BSimplex and -9404

Size: px
Start display at page:

Download "BSimplex 4001-9403 and -9404"

Transcription

1 BSimpex and Fire Aarm Systems Instaation and Operating Instructions Simpex Time Recorder Co. FA ( ) A specifications and other information shown were current as of pubication. and are subject to change without notice. Ed495 Technica Manuas Onine! -

2 Contact your oca Simpex Time Recorder Co. Branch Office (isted in the Yeow Pages under Fire Aarm) for Warranty Registration & Information. Technica Manuas Onine! -

3 TABLE OF CONTENTS IMPORTANT DEFINITIONS SYSTEM INTRODUCTION INSTALLATION INSTRUCTIONS Introduction... 3 Toos and Equipment Required... 3 Genera Notes... 3 Genera Requirements for System Wiring... 4 System Wiring Specifications... 4 Instaation Check List... 6 INSTALLATION PROCEDURES Contro Pane Mounting... Mounting and Wiring Periphera Devices... 9 Buiding Wiring Checkout Procedure Contro Pane Termina Connections Transient Suppressor, Zone Disconnect, or Combination Transient Suppressor/Zone Disconnect Board Termina Connections System Programming System Power-Up a OPERATING INSTRUCTIONS Introduction How to Recognize Norma, Troube, and Aarm Indications How to Operate the Pane During an Aarm Condition How to Reset the Fire Aarm System Foowing an Aarm Condition How to Operate the Pane when Water is Fowing in the Sprinker System What to Do in Case of Troube Aarm Verification Feature Troubeshooting How to Test the System How to Perform the LED Test BATTERY TESTING INFORMATION Genera Information Testing Pk -J I I CAUTION ELECTRICAL HAZARD Disconnect eectrica power when making any interna adjustments or repairs. Instaation and servicing shoud be performed by quaified Simpex Representatives. These instructions ony appy to United States instaations. i Technica Manuas Onine! -

4 Technica Manuas Onine! -

5 IMPORTANT DEFINITIONS Aarm-Initiating Device: A device which, when actuated, initiates an aarm. Such devices, depending on their type, can be operated manuay or actuated automaticay in response to smoke, fame, heat or water-fow. (Exampes: pu stations, heat detectors, smoke detectors, sprinker fow switches, etc.) Aarm-Notification Appiance: A device that produces an audibe and/or visua aarm signa in response to a fire emergency. (Exampes: horns, bes, chimes, fashing ights, etc.) Annunciator: An eectricay operated visua signaing device having one or more amps or LEDS to dispay the status of the fire aarm system. End-of-Line Device: A device used to terminate a supervised circuit. Initiating-Device Circuit: A circuit to which automatic or manua initiating devices are connected. Loca Energy Master Box: A municipa master box that uses eectrica energy from the protected premises to energize its eectromagnetic tripping mechanism. See definition for shunt master box. Notification-Appiance Circuit: A circuit to which notification appiances are connected. Shunt Master Box: A municipa master box that uses eectrica energy from the municipa fire aarm system to energize its eectromagnetic tripping mechanism. See definition for oca energy master box. Zone: A designated area of a buiding. Commony, zones within a buiding are annunciated to aid in ocating a fire. SYSTEM INTRODUCTION The and are four-zone, eectricay supervised, fire aarm panes. The connects to a 12OVAC 60 Hz source. The connects to a 220/24OVAC, 50 Hz source. Each system contains one notification appiance circuit, battery standby power, and battery charger. The systems provide an eary warning evacuation signa for buiding occupants if a fire occurs. The systems consist of: Aarm-initiating devices - Smoke detectors, heat detectors, pu stations, etc. Aarm-notification appiances - Horns, bes, and visua units. A contro pane. Each system may aso contain optiona features. Since the and operate the same except for input power, we wi discuss system operation as it appies to the Aarm-initiating devices are instaed in the buiding and connected to one of four initiating-device circuits on the contro pane. Each initiating-device circuit is given a zone number (1, 2, 3, or 4). Thus, the various areas of the buiding can be designated as zone 1, zone 2, zone 3, or zone 4. The contro pane monitors each zone for troubes and aarms. 1 Technica Manuas Onine! -

6 SYSTEM INTRODUCTION - Continued Aarm-notification appiances are ocated throughout the buiding to provide acceptabe sound eves. These appiances are connected to a notification-appiance circuit on the contro pane. The contro pane activates the notification appiances from a centra ocation. You operate the system using the LED indicators and switches on the contro pane. When an aarm or troube condition exists, the pane LEDs indicate the ocation and type of condition. Red LEDs indicate an aarm condition when on. Amber LEDs indicate a troube condition when on. Switches aow you to interact with the system in various ways (see Operating Instructions on Page 23). A diagram of a typica system is shown in Figure K. 1W. 5% ANNUNCIATOR 10K. /ZW.S% 3.3K. 1W. 5% CONTACTS RATINGS ZA.@ 30 VACWDC JW3 F3 SIG CKT -. GND JW2 K2 r OPTIONAL RIBBON - CABLE CONNECT TO 120 VAC SOHZ (FUSED SOURCE) PANEL DRAWS 1.2A F2 AUX PWR 0.75A BRN OUT 0 xx 0 PWR TBL F AC INPUT cc+ 1 r ztt xxmm WEea 1 F4 BATERY ow ITROUBLE I JW 0 3 : 6, OPTIONAL TRANSIENT SUPPRESSOR. ZONE DISCONNECT. OR TRANSIENT SUPPRESSOR ZONE --w DISCONNECT BOARD 9 + I FIGURE 1 Technica Manuas Onine! - 2

7 INSTALLATION INSTRUCTIONS INTRODUCTION Be sure that you are thoroughy famiiar with this instaation procedure before instaing the system. To hep you with the instaation of this and other Simpex systems, the foowing pubication is avaiabe for genera reference: How to Wire a Buiding for a Fire Aarm System. TOOLS AND EQUIPMENT REQUIRED /4-Inch Fat-tip Screwdriver, 8-Inches ong /8-Inch Fat-tip Screwdriver, 4-Inches ong Vot-ohmmeter Diagona Cutting Piers 0 Wire Strippers End-Of-Line resistors (EOLRs) (suppied by Simpex): five 3.3K, 1 watt resistors; two 1 OK, /2 watt resistors; two K, 1 watt, resistors System Wiring Diagram GENERAL NOTES Notify appropriate personne (buiding occupants, fire department or monitoring faciity, etc.) of the instaation. When running wires to contro pane, identify wires appropriatey: 12OVAC input power, notification (signa) circuit, zone 1, zone 2, etc., and identify a I+ wires and I- wires. The pane s termina boards are abeed with a TB number (TBI, TB2, TB3, etc.), and each termina is designated a termina number (1, 2, 3, etc.). Therefore, TB-1 is termina 1 on termina board TB, TB-2 is termina 2 on termina board TB, etc. Each termina is aso identified with an abbreviation of the circuit wire that is to be connected to it (SIG -, SIG +, ZON -, ZON+, etc.). Use the foowing resistor coor code (Fig. 5) to identify the end-of-ine resistors (EOLRs) used in the instaation: ORANGE ORANGE RED GOLD BROWN BLACK ORANGE GOLD BROWN BLACK RED GOLD 3,300-OHM (3.3K, 1 WAT) RESISTOR O,OOO-OHM (OK, /2 WATT) RESISTOR 1,OOO-OHM (1 K, 1 WAT) RESISTOR FIGURE 2 3 Technica Manuas Onine! -

8 GENERAL NOTES - Continued A wiring must be in accordance with oca codes. A wiring shoud be in accordance with Nationa Eectric Code, Artice 760. A neaty wired system wi hep assure an accurate inspection of a connections and simpify troubeshooting. GENERAL REQUIREMENTS FOR SYSTEM WIRING These requirements are intended to aid the instaer in making a safe and troube-free instaation, but they are not intended to circumvent any pertaining and/or required codes, aws, reguations, etc. Note: These wiring specifications are subject to oca authority approva. Genera Wiring Requirements For Fire Aarm Systems 1. A wires are to be copper conductors ony. 2. A wiring, except incoming power and ground connecting wires, must be free from grounds or shorts and have a resistance of one megohm, or higher, to earth. 3. Metaic conduit, metaic raceway, pastic pipe, or pastic raceways may be used. If metaic conduit is used, the foowing must be observed: If the continuity of the metaic conduit is not maintained, then a 12AWG (minimum) drain wire must be used between the break of metaic conduit. The drain wire wi be connected to the metaic conduit at both ends. 4. Ony system wiring can be run in the same conduit, pipe raceway, or muticonductor cabes. 5. Where system wires pass through foors or fire-rated was, the instaation sha be made to prevent the spread of fire from foor to foor (i.e. patching of hoes, fire stops, etc.). 6. A system wiring subject to physica damage sha be mechanicay protected based on the environment the cabe is subjected to. 7. Each device - pu station, detector, horn, be, etc. - must have its own encosure such as a back box, outet box, etc. 8. A minimum of 6 inches of free conductor wi be required in each eectrica box to faciitate terminations. A 12- inch service oop of cabe is required for a continuous pus through an eectrica box. 9. Unused openings in eectrica boxes sha be propery banked off with suitabe protection equivaent to the wa thickness of the equipment. A spice boxes sha have a bank cover. 10. A wiring sha be terminated with U.L. isted devices (i.e. wire nuts, pressure connectors, etc.). Wiring terminated with ony eectrica tape is not permitted. A spicing (free ends of conductors) sha be covered with an insuation equivaent to that of the conductors. SYSTEM WIRING SPECIFICATIONS Incoming Source - Wiring - Power Wiring Life Safety Branch Circuit, or as required by oca code. Pane draws 2A maximum at 12OV, 60Hz via a fused disconnect or circuit breaker. Use two 14 AWG wires, or 14AWG cabe. 4 Technica Manuas Onine! -

