Data Center Efficiency Metrics and Methods

Size: px
Start display at page:

Download "Data Center Efficiency Metrics and Methods"

Transcription

1 Data Center Efficiency Metrics and Methods q q q q

2 Elements of Data Center Efficiency in effect, what a data center is and does can define what metric is used to decide what is efficient or inefficient. So how do we judge data center efficiency? Because the output of data centers is not a physical object per se, we have been forced to split our metrics into two distinct groups: computing efficiency and physical infrastructure efficiency. Ultimately, the ideal metric would include both. Computing efficiency has had a long history of metrics, almost since the first vacuum tube mainframe could add the proverbial In addition, the speed of the sub-system hardware such as memory, I/O and storage has many of its own individual metrics, all of which are necessary to provide the actual system throughput. Computing systems as a whole have many different system and industry benchmarks. In addition, the nature of output is constantly changing and being redefined. In essence, the system is not just hardware that can be quantitatively measured but also the software as well as the different tasks that it performs. That can make it difficult to define and compare the useful work that a system produces. In October 2007, The Green Grid, a global consortium of IT companies and professionals seeking to improve energy efficiency in data centers, tried to address this question and introduced the following metric: Data Center Productivity = Useful Work/Total Facility Power This was part of its original PUE and DCiE metrics. Still, this is an open issue because the concept of what a data center s useful work is makes it a difficult if not impossible metric to calculate or to get any groups to agree on. This concept was also put forth in 2008 as Corporate Average Data Efficiency (CADE) by the Uptime Institute, a data center research, education and consulting 2 D A T A C E N T E R E F F I C I E N C Y M E T R I C S A N D M E T H O D S

3 organization in New York, and management consulting firm McKinsey & Co.: CADE = Facility Efficiency x IT Asset Efficiency Facility Efficiency = Facility Energy Efficiency Percentage x Facility Utilization Percentage IT Asset Efficiency = IT Utilization Percentage x IT Energy Efficiency Percentage But neither CADE nor Data Center Productivity caught on the way the PUE standard has taken hold. That may be because the PUE metric is easier to implement, and it does not involve any of the complexity of a common agreement on what useful work, computing efficiency or IT asset efficiency is only direct infrastructure power measurements. Infrastructure efficiency is a relatively new area of interest. Until just recently, the concept of energy efficiency in data centers was a distant second to reliability and availability. The Green Grid and the PUE metric came into existence only three years ago. And although there are many critics of the PUE metric, it has helped the industry begin to address energy usage and efficiency. Fortunately, infrastructure energy efficiency is a relatively concrete area, whose components can be quantified and calculated: PUE = Total Facility Power/IT Equipment Power And its reciprocal, DCIE, is defined as: IT Equipment Power/Total Facility Power x 100% For example: PUE = (Total Facility Power) 200 KW/100 KW (IT Equipment Power) = 2.0 DCiE = (IT Equipment Power) 100 KW/200 KW (Total Facility Power) = 50% 3 D A T A C E N T E R E F F I C I E N C Y M E T R I C S A N D M E T H O D S

4 PUE and DCiE are really the same metric, but PUE has become the more common reference. The major positive factor of this metric is its inherent simplicity, which allows it to be easily understood and, therefore, broadly accepted. One the problems with the PUE metric, though, is that it uses power, which is an instantaneous value so that claims of a favorable PUE can be made, but they may not represent a monthly or true annualized average of the data center s efficiency. Of course, once everyone became familiar with PUE, many sites and even some equipment manufacturers started posting how low their PUE is although equipment cannot have a PUE. Some manufacturers have even claimed that they are very close to the perfect PUE of 1.0, which would represent an infrastructure that uses no energy. In reality, most sites have PUE ranges from 1.5 to 2.5, if they properly take measurements according to The Green Grid s guidelines. As a result, there are now also references to an annualized PUE to more accurately reflect the overall efficiency. The ability to accurately monitor the total power to a data center facility in real time as opposed to waiting for the monthly utility bill requires that sensors be installed at the key measurement points. But to measure the energy usage, the electrical distribution panels will need to have a potential voltage transformer, as well as current transformers installed on each output circuit leading to a cooling component. If the entire panel is dedicated to cooling only, then you only need to monitor the main feed to obtain the total cooling energy reading. This is lower in cost and will allow you to calculate your PUE but does not provide detailed information to optimize individual areas or sub-systems. Although each type of cooling system is different, it is important to remember to include all the components not just the computer room air conditioning units (CRACs), such as chillers, external fan decks or pumps. Also make sure that the system you are considering is capable of measuring actual power KW not just KVA and can also record and display energy use over time and pro- 4 D A T A C E N T E R E F F I C I E N C Y M E T R I C S A N D M E T H O D S

5 vide useful information analysis. It should also be able to do subsets of the information, such as cooling and IT load. And last, but not least, it should be able to calculate PUE. In fact, during the U.S. Environmental Protection Agency s sample study in as part of the Energy Star for Data Centers program, it became apparent that of the 120 sites that were involved, a majority were not capable of accurately monitoring the total facility load and the IT load. This was especially true for data centers that were part of a mixed-use building. In the end, the EPA decided to soften the measurement requirements and accept the UPS output instead of the actual IT load. Ideally, the measurement points should be more granular to allow for a more detailed analysis of where the power is going, such as down to the rack level or even the device level. This program has been more than two years in the making and originally involved monitoring more than 120 data centers, but only 61 became valid reference sites. Nonetheless, after 11 months of efficiency sampling, the PUE ranged from a best case of 1.36, a worst case of 3.6 and a median of 1.9. In addition to the EPA program, the U.S. Department of Energy has its Power vs. Energy ALTHOUGH MOST PEOPLE use the terms power and energy interchangeably, they are not the same. Power is an instantaneous measurement expressed in watts or kilowatts (KW) while energy is power over time expressed in kilowatt hours (KWH). The U.S. Environmental Protection Agency originally started to use the term energy usage efficiency (EUE), during the early part of the program and later decided to change it to power usage effectiveness, or PUE, because the industry had adopted PUE. However, although the EPA is calling it PUE in its final version of the program, it has intermixed terms and has redefined its version of PUE = Total Energy/IT Energy. 5 D A T A C E N T E R E F F I C I E N C Y M E T R I C S A N D M E T H O D S

