1211 Geneva Telephone , Fax ,
2 Masthead Instructing party Agent Dr. Bernard Aebischer CEPE (Centre for Energy Policy and Economics) ETH Zürich Zürichbergstrasse 18 CH-8032 Zurich Tel : Fax : [email protected] AMSTEIN + WALTHERT SA Rue Pécolat 1 CP 1044 CH-1211 Genève 1 JOBST WILLERS Engineering AG Quellenstrasse 1 CH-4310 Rheinfelden Authors Tel Fax Corentin Maucoronel Pierre-Jean Duc Tel Fax Jobst Willers Distribution Dr. Bernard Aebischer Versions Version 5 Validation Date Signature Entitled R2728MC5_Coefficient_C1.doc H:\Cepe\Projekte\Data Centers\2007-\ScanE\Messkonzept\english\Measurement-concept_aebischer_ doc 2/20
3 Contents Accepted modifications... 4 List of the main abbreviations Presentation of the study Methodology Consumers to take into account Configurations Energy measurement principle Basic data Aim of the energy measurement concept Structure of the measurement concept Data processing Measuring devices Requirements of measuring devices Recommended measuring devices Costs Annexes H:\Cepe\Projekte\Data Centers\2007-\ScanE\Messkonzept\english\Measurement-concept_aebischer_ doc 3/20
4 Accepted modifications The following modifications are accepted by the parties and are covered in the corresponding individual chapters in the list of specifications. N. Date Index Signature Entitled MAUC Merge of the A+W and Willers reports MAUC Corr. according to Aebischer of MAUC Aebischer data table integration MAUC Insertion of abbreviation glossary H:\Cepe\Projekte\Data Centers\2007-\ScanE\Messkonzept\english\Measurement-concept_aebischer_ doc 4/20
5 List of the main abbreviations AHU: Air Handling Unit. Critical MCC (Motor Controlled Center): motorized systems outside of computer racks which need to be supplied with backed-up power (for example pumps, ventilators, etc.). C1 = DCiE = 1/PUE DCiE = 1/PUE = C1 EJPD: Federal Justice and Police Department. CSV file: A CSV file is a tabular file containing data on each line separated by a separator character (generally a comma or a semi-colon). GEN: Diesel motor type back-up group. Gen Sw Gear: electricity distribution cabinet for the back-up power supply IEC: International Electrotechnical Commission. M-bus: The M-Bus (Meter Bus) is a European standard for remote reading of heat or electricity meters. Mech Sw Gear: electricity distribution cabinet for ventilation and air conditioning systems. No-break: Uninterruptible electrical power supply systems with flywheel. NOE: New Electricity Supply developed by the utility Geneva Industrial Services. OPC: OLE (object linking and embedding) for Process Control is a technical specification defining a standard set of interfaces based on OLE COM/DCOM technology developed by Microsoft. PDU: Power Distribution Unit. SICC: Society of Heating and Air Conditioning Engineers. UPS/ASC: Uninterruptible power supply system, battery-powered inverter. Utility Sw Gear: Main electricity distribution cabinet. H:\Cepe\Projekte\Data Centers\2007-\ScanE\Messkonzept\english\Measurement-concept_aebischer_ doc 5/20
6 1 Presentation of the study The Standards Commission of the Canton of Geneva mandated Bernard Aebischer from CEPE (Centre for Energy Policy and Economics) at ETH Zürich to prepare a standardized measurement concept for DCiE. DCiE is the ratio between the electrical energy consumed by the IT equipment inside a data center and the total electrical energy needed for the correct functioning of the same data center (IT equipment and infrastructure). Electricity consumption of IT equipment DCiE = 1/PUE = C1 = Total electricity consumption of the data center This measurement concept shall then be used by mandated engineering firms to measure DCiE of individual data centres. The collected data of all data centres will be pooled together in a benchmarking process. To get comparable data, the measurement concept must present a clear methodology to perform measurements according to the same principles, in order to guarantee reliable results and optimal costs. This document has been jointly drawn up by Amstein + Walthert Genève SA and Jobst Willers Engineering AG. H:\Cepe\Projekte\Data Centers\2007-\ScanE\Messkonzept\english\Measurement-concept_aebischer_ doc 6/20
7 2 Methodology 2.1 Consumers to take into account The different main consumers to take into account for the coefficient DCiE measurement are presented in the table below. We also give some comments regarding the measurement principle and the possible alternatives. The comments are of a general nature and an in situ analysis/study of the data center and building configuration is indispensable before installing energy meters. The main difficulty remains the calculation of the electrical energy consumed by air conditioning as, in most cases, a single cooling system supplies refrigeration to the whole building housing the data center. Main consumers IT equipment (computer racks and servers). Uninterruptible power supply systems (UPS/ASC, No-break) Server room lighting Air conditioning cabinets Comments on energy measurements Measuring devices to be installed on the PDU(s) incoming power supply line if power is supplied only to the IT equipment. Otherwise, one meter per outgoing power supply line from the PDU(s). The short-break back-up units (ex: diesel back-up units) may be disregarded as they have very little or no electricity consumption in stand-by and operating mode, unlike no-break systems. If the lighting is not powered by the PDU or a specific power supply unit for the server room, a specific electrical meter should be installed to measure the energy consumed by lighting. If the lighting power supply comes from a unit shared by the whole building, it is possible to calculate the installed capacity in person and install a light-detecting meter. Most data centers are cooled using air conditioners located in the data center itself or in adjoining premises. The electricity consumption of these devices can essentially be imputed to the ventilators, but sometimes also to directly integrated thermodynamic systems (compressors Split system). H:\Cepe\Projekte\Data Centers\2007-\ScanE\Messkonzept\english\Measurement-concept_aebischer_ doc 7/20