9 Earth Detection Source - Connection sha be made to an approved dedicated earth connection per NEC Artice 250 (NFPA 70). Wiring -Use Aarm-Initiating 14AWG wire. Device Wiring Aarm-initiating devices - Manua pu stations, automatic heat detectors and automatic smoke detectors. Wiring - Four circuits with two wires per circuit. Each circuit terminates with a 3.3K end-of-ine resistor. Use 18AWG to 14AWG wire. Note: If using 4-wire detectors, refer to Step 4 (page 9). The RMT +I output used can suppy up to 500MA of fitered, reguated 24VDC. Max. oop ine resistance for each circuit is 50 ohms if P-wire detectors are used. Aarm-Notification Appiance Wiring Afarm-notification appiances - Horns, bes and visua units. Wiring - 2-wire circuit terminating with a 1 OK end-of-ine resistor. Use 18AWG to 14AWG wire. Note: Because the system s tota signa power is 2A, the number of notification appiances and the wire ength that can be used in the notification circuit is imited. Refer to Tabe 1 to determine the maximum number of notification appiances and the tota wire ength that can be used in the notification circuit. TABLE 1 Technica Manuas Onine! -

10 SYSTEM WIRIING SPECIFICATIONS - Continued Auxiiary Aarm Reay Contacts (If Used) Devices - Source - Wiring - Damper and fan contros, smoke door reeases, eevator contro, etc. Externa 2A, dependent upon devices that are used. Two Form C contacts avaiabe which transfer upon automatic aarm. Use 18AWG to 14AWG wire. Troube Reay Contacts (If Used) Devices - Source - Wiring - Horns, bes, ights, etc. Externa 3OVAC/SOVDC dependent upon devices that are used. Max. oad is 2A resistive. One Form C contact avaiabe which transfers upon a troube condition. Use 18AWG to 14AWG wire. INSTALLATION CHECK LIST (REFER TO WIRING DIAGRAM ) This section provides a systematic method for instaing the system. Upon competion of a procedura step, pace a check mark in the appropriate box in the eft coumn. If a probem occurs with the instaation, refer to the appropriate page isted in the right coumn of the checkist. The information found on that page wi provide a detaied description of a specific part of the instaation. If your probem is not resoved, contact your oca Simpex Branch Office (isted in the Yeow Pages under Fire Aarm). If you wish, you may go directy to the detaied instructions to insta the system (Page 8). INSTALLATION CHECK LIST DETAILED q Procedure INSTRUCTION SEE PAGE(S) Mount contro pane. If using optiona modues, battery meter modue and/or q 1. aarm reay modue, mount them using the instructions suppied with each 8 modue. q 2. If using externa battery cabinet, insta it. 8 Insta periphera devices and connect end-of-ine resistors across terminas q 3. of the ast device in the notification-appiance circuit and initiating-device 9 circuits used. q 4. Check buiding (system) wiring for absence of votage, opens, and shorts. 10 Steps 5 through 21 describe the connections to the pane s terminas. q 5. Connect ground wire to green ground screw. 11 (Step 1A) Connect notification-appiance circuit to TB2-5 (SIG +) and TB2-6 (SIG -). q 6. (Connect circuit to transient suppressor or combination board if used [see 11 (Step 2) pages 18 and 191). Connect initiating-device circuits to appropriate terminas on TB4 (connect circuits to transient suppressor board, zone disconnect board, or transient q 7. suppressor/zone disconnect board if used [see pages 28 and 291). If system 11 (Step 3) contains coded manua station, connect coded stations to terminas designated for Zone 1 and cut jumper JW2. 6 Technica Manuas Onine! -

11 DETAILED 0 Procedure INSTRUCTION SEE PAGE(S) If 4-wire detectors are used, connect circuit for detectors to TB2-3 (AUX +) 0 8. and TB2-4 (AUX -). Connect TB3-9 (RMT +) to TB2-2 (EXT PWR) and cut 12 (Step 4) jumper JW If using an auxiiary power suppy, connect it to TB2-2 (EXT PWR) and TB2-4 (AUX -). Cut jumper JW3. 12 (Step 5) If using a waterfow switch, connect as foows: Connect waterfow switch (N/O) to TB4-5 (ZONE3 +) and TB4-6 (ZON3 -). Connect tamper switch (N/C), if used, to TB4-7 (ZON4 +) and TB4-8 (ZON4 -). (Connect switches 13 (Step 6) to transient suppressor board, zone disconnect board, or transient suppressor/zone disconnect board, if used [see pages 28 and 291) If using a remote annunciator, connect it to terminas on TB2 and TB3. If supervision of annunciators is desired, and if aarm reay modue is not being used, remove appropriate jumpers JW4, JW5, JW6 and JW7 (refer to Tabe 4), and appropriate resistors R84, R85, R86, and R (Step 7) If using an aarm reay modue, connect it to terminas on TB2 and TB3. If using with an annunciator, DO NOT REMOVE INDICATED ANNUNCIATOR 14 (Step 8) JUMPERS OR RESISTORS If remote troube devices are used, connect them to the troube reay terminas (TB3) If remote aarm devices are used, connect them to the auxiiary reay terminas (TB5). 14 (Step 9) 15 (Step 10) Configure jumpers on JW in accordance with Figure (Step 11) If city circuit is used, connect it to TB5-1 (CITY+) and TB5-2 (CITY -) 16 (Step 12) Connect AC power to transformer eads. DO NOT APPLY POWER. 16 (Step 13) Connect batteries as indicated. DO NOT CONNECT WHITE BATTERY WIRES NOW. If used, connect battery meter modue to batteries. 16,17 E 19. Set DIP switch package SW1 in accordance with Tabe Appy system power. 21 and Test the system. I 28 7 Technica Manuas Onine! -

12 INSTALLATION PROCEDURES CONTROL PANEL MOUNTING (Refer to Figure 3) 1. Unock and open pane door. 2. Unsnap and remove pane overay from circuit card. 3. Remove knockout pugs on box assemby for wire entry. 4. At contro pane mounting ocation, position contro pane and secure with fasteners which are capabe of supporting pane with batteries. Hoes are provided at rear of box for securing pane to wa. 5. Enter externa wires into contro pane. For semi-fush mounting, insta trim pane and secure with six screws. 6. If using transient suppressor, zone disconnect, or combination transient suppressor/zone disconnect board, insta board as foows: a. Secure hex spacers to studs on box assemby. b. Aign board with spacers and secure with four screws. c. Connect cabe to board and contro pane as shown (bue edge of cabe shoud ine up with pin 9 on each connector). 7. If using externa battery cabinet, mount it using the instruction provided with the cabinet. The battery cabinet shoud be cose-nipped to the contro pane (maximum two feet apart). 8. If using battery meter modue or aarm reay modue, mount it using the instructions provided with the modue. Make sure the modue is within six inches of the contro pane. 9. PERFORM THIS STEP ONLY IF PANEL USES ALARM VERIFICATION. An aarm verification abe (P/N ) is provided with the contro pane. In the space abeed CIRCUIT (ZONE), indicate the zones for which aarm verification is used. (Refer to Notes 2 and 3 on Page 26.) In the space abeed CONTROL UNIT DELAY-SEC, enter the number If required by oca codes, insta the red pee-and-stick appique on the contro pane door using the instructions provided with the appique. MOUNTING HOLES CIRCUIT CARD BOX ASSEMBLY SUPPRESSOR SUPPRESSOR/ZONE DISCONNECT BOARD NOTE: DO NOT ENTER WIRES AT BATTERY LOCATION. FIGURE 3 8 Technica Manuas Onine! -

13 MOUNTING AND WIRING PERIPHERAL DEVICES (REFER TO WIRING DIAGRAM ) 1. Determine mounting ocations of periphera devices and insta system wires from the mounting ocation of each periphera device to the contro pane via junction boxes (if used): 2. Insta wires for the pane s input power. WARNING: DANGEROUS VOLTAGE (120VAC) MAY EXIST AT POWER INPUT. MAKE SURE PROPER CIRCUIT BREAKER OR FUSED DISCONNECT SWITCH AT BUILDING S POWER DISTRIBUTION IS SET TO THE OFF POSITION. 3. Insta a periphera devices (detectors, horns, pu stations, etc.) and connect them to the appropriate wires (refer to the instaation instructions packed with the devices). Connect a 3.3K end-of-ine resistor (EOLR) across the terminas of the ast device in each initiating circuit and mark the device accordingy (see Figure 4). Connect a 1 OK EOLR across the terminas of the ast device in each notification appiance circuit and mark the device accordingy (see Figure 5). ~~&A&NG - CIRCUIT (ZONE 1,2,3, OR 4) NOTIFICATION - tjv bt;ce FIGURE 4 FIGURE 5 4. If any of the designated zone terminas on the pane do not have initiating devices connected to them, connect a 3.3K EOLR across those terminas (Fig. 6). (If using the transient suppressor, the zone disconnect, or combination board, see page 18.) TB4 WHEN NO WIRES ARE CONNECTED TO ZONE (INITIATING) TERMINALS, CONNECT A 3.3K EOLR ACROSS THOSE TERMINALS. FIGURE 6 9 Technica Manuas Onine! -