6 DC Pro Software Tool Suite, which includes a Profiling Tool and System Assessment Tools to perform energy assessments on data center systems. The EPA released the final official version of the first Energy Star for Data Centers program on June 7. Although this is still a voluntary standard, the data center industry should take heed and consider the inherent advantages of improving energy efficiency now, even if only lowering operating costs. Many vendors both start-ups as well as major vendors are offering energy monitoring and management packages. They can accept information that may already be available from different brands of equipment such as the UPS, and some can also integrate with existing building management systems. There are a variety of systems that offer a choice or combination of hardwired, networked or even wireless remote units for measuring temperature, humidity and power. The cost of the systems vary widely, based on the number of points and type of measurement, as well as the sophistication and features of the monitoring software package. Costs range from $5,000 to $10,000 for a basic system to between $50,000 and $100,000 or higher for a large-scale installation. Some vendors even offer hosted monitoring solutions for a monthly fee to lower the capital cost of entry. Although you may not have given any serious thought as to how data center efficiency may affect your existing data center s operation, it will force you to reconsider your existing operating practices. Additionally, it certainly will have an impact any future data center designs and the equipment that you purchase. Remember that efficiency has its own economic reward an improved bottom line. Keep in mind that a data center is a 24/7 operation, and IT loads operate year around. This equals 8,760 hours in a year. At 11.5 cents per KWH, each KW saved or wasted represents a $1,000 a year. If your data center operates at a PUE of 2.0, then each KW of IT load will result in a $2,000 annual cost. Ideally, the most efficient data center will be one whose hardware and software delivers the most useful work and is built with an infrastructure that will support the IT load with the lowest overhead. 6 D A T A C E N T E R E F F I C I E N C Y M E T R I C S A N D M E T H O D S

7 SERVER Server Efficiency today s swirling market of green technologies has brought energy-saving technologies to the forefront of most any IT discussion. Although that s good news for savvy, energy-smart resellers, there is a dark side that presents a real challenge to resellers and their customers how to quantify energy use and report it in an actionable fashion. Some would be quick to say it is an easy problem to solve just measure the power used by a server in kilowatt hours, apply an hourly rate and get an answer. Seems simple enough? But there is much more to judging energy efficiencies than counting watt hours. Often forgotten are essential elements, such as CPU utilization, cooling costs, component costs and the effect of loads on the server s subsystems. Add to that often overlooked factors such as power supply efficiencies and rack-based component demands, and it becomes easy to see that there is a lot more to power efficiency than the electric company s energy delivery fees. JUSTIFYING A SERVER REFRESH Server efficiency has a dramatic impact on the PUE ratio, helping to justify the expenses associated with a server refresh, by demonstrating the impact on PUE. Proving server efficiency is dictated by loads. For example, a server that uses little power yet has no CPU utilization is far from efficient. To truly estimate server efficiency, one has to look at CPU utilization as a starting point. Many studies have shown that typical server CPU utilization proves to be less than 15% and, in most cases, as low as single digits. Those numbers can be vastly improved by turning to virtualization technologies, where CPU utilization is often increased to beyond 60%, thus increasing the inherent efficiency without requiring a server refresh. Although increased CPU utilization does lead to increased server efficiency, 7 D A T A C E N T E R E F F I C I E N C Y M E T R I C S A N D M E T H O D S

8 SERVER other methodologies should not be discounted, and other measurements should be taken before finalizing on virtualization as the only way to affordably enhance efficiency and improve PUE. Processing power per rack and the power footprint of each rack should be incorporated into efficiency calculations. It all comes down to a matter of density where density is defined as the number of processor cores per rack. Here, the implementation of blade server technologies leveraging multiple-core CPUs can increase rack density to as many as 1,024 CPU cores per rack. That high density level has the potential to replace dozens of racks in a data center and reduce the power and cooling footprints of the facility. Server design is the primary catalyst for achieving densities of that magnitude. Achieving maximum efficiencies using heavily populated racks usually requires looking at the rack and the integrated components as a whole because high CPU densities dictate that the rack be designed to deliver the power, cooling and management needs of the installed blades. That said, physical server consolidation combined with virtualization technologies lead to the most efficient solution. Nevertheless, there are still many other factors that lead to quantifying server efficiency and consist of the technologies designed to reduce power consumption as well as cooling needs. A closer look at each of those technologies helps to quantify the impact a server refresh may have on server efficiencies. Those technologies include: D Energy Star Specifications: Servers that meet Energy Star requirements incorporate various technologies to reduce power consumption and usually have a savings percentage stated. D New CPUs: Many of the latest-generation CPUs incorporate technologies designed specifically for power consumption reduction such as multiple cores, throttling, voltage drop, integrated virtualization support, ability to shut down unused cores and across core load balancing. 8 D A T A C E N T E R E F F I C I E N C Y M E T R I C S A N D M E T H O D S

9 SERVER D Power Supplies: New standards are increasing the efficiencies of power supplies from lows of 60% to more than 90% in the latest designs. D Fanless Designs: The elimination of cooling fans reduces power consumption. Fanless server designs use less energy and generate less heat. D Increased Density: More CPUs and more cores are being integrated into individual servers or server blades, delivering much more processing power without increased power consumption. To properly calculate the potential savings of a server refresh, each of those above elements must be considered, with the goal of reducing operational costs, which is what improved efficiencies should lead to. REDUCING OPERATING COSTS A 2007 study performed by Lawrence Berkeley National Laboratory showed that servers in a data center account for about 55% of the electricity costs. The remaining power is used by the supporting equipment. With that in mind, it is easy to see how servers affect power consumption and drive the power requirements of the supporting equipment. Simply put, server consolidation can deliver the largest payback over the shortest amount of time for most data centers. Consolidating can save about $560 per year per server. Using virtualization and newer blades, achieving server consolidations of 10 servers into one, can deliver substantial savings for even a small company and deliver a large opportunity for a solution provider in both hardware sales and services. Consolidation also cuts down on the amount of heat generated in data centers. But, like power consumption, it isn't just the servers that generate heat, it's also the equipment supporting the servers that add to the heat generation. 9 D A T A C E N T E R E F F I C I E N C Y M E T R I C S A N D M E T H O D S