8 Main consumers Ventilation Comments on energy measurements If an air handling unit (AHU) is dedicated exclusively to the data center, then it will be necessary to install an electricity meter on this AHU. Proposal: if the air renewal system of the data center is part of a general AHU for the building, for which the total flow is >80% of the air renewal flow for the data center, then the consumption of this general AHU does not need to be measured. Refrigerating machines If the refrigerating machines supply refrigeration to consumers other than those dedicated to data center air conditioning, it will be necessary to install a refrigeration energy meter on the primary chilled water circuit as well as a meter on the secondary distribution circuit(s) to the consumers dedicated to data center air conditioning. Air coolers and cooling towers Cooling pump(s) Primary and secondary chilled water pumps Table 1: main consumers and particular comments Measuring devices to be installed on the power supply unit of this piece of equipment. If this (these) pump(s) is (are) supplied by a different electrical power unit from the power supply unit of the air coolers or cooling towers, or by a different electrical power unit from the hydraulic refrigeration distribution power supply unit, it must be fitted with an electrical energy meter, on the condition that its electrical power or the total electrical power of the pumps is above 1.5 kw If these pumps are supplied by a different electrical power unit from the hydraulic refrigeration distribution power supply unit, they must be fitted with electrical energy meters on the condition that their electrical power or the total electrical power of the pumps is above 1.5 kw (proposal). H:\Cepe\Projekte\Data Centers\2007-\ScanE\Messkonzept\english\Measurement-concept_aebischer_ doc 8/20
9 2.2 Configurations The configuration of data centers is not uniform and varies strongly from one site to another and according to year of completion. This variety is the main difficulty in defining a global and universal measurement concept. We can classify the data centers based on the electrical distribution topology and the type of cooling system Main electrical configurations The electrical configuration types (electrical distribution to servers and infrastructure) are the simplest to define: for this purpose, we can take the 4 configurations presented by the Uptime Institute for Tier Level classification 1 (see Figures 1 to 3). Figure 1: typical configuration of the electrical system topology of a data center at Tier Level I (left) and Tier Level II (right) source: Uptime Institute 1 H:\Cepe\Projekte\Data Centers\2007-\ScanE\Messkonzept\english\Measurement-concept_aebischer_ doc 9/20
10 Figure 2 : typical configuration of the electrical system topology of a data center at Tier Level III source: Uptime Institute Figure 3 : typical configuration of the electrical system topology of a data center at Tier Level IV source: Uptime Institute Air conditioning systems for data centers can be classified in two main areas: Technology used: chilled water, direct expansion refrigeration system, cooling by air conditioning cabinet, centralized monoblock, autonomous racks, use of cooling towers, air coolers, air condensers, etc. Refrigeration production dedicated to the Data center or not. It is in relation to this last comment that we shall distinguish the two main methods of measurement. H:\Cepe\Projekte\Data Centers\2007-\ScanE\Messkonzept\english\Measurement-concept_aebischer_ doc 10/20
11 2.2.2 Refrigeration production dedicated to the Data center This is the simplest and most favourable case for electricity measurement. To explain the measurement principle, we shall detail the distribution of energy meters on the schematic diagram of Tier Level IV (which is the most complex). We present below two typical diagrams, which summarize certain comments from Table 1. When refrigeration production is dedicated to the data center, electricity measurements are simplified. However, it is advised to pay attention to the position of the electrical meter measuring the power supplied to the servers: The elctrical meter shall be installed on the PDU incoming power line if, and only if, the PDU only supplies power to the IT equipment (computer and server racks) and not to other ancillary component that is part of the infrastructure (lighting, decentralized ventilator, etc.). An electrical meter shall be installed on every outgoing power supply line of the PDU (so there may be several meters) from the racks and/or servers if the PDU supplies other ancillary components which are part of the infrastructure (lighting, decentralized ventilator, etc.). These different variants are illustrated in figures 4 and 5. Figure 4: measurement principle with dedicated refrigeration production and two lighting variants Electricity meter H:\Cepe\Projekte\Data Centers\2007-\ScanE\Messkonzept\english\Measurement-concept_aebischer_ doc 11/20