14 BUILDING WIRING CHECKOUT PROCEDURE (REFER TO WIRING DIAGRAM ) 1. Check notification-appiance and initiatingdevice circuits for absence of votage, shorts, or opens as foows: A. At the contro pane, ocate the notificationappiance or one of the initiating-device circuits. B. Set vot-ohmmeter to 300VAC. C. Pace meter probes so that back probe is on I - wire and red probe is on I + wire. Vot-ohmmeter shoud read OV (Fig. 7). If you read a votage, check circuit wiring. D. Set vot-ohmmeter to GOVDC and repeat step 1C. E. Set vot-ohmmeter to OHMS X 10 and pace meter probes as described in Step 1 C. If reading indicates no continuity (open circuit, see Fig. 8) or a short circuit (see Fig. 9), ocate and correct open/short in circuit. Note: If reading indicates an open circuit in an initiating circuit, make sure that a smoke detector heads are mounted and seated in their bases. F. Repeat Steps 1A thru 1 E for a zone circuits. 2. Check system s other externa circuits as foows: A. Locate wires for each of the systems circuit not yet tested. B. Check for votage on circuit as described in Steps 1 B thru 1 D. C. Set vot-ohmmeter to OHMS X 10 and pace meter probes across circuit being tested Reading shoud indicate an open circuit (Fig. 8). If reading indicates a short circuit (Fig. 9) or something ess than infinity (-), check circuit wiring. FIGURE 7 FIGURE 8 NORMAL RANGE NORMAL RANGE THIS READING INDICATED NO THIS READING INDICATES AN OPEN CIRCUIT Notes: 1. Normay-cosed (N/C) reay circuits (auxiiary reays and troube reay) wi correcty read 0 ohms. 2. City circuit (if. used) wi read 15 to 5000 ohms depending on type of city connection. D. Repeat Steps 2A thru 2C for the externa circuits not yet checked. FIGURE 9 THIS READING INDICATES AN OPEN CIRCUIT 10 Technica Manuas Onine! -

15 CONTROL PANEL TERMINAL CONNECTIONS (REFER TO WIRING DIAGRAM ) Note: The pane must be connected to a separate earth ground per Artice 250 of the Nationa Eectrica Code (NFPA 70). 1. Connect earth ground detection circuit as foows: A. B. Connect ground wire to green ground screws (Fig. 10) on box assemby. Connect other end of ground wire to an approved earth ground (metaic cod water pipe, driven ground rod, etc.). GREEN GROUND SCREW FIGURE Connect indicating appiance circuit to TB2-5 (SIG +) and TB2-6 (SIG -) (Fig. 18). Note: If the system contains the transient suppressor board, connect notification circuit to instead of the pane terminas (see Page 18). the suppressor board TO NOTIFICATION APPLIANCE CIRCUIT (IF SUPPRESSOR/ DISCONNECT BD IS NOT USED) TRANSIENT FIGURE Connect initiating (zone) circuits to the foowing terminas (refer to Tabe 3 and Fig. 12). TO INITIATING CIRCUITS (IF SUPPRESSOR/DISCONNECT BD IS NOT USED) TABLE 3 JW2 / ZONE TERMINALS 1 TB4-1 (ZON +) & TB4-2 (ZON -) 2 TB4-3 (ZON2 +) & TB4-4 (ZON2 -) 3 TB4-5 (ZON3 +) & TB4-6 (ZON3 -) 4 TB4-7 (ZON4 +) & TB4-8 (ZON4 -) FIGURE Technica Manuas Onine! -

16 CONTROL PANEL TERMINAL CONNECTIONS - Continued Notes: 1. If the system contains the transient suppressor board, the zone disconnect board, or the transient suppressor/zone disconnect board, connect initiating device circuits to the suppressor or disconnect board instead of the pane terminas (see Page 18). 2. If any of the designated zone terminas do not have aarm devices connected to them, a 3.3K EOLR must be connected across those terminas (or the appropriate terminas on the suppressor board or zone disconnect board, if used). 3. If the system contains the waterfow/sprinker feature, connect waterfow-initiating devices to terminas designated for zones 3 and 4 (see Page 13). 4. If the system contains coded manua stations, connect stations to zone 1 and cut jumper JW2 (Fig. 12). 4. If the system contains 4-wire detectors, do the foowing: A. Connect a wire between the RMT + termina (TB3-9 [Fig. 16, Page 141) and the EXT PWR termina (TB2-2). B. Cut jumper JW3 on the contro pane as shown in Figure 13. C. Connect the wires used to power the detectors as shown in Figure 13. TB3 TB2 FIGURE If using a 24VDC auxiiary power suppy, cut jumper JW3 and connect the suppy as shown in Figure 14. USE OF EXTERNAL POWER MAY VOID POWER LISTING ON THAT CIRCUIT. CAUTION: Make sure that power is not connected to the auxiiary power suppy throughout the instaation. Its votage (24VDC) may cause damage to the pane during the instaation. TB2 FIGURE Technica Manuas Onine! -

17 6. If waterfow/sprinker switch circuits are used, connect as foows: A. Connect the waterfow switch (normay open) as shown in Figure 15. Make sure 3.3K resistor is connect to circuit as shown in wiring diagram B. Connect the sprinker tamper switch (normay cosed) as shown in Figure 15. Make sure resistors (1 K and 820 ohm, 1 watt) are connected to circuit as shown in wiring diagram Note: If the system contains the transient suppressor, zone disconnect or transient suppressor/zone disconnect board, connect the waterfow/sprinker circuits to the board instead of the pane terminas (see Page 18). TO WATERFLOW SW AND SPRINKLER TAMPER SW (IF SUPPRESSOR/DISCONNECT ED IS NO_T USED) FIGURE If using a remote annunciator or remote annunciator with remote troube station and remote acknowedge switch, connect to pane as foows (see Fig. 16, page 14, for reference): Notes: 1. Perform ony Steps 7A through 7C if you are instaing the remote annunciator. 2. Perform Steps 7A through 7E if you are instaing the remote annunciator with troube and acknowedge. A. Connect the annunciator - wires as indicated in Tabe 2. B. If supervision of annunciators is desired, remove the appropriate jumper(s) and resistor(s) indicated in Tabe 2. C. Connect the RMT + wire to TB3-9 (RMT +). D. Connect the REM ACK wire to TB2-1 (REM ACK). E. Connect the TBL RMT wire to TB3-8 (TBL RMT). I ZONE I TERMINAL I TABLE 2 JUMPER REMOVED RESISTOR REMOVED (See Caution Beow) (See Caution Beow) I 1 TB3-4 (ANN-) JW4 R84 2 (if used) TB3-5 (ANN2-) JW5 R85 3 (if used) TB3-6 (ANNS-) JW6 R86 4 (if used) TB3-7 (ANN4-) JW7 R87 CAUTION: If aarm reay modue is used, DO NOT REMOVE JUMPERS OR RESISTORS! 13 Technica Manuas Onine! -

18 CONTROL PANEL TERMINAL CONNECTIONS - Continued 162 JW4 JW5 JW6 JW7 FIGURE If aarm reay modue is used, connect it to TB2, TB3, and TB5 on the pane as foows (refer to Figure 16): A. Connect the reay modue s ANN1 wire (TB-1) to TB3-4 (ANN-). Connect the reay modue s ANN2 wire (TB-2) to TB3-5 (ANN2-). Connect the reay modue s ANN3 wire (TB-3) to TB3-6 (ANN3-). Connect the reay modue s ANN4 wire (TB-4) to TB3-7 (ANN4-). B. Connect the reay modue s AUX- wire (TB2-8) to TB2-4 (AUX-). Connect the reay modue s AUX+ wire (TB2-7) to TB5-6 (NO of AUX). C. Connect a wire from the pane s RMT+ (TB3-9) to TB5-7 (C of AUX). D. Refer to wiring diagrams for information on connecting externa devices. 9. If remote troube devices are used, connect them to troube reay as foows (Refer to Fig. 17): The troube reay may be used to operate externa circuits. These externa circuits may contain horns, bes, ights, or other devices associated with fire aarm systems. Notes: 1. Troube reay activates upon a troube condition. Troube sience switch activation turns off the troube reay. 2. Troube reay contacts are Form C dry contacts, and are rated 2A maximum at 30VACMOVDC (resistive rating). A. Connect positive (DC) or hot (AC) ead of votage source to TB3-2 (the common [C] contact of the troube reay). B. If devices are to be turned on during a troube condition, connect ead from remote devices to TB3-3 (the normay open [N/O] contact of the troube reay); if devices are to be turned off during a troube condition, connect ead from remote devices to TB3-1 (the normay cosed [N/C] contact of the troube reay. 14 Technica Manuas Onine! -