10 Energy efficiency should be a plan, not a response. Start planning today. Introducing APC interactive TradeOff Tools, Web-based calculators for predicting efficiency and availability in your data center planning The time has come to shift the efficiency debate from efficiency as a conceptual ideal to implementation the measuring of and planning for efficiency in your installation. Decisions you make today will certainly affect your efficiency tomorrow. Want to virtualize but unsure of how it will affect your power and cooling efficiency? Considering changes to your data center architecture approach or heat containment strategy, but reluctant to rock the boat? Balancing the pros and cons of data center planning can be a real challenge. The effects of a bad decision are further complicated by rising energy costs and the need for green. Introducing the latest innovation for critical decisions from APC : the TradeOff Tools suite. These interactive, online, and (most important) precisely formulated calculators deliver the actual implications of decisions in your data center design or planning. With TradeOff Tools, you can accurately calculate the impact that new equipment, server virtualization, design changes, and heat containment strategies will have on your facility. Because the data plugged in is your own data, and not industry averages, the results are your own, too. More than a widget The benefit of TradeOff Tools is easy to calculate. Now you can know, ahead of time, without question, how changes will affect your facility. There has never been a tool this easy to use, that provides information this actionable. And did we mention these great tools are FREE for a limited time? Saving money, energy, and time has never been so simple. Try out TradeOff Tools today and know before you go. APC s Web-based TradeOff Tools are the practical application of data center best practices. The tool s decision-making criteria and recommendations stem from customer feedback about actual installations and are founded upon the logic and research determined by the APC Science Center, the internationally renowned research team responsible for more than 100 white papers on the subject. Try online for the next 30 days for FREE! Visit Key Code r299w Call APCC x6207 Fax Schneider Electric Industries SAS, All Rights Reserved. Schneider Electric, APC, and TradeOff Tools are owned by Schneider Electric, or its affiliated companies in the United States and other countries. esupport@apc.com 132 Fairgrounds Road, West Kingston, RI USA

11 COOLING Data Center Cooling Efficiency cooling is the second largest use of energy outside of the IT load itself. In fact, if your data center has a PUE of 2.2 or greater and many do it is highly likely that your cooling system may be using more power than the IT load. Consequently, cooling is the area that can offer the greatest opportunity for improvement. Until you have installed some form of energy monitoring and metering, however, it is impossible to determine if you have made any improvements. At a minimum, you will need to measure the energy to all the components of the cooling system. This is not as easy as it sounds because many installations do not have a centralized panel where all the cooling system components appear in one place so that you can measure the total. One of the most frequent cooling problems is an indirect byproduct of the latest trend in computing efficiency improvements virtualization and blade servers. The average blade server requires 4 KW to 5 KW of power some units as much as 8 KW and that produces much heat. Given today s cooling systems capacities and methodologies, consider the various power/heat density levels: Heat Load per Rack Low Density (Standard)...1KW to 3 KW Moderate Density...3 KW to 5 KW (one blade server) High Density (Threshold)...6 KW to 8 KW (two blade servers) High Density (Moderate)...9 KW to 14 KW (three blade servers) High Density (Very)...15 KW to 20 KW (four blade servers) High Density (Extreme)...20 KW and up 1 1 D A T A C E N T E R E F F I C I E N C Y M E T R I C S A N D M E T H O D S

12 COOLING This has led to the development of many different methods for dealing with these high-density cooling loads. One of the growing trends is the increased use of high-density localized cooling. It comes in various forms such as in-row or overhead cooling and other forms of contained cooling, either at the aisle level or even the rack level. Generally this is considered closecoupled cooling. Some systems use Although not a necessarily a mainstream water to remove the heat from in-row cooling units, while others use a refrigerant gas. Still others use CO2 under solution, water or other fluids are far pressure, using phase change to handle more efficient than extreme density racks, claimed to handle up to 50 KW per rack. air to remove heat. Besides being able to effectively handle these high-density loads, close-coupled cooling is also more efficient because it requires much lower fan power to move the air 3 to 10 feet rather than the 15 to 30 feet for traditional raised-floor cooling. Many users are not comfortable with the concept of water being near computer equipment, but early mainframes used water that ran directly into the equipment cabinets. Coming full circle, IBM introduced the Hydrocluster in 2008, which runs the water directly into the server chassis and even into the CPU itself. Although not a necessarily a mainstream solution, water or other fluids are far more efficient than air to remove heat. In addition, water allows higher densities and less cooling energy. IBM has said it envisions that the heated water could be used to heat adjunct buildings or provide hot water for facilities. MORE CONVENTIONAL SOLUTIONS For those who want to improve their data center s cooling efficiency without going to these extremes, there are many more conventional solutions. One of 1 2 D A T A C E N T E R E F F I C I E N C Y M E T R I C S A N D M E T H O D S

13 COOLING the most common problems is the mixing of hot and cold air from the hot and cold aisles. The addition of a containment system will mitigate this problem and improve efficiency. Another common problem is so-called bypass air within the cabinets themselves. A simple solution is the installation of blanking panels in the unused spaces in the racks to prevent the warm air from the rear being drawn forward within the cabinet. A method to improve cooling efficiency is The underlying to raise the air temperature from the traditional 68 to 70 degrees Fahrenheit to 75 to concept of using air 78 degrees Fahrenheit. In 2008, the American Society of Heating, Refrigerating and relatively simple economizers is Air-Conditioning Engineers (ASHRAE) just open the window recognized this and released its 9.9 standard in 2008, which stated that IT equip- when it is cooler outside than inside. ment could safely operate at up to 80.6 degrees Fahrenheit. It is imperative that the temperature is raised slowly and that all equipment intake air temperatures are constantly monitored to make sure that none exceed the maximum allowable temperature limits. FREE COOLING No discussion of cooling efficiency would be complete without including socalled free cooling, also known as economizers: D Air Side Economizers: The underlying concept of using air economizers is relatively simple just open the window when it is cooler outside than inside. However, the implementation in a data center is not quite that easy. The temperature and humidity must be controlled, and any sudden changes in either must be avoided. Air side economizers cannot just bring in cooler outside air and ex- 1 3 D A T A C E N T E R E F F I C I E N C Y M E T R I C S A N D M E T H O D S