12 NO BREAK (standby) Figure 5: measurement principle with dedicated refrigeration production, another lighting variant and no break Refrigeration production not dedicated to the data center For refrigeration production not dedicated to the data center, we have produced a typical diagram which we feel reflects the vast majority of data center chilled water supply systems. This is a system of chilled water production from 1 or 2 refrigerating units cooled by air via air coolers or cooling towers. Based on this diagram (see annex 5.1), it is easy to deduce other system configurations such as cooling by water for example (one need only blank the air cooling system to have the measurement principle for water cooling of the refrigerating units (municipal water, river water, lake water). To deduce the consumption of electrical energy dedicated to data center air conditioning, it is necessary to measure refrigerating energy. These measurements shall be taken: On the primary chilled water circuit to measure the total quantity of cooling energy produced by refrigeration machines. On the secondary circuit, on the outgoing line to consumers dedicated to data center air conditioning. H:\Cepe\Projekte\Data Centers\2007-\ScanE\Messkonzept\english\Measurement-concept_aebischer_ doc 12/20
13 E Machine froid 1 Q1 Autres consommateurs Datacenter Machine froid n Q2 Figure 6: measurement principle for electrical consumption by refrigeration machines in the case of non-dedicated production Electrical refrigeration energy for the data center shall then be calculated as follows: With Ed = E x Q2 / Q1 E = total electrical energy consumed by the refrigeration units Q1 = total cooling energy produced by the refrigeration units Q2 = cooling energy distributed to data center air conditioning A reading of the measurements and transmission of data to the monitoring organization (for example CEPE Centre for Energy Policy and Economics) must be made at least every 2 weeks. H:\Cepe\Projekte\Data Centers\2007-\ScanE\Messkonzept\english\Measurement-concept_aebischer_ doc 13/20
14 3 Energy measurement principle 3.1 Basic data In building technology, there are different standards and directives for the logging and analysis of energy consumption. In Switzerland, the directive SICC 98-1 energy and fluid measurement concept establishes the basis for most projects. On an international level, USA institutes and businesses are particularly involved in standardized consumption logging in data centers. Energy efficiency expressed by coefficient DCiE has been generally imposed. 3.2 Aim of the energy measurement concept The energy measurement concept must create the conditions to reach the following goals: homogenous and consistent measurement concept, simple analysis with report on several installations, assessment of coefficient DCiE. presentation of areas to investigate for optimization measures. 3.3 Structure of the measurement concept Data recording Recording data can be done automatically or manually. In the case of manual recording, the measurements are taken on-site, from meters, periodically. They are then entered into a table provided for this. In the case of automatic data recording, it is advised to connect the meter to a bus system using the M-bus protocol. Using this system, it is also possible to read data in a monthly/weekly/daily or even hourly basis Measurement concept with M-Bus (OPC server) The M-Bus is a system that has been developed to read data from the meter. The M-Bus has the following advantages: widely accepted by measuring device manufacturers, protected against polarity inversion, freedom of network topology: bus, star or tree-type, economical due to low installation costs. Meter information is collected, via de bus, using a signal converter (master) It is possible to connect up to 64 M-Bus meters (slaves) to a signal converter. Once the meters fitted with an M-Bus interface are installed, they are directly connected to the bus. Meters that do not have an M-Bus interface are incorporated using an pulse meter on the M-Bus. The structure of the system with M-Bus appears as follows: H:\Cepe\Projekte\Data Centers\2007-\ScanE\Messkonzept\english\Measurement-concept_aebischer_ doc 14/20
15 Figure 7: M-Bus system topology The signal converters are connected to the OPC server using a TCP/ IP router. In order to avoid excessive calculation loads, it is advised to avoid connecting more than 40 meters (maximum theoretical expansion: 254 components) to an OPC server Remote analysis Remote data analysis can be beneficial in the case of a measurement concept aimed at several installations or a large data center. In this case, data transfer must be controlled using a web inquiry. Figure 8: M-Bus system topology with remote analysis For example, the structure of the system can be as above. Data can be recorded using a Programmable Logic Controler (PLC) with M-Bus interface and integrated web server. The data can then be made available on the internet. H:\Cepe\Projekte\Data Centers\2007-\ScanE\Messkonzept\english\Measurement-concept_aebischer_ doc 15/20