19 FIGURE If remotey controed devices are used, connect them to auxiiary master aarm reay as foows (refer to Fig. 17): The auxiiary reay may be used to operate externa circuits. These externa circuits may contain ights, fan contros, door reeases, or other devices associated with fire aarm systems. Notes: 1. Reay wi activate upon aarm. 2. Auxiiary reay contacts are Form C dry contacts and are rated 2A maximum at 30VAC30VDC (resistive rating). A. Connect positive (DC) or hot (AC) ead of votage source to TB5-7 (the common [C] contact of the AUX 1 reay). B. If devices are to be turned on during aarm, connect ead from remote devices to TB5-6 (the normay open [N/O] contact of the AUX 1 reay). If devices are to be turned off during aarm, connect ead from remote devices to TB5-8 (the normay cosed [N/C] contact of the AUX 1 reay). C. Repeat steps 1 thru 3 for the AUX 2 reay (if used). Use appropriate terminas TB5-4 (common). TB5-3 (normay open) and TB5-5 (normay cosed). City Connections 11. Configure jumper JW as shown in Figure 18. (If unabe to determine type of monitoring method being connected to the pane, ask the municipa monitoring faciity.) Note: Jumper JW is a header pug with pug-in jumpers. This pug is used to configure the-system when the city feature is not used - or when using reverse poarity, oca energy master box, or shunt city connections. FOR REVERSE POLARITY FOR SHUNT FOR LOCAL ENERGY FOR NO CITY JW JW CONNECTION JW : z FIGURE Technica Manuas Onine! -

20 CONTROL PANEL TERMINAL CONNECTIONS - Continued 12. If using a city circuit (municipa monitoring faciity), connect it as shown in Figure 19. FIGURE 19 WARNING: DANGEROUS VOLTAGE (1TOVAC) MAY EXIST AT POWER INPUT. MAKE SURE PROPER CIRCUIT BREAKER OR DISCONNECT SWITCH AT BUILDING S POWER DISTRIBUTION IS SET TO THE OFF POSITION. AC Power Connection The contro pane must be connected to 12OV 60Hz power, and a 120VAC wires must be routed separatey from other wires in the contro pane. (220/24OV 50Hz is used if your system is a ). 13. Connect back power ead (hot) to back ead from transformer input. Connect white power TO 120 VAC ead (neutra) to white ead from transformer FUSED OUTLET input (Fig. 20). 14. PERFORM THIS STEP ONLY IS USING THE BATTERY METER MODULE Insta the battery meter modue using the instructions provided with it. Discard the harness shipped with the contro pane and use the harness suppied with the meter modue. Connect the battery meter modue to the batteries as shown in Figure 21A. DO NOT BATTERY JUMPER. ON ox CONTROL LEA E WHTE BLACK -- CONNECT WHITE NOTE BATTERIES MOVNT IN CONTROL PANEL DO NOT USE HARNESS SHIPPED WITH BATTERIES II FIGURE 21A Note: If using 18Ah batteries in an externa cabinet without meter modue, proceed to Step Technica Manuas Onine! -

21 15. Connect battery to contro pane as foows: CAUTION: Check a battery connections carefuy for poarity. REVERSED CONNECTONS MAY DAMAGE EQUIPMENT A. Connect red wire of battery harness (without connector) to TB-3 (BAT +). Connect back wire (without connector) to TB-4 (BAT -). See Figure 21 B. B. Pace two 12V batteries in box assemby as shown in Figure 21 B C. Connect red wire of battery harness (with connector) to positive (+) termina of one battery. Connect back wire of battery harness (with connector) to negative (-) termina of other battery. See Figure 21 B. CAUTION: Do not connect the white jumper wire to battery terminas now. BATTERY POWER MAY CAUSE DAMAGE TO EQUIPMENT DURING INSTALLATION. 16. PERFORM THIS STEP ONLY IF 18Ah BATTERIES ARE BEING USED WITHOUT BATTERY METER MODULE INAN EXTERNAL BATTERY CABINET A harness is provided that extends from the battery cabinet to the contro pane. Discard the harness suppied with the contro pane and use the harness suppied with the battery cabinet. Connections are described beow. Note that you must run the harness through the knockout in the battery cabinet cosest to the contro pane, and up to the battery termina (TB). CAUTION: Check a battery connection carefuy for poarity. REVERSED CONNECTIONS MAY DAMAGE EQUIPMENT: Connect battery to contro pane as foows: A. Connect red wire of battery harness (without connector) to TB-3 (BAT +). Connect back wire (without connector) to TB-4 (BAT-). See Figure 21 B. B. Pace two 12V batteries in box assemby. C. Connect red wire of battery harness (with conn&tor) to positive (+) termina of one battery. Connect back wire of battery harness (with connector) to negative (-) termina of other battery. See Figure 21 B. CAUTION: Do not connect the white jumper wire to battery terminas now. BATTERY POWER MAY CAUSE DAMAGE TO EQUIPMENT DURING INSTALLATION. LEAVE WHITE ) JUMPER DISCONNECTED NOTE: IF BATTERIES ARE IN EXTERNAL CABINET, ROUTE HARNESS THROUGH KNOCKOUT CLOSEST TO CONTROL PANEL. FIGURE 21 B 17 Technica Manuas Onine! -

22 TRANSIENT SUPPRESSOR, ZONE DISCONNECT, OR COMBINATION TRANSIENT SUPPRESSOR/ZONE DISCONNECT BOARD TERMINAL CONNECTIONS (REFER TO WIRING DIAGRAM AND FIGURE 22) Note: Perform Steps 1 through 4 if the system is using the transient suppressor board or combination board. Perform ony Steps 2 through 4 if the system is using the zone disconnect board. 1. Connect notification appiance circuit to the foowing terminas on the transient suppressor board: TB-9 (SIG +) and TBI-10 (SIG -). TO NOTIFICATION APPLIANCE CIRCUIT (SEE STEP 1) TO INITIATING DEVICE TO NOTIFICATION TO INITIATING DEVICE CIRCUITS (SEE APPLIANCE CIRCUIT CIRCUITS (SEE TO INITIATING DEVICE STEPS 3 814) (SEE STEP 1) STEPS 3 & 4) I CIRCUITS (SEE STEPS 3 814) TRANSIENT SUPPRESSOR BOARD COMBINATION TRANSIENT SUPPRESSOR/ZONE DISCONNECT BOARD ZONE DISCONNECT BOARD FIGURE 22 IMPORTANT: WHEN NO WIRES ARE CONNECTED TO ZONE (INITIATING) TERMINALS, CONNECT A 3.3K EOLR ACROSS THOSE TERMINALS. 2. (If not aready done) Route ribbon cabe from connector P on board to connector P on contro pane. Ensure that the side of the cabe marked in dark bue ines up with pin 9 on each P. 3. Connecting initiating device circuits to the foowing terminas (refer to Tabe 3): Notes: 1. If any of the designated zone terminas on the suppressor or disconnect board do not have initiating devices connected to them, a 3.3K EOLR must be connected across these terminas. 2. If the system contains the waterfow/sprinker feature, connect waterfow-initiating devices to the suppressor or disconnect board terminas designated for zones 3 and 4 (see Step 4). 18 Technica Manuas Onine! -

23 TRANSIENT SUPPRESSOR, ZONE DISCONNECT, OR COMBINATION BOARD TERMINAL CONNECTIONS - Continued TABLE 3 rzone 1 TERMINALS I (ZON +) & TB4-2 (ZON -) TB4-3 (ZON2 +) 81 TB4-4 (ZON2 -) TB4-5 (ZON3 +) & TB4-6 (ZON3 -) TB4-7 (ZON4 +) & TB4-8 (ZON4 -) 4. Connect water-fow/sprinker circuits (if used) to suppressor, disconnect, or combination board as foows: A. Connect the waterfow switch (normay open) to TB-5 (ZON3 -) and TB-6 (ZON3 +). B. Connect the sprinker tamper switch (normay cosed) (if used) to TB-7 (ZON4 -) and TB-8 (ZON4 +). 19 Technica Manuas Onine! -

24 Notes: 1. DIP switch package SW1 programs the system for genera aarm operation or for the options isted in Tabe If no options are desired, make sure a DIP switches are set to the ON position. 3. When the system has operating power, you must RESET it when switch positions are changed. 1. Go to the OPTIONS coumn in Tabe 4 and seect one option from each of the tabe s six groups: TEST, CODING, CODED INPUT ON ZONE 1, WATERFLOW/SPRINKLER OR SILENCE INHIBIT, ALARM VERIFICATION or SIGNAL CUTOUT (Fig. 23). 2. Set DIP switch package SW1 in accordance with the options seected. OFF POSITION \ SW1, ON POSITION. TEST CODING (GROUP 1) (GROUP 3) c CODED INPUT ON ZONE 1 (GROUP 3). WATERFLOW/SPRINKLER OR SILENCE INHIBIT (GROUP 4).ALARM VERIFICATION (GROUP 5) SIGNAL CUTOUT (GROUP 6) FIGURE 23 TABLE 4 GROUP 1 GROUP 2 GROUP 3 C Simpe Coding (notification appiance. puses indicate zone in aarm) CODED INPUT ON ZONE 1 (Seect 1) Coded hut On Zone 1 OFF NO Coded Input On Zone 1 WATERFLOW SPRINKLER OR SILENCE INHIBIT (Seect 1) OFF OFF ON Note: For Genera aarm, a switches shoud be ON. GROUP 4 GROUP 5 GROUP 6 1 -I -Ic Neither Option Seected Waterfow Sprinker Sietyze Inhibit for 1 Min,ute (notification appq~;,ces cannot be sienced for 1 Sience Inhibit for 3 Minutes I ON ON OFF ON OFF ON OFF 1 OFF 1 ALARM VERIFICATION (Seect 1) 1 I I I I I I I Aarm Verification Not Seected I I I I I I 1 ON 1 I Aarm Verification Seected I INDICATING APPLIANCE CUTOUT (Seect 1) I I I I I 1 Notification Appiance Cutout Not Seected Notification Appiance Cutout (signas stop sounding 10 min,,+~c Laftar Irm, Note: I OFF 1 ON Aways RESET the system after programming or reprogramming. OFF 20 Technica Manuas Onine! -