14 COOLING haust the warm air to reduce the mechanical cooling requirements, they also need to filter the outside air and provide a range of humidity control without expending more compressor energy than necessary. D Water Side Economizers: The more popular water side fluid cooler systems are incorporated with control valves into the warmed return side of the chilled water or glycol loop, which can then be re-routed through a fluid-to-air heat exchanger before coming back to the chiller plant. This allows partial or total free cooling by either reducing or totally eliminating the need for the chiller compressors to run on cold days. Some of the newer large data centers have begun to incorporate water recycling into their cooling systems. It should be noted that a significant portion of larger data centers use evaporative cooling systems. Although they are more energy-efficient than air cooled systems, they do use a significant amount of water. Some large data centers use millions of gallons per month, but in all The Green Grid and EPA metrics, the issue of water usage is ignored. Water shortages may become a critical factor in the coming years. Some of the newer large data centers have begun to incorporate water recycling into their cooling systems. Others are located where water is readily available and unconstrained at least for the present. Although the issue of water usage is not just a data center problem many energy-intensive industries also use huge amounts of water for cooling, including the utility power plants themselves it would seem disingenuous to speak of data center efficiency metrics without any mention of water usage. 1 4 D A T A C E N T E R E F F I C I E N C Y M E T R I C S A N D M E T H O D S

15 DISTRIBUTION UPS and Power Distribution Efficiency conditioned and reliable power is taken for granted in data centers. Up until recently, the efficiency of an uninterruptible power supply was almost a side note in many purchasing decisions. With the rising cost of energy, the focus has now included efficiency when reviewing UPS potential purchases for new data centers. UPS has a range of specifications that are sometimes misinterpreted and confused with actual energy efficiency. In order to understand and calculate a UPS s true efficiency, let s examine each term and understand its inherent relationship with the others: D Voltage: Three phase/single phase voltage in the U.S. and North America is normally specified as 480/277V or 208/120V and 400/230V for Europe. Also important to note is that 400/230V is representational composite of various European and Asian systems, which include 380/220V 400/230V and 415/240V. In addition, there are also 600V systems, used in some Canadian and U.S. facilities. D KVA: Kilo Volt Amps, also known as apparent power. This represents volts x amps expressed in thousands. For example: For single phase only: 120V x 50A = 6,000 VA = 6 KVA. For three-phase power: 208V x 50A x = 18,012 VA = 18 KVA (note: is the square root of 3) D KW: Kilowatts, also known as actual power or heat value. This is calculated by multiplying KVA x power factor. For example, 18 KVA at 0.9 power factor = 16.2 KW 1 5 D A T A C E N T E R E F F I C I E N C Y M E T R I C S A N D M E T H O D S

16 DISTRIBUTION D Power Factor: Although a simplified explanation, power factor (PF) represents the difference expressed as a decimal multiplier such as 0.9 between KVA, which is apparent power, and KW actual power, or heat value for non-linear reactive loads, such as computer power supplies, which are unlike pure resistive loads, such as incandescent bulbs or heaters. D Power Factor Corrected: Also known as PFC, power factor corrected represents a non-linear reactive device s ability to compensate and improve its power factor to approach that of a pure non-reactive load. For example, older computer power supplies typically had a 0.8 input power factor. This meant that the UPS had to provide the equipment with 1,000 VA to deliver 800 watts. Most modern computer power supplies are now power factor corrected at 0.95 or better, meaning that the UPS only needs to provide approximately 842 VA to deliver 800 watts. D Input Power Factor: This is important to the upstream equipment in the power chain. Like older computer power supplies, older UPSes were rated at 0.8 PF and required more apparent power (KVA) to deliver actual power (KW). For example, an older UPS 100 KVA with an input power factor of 0.8 would require approximately 125 KVA from the upstream equipment. A modern 100 KVA UPS with an Input Power Factor of 0.95 would only require approximately 105 KVA. D Output Power Factor: Most uninterruptible power supplies today are offered by different vendors with different output power factors, typically rated at 0.8, 0.9 and 1.0. This is a commonly misunderstood specification and represents the real net power rating of the UPS and how much actual power it can deliver to the IT load. For example, a 100 KVA UPS with a 0.8 output power factor can deliver only 80 KW. However, if it were rated at 0.9 PF, it could deliver 90 KW, and at 1.0 it could deliver 100KW to the IT load. As you can see, this is especially important because most IT loads today are power factor corrected at 1 6 D A T A C E N T E R E F F I C I E N C Y M E T R I C S A N D M E T H O D S

17 DISTRIBUTION 0.95 or better. When evaluating different UPSes and their relative costs, consider the output power rated in KW, not in KVA. MORE ABOUT UPS energy efficiency can only be correctly calculated in KW not KVA. Do not be misled by anyone calculating in KVA or citing power factors as efficiency. It represents the amount of actual power delivered in KW of the UPS output, divided by the input power in KW. For example, a UPS with a 91 KW measured output with a 100KW actual input = 91% efficiency. This specification or measurement is usually based on the UPS operating with a fully charged battery. In effect, the other 9 KW are UPS losses and are converted to heat. Not all UPSes will report their input and output in KW some may only report KVA. To get a valid measurement a true power meter, which will measure KVA, KW and PF is required. The biggest gray area by UPS vendors that promote their efficiency claims is citing just a single number such as 91% when providing a UPS efficiency specification. Although the claim of 91% efficiency may be true, it is usually only valid at or near full load. This is not really how most uninterruptible power supplies operate. In many cases, a UPS will typically operate at 40% or less than its rated capacity. This is especially true for N+1 or 2N redundant UPS Installations. It is extremely important to get full disclosure of the efficiency curve over the entire load curve 10% to 100% from the manufacturer. Because the UPS is an essential component in the computing power chain, the EPA is in the process of establishing an Energy Star standard for the UPS at this time. Older UPSes have extremely poor efficiency when operating in their lower ranges. In some cases, they are only 60% to 70% efficient when at a 30% load. In contrast, a modern UPS will have 85% to 90% efficiency rating at only 30% 1 7 D A T A C E N T E R E F F I C I E N C Y M E T R I C S A N D M E T H O D S