16 Another possibility consists of transmitting the data to the central workstation periodically by Data retrieval There are many possible ways to retrieve data collected with the OPC server (M-Bus), the remote reading system via internet, or through manual readings. For manual readings, the data recorded are entered into a table prepared in an MS Excel spreadsheet. In the case of data recorded using an OPC server (M-Bus), the data is loaded via an OPC Datalogger. The latter provides a CSV file for processing at a later date. The data can be read either with an Excel spreadsheet, or processed using an analytical tool. Regarding remote analysis via internet, the PLC provides a CSV file containing the data collected. The CSV file can be read either with an Excel spreadsheet, or processed using an analytical tool Measurement periodicity We recommend that measurements are taken every ¼ of an hour. This time interval is sufficient for energy measurements and reduce the risk of overloading the memory of measurement devices. 3.4 Data processing For the analysis of energy data, different tables and graphics must be provided for the user. The aim of these tables is to provide a clear overview of data center energy consumption. Here below are the aims of these tables and graphics: Controlling energy consumption Here, the consumption data of an installation or system is monitored in order to determine the variations in energy consumption under constant load conditions. Installations in the area of building technology (ventilation, heating, air conditioning) often work according to the outdoor temperature. Consequently, outdoor temperatures must also be taken into account in the analysis. (Meteosuisse supplies average outdoor temperatures by week and by month). Infrastructure energy efficiency indicator (DCiE) The energy efficiency of a data center (represented by DCiE) can be calculated on the condition that all the required values are recorded. This coefficient is obtained using the following formula: Electricity consumption of IT equipment DCiE = Total electricity consumption of the data center (infrastructures + IT) H:\Cepe\Projekte\Data Centers\2007-\ScanE\Messkonzept\english\Measurement-concept_aebischer_ doc 16/20
17 The presentation of the data analysis can be divided as follows: Energy flow diagram Overview per consumer, per week, month and year Infrastructure energy efficiency coefficient (DCiE) Energy consumption compared to the previous year Presentation Graphic Table X Overall overview by cost centre X X Table 2: presentation of energy consumption data X X X X X X For detailed analysis of the installations, it is advised to distribute the measurement points according to the different cost centres (installations, groups of installations, sectors etc.). The cost centre distribution differs according to each installation configuration and can be presented as follows: Refrigeration production, refrigeration distribution. Air conditioning and ventilation devices. Electrical devices, lighting, etc. Computer systems / racks. H:\Cepe\Projekte\Data Centers\2007-\ScanE\Messkonzept\english\Measurement-concept_aebischer_ doc 17/20
18 4 Measuring devices 4.1 Requirements of measuring devices An appropriate measuring device must meet the following requirements: according to decree SR by the EJPD, regarding business premises, it is compulsory to install meters which are classed in accuracy category B at least. This corresponds to class 1 according to IEC (accuracy of 1%). The device must have an M-Bus interface or impulse output to read measurement values and transfer energy data, Devices installed for electrical energy rebilling must be monitored and calibrated by certified calibration organizations. Specific provisions apply here regarding the periodical calibration of these devices. These provisions are described here below: If electrical energy is rebilled, meters must be calibrated by a certified calibration organization. The devices must be re-calibrated at regular intervals. Decree SR by the EJPD specifies that active energy meters must be re-calibrated every ten years by a certified calibration organization. For electromechanical measurement system meters, the calibration frequency is 15 years. 4.2 Recommended measuring devices Electricity measurements We recommend the electricity meter ELKO. This device especially distinguishes itself by its good value for money compared with other competitors. Device reference DIZ D665DMi (indirect measurement) DIZ D651DMi (direct measurement) Manufacturer Data recording * DT = Time of Day Tarif It is possible to read energy data on-site via a digital screen. Table 3: recommended electricity meters DT* Pulse Analog. M-Bus ELKO X X X ELKO X X X Energy meters have an M-Bus interface and a pulse transmitter. It is therefore possible to connect the device to a Programmable Logic Controler (PLC) via the M-Bus, or via the pulse transmitter. The measurement is taken directly below 65 A. Above this value, the measurement is taken indirectly using a current H:\Cepe\Projekte\Data Centers\2007-\ScanE\Messkonzept\english\Measurement-concept_aebischer_ doc 18/20
19 transformer The mode of operation of the current transformer can be set on the device Thermal measurements The recommended brands for thermal energy metering are Aquametro type Amflo Sonic (ultrasonic) Ambus. 4.3 Costs Electricity meter The average cost of an electricity measurement point without a datalogger is estimated at: Meter ( 63A inc. M-Bus) + wiring + assembly = CHF (EUR 1 000) Heat meter To avoid any additional pressure drop which would disrupt operation, we recommend installing ultrasonic heat meters. The average cost of a heat measurement point without a datalogger is estimated at: Meter + M-Bus interface + wiring + assembly = CHF (EUR 2 300) This estimate is based on a meter for a hydraulic line of DN Datalogger The datalogger is only necessary if the site does not possess a supervision system or if it is not possible to integrate measurement points easily, or if the client does not wish to integrate these points into their B.M.S. (Building Management System). The average cost of a datalogger is estimated at: Datalogger + program + commissioning = CHF (EUR 2 700) H:\Cepe\Projekte\Data Centers\2007-\ScanE\Messkonzept\english\Measurement-concept_aebischer_ doc 19/20