25 SYSTEM POWER-UP Important: Notify appropriate personne (buiding occupants, fire department or monitoring faciity, etc.) of powerup. 1. Appy system power for severa seconds, then turn power off. 2. At arge circuit board, check fuses (Fig. 24) and at buiding s power distribution, check system circuit breaker or fuse. If fuses/circuit breaker are OK, go to Step 3. If fuses have opened or circuit breaker has tripped, check fied wiring as described on page 10. (Make sure power is removed from pane and appropriate circuit is disconnected from pane when checking circuit.) Repeat Steps 1 and 2 above. If fuses continue to open or circuit breaker continues to trip, contact your oca Simpex Branch Off ice (isted in the Yeow Pages under Fire Aarm). 3. Appy system power and press SYSTEM RESET switch (Fig. 24). Observe pane indicators: The SYSTEM TROUBLE LED, SIGNAL TROUBLE LED, and the four ZONE ALARM and TROUBLE LED S iuminate for five seconds. The tone device sounds for /2 second, and the green AC POWER ON LED iuminates continuousy. Note: If ony POWER TROUBLE, SYSTEM TROUBLE and AC POWER ON LEDs are iuminated and the tone device is sounding, set the TROUBLE SILENCE switch to the down position and go to Step 4. FUSE F3 FUSE F2 FUSE F TROUBLE SILENCE SWITCH ACK SWITCH FUSE F4 SYSTEM RESET SWITCH FIGURE 24 If any other system ALARM or TROUBLE LEDs are iuminated, or it system s green AC POWER ON LED is not iuminated, perform the foowing: Check fied wiring as described on Page 10. (Make sure power is removed from pane and appropriate circuit is disconnected from pane when checking circuit.) Repeat Steps 1 through 3 above. If the ALARM or TROUBLE LEDs (except POWER TROUBLE and SYSTEM TROUBLE) are iuminated or the system s green AC POWER ON LED is not iuminated, contact your oca Simpex Branch Office (isted in the Yeow Pages under Fire Aarm). Technica Manuas Onine!

26 SYSTEM POWER-UP (continued) Note: If system shows continuous aarm, check for activate initiating devices (construction dust in a smoke detector can cause fase aarms). 4. At battery harness, connect one end of the white jumper to positive termina of one battery and other end to negative termina of other battery (Fig. 25). The POWER TROUBLE and SYSTEM TROUBLE LEDs go out and the tone device sounds. 5. Set the TROUBLE SILENCE switch back to the NORMAL (up) position. 6. To test the system for proper operation, perform the procedure on Page 28 (How to Test the System). FIGURE 25 Technica Manuas Onine!

27 OPERATING INSTRUCTIONS INTRODUCTION The 4001 Fire Aarm System provides audibe and visua indications during aarm conditions. When an aarm condition occurs, the system activates the notification appiances and fashes appropriate aarm LEDs on the contro pane. The system s notification appiances operate unti you acknowedge the aarm or reset the system. You do two things when you acknowedge an aarm condition: You sience the notification appiances. You change the fashing LEDs on the contro pane to a steady iumination. Note: If the system has been programmed to incude certain options (see Page 24, Note 3), you cannot immediatey sience the notification appiances or reset the system. The system has resound capabiity. If - after an aarm has been acknowedged - another aarm occurs on another zone, the notification appiances wi operate again. The system can aso be set up for aarm verification, which essentiay verifies that a smoke detector is indeed in aarm. (See description of aarm verification on Page 26 for detais). The system constanty checks for eectrica troubes (opens, shorts, grounds, abnorma city connections, power oss, ow battery votage, etc.). If a troube condition occurs, the tone device on the pane sounds and the appropriate troube LEDs iuminate to indicate the type of troube. The system contains the foowing LED indicators (Figure 26) and switches (Figure 27). ALARM-THE RESPECTIVE ZONE ALARM LED IS ON WHEN AN ALARM CONDITION EXISTS IN ANY OF THE ZONES. \ \ I TROUBLE -THE RESPECTIVE ZONE TROUBLE LED IS ON 7 WHEN AN OPEN EXISTS IN ANY OF THE INITIATING DEVICE CIRCUITS. SGNAL TROUBLE - ON WHEN SHORT OR OPEN IN A NOTIFICATION-APPLIANCE CIRCUIT OCCURS. ANNUNCIATOR TROUBLE - ON WHEN OPEN IN ANY ANNUNCIATOR LINE OCCURS, OR WHEN ANNUNCIATOR LED FAILS. SYSTEM TROUBLE- ON WHEN ANY TROUBLE LED IS ON. IF ON AND OTHER TROUBLE INDICATORS ARE OFF, INDICATES AN OPEN IN CITY CIRCUIT OR A REMOTE ACK SWITCH IN THE ON POSITION. TONE DEWCE - ON FOR ABNORMAL SYSTEM CONDITIONS. POWER TROUBLE - ON FOR NO OR LOW INPUT VOLTAGE, AC P&VER -ON WHEN AC POWER IS ON. LOW BA-ITERY VOLTAGE, OR WHEN BATTERIES ARi DISCONNECTED. / GROUND TROUBLE-ON WHEN ANY CIRCUIT SHORTS TO EARTH. System Indicators FIGURE Technica Manuas Onine! -

28 CTY DSCONNECT - WHEN SET TO THE DOWN POSITION, OR WHEN CITY IS DISCONNECTED FOR TEST PURPOSES OR SYSTEM MAINTENANCE. TROUBLE SLENCE - WHEN SET TO THE DOWN POSITION, TONE DEVICE IS SILENCED DURING TROUBLE CONDITION. AFTER TROUBLE CONDITION CLEARS, TONE DEVICE WILL SOUND UNTIL SWITCH IS SET BACK TO THE UP POSITION. ACKNOWLEDGE (ACK) - WHEN PRESSED, ALARM- NOTIFICATION APPLIANCES ARE SILENCED AND ZONE ALARM INDICATORS CHANGE FROM A FLASHING CONDITION TO A STEADY ILLUMINATION. SYSTEM RESET - WHEN PRESSED, RESETS SYSTEM FOLLOWING AN ALARM CONDITION. System Switches FIGURE 27 HOW TO RECOGNIZE NORMAL, TROUBLE, AND ALARM INDICATIONS Norma Condition The green AC POWER ON indicator is on. A other indicators are off. Troube Condition Tone device is sounding a steady tone. One or more amber indicators are on. Aarm Condition The notification appiances throughout the buiding are operating. One or more red ALARM indicators are fashing indicating the zone(s) reporting the aarm. HOW TO OPERATE THE PANEL DURING AN ALARM CONDITION Important: Consut oca code authorities for specific actions to be taken during an aarm condition. When appropriate, unock and open the pane door. To sience notification appiances, press the ACK (acknowedge) switch (Fig. 27). Notes: 1. Upon pressing the ACKNOWLEDGE switch, any red indicator that was fashing changes to a steady iumination. 2. If another aarm is reported from another zone, the notification appiances operate again and the red indicator representing the new zone in aarm fashes (unti the new aarm is acknowedged). 3. The foowing options wi affect the acknowedge feature as foows: Coded Input On Zone 1 - notification appiances cannot be sienced when zone 1 is in aarm; however, fashing indicators change to a steady iumination when acknowedged. (Notification appiances sience automaticay upon code competion.) Sience Inhibit - notification appiances cannot be sienced unti the specified time period has eapsed (1 or 3 minutes). Water-fow/Sprinker - notification appiances cannot be sienced if water is fowing in the sprinker system. 24 Technica Manuas Onine! -

29 HOW TO RESET THE FIRE ALARM SYSTEM FOLLOWING AN ALARM CONDITION When the aarm situation has been ceared, restore or repace a affected aarm-initiating devices (pu stations and detectors), if required, in accordance with the instructions provided with each device. Press the SYSTEM RESET switch (Fig. 27) unti LEDs iuminate. Note: The foowing options wi affect the RESET feature as foows: Sience Inhibit - you cannot RESET the system unti the specified time period has eapsed. WaterfowSprinker - you cannot RESET the system if water is fowing in the sprinker system. HOW TO OPERATE THE PANEL WHEN WATER IS FLOWING IN THE SPRINKLER SYSTEM (OPTIONAL) When water is fowing in the sprinker system, the foowing indications exist: The sprinker ALARM (ZONE 3) red indicator is fashing. The notification appiances are operating. After the fire has been extinguished exist: and the water to the sprinker system has been shut off, the foowing indications The sprinker ALARM (ZONE 3) red indicator is on steady. The tamper switch ALARM (ZONE 4) red indicator is on steady (indicating that the water to the sprinker system has been shut off). The notification appiances are sti operating. The tone device is sounding a sow puse (indicating that the water to the sprinker system has been shut off). If the water to the sprinker system has been shut off, proceed as foows: At the pane, press the ACK switch (Fig. 27) notification appiances are sienced, the sprinker ALARM (ZONE 3) red indicator turns off, the tone device continues to sound a sow puse, and the tamper switch ALARM (ZONE 4) indicator remains on). Note: Tone device cannot be sienced when water to the sprinker system has been shut off. Restore or repace sprinker heads in accordance with the instructions provided with the devices. Restore water to sprinker system in accordance with the instructions provided with the sprinker system (this causes the tamper switch ALARM (ZONE 4) indicator to fash and the tone device to puse rapidy). Press the RESET switch (Fig. 27) unti LEDs iuminate (system returns to its norma condition). Note: Unti the sprinker system is fuy recharged, waterfow may be detected by the pane and the fire aarm system may go into aarm again. Therefore, you may have to repeat this procedure severa times whie recharging the sprinker system. 25 Technica Manuas Onine! -