18 DISTRIBUTION of full load and 90% to 95% over the higher load range. Several manufacturers now offer modular UPS systems, which offer several advantages. They generally lower the initial capital costs because the UPS can be purchased with a lower initial capacity. It also allows the UPS to operate at a higher utilization factor, which allows for more efficient operation. If your UPS is five years old or older, it may pay to review its actual operating range and efficiency. The capital cost of a new UPS may have a fairly quick cost recovery if you can have an overall 15% to 20% gain in UPS efficiency. One of the other areas that can affect electrical efficiency is the voltage that is used to feed the UPS and to distribute to the floor level power distribution units (PDUs), as well as the IT equipment itself. Generally speaking, it is preferable to operate at the highest possible voltage, start- If your UPS is five years old or older, ing at the UPS. it may pay to review Also, it is more efficient, both from a its actual operating distribution point and from the IT equipment perspective, to operate at 208V instead of 120V. Virtually all modern power range and efficiency. supplies are universal and can operate from 100V to 250V, but they are 3% to 5% more efficient at 208V to 240V than at 120V. If possible, it is best to bring threephase 208V power to every rack because power densities are increasing, and it is less costly to install the extra two conductors initially than to rewire later. This will allow three times the power for very little extra up-front cost. A final note about the IT load itself: Check and inventory all the IT equipment. It has been shown repeatedly that there is a lot of equipment still plugged in and drawing power, but no one knows who owns it or what it does. The best way to improve data center efficiency is simply to turn off and remove all the equipment that no longer is needed or producing useful work. 1 8 D A T A C E N T E R E F F I C I E N C Y M E T R I C S A N D M E T H O D S

19 ABOUT THE AUTHORS Julius Neudorfer is chief technical officer and a founding principal of Hawthorne, N.Y.-based North American Access Technologies Inc., which specializes in analyzing, designing, implementing and managing technology projects. He has designed and managed communications and data center projects for both commercial clients and government customers since Contact him at julius@naat.com. Frank J. Ohlhorst is an award-winning technology journalist, professional speaker and IT business consultant with more than 25 years of experience in the technology arena. Ohlhorst has worked with all major technologies and accomplished several high-end integration projects in a range of industries, including federal and local governments as well as Fortune 500 enterprises and small businesses. Contact him at fohlhorst@gmail.com. Cathleen Gagne Editorial Director cgagne@techtarget.com Matt Stansberry Executive Editor mstansberry@techtarget.com Christine Casatelli Editor ccasatelli@techtarget.com Marty Moore Copy Editor mmoore@techtarget.com Linda Koury Art Director of Digital Content lkoury@techtarget.com Jonathan Brown Publisher jebrown@techtarget.com Peter Larkin Senior Director of Sales plarkin@techtarget.com TechTarget 275 Grove Street, Newton, MA TechTarget Inc. No part of this publication may be transmitted or reproduced in any form or by any means without written permission from the publisher. For permissions or reprint information, contact Renee Cormier, Director of Product Management, Data Center Media, TechTarget (rcormier@techtarget.com). 1 9 D A T A C E N T E R E F F I C I E N C Y M E T R I C S A N D M E T H O D S

20 about our sponsor q Energy University Become a champion of Energy Efficiency. Enroll today. q APC Trade-Off Tools Simple, automated tools to support specific planning decisions. q Introducing the smarter Smart-UPS. About APC by Schneider Electric: APC by Schneider Electric, a global leader in critical power and cooling services, provides industry leading product, software and systems for home, office, data center and factory floor applications. APC delivers pioneering, energy efficient solutions for critical technology and industrial applications. 2 0 D A T A C E N T E R E F F I C I E N C Y M E T R I C S A N D M E T H O D S

Reducing Data Center Energy Consumption

Reducing Data Center Energy Consumption Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate

More information

Managing Power Usage with Energy Efficiency Metrics: The Available Me...

Managing Power Usage with Energy Efficiency Metrics: The Available Me... 1 of 5 9/1/2011 1:19 PM AUG 2011 Managing Power Usage with Energy Efficiency Metrics: The Available Metrics and How to Use Them Rate this item (1 Vote) font size Data centers consume an enormous amount

More information

Data Centers: Definitions, Concepts and Concerns

Data Centers: Definitions, Concepts and Concerns Data Centers: Definitions, Concepts and Concerns Arash Mousavi DCC September 2013 Agenda 1. Introduction 2. Issues in Modern Data Centers: Siemens Integrated Data Center Solutions 3. Issues in Modern Data

More information

Measuring Power in your Data Center

Measuring Power in your Data Center RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Raritan Measuring Power in your Data Center Herman Chan, Director, Power Solutions Business Unit, and Greg More, Senior Product Marketing Manager There

More information

Overview of Green Energy Strategies and Techniques for Modern Data Centers

Overview of Green Energy Strategies and Techniques for Modern Data Centers Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.

More information

Guideline for Water and Energy Considerations During Federal Data Center Consolidations

Guideline for Water and Energy Considerations During Federal Data Center Consolidations Guideline for Water and Energy Considerations During Federal Data Center Consolidations Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

DataCenter 2020: first results for energy-optimization at existing data centers

DataCenter 2020: first results for energy-optimization at existing data centers DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction

More information

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the

More information

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

Re Engineering to a "Green" Data Center, with Measurable ROI

Re Engineering to a Green Data Center, with Measurable ROI Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices

More information

Managing Data Centre Heat Issues

Managing Data Centre Heat Issues Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design

More information

FEAR Model - Review Cell Module Block

FEAR Model - Review Cell Module Block F.E.A.R. Returns: 5 Steps Toward Data Center Efficiency Today Objectives Benefits for ITS professionals Brief review of the FEAR data center Define data center efficiency Link efficiency to the FEAR data

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200

More information

Raising Inlet Temperatures in the Data Centre

Raising Inlet Temperatures in the Data Centre Raising Inlet Temperatures in the Data Centre White paper of a round table debate by industry experts on this key topic. Hosted by Keysource with participants including the Uptime Institute. Sophistication