20 5 Annexes 5.1 Non-dedicated refrigeration production metering principle 5.2 Example of measurement results presentation H:\Cepe\Projekte\Data Centers\2007-\ScanE\Messkonzept\english\Measurement-concept_aebischer_ doc 20/20
21 DRY COOLER or COOLING TOWER MECHANICAL SW GEAR Cooling pump GENERATOR E MAIN ELECTRICAL BOARD Other energy consumption not for datacenter COOLING MACHINE n COOLING MACHINE 1 Main cold water pump UPS 1 UPS n MECHANICAL SW GEAR Q1 ELECTRICAL SW GEAR Other energy consumption for datacenter Secondary cold water pump Building Air Conditionning (without datacenter) Q2 Other use (without datacenter) ORDINATEURS COMPUTER SERVEURS SERVERS ROOM AIR HANDLING UNIT ELECTRICAL ENERGY METER COOL ENERGY METER ELECTRICAL WIRE COLD WATER PIPES COOLING WATER PIPES C1 MEASUREMENT INTO DATACENTER Non-dedicated refrigeration production metering principle Amstein + Walthert
22 Annex 5.2 Example of data sheet Source: CEPE - Aebischer Data Centre nr 1 Location Zurich Current year 2006 Month Total consumption Consommation ITequipment DCiE Mean electric load ITequipment Floor area IT rooms Mean electric load ITequipment by floor area Mean outside temperature [kwh] [kwh] [KW] [m2] [W / m2] [ C] January February March April Mai June July August September October November December Total 11'312'109 7'026' ' Past year 2005 Month Total consumption Consommation ITequipment DCiE Mean electric load ITequipment Floor area IT rooms Mean electric load ITequipment by floor area Mean outside temperature [kwh] [kwh] [KW] [m2] [W / m2] [ C] January February March April Mai June July August September October November December Total 8'462'758 5'331' '
System integration oriented data center. planning. In terms of ATEN's eco Sensors DCIM solution
System integration oriented data center planning In terms of ATEN's eco Sensors DCIM solution 1. Introduction The reliability of an enterprise data center servicing either external or internal clients
Recommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE for Data Centers 17 May 2011 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations for Measuring
Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics
On January 13, 2010, 7x24 Exchange Chairman Robert Cassiliano and Vice President David Schirmacher met in Washington, DC with representatives from the EPA, the DOE and 7 leading industry organizations
How To Save Energy With High Pressure Control
Energy savings in commercial refrigeration equipment : High Pressure Control July 2011/White paper by Christophe Borlein AFF and IIF-IIR member Make the most of your energy Summary Executive summary I
AMTRON E-30 Compact heat and cooling meter
AMTRON E-30 Compact heat and cooling meter Application The compact AMTRON E-30 meter is used for energy consumption measurements for heating and cooling applications in small premises such as apartments,
Documentation. M-Bus 130-mbx
Documentation M-Bus 130-mbx Introduction The mx M-Bus module is part of the mx Smart Slot communications family. With the integrated SmartSlot technology, mx systems ag offers automatic consumer data read-out
POLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, 2014. C arastro & A ssociates, C&A# 5747
POLK STATE COLLEGE WINTER HAVEN, FLORIDA CHILLER PLANT EVALUATION APRIL 2, 2014 C&A# 5747 C arastro & A ssociates, c o n s u l t i n g e n g i n e e r s inc. 2609 W. De Leon Street, Tampa, Florida 33609
Guidance for Calculation of Efficiency (PUE) in Data Centers
Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 1 by Victor Avelar > Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or
Recommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 1 Measuring PUE at Dedicated Data Centers 15 July 2010 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations
Guidance for Calculation of Efficiency (PUE) in Data Centers
Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 3 by Victor Avelar Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or other
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
COOLSIDE box R410A. conditioned server - racks for direct installation into the room INVERTER E C
COOLS conditioned server - racks for direct installation into the room COOLSIDE box INVERTER R410A E C 2 COOLSIDE box GENERAL FEATURES COOLSIDE BOX is a split system consisting of an outdoor motocondensing
Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME
Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME 2 AGENDA SESSION -1 What is Data Center? SESSION -2 Equipment and Components SESSION -3 Standard in designing Data Center
I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015
I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 8, Loughborough University, 29 th June 2015 Topics to be considered 1. Progress on project tasks 2. Development of data centre test facility
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied
European Code of Conduct for Data Centre. Presentation of the Awards 2014
European Code of Conduct for Data Centre Presentation of the Awards 2014 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European
Power Proportional Distribution (PPD)
1. Description The feature supplies the user with a reasonably calculated apportionment of the total power consumption by the Daikin air-conditioning system to individual indoor units in the system. Because
RULES FOR THE SETTING UP OF SUSTAINABLE BRANCHES Summary
RULES FOR THE SETTING UP OF SUSTAINABLE BRANCHES Summary January 2013 TABLE OF CONTENTS INTRODUCTION... 3 GENERAL RECOMMENDATIONS... 3 Communication with customers in the field of environmental sustainability...