30 WHAT TO DO IN CASE OF TROUBLE Notify appropriate personne. (If the system is connected to the city, notify the fire department monitoring faciity.) Unock and open pane door. If tone device is sounding, set TROUBLE SILENCE switch (Fig. 27 on Page 24) to its down position. Note: When the troube has ceared, the tone device wi sound again as a reminder to set the TROUBLE SILENCE switch back to its norma position. Corrective Actions Observe TROUBLE indicators and perform the corrective action outined in Tabe 5 (see Page 27). When the troube cears, set TROUBLE SILENCE switch to its NORMAL (up) position. If troube is on the pane s circuit board, contact your oca Simpex Branch Office (isted in the Yeow Pages under Fire Aarm). Important: Any attempt to repace any components on the pane s circuit board voids the warranty. CAUTION: 24VDC exists at contro pane circuit board. This votage may cause damage to equipment during fuse repacement, resistance measurements, or wire checks. When performing these activities, ensure that the battery jumper (white wire) is disconnected from the battery and that a AC power is removed from the system s pane and peripheras. When repacement or checks are compete, restore power (AC power first then batteries) and press RESET switch unti the zone LEDs iuminate. Note: When checking a suspected circuit, remove the circuit from the pane terminas (see Page 10, Buiding Wiring Checkout Procedure), and the system wiring diagram ( ) provided with the pane. ALARM VERIFICATION FEATURE (OPTIONAL) The 4001 Fire Aarm System can be programmed for aarm verification (see Page 20, System Programming). Aarm verification works on/y with Simpex smoke detectors. This feature requires the verification of any aarm initiated by a smoke detector, but aows contact devices (heat detectors and manua stations) residing in the same zone to initiate aarms upon activation. The feature works as foows: a. If a smoke detector senses an aarm, the 4001 starts a 30-second timer, but otherwise ignores the aarm. b. If, during the 30 seconds, no contact device in any zone (or smoke detector in another zone) activates, the zone enters a 15second reset cyce. c. Foowing the reset cyce, the 4001 enters a 120-second confirmation period. If, during this period, the smoke detector re-aarms (or another smoke detector in the same zone initiates an aarm) the 4001 aarms immediatey. d. If no aarms occur during the 120-second confirmation period, the 4001 automaticay returns to norma operation. Notes: 1. If, at any time during the above time period, a smoke detector in another zone (or contact device in any zone) activates, the 4001 aarms immediatey. 2. If Zone 1 is used with the coded input option, then aarm verification wi not work on Zone If Zones 3 and 4 use the sprinker/water-fow options, then aarm verification wi not work on Zones 3 and Technica Manuas Onine! -

31 TROUBLESHOOTING TABLE 5 SYMPTOM CORRECTIVE ACTION AC POWER ON indicator OFF. Check system s 120 VAC circuit breaker at the buiding s power distribution box. Remove overay (Fig. 4 on page 10) and check fuse F (Fig. 4). If F is open, contact Simpex for service. Check input wiring at TB-1 (XMER) and TB-2 (XMER). I GROUND TROUBLE and SYSTEM TROUBLE LEDS are on. Individuay remove each externa wire from the contro pane unti the ground faut cears. Locate and repair ground faut. POWER TROUBLE and If AC POWER ON LED is off, perform the corrective action specified for this SYSTEM TROUBLE LED are symptom (see above). If AC POWER ON LED is on, check for AC brownout, on. battery votage, and battery connections. Make sure CITY DISC switch is set to the CONNECT position. Check jumper SYSTEM TROUBLE (ony) is JW configuration (see Figure 21 on page 25). Check city wires (if used) at on. TB5-1 (CITY +) and TB5-2 (CITY -). This may indicate a tripped city box. A remote ACK switch coud aso be on. ANNUN TROUBLE and SYSTEM TROUBLE LEDs are on. SIGNAL TROUBLE and SYSTEM TROUBLE LEDs are ^ ^ UII. - One or more of the ZONE LEDs and SYSTEM TROUBLE LED are on. System continuousy indicates and aarm condition after a SYSTEM RESET and no fire condition exists. Check annunciator LEDs. Repace any bad LEDs. Check annunciator wiring (refer to page 20 and the pubication provided with the annunciator). Remove wires from TB2-5 (SIG +) and TB2-6 (SIG -) or, if the suppressor board is used, TB-9 (SIG +) and TBi-10 (SIG -) on the suppressor board. Then connect a IOK resistor across the terminas. If the indicators go out, check circuit wiring. If indicators remain on, see box beow. Remove wires from terminas associated with the zone indicated by the TROUBLE LED. Then connect a 3.3K resistor acrossthe terminas (zone wires wi be connected to the suppressor, disconnect or combination board, if used). Remove the resistors and reconnect the zone wiring after testing. If indicators go out, check circuit wiring. If indicators remain on, see box beow. Check for she brts in the zone circuit(s) associated with iuminated ALARM LED. Check periph eras in the zone circuit(s) (refer to the pubication provided with each device). System fais to initiate an Pace a soid conductor (short) across the appropriate zone terminas. If the aarm when an aarm-initiating aarm is activated, check the aarm-initiating device (refer to pubication device is activated. provided with the device). If aarm is not activate, see box beow. If troube condition persists, contact your oca Simpex Branch Office (isted in the Yeow Pages under Fire Aarm). 27 Technica Manuas Onine! -

CHANNEL LETTER LIGHTING

CHANNEL LETTER LIGHTING LIGHTING UNIQUE LIGHTING SOLUTIONS WARNING The retrofit instaation must ony be performed by a icensed eectrician. To prevent death, injury or damage to property this product must be instaed in accordance

More information

asimplex Operating Instruction< 4020 Fire Alarm www.bevansecurity.com FA4-31-401 (574-062) 0 1995 Simplex Time Recorder Co.

asimplex Operating Instruction< 4020 Fire Alarm www.bevansecurity.com FA4-31-401 (574-062) 0 1995 Simplex Time Recorder Co. asimpex 4020 Fire Aarm Operating nstruction< 0 1995 Simpex Time Recorder Co. FA4-31-401 (574-062) A specifications and other information shown were current as of pubication, and are subject to change without

More information

CHANNEL LETTER LIGHTING

CHANNEL LETTER LIGHTING LIGHTING UNIQUE LIGHTING SOLUTIONS WARNING The retrofit instaation must ony be performed by a icensed eectrician. To prevent death, injury or damage to property this product must be instaed in accordance

More information

HM-W536 Install Guide

HM-W536 Install Guide HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.

More information

Eaton Advanced Enclosure Power Distribution Unit (epdu ) User s Guide

Eaton Advanced Enclosure Power Distribution Unit (epdu ) User s Guide Eaton Advanced Encosure Power Distribution Unit (epdu ) User s Guide Eaton and epdu are registered trademarks of Eaton Corporation or its subsidiaries and affiiates. Googe Chrome is a trademark of Googe,

More information

Fire Fighter Phone System Installation Instructions

Fire Fighter Phone System Installation Instructions Fire Fighter Phone System Installation Instructions Introduction This publication describes the installation procedure for the Fire Fighter s Phone on a 4100U or a 4100ES Fire Alarm Control Panel (FACP).

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................

More information

Power-D-Box Printed Circuit Board Version for 2216/REF16

Power-D-Box Printed Circuit Board Version for 2216/REF16 Power-D-Box Printed Circuit Board Version for 226/REF6 Description The Power-D-Box based on a is a compact power distribution system, designed as a 9" 2U rack made of auminium profies with anodised front

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment

More information

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12)

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) UL864 (Commercial Fire) Compliance General Requirements The VISTA-128FBPT/VISTA250FBPT

More information

Eaton Network Card-MS. User s Guide

Eaton Network Card-MS. User s Guide Eaton Network Card-MS User s Guide Cass B EMC Statements FCC Part 15 Cass B This equipment has been tested and found to compy with the imits for a Cass B digita device, pursuant to part 15 of the FCC Rues.

More information

GWPD 4 Measuring water levels by use of an electric tape

GWPD 4 Measuring water levels by use of an electric tape GWPD 4 Measuring water eves by use of an eectric tape VERSION: 2010.1 PURPOSE: To measure the depth to the water surface beow and-surface datum using the eectric tape method. Materias and Instruments 1.