More information

The Green Data Center

The Green Data Center The Green Data Center Energy Efficient Computing In The 21st Century The Green Data Center: Energy Efficient Computing In The 21 st Century Matt Stansberry Site Editor TechTarget mstansberry@techtarget.com

More information

Metrics for Data Centre Efficiency

Metrics for Data Centre Efficiency Technology Paper 004 Metrics for Data Centre Efficiency Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile: 0121 354

More information

Managing Today s Data Centers Avoiding the Impending Crisis

Managing Today s Data Centers Avoiding the Impending Crisis Managing Today s Data Centers Avoiding the Impending Crisis Steven Yellen Aperture Research Institute EXECUTIVE SUMMARY Organizations are facing an impending data center management crisis. The constant

More information

Recommendations for Measuring and Reporting Overall Data Center Efficiency

Recommendations for Measuring and Reporting Overall Data Center Efficiency Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE for Data Centers 17 May 2011 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations for Measuring

More information

THE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE

THE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE THE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200

More information

Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics

Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics On January 13, 2010, 7x24 Exchange Chairman Robert Cassiliano and Vice President David Schirmacher met in Washington, DC with representatives from the EPA, the DOE and 7 leading industry organizations

More information

Measuring Energy Efficiency in a Data Center

Measuring Energy Efficiency in a Data Center The goals of the greening of the Data Center are to minimize energy consumption and reduce the emission of green house gases (carbon footprint) while maximizing IT performance. Energy efficiency metrics

More information

Guidance for Calculation of Efficiency (PUE) in Data Centers

Guidance for Calculation of Efficiency (PUE) in Data Centers Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 1 by Victor Avelar > Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or

More information

GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.

GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.

More information

Optimizing Power Distribution for High-Density Computing

Optimizing Power Distribution for High-Density Computing Optimizing Power Distribution for High-Density Computing Choosing the right power distribution units for today and preparing for the future By Michael Camesano Product Manager Eaton Corporation Executive

More information

Data Center Technology: Physical Infrastructure

Data Center Technology: Physical Infrastructure Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider

More information

The Pros and Cons of Modular Systems

The Pros and Cons of Modular Systems The Pros and Cons of Modular Systems Kevin Brown, Vice President Global Data Center Offer Schneider Electric Schneider Electric 1 Foundational BUSINESS OVERVIEW Rev 2 Desired characteristics of pre-fabricated

More information

Analysis of data centre cooling energy efficiency

Analysis of data centre cooling energy efficiency Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe

More information

Data Center Facility Basics

Data Center Facility Basics Data Center Facility Basics Ofer Lior, Spring 2015 Challenges in Modern Data Centers Management, Spring 2015 1 Information provided in these slides is for educational purposes only Challenges in Modern

More information

Data Center Energy Use, Metrics and Rating Systems

Data Center Energy Use, Metrics and Rating Systems Data Center Energy Use, Metrics and Rating Systems Steve Greenberg Energy Management Engineer Environmental Energy Technologies Division Lawrence Berkeley National Laboratory October 31, 2007 Today s s

More information

Airflow Simulation Solves Data Centre Cooling Problem

Airflow Simulation Solves Data Centre Cooling Problem Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length

More information

Guidance for Calculation of Efficiency (PUE) in Data Centers

Guidance for Calculation of Efficiency (PUE) in Data Centers Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 3 by Victor Avelar Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or other

More information

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer

More information

Energy Savings in the Data Center Starts with Power Monitoring

Energy Savings in the Data Center Starts with Power Monitoring Energy Savings in the Data Center Starts with Power Monitoring As global competition intensifies, companies are increasingly turning to technology to help turn mountains of data into a competitive edge.

More information

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program

More information

Recommendations for Measuring and Reporting Overall Data Center Efficiency

Recommendations for Measuring and Reporting Overall Data Center Efficiency Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 1 Measuring PUE at Dedicated Data Centers 15 July 2010 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations

More information

AIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland

AIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland AIA Provider: Colorado Green Building Guild Provider Number: 50111120 Office Efficiency: Get Plugged In AIA Course Number: EW10.15.14 Speaker: Geoff Overland Credit(s) earned on completion of this course

More information

Data Centers: How Does It Affect My Building s Energy Use and What Can I Do?

Data Centers: How Does It Affect My Building s Energy Use and What Can I Do? Data Centers: How Does It Affect My Building s Energy Use and What Can I Do? 1 Thank you for attending today s session! Please let us know your name and/or location when you sign in We ask everyone to

More information

Allocating Data Center Energy Costs and Carbon to IT Users

Allocating Data Center Energy Costs and Carbon to IT Users Allocating Data Center Energy Costs and Carbon to IT Users Paper 161 Revision 1 by Neil Rasmussen Executive summary Are complicated software and instrumentation needed to measure and allocate energy costs

More information

Increasing Data Center Efficiency by Using Improved High Density Power Distribution

Increasing Data Center Efficiency by Using Improved High Density Power Distribution Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Executive Summary A new approach to power distribution for high density server installations

More information

Electrical Efficiency Modeling for Data Centers

Electrical Efficiency Modeling for Data Centers Electrical Efficiency Modeling for Data Centers By Neil Rasmussen White Paper #113 Revision 1 Executive Summary Conventional models for estimating electrical efficiency of data centers are grossly inaccurate

More information

Greener Pastures for Your Data Center

Greener Pastures for Your Data Center W H I T E P A P E R Greener Pastures for Your Data Center 2 Executive Summary Following a green path, once a concept relegated to a small group of environmentalists and the U.S. Environmental Protection

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

Control of Computer Room Air Handlers Using Wireless Sensors. Energy Efficient Data Center Demonstration Project

Control of Computer Room Air Handlers Using Wireless Sensors. Energy Efficient Data Center Demonstration Project Control of Computer Room Air Handlers Using Wireless Sensors Energy Efficient Data Center Demonstration Project About the Energy Efficient Data Center Demonstration Project The project s goal is to identify

More information

Data Center Equipment Power Trends

Data Center Equipment Power Trends Green field data center design 11 Jan 2010 by Shlomo Novotny Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. explores water cooling for maximum efficiency - Part 1 Overview Data