DATA CENTER ASSESSMENT SERVICES
DATA CENTER ASSESSMENT SERVICES ig2 Group Inc. is a Data Center Science Company which provides solutions that can help organizations automatically optimize their Data Center performance, from assets to
CoolTeg Plus Chilled Water (CW) version: AC-TCW
version: 12-04-2013 CONTEG DATASHEET TARGETED COOLING CoolTeg Plus Chilled Water (CW) version: AC-TCW CONTEG, spol. s r.o. Czech Republic Headquarters: Na Vítězné pláni 1719/4 140 00 Prague 4 Tel.: +420
Data Center Energy Use, Metrics and Rating Systems
Data Center Energy Use, Metrics and Rating Systems Steve Greenberg Energy Management Engineer Environmental Energy Technologies Division Lawrence Berkeley National Laboratory October 31, 2007 Today s s
Improve competiveness of IDC and enterprise data centers with DCIM
Improve competiveness of IDC and enterprise data centers with DCIM This paper studies the implementation of modern DCIM systems for data centers to improve operational competitiveness with ATEN's DCIM
scalable data centre energy management solution
scalable data centre energy management solution scalable data centre energy management solution EcoMeasure - Scalable Data Centre Energy Management & Efficiency Measurement Solution by Workspace Technology
Application Briefs: Remote Office Environment
Overview Remote offices are a definite sign of growth, but it can constitute an immense challenge from an IT infrastructure standpoint. Remote offices may include a wide variety of wiring closets and small
Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres
What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy
Web Datalogger. Unit RS232C. General-purpose modem RS485. IP address search screen
Equipment, facilities, and service networks for data collection/logging, data transfer via e-mail/website, and system streamlining can be established without special knowledge. Energy saving system in
9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS
9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9.1 Introduction Air conditioning and refrigeration consume significant amount of energy in buildings and in process industries. The energy consumed in
Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
GREEN DATA CENTER DESIGN
Jeffrey Menig Global Facilities Facility Engineering The application of multiple available technologies resulting in improved energy optimization without significantly increasing capital investment. A
Impedance 50 (75 connectors via adapters)
VECTOR NETWORK ANALYZER PLANAR TR1300/1 DATA SHEET Frequency range: 300 khz to 1.3 GHz Measured parameters: S11, S21 Dynamic range of transmission measurement magnitude: 130 db Measurement time per point:
Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM)
Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM) Salim Janbeh Physical Infrastructure Consultant [email protected] PANDUIT You Can t Manage What You Don t Measure:
ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric energy and heat -
Doc. : 08C00031_e Date : 10.02.2009 Page : 1 / 9 ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric - (Preliminary) Doc. : 08C00031_e
Implement Data Center Energy Saving Management with Green Data Center Environment and Energy Performance Indicators
Implement Data Center Energy Saving Management with Green Data Center Environment and Energy Performance Indicators Awareness of environmental protection issues, has many industry types focusing and pursuing
The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space.
The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space. Terminology: Telco: Dmarc: NOC: SAN: GENSET: Switch: Blade
ENERGY AUDIT REPORT MINIMUM REQUIREMENTS
ENERGY AUDIT REPORT MINIMUM REQUIREMENTS Energy Audit Reports must contain the following: 1) Eligibility Criteria: a) Evidence demonstrating that the Eligibility Criteria were met. 2) Participant Information:
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,
Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015
Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Presentation Outline Mechanical Overview Chillers and Pumps Pipework and Ancillaries In Row Cooling Units
Electrical Systems. <Presenter>
Review Root Causes of Energy Inefficiency Roadmap to Maximize Energy Efficiency Best Practices Alternative Energy Sources Controls Take Aways Seek Professional Help. ENERGY INEFFICIENCY OF
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical
Energy savings in commercial refrigeration. Low pressure control
Energy savings in commercial refrigeration equipment : Low pressure control August 2011/White paper by Christophe Borlein AFF and l IIF-IIR member Make the most of your energy Summary Executive summary
Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources
Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources ALEXANDRU SERBAN, VICTOR CHIRIAC, FLOREA CHIRIAC, GABRIEL NASTASE Building Services
NEW GENERATION PROGRAMMABLE AUTOMATION CONTROLLER
NEW GENERATION PROGRAMMABLE AUTOMATION CONTROLLER NEW GENERATION PROGRAMMABLE AUTOMATION CONTROLLER Understanding what a PAC is starts from the understanding of PLC. A PLC is a Programmable Logic while
Modular Chiller Plants for data centers. Downtime isn t acceptable
Modular Chiller Plants for data centers Downtime isn t acceptable Reducing risk with Quick Start A direct solution to your most important challenge uptime. At Johnson Controls we protect our customers
State of the Art Energy Efficient Data Centre Air Conditioning
- White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel
Metering and Managing University of Sheffield Data Centres. Chris Cartledge Independent Consultant [email protected]
Metering and Managing University of Sheffield Data Centres Chris Cartledge Independent Consultant [email protected] Summary ICT Electricity Use Footprint Data Centre Electricity Use European
SHORT TRAINING COURSES
Post Office Box SR 95, Spintex Road, Ghana Tel: +233 302 812680, Fax: +233 302 814709 E mail: [email protected] Website: www.automationghana.com SHORT TRAINING COURSES Equipping industries with
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.