More information

Fire Alarm System Plans Review Checklist Property location Date of Review

Fire Alarm System Plans Review Checklist Property location Date of Review Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include

More information

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:

More information

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000

More information

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way

More information

Energy Performance Certificate

Energy Performance Certificate Energy Performance Certificate Sampe EPC TheDomesticEnergyAssessorcom Dweing type: Date of assessment: Date of certificate: Reference number: Tota foor area: Mid-terrace house 09 June 2007 31 August 2007

More information

Precise assessment of partial discharge in underground MV/HV power cables and terminations

Precise assessment of partial discharge in underground MV/HV power cables and terminations QCM-C-PD-Survey Service Partia discharge monitoring for underground power cabes Precise assessment of partia discharge in underground MV/HV power cabes and terminations Highy accurate periodic PD survey

More information

Operation Guide 3440 3441

Operation Guide 3440 3441 MO1504-EB 2015 CASIO COMPUTER CO., LTD. Operation Guide 3440 3441 Getting Acquainted Congratuations upon your seection of this CASIO watch. To get the most out of your purchase, be sure to read this manua

More information

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell Data, installation, operation and maintenance 4 & 8 Zone Fire Panels Zircon range BARDIC by Honeywell LED flashing LED Continuous FAULT DISABLE/TEST Power General Fault Sounder Fault/ Disable System Fault

More information

SNMP Reference Guide for Avaya Communication Manager

SNMP Reference Guide for Avaya Communication Manager SNMP Reference Guide for Avaya Communication Manager 03-602013 Issue 1.0 Feburary 2007 2006 Avaya Inc. A Rights Reserved. Notice Whie reasonabe efforts were made to ensure that the information in this

More information

Lucent Technologies Bell Labs Innovations. PARTNER II Communications System PARTNER Plus Communications System Release 4.1.

Lucent Technologies Bell Labs Innovations. PARTNER II Communications System PARTNER Plus Communications System Release 4.1. Lucent Technoogies Be Labs Innovations PARTNER II Communications System PARTNER Pus Communications System Reease 4.1 System Panner 518-455-338 Issue 2 August 1996 Copyright 1996 Lucent Technoogies A Rights

More information

Technical Support Guide for online instrumental lessons

Technical Support Guide for online instrumental lessons Technica Support Guide for onine instrumenta essons This is a technica guide for Music Education Hubs, Schoos and other organisations participating in onine music essons. The guidance is based on the technica

More information

Control Panels D9412GV3/D7412GV3/D7212GV3. UL Installation Instructions

Control Panels D9412GV3/D7412GV3/D7212GV3. UL Installation Instructions Control Panels D9412GV3/D7412GV3/D7212GV3 en UL Installation Instructions Control Panels Table of Contents en 3 Table of Contents 1 Installation 4 1.1 Installation Preparation 4 1.2 Enclosure Options

More information

Release Control Fire Alarm Systems

Release Control Fire Alarm Systems SYSTEM ABORT PUSH AND HOLD COIL SUPERVISION MODULE (2 AMP) 2081-9046 RED INSTALLATION INSTRUCTIONS 574-437 REV YEL NAC+ MAINTAIN 1/4" SEPARATION BETWEEN POW ER LIMITED (RED/) AND NONPOWER S LIMITED (YEL/)

More information

Enhanced continuous, real-time detection, alarming and analysis of partial discharge events

Enhanced continuous, real-time detection, alarming and analysis of partial discharge events DMS PDMG-RH DMS PDMG-RH Partia discharge monitor for GIS Partia discharge monitor for GIS Enhanced continuous, rea-time detection, aarming and anaysis of partia discharge events Unrivaed PDM feature set

More information

A.1. a Division of Pittway Corporation. Documento: M-010.1-MGAS-ENG. Edizione: 01/1997 Rev.:

A.1. a Division of Pittway Corporation. Documento: M-010.1-MGAS-ENG. Edizione: 01/1997 Rev.: Documento: M-010.1-MGAS-ENG Edizione: 01/1997 Rev.: A.1 a Division of Pittway Corporation FRONT PANEL & VISUAL INDICATIONS GENERAL TROUBLE GENERAL PROGRAMMING IN PROGRESS ENABLE/ALARM/TROUBLE (ZONE 1 ALARM

More information

4100U/4100ES to TFX Fire Fighter Phone System Installation Instructions

4100U/4100ES to TFX Fire Fighter Phone System Installation Instructions 4100U/4100ES to TFX Fire Fighter Phone System Installation Instructions Introduction This publication describes the installation procedure for the 4100U/4100ES to TFX Fire Fighter s Phone card used to

More information

>2033DUPS UNINTERRUPTIBLE P O W E R SUPPLIES

>2033DUPS UNINTERRUPTIBLE P O W E R SUPPLIES >2033DUPS UNINTERRUPTIBLE P O W E R SUPPLIES Mitsubishi The Leader in UPS Technoogy, Quaity & Reiabiity 2033D ONE-LINE DIAGRAMS Superior Performance, Reiabiity and Safety Come from Experience. Our Uninterruptibe

More information

SP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE

SP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE SP4LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE INSTALLATION AND OPERATION MANUAL MASS NOTIFICATION SYSTEM Part Number: P84767 Rev. A Copyright 2006 Cooper Wheelock, Inc. All rights reserved.

More information

Installation Instructions & Owner s Operation Manual for Two to Eight Zone 2400 Series Fire Alarm Control Panels

Installation Instructions & Owner s Operation Manual for Two to Eight Zone 2400 Series Fire Alarm Control Panels Installation Instructions & Owner s Operation Manual for Two to Eight Zone 2400 Series Fire Alarm Control Panels P/N 46000-1320, Rev. 1.6 Edwards This product has been designed to meet the requirements

More information

Eaton Intelligent Power Protector (IPP) Quick Start Installation Manual

Eaton Intelligent Power Protector (IPP) Quick Start Installation Manual Eaton Inteigent Power Protector (IPP) Quick Start Instaation Manua Eaton is a registered trademarks of Eaton Corporation or its subsidiaries and affiiates. Googe Chrome is a trademark of Googe, Inc. HyperTermina

More information

INSTALLATION & SERVICE MANUAL. Display Panel

INSTALLATION & SERVICE MANUAL. Display Panel INSTALLATION & SERVICE MANUAL Display Panel The PowerLine EMS TM is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed

More information

FA-300 Series. LCD Fire Alarm Control Panel. User Guide. LT-954 Rev. 0.1 February 2013. FA-300 SERIES Fire Alarm Control Panel

FA-300 Series. LCD Fire Alarm Control Panel. User Guide. LT-954 Rev. 0.1 February 2013. FA-300 SERIES Fire Alarm Control Panel ABC DEF GHI JKL MNO PQR STU YZ WXY FA-300 Series LCD Fire Alarm Control Panel Advanced Life Safety Solutions System Normal 10:36AM WED 2003-10-01 SYSTEM RESET A.C. ON ALARM SUPV TRBL CPU FAIL SIGNAL SILENCE

More information

DTW Works Master Specification Version 2006

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4

More information

FC-72 SERIES FIRE ALARM SYSTEM

FC-72 SERIES FIRE ALARM SYSTEM FC-72 SERIES FIRE ALARM SYSTEM INSTRUCTION/OPERATING MANUAL Copyright 1988 Part Number: 9000-0007 Published in the U.S.A. Version 5.1 All rights reserved Serial Number 301 2nd Ave. Waltham, MA 02451-1133

More information

4002 Life Alarm Fire Alarm Systems

4002 Life Alarm Fire Alarm Systems 4002 Life Alarm Fire Alarm Systems Service Instructions 0 1994 Simplex Time Recorder Co. FA4-51-154 All specificallons and other information shown were current as of pubkatlon, and are subject to change

More information

Advantium 2 Plus Alarm

Advantium 2 Plus Alarm ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia

More information

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval. Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's

More information

PN 15153:G1 ECN 02-539. Fire Alarm Control Panel MS-4424. Instruction Manual. Document 15153 10/22/2002 Rev: G

PN 15153:G1 ECN 02-539. Fire Alarm Control Panel MS-4424. Instruction Manual. Document 15153 10/22/2002 Rev: G PN 15153:G1 ECN 02-539 Fire Alarm Control Panel MS-4424 Instruction Manual Document 15153 10/22/2002 Rev: G Fire Alarm System Limitations An automatic fire alarm system typically made up of smoke detectors,

More information

Installation and Operation Guide PD4600 Series Converter Replacement

Installation and Operation Guide PD4600 Series Converter Replacement Installation and Operation Guide PD4600 Series Converter Replacement Extended warranties are available for purchase at www.progressivedyn.com Member Thank you for selecting Progressive Dynamics as your

More information

Advanced ColdFusion 4.0 Application Development - 3 - Server Clustering Using Bright Tiger

Advanced ColdFusion 4.0 Application Development - 3 - Server Clustering Using Bright Tiger Advanced CodFusion 4.0 Appication Deveopment - CH 3 - Server Custering Using Bri.. Page 1 of 7 [Figures are not incuded in this sampe chapter] Advanced CodFusion 4.0 Appication Deveopment - 3 - Server

More information

D287/D288/D292/D293A/D293E

D287/D288/D292/D293A/D293E D87/D88/D9/D9A/D9E EN Installation Guide Smoke Detector Bases D87/D88/D9/D9A/D9E Installation Guide.0 Overview.0 Overview The D87/D88/D9/D9A/D9E Smoke Detector Bases are designed for use with the D8 Ionization

More information

WINMAG Graphics Management System

WINMAG Graphics Management System SECTION 10: page 1 Section 10: by Honeywe WINMAG Graphics Management System Contents What is WINMAG? WINMAG Text and Graphics WINMAG Text Ony Scenarios Fire/Emergency Management of Fauts & Disabement Historic

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM 1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this

More information

Fire Alarm Control Panel. Family. Operating Manual

Fire Alarm Control Panel. Family. Operating Manual Fire Alarm Control Panel Family Operating Manual CONTENTS System Description AH-03312 System Characteristics... Fire Signal Receiving Board Description-4L... Fire Signal Receiving Board Description-8L...