More information

Calculating Total Power Requirements for Data Centers

Calculating Total Power Requirements for Data Centers Calculating Total Power Requirements for Data Centers By Richard Sawyer White Paper #3 Executive Summary Part of data center planning and design is to align the power and cooling requirements of the IT

More information

U.S. Department of Energy, National Renewable Energy Laboratory, IT Sustainability Case Study

U.S. Department of Energy, National Renewable Energy Laboratory, IT Sustainability Case Study SUMMARY The U.S. Department of Energy s (DOE) National Renewable Energy Laboratory (NREL) designed the Research Support Facility (RSF) to demonstrate that a large office building could lead the way in

More information

Greening Data Centers

Greening Data Centers Greening Data Centers Dallas Thornton SDSC Division Director, Cyberinfrastructure Services March 2, 2011 Data Centers Are Enormous Users of Power US Data Centers (TeraWatt Hours per Year) 125 US Televisions

More information

Environmental Data Center Management and Monitoring

Environmental Data Center Management and Monitoring 2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor

More information

Expert guide to achieving data center efficiency How to build an optimal data center cooling system

Expert guide to achieving data center efficiency How to build an optimal data center cooling system achieving data center How to build an optimal data center cooling system Businesses can slash data center energy consumption and significantly reduce costs by utilizing a combination of updated technologies

More information

A Comparison of AC and DC Power Distribution in the Data Center Transcript

A Comparison of AC and DC Power Distribution in the Data Center Transcript A Comparison of AC and DC Power Distribution in the Data Center Transcript Slide 1 Welcome to the Data Center University course on the A Comparison of AC and DC Power Distribution in the Data Center. Slide

More information

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel

More information

Power Distribution Units (PDUs): Power monitoring and environmental monitoring to improve uptime and capacity planning

Power Distribution Units (PDUs): Power monitoring and environmental monitoring to improve uptime and capacity planning Power Distribution Units (PDUs): Power monitoring and environmental monitoring to improve uptime and capacity planning 2009, Raritan Inc. Overview Corporate America is more dependent than ever on computing

More information

AIRAH Presentation April 30 th 2014

AIRAH Presentation April 30 th 2014 Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining

More information

Datacenter Efficiency

Datacenter Efficiency EXECUTIVE STRATEGY BRIEF Operating highly-efficient datacenters is imperative as more consumers and companies move to a cloud computing environment. With high energy costs and pressure to reduce carbon

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

Data Centre Capacity and Electricity Use How the EU Code of Conduct can help your data centre electricity bill

Data Centre Capacity and Electricity Use How the EU Code of Conduct can help your data centre electricity bill Data Centre Capacity and Electricity Use How the EU Code of Conduct can help your data centre electricity bill Chris Cartledge Independent Consultant C.Cartledge@sheffield.ac.uk Summary ICT Electricity

More information

Increasing Data Center Efficiency through Metering and Monitoring Power Usage

Increasing Data Center Efficiency through Metering and Monitoring Power Usage White Paper Intel Information Technology Computer Manufacturing Data Center Efficiency Increasing Data Center Efficiency through Metering and Monitoring Power Usage To increase data center energy efficiency

More information

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London.

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London. Energy Efficient Data Centre at Imperial College M. Okan Kibaroglu IT Production Services Manager Imperial College London 3 March 2009 Contents Recognising the Wider Issue Role of IT / Actions at Imperial

More information

Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency. Steve Hammond NREL

Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency. Steve Hammond NREL Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency NREL 1 National Renewable Energy Laboratory Presentation Road Map A Holistic Approach to Efficiency: Power, Packaging, Cooling, Integration

More information

Data centre energy efficiency metrics. Existing and proposed metrics to provide effective understanding and reporting of data centre energy

Data centre energy efficiency metrics. Existing and proposed metrics to provide effective understanding and reporting of data centre energy Existing and proposed metrics to provide effective understanding and reporting of data centre energy Liam Newcombe Data Centre Specialist Group 1 Introduction... 2 2 Summary... 6 3 Overview of metrics...

More information

The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity

The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity The Quest for Energy Efficiency A White Paper from the experts in Business-Critical Continuity Abstract One of the most widely discussed issues throughout the world today is the rapidly increasing price

More information

Design Best Practices for Data Centers

Design Best Practices for Data Centers Tuesday, 22 September 2009 Design Best Practices for Data Centers Written by Mark Welte Tuesday, 22 September 2009 The data center industry is going through revolutionary changes, due to changing market

More information

The Efficient Enterprise. Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric

The Efficient Enterprise. Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric Ee The Efficient Enterprise Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic! 30,000

More information

Unleashing Stranded Power and Cooling Data

Unleashing Stranded Power and Cooling Data Unleashing Stranded Power and Cooling from New and Existing Data Centers An affordable, five-step approach to addressing power and cooling shortages By Dr. Kenneth Uhlman, P.E. Director of Data Center

More information

Data Centers That Deliver Better Results. Bring Your Building Together

Data Centers That Deliver Better Results. Bring Your Building Together Data Centers That Deliver Better Results Bring Your Building Together 1 Meeting the high demands of your data center Meeting the increasing heat loads associated with growing computational needs requires

More information

Green Data Centre Design

Green Data Centre Design Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS

More information

Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources

Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources ALEXANDRU SERBAN, VICTOR CHIRIAC, FLOREA CHIRIAC, GABRIEL NASTASE Building Services

More information

Data Center Power Consumption

Data Center Power Consumption Data Center Power Consumption A new look at a growing problem Fact - Data center power density up 10x in the last 10 years 2.1 kw/rack (1992); 14 kw/rack (2007) Racks are not fully populated due to power/cooling

More information

How To Find A Sweet Spot Operating Temperature For A Data Center

How To Find A Sweet Spot Operating Temperature For A Data Center Data Center Operating Temperature: The Sweet Spot A Dell Technical White Paper Dell Data Center Infrastructure David L. Moss THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES ONLY, AND MAY CONTAIN TYPOGRAPHICAL

More information

Green Data Center Program

Green Data Center Program Green Data Center Program Alan Crosswell Fall Internet2 Member Meeting, San Antonio Agenda The opportunities Status of the main University Data Center and others around campus Green data center best practices

More information

AbSTRACT INTRODUCTION background

AbSTRACT INTRODUCTION background february 20, 2007 GREEN GRID METRICS: Describing Datacenter Power Efficiency Technical Committee White Paper white paper 1 Abstract The Green Grid is an association of IT professionals seeking to dramatically

More information

Convergence of Complexity

Convergence of Complexity Convergence of Complexity Optimize Existing Data Center Space Measure And Allocate Energy Cost Plan for new data centers or additional capacity How to make your Data Center Last Longer, Gartner, December

More information

Data Center Efficiency in the Scalable Enterprise

Data Center Efficiency in the Scalable Enterprise FEATURE SECTION: POWERING AND COOLING THE DATA CENTER Data Center Efficiency in the Scalable Enterprise 8 DELL POWER SOLUTIONS Reprinted from Dell Power Solutions, February 2007. Copyright 2007 Dell Inc.