Defining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
CONTOIL DFM 8EDM. Table of contents. Mounting and operating instructions
Mounting and operating instructions CONTOIL DFM 8EDM Table of contents Safety instructions 2 - Designed use - Installation, commissioning and operation - Operational safety - Return of the instruments
How To Improve Energy Efficiency In A Data Center
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment
SHARKY 775 COMPACT ENERGY METER ULTRASONIC
APPLICATION The ultrasonic compact energy meter can be used for measuring the energy consumption in heating / cooling application for billing purposes. FEATURES 4 Approval for ultrasonic meter with dynamic
AIRAH Presentation April 30 th 2014
Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining
Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
Legacy Data Centres Upgrading the cooling capabilities What are the options?
Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems
INFO HTK. Hybrid dry cooler. The reference for hybrid dry cooling. 100 4,000 kw
INFO HTK Hybrid dry cooler The reference for hybrid dry cooling 4, kw JAEGGI The Original Since 929, JAEGGI has been engaged in the development, production and sale of heat exchangers. Since 995, the company
How to choose a heat pump and use it wisely
How to choose a heat pump and use it wisely Contents How does a heat pump work? 2 Insulating your home 3 Heat loss in the home Not all heat pumps are created equal 4 Choosing a heat pump 4 Choosing by
Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues
Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
Control of Computer Room Air Handlers Using Wireless Sensors. Energy Efficient Data Center Demonstration Project
Control of Computer Room Air Handlers Using Wireless Sensors Energy Efficient Data Center Demonstration Project About the Energy Efficient Data Center Demonstration Project The project s goal is to identify
your comfort. our world. DNSS EcoSave A/C remote monitoring and malfunction prediction
your comfort. our world. DNSS EcoSave A/C remote monitoring and malfunction prediction What is DNSS EcoSave? The Daikin Network Service System (DNSS EcoSave) is a Daikin developed internet based remote
RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
Analysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National
Statement of Work. 3.0 Details of Service Pre Start-up. - 1 - Cooling Start-up Service. Installation Service. Table of Contents. 1.0 Executive Summary
Installation Service Statement of Work - 1 - Cooling Start-up Service Cooling Start-up Service Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0 Details
Products and solutions for pumping, irrigation and piping
Products and solutions for pumping, irrigation and piping 100% electricity www.lovatoelectric.com Tra dition and Innovation LOVATO Electric S.p.A. - Bergamo - Italy Since 1922 The first LOVATO Electric
DOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers
DOE FEMP First Thursday Seminar Achieving Energy Efficient Data Centers with New ASHRAE Thermal Guidelines Learner Guide Core Competency Areas Addressed in the Training Energy/Sustainability Managers and
By Authority Of THE UNITED STATES OF AMERICA Legally Binding Document
By Authority Of THE UNITED STATES OF AMERICA Legally Binding Document By the Authority Vested By Part 5 of the United States Code 552(a) and Part 1 of the Code of Regulations 51 the attached document has
Pure Efficiency. C.C.I.A.A.: N REA. 0195268 Cod. Fiscale e P. IVA: 00483230173 Capitale Sociale versato 100.000,00
Pure Efficiency. The need to significantly reduce the production costs to remain competitive on the global market and the requirement to control and lessen the environmental impact of all activities are
Classification and Qualification STANDARDS
Classification and Qualification STANDARDS HVAC Series Classification Title Class Code Date Established Date Revised Operating Engineer Building Service Engineer Air Conditioning/Refrigeration Mechanic
ENERGY TRANSFER SYSTEMS AND THEIR DYNAMIC ANALYSIS
ENERGY TRANSFER SYSTEMS AND THEIR DYNAMIC ANALYSIS Many mechanical energy systems are devoted to transfer of energy between two points: the source or prime mover (input) and the load (output). For chemical
Data Center Commissioning: What you need to know
Data Center Commissioning: What you need to know Course # CXENERGY1511 AIA Provider # 50111116 AABC Commissioning Group CxEnergy Conference Henderson, NV April 30, 2015 Presented by: Judson H. Adams, P.E.,
New Data Center Energy Efficiency Evaluation Index DPPE (Datacenter Performance per Energy) Measurement Guidelines (Ver 2.05)