More information

Utilizing Temperature Monitoring to Increase Datacenter Cooling Efficiency

Utilizing Temperature Monitoring to Increase Datacenter Cooling Efficiency WHITE PAPER Utilizing Temperature Monitoring to Increase Datacenter Cooling Efficiency 20A Dunklee Road Bow, NH 03304 USA 2007. All rights reserved. Sensatronics is a registered trademark of. 1 Abstract

More information

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National

More information

GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCIE

GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCIE WHITE PAPER #6 GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCIE EDITORS: CHRISTIAN BELADY, MICROSOFT CONTRIBUTORS: ANDY RAWSON, AMD JOHN PFLEUGER, DELL TAHIR CADER, SPRAYCOOL PAGE 2 ABSTRACT

More information

Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.

Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite

More information

Energy Efficiency and Availability Management in Consolidated Data Centers

Energy Efficiency and Availability Management in Consolidated Data Centers Energy Efficiency and Availability Management in Consolidated Data Centers Abstract The Federal Data Center Consolidation Initiative (FDCCI) was driven by the recognition that growth in the number of Federal

More information

Greening Commercial Data Centres

Greening Commercial Data Centres Greening Commercial Data Centres Fresh air cooling giving a PUE of 1.2 in a colocation environment Greater efficiency and greater resilience Adjustable Overhead Supply allows variation in rack cooling

More information

Data Center Energy Efficiency

Data Center Energy Efficiency THE INFORMATION SOURCE FOR THE DATA CENTER INDUSTRY EXECUTIVE GUIDE SERIES PART 3 Data Center Energy Efficiency by Julius Neudorfer August 2012 This is the third of a six part series of our Executive Guide

More information

Qualitative Analysis of Power Distribution Configurations for Data Centers

Qualitative Analysis of Power Distribution Configurations for Data Centers Qualitative Analysis of Power Distribution Configurations for Data Centers White Paper #4 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,

More information

Server Technology, Inc.

Server Technology, Inc. Server Technology, Inc. Cabinet Power Monitoring, Management & Control Within the Data Center White Paper STI-100-011 2010-Sept-27 by Calvin Nicholson, Senior Director Software and Strategic Alliances,

More information

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

National Grid Your Partner in Energy Solutions

National Grid Your Partner in Energy Solutions National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw

More information

High-Efficiency AC Power Distribution for Data Centers

High-Efficiency AC Power Distribution for Data Centers High-Efficiency AC Power Distribution for Data Centers White Paper 128 Revision 2 by Neil Rasmussen > Executive summary The use of 240 volt power distribution for data centers saves floor space, simplifies

More information

ICT and the Green Data Centre

ICT and the Green Data Centre ICT and the Green Data Centre Scott McConnell Sales Manager c/o Tanya Duncan MD Interxion Ireland Green Data Centres Our Responsibility Data centre greenhouse gas emissions are projected to quadruple by

More information

Metering and Managing University of Sheffield Data Centres. Chris Cartledge Independent Consultant C.Cartledge@sheffield.ac.uk

Metering and Managing University of Sheffield Data Centres. Chris Cartledge Independent Consultant C.Cartledge@sheffield.ac.uk Metering and Managing University of Sheffield Data Centres Chris Cartledge Independent Consultant C.Cartledge@sheffield.ac.uk Summary ICT Electricity Use Footprint Data Centre Electricity Use European

More information

Legacy Data Centres Upgrading the cooling capabilities What are the options?

Legacy Data Centres Upgrading the cooling capabilities What are the options? Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems

More information

How To Improve Energy Efficiency In A Data Center

How To Improve Energy Efficiency In A Data Center Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

The Mission Critical Data Center Understand Complexity Improve Performance

The Mission Critical Data Center Understand Complexity Improve Performance The Mission Critical Data Center Understand Complexity Improve Performance Communications Technology Forum Fall 2013 Department / Presenter / Date 1 Rittal IT Solutions The State of the Data Center Market

More information

IT Cost Savings Audit. Information Technology Report. Prepared for XYZ Inc. November 2009

IT Cost Savings Audit. Information Technology Report. Prepared for XYZ Inc. November 2009 IT Cost Savings Audit Information Technology Report Prepared for XYZ Inc. November 2009 Executive Summary This information technology report presents the technology audit resulting from the activities

More information

The Different Types of Air Conditioning Equipment for IT Environments

The Different Types of Air Conditioning Equipment for IT Environments The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.

More information

Understanding Power Factor, Crest Factor, and Surge Factor. White Paper #17

Understanding Power Factor, Crest Factor, and Surge Factor. White Paper #17 Understanding Power Factor, Crest Factor, and Surge Factor White Paper #17 Executive Summary This paper explains the technical terms of Power Factor, Crest Factor, and Surge Factor. The use of these terms

More information

EU Code of Conduct for Data Centre Efficiency

EU Code of Conduct for Data Centre Efficiency EU Code of Conduct for Data Centre Efficiency A Green Practice Accredited by British Computer Society (BCS) EU Code of Conduct for Data Centre Efficiency Local Organizer Practices in Data Centre Industry

More information

White Paper: Free Cooling and the Efficiency of your Data Centre

White Paper: Free Cooling and the Efficiency of your Data Centre AIT Partnership Group Ltd White Paper: Free Cooling and the Efficiency of your Data Centre Using free cooling methods to increase environmental sustainability and reduce operational cost. Contents 1. Summary...

More information

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent

More information