New Data Center Energy Efficiency Evaluation Index DPPE (Datacenter Performance per Energy) Measurement Guidelines (Ver 2.05) March 3, 2012 Green IT Promotion Council 1/70 Table of Contents 1. Basic Concepts
GHG Protocol Product Life Cycle Accounting and Reporting Standard ICT Sector Guidance. Chapter 8: 8 Guide for assessing GHG emissions of Data Centers
GHG Protocol Product Life Cycle Accounting and Reporting Standard ICT Sector Guidance Chapter : Guide for assessing GHG emissions of Data Centers DRAFT March 0 Table of Contents GHG Protocol ICT Sector
Energy Depot GmbH PRODUCT AND APPLICATION GUIDE. Total Monitoring Solution for PV. Delivering Solutions for Energy Management
Energy Depot GmbH Delivering Solutions for Energy Management PRODUCT AND APPLICATION GUIDE Total Monitoring Solution for PV SOLAR LOGGER & ANALYSIS DC STRING MONITORING Residential Comprehensive Solar
Energy Efficiency Best Practice Guide Data Centre and IT Facilities
2 Energy Efficiency Best Practice Guide Data Centre and IT Facilities Best Practice Guide Pumping Systems Contents Medium-sized data centres energy efficiency 3 1 Introduction 4 2 The business benefits
Daikin Altherma hybrid heat pump. The natural combination
Daikin Altherma hybrid heat pump The natural combination Daikin Altherma hybrid heat pump, the natural combination Why choose Daikin Altherma hybrid heat pump? What the customer wants: more energy efficient
The Different Types of Air Conditioning Equipment for IT Environments
The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.
Intelligent Vibration Monitoring
Diagnostic Systems Condition Based Monitoring Diagnostic Systems Condition Based Monitoring Intelligent Vibration Monitoring efector Octavis for real-time vibration monitoring Solutions for Predictive
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
Measuring Power in your Data Center
RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Raritan Measuring Power in your Data Center Herman Chan, Director, Power Solutions Business Unit, and Greg More, Senior Product Marketing Manager There
Graphical Representation of Installations Renewable Energies and Energy Efficiency Fitting, Quality and Maintenance Management
EUROPASS DIPLOMA SUPPLEMENT TITLE OF THE DIPLOMA (ES) Técnico Superior en Mantenimiento de Instalaciones Térmicas y de Fluidos TRANSLATED TITLE OF THE DIPLOMA (EN) (1) Higher Technician in Thermal and
Managing Power Usage with Energy Efficiency Metrics: The Available Me...
1 of 5 9/1/2011 1:19 PM AUG 2011 Managing Power Usage with Energy Efficiency Metrics: The Available Metrics and How to Use Them Rate this item (1 Vote) font size Data centers consume an enormous amount
Data Centre Testing and Commissioning
Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to
Ammonia Detection System Codes and Design Specifications
Ammonia Detection System Codes and Design Specifications December 28, 2015 Revision 5 920 N Trade Winds Pkwy Columbia, MO 65201 Ammonia detection system codes and design specifications Following is a discussion
The Second Law of Thermodynamics
Objectives MAE 320 - Chapter 6 The Second Law of Thermodynamics The content and the pictures are from the text book: Çengel, Y. A. and Boles, M. A., Thermodynamics: An Engineering Approach, McGraw-Hill,
How to Meet 24 by Forever Cooling Demands of your Data Center
W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the
Data Center Infrastructure Management: ERP for the Data Center Manager
Data Center Infrastructure Management: ERP for the Data Center Manager 1 2 Topics What s DCIM & the ERP Analogy Why DCIM How DCIM Works How DCIM Helps 3 DCIM by Definition DCIM is a system that collects
Green Computing: Datacentres
Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material
Data Center Energy Profiler Questions Checklist
Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space
News in Data Center Cooling
News in Data Center Cooling Wednesday, 8th May 2013, 16:00h Benjamin Petschke, Director Export - Products Stulz GmbH News in Data Center Cooling Almost any News in Data Center Cooling is about increase
Energy Efficiency and Green Data Centers. Overview of Recommendations ITU-T L.1300 and ITU-T L.1310
Energy Efficiency and Green Data Centers Overview of Recommendations ITU-T L.1300 and ITU-T L.1310 Paolo Gemma Chairman of Working Party 3 of ITU-T Study Group 5 International Telecommunication Union Agenda
Elements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
Green Computing: Datacentres
Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material