More information

HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS

HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS USER MANUAL USER MANUAL ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS INTRODUCTION The (HA-841K) is a complete

More information

Avaya Remote Feature Activation (RFA) User Guide

Avaya Remote Feature Activation (RFA) User Guide Avaya Remote Feature Activation (RFA) User Guide 03-300149 Issue 5.0 September 2007 2007 Avaya Inc. A Rights Reserved. Notice Whie reasonabe efforts were made to ensure that the information in this document

More information

Design and Construction Standards SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS

Design and Construction Standards SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES: A. Fire alarm and smoke detection systems. 1.2 REFERENCES 1.3 NFPA 72 1.4 NFPA 101 1.5 REGULATORY REQUIREMENTS

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM SECTION 16721 FIRE ALARM AND DETECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat

More information

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description SFC-200 SERIES FIRE ALARM CONTROL PANELS SFC-200 Series Fire Alarm Control Panels Description Summit s SFC-200 Series fire alarm control panels consist of six and twelve zone models which are equipped

More information

Life Alarm Fire Alarm Controls

Life Alarm Fire Alarm Controls FIRE SUPERVISORY SUPV SILENCED SILENCE AC POWER RESET UL, ULC Listed FM Approved MEA Approved* Life Alarm Fire Alarm Controls Fire Alarm Controls 4005 Series Fire Alarm Control Panels Eight through Thirty-Six

More information

TS510 & TS500. Installation & User Guide. Compatible Equipment

TS510 & TS500. Installation & User Guide. Compatible Equipment Installation & User Guide Compatible Equipment TS510 REM - Remote Keypad 9040 - Loudspeaker DC54/58 - Digital Communicator SD1+ - Speech Dialler 496525 Issue A 1 of 10 TS510 and TS500 Overview Introduction

More information

Xerox Document Centre User Guide 460 DC/ST 265 DC/ST 255 DC/ST 240 DC/ST

Xerox Document Centre User Guide 460 DC/ST 265 DC/ST 255 DC/ST 240 DC/ST Xerox Document Centre User Guide February 2000 701P34104 470 DC/ST 460 DC/ST 265 DC/ST 255 DC/ST 240 DC/ST Document Centre DC Document Centre ST Document Centre 470/460/265/255/240 DC/ST User Guide February

More information

Manual for Fire Suppression & Methane Detection System

Manual for Fire Suppression & Methane Detection System Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327

More information

SILENT KNIGHT MODEL 5207

SILENT KNIGHT MODEL 5207 SILENT KNIGHT MODEL 5207 Fire Control / Communicator Installation, Programming, and Operation Manual Part Number 150865 Rev. C, 04/03 Contents Section 1 Introduction.......................................................................1-1

More information

VFR-400 Installation, Operation, and Instruction Manual

VFR-400 Installation, Operation, and Instruction Manual VFR-400 Installation, Operation, and Instruction Manual Releasing Panel for Sprinkler Systems All specifications subject to revision. Manual #5403548 Rev. Q 10/11 NOTES: i Table of Contents Operating

More information

SECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM

SECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM KNOXVILLE, TENNESSEE SECTION 28 31 11 PAGE 1 PART 1 - GENERAL 1.01 DESCRIPTION OF WORK SECTION 28 31 11 A. Extent of fire alarm and detection system work shall be as described in this specification, as

More information

Manifold Technology. ----------------------------------------------------- made in Germany

Manifold Technology. ----------------------------------------------------- made in Germany Manifod Technoogy. ----------------------------------------------------- made in Germany I EVERYTHING UNDER CONTROL. Manifod Technoogy BEULCO heating and cooing manifods made of high-quaity brass ensure

More information

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual P/N 315-049403-1 Siemens Building Technologies Fire Safety Table Of Contents Introduction...1 The Access levels...1 User Level...1 Maintenance

More information

Occupancy sensors & PIRs

Occupancy sensors & PIRs Occupancy sensors & PIRs Various ocations where motion sensors can be used are genera office, stairwe, corridors outdoor appications. Master & save fush ceiing motion sensors Crabtree s range of occupancy

More information

Data sheet. June 2000 DKACT.PD.P10.F1.02 520B0370

Data sheet. June 2000 DKACT.PD.P10.F1.02 520B0370 Pressure contros and thermostats types KPI and KP June 2000 DKACT.PD.P10.F1.02 520B0370 Pressure contros and thermostats, types KPI and KP Contents Pressure contros KP 35, KP 36, KPI 35, KPI 36 and KPI

More information

BC80 system catalog. Building Technologies

BC80 system catalog. Building Technologies BC80 system cataog. Buiding Technoogies 1 A wide range of appications. BC80 comprises an extensive product portfoio and can be instaed in various buiding types. For instance, it is a perfect soution for:

More information

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description

More information

SFC-200 SERIES LCD FIRE ALARM PANEL

SFC-200 SERIES LCD FIRE ALARM PANEL SFC-200 SERIES LCD FIRE ALARM PANEL User Guide LT-954SUM SFC-200 Series LCD Version User Guide Contents Introduction... 1 About this Manual... 1 Technical Support... 1 Main Display... 1 The Buzzer and

More information

SECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM

SECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM SECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 SECTION INCLUDES A. Fire alarm system requirements B. Fire alarm equipment C. Fire alarm peripheral devices 1.02 RELATED SECTIONS

More information

SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION

SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION A. This section of the specifications includes the furnishing, installation, and connection of the microprocessor-controlled

More information

INSTALLATION MANUAL PC2525. Version 1.1

INSTALLATION MANUAL PC2525. Version 1.1 INSTALLATION MANUAL PC2525 Version 1.1 TABLE OF CONTENTS FEATURES 1 SPECIFICATIONS 1 INSTALLATION 2 Mounting the Panel... 2 Mounting the Keypad... 2 Auxiliary Power Connection... 2 Bell/Siren Connection...

More information

SECTION 13850 DETECTION AND ALARM

SECTION 13850 DETECTION AND ALARM SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring

More information

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected

More information

16720S01 - FIRE ALARM SYSTEM (HARDWIRED), MANUAL AND AUTOMATIC

16720S01 - FIRE ALARM SYSTEM (HARDWIRED), MANUAL AND AUTOMATIC 1. GENERAL 1. Fire alarm system shall be manufactured by Simplex, Autocall or Edwards. Simplex part numbers are provided in this spec for clarification only and do not exclude equivalent part numbers of

More information

ESL 1500 Series Fire Alarm Control Panel Installation and Operations Manual

ESL 1500 Series Fire Alarm Control Panel Installation and Operations Manual g GE Security ESL 1500 Series Fire Alarm Control Panel Installation and Operations Manual Table of Contents Precautions and Warnings... 1 System Overview... 1 Panel Listing...1 Panel Description... 2

More information

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual CONTENTS Installation Precautions... 1 EN 54 Information... 2 Chapter 1 Product Overview... 3 1.1 Features... 3 1.2 Technical Specifications... 3 1.2.1 Operating Voltage... 3 1.2.2 Batteries... 4 1.2.3

More information

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 Instruction Sheet 1-2003 Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 PURPOSE OF KIT A CCM-T is used to monitor and control an automatic transfer switch. The

More information

DIGITAL ALARM II FOR HOSPITALS AND LABORATORIES INSTALLATION AND OPERATING INSTRUCTIONS 52 635.0

DIGITAL ALARM II FOR HOSPITALS AND LABORATORIES INSTALLATION AND OPERATING INSTRUCTIONS 52 635.0 Form No. 74-00-4001 S168-195-001 Revision E DIGITAL ALARM II FOR HOSPITALS AND LABORATORIES INSTALLATION AND OPERATING INSTRUCTIONS 52 635.0 INTRODUCTION Allied Healthcare Products, Inc. s Digital Alarm

More information

Operation Guide 5208

Operation Guide 5208 MO1106-EA Operation Guide 5208 Getting Acquainted ongratuations upon your seection of this ASIO watch. To get the most out of your purchase, be sure to read this manua carefuy. Keep the watch exposed to

More information

Meeting Exchange 5.0 Installing the S6200 and S6800 Conferencing Servers

Meeting Exchange 5.0 Installing the S6200 and S6800 Conferencing Servers Meeting Exchange 5.0 Instaing the S6200 and S6800 Conferencing Servers 04-602172 Issue 1 August 2007 2007 Avaya Inc. A Rights Reserved. Notice Whie reasonabe efforts were made to ensure that the information

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.

More information

PC4020CF v3.0 and higher Commercial Fire Installation Guide DLS-3 v1.3

PC4020CF v3.0 and higher Commercial Fire Installation Guide DLS-3 v1.3 PC4020CF v3.0 and higher Commercial Fire Installation Guide DLS-3 v1.3 Table of Contents Section 1: Introduction 1 1.1 Introduction...1 1.2 Hardware Description and Specifications...1 Section 2: Fire Zone

More information

AC-115 Compact Networked Single Door Controller. Installation and User Manual

AC-115 Compact Networked Single Door Controller. Installation and User Manual AC-115 Compact Networked Single Controller Installation and User Manual December 2007 Table of Contents Table of Contents 1. Introduction...5 1.1 Key Features... 6 1.2 Technical Specifications... 7 2.

More information

Control Panel. D9412GV4/D7412GV4 v2.03. en UL Installation Instructions

Control Panel. D9412GV4/D7412GV4 v2.03. en UL Installation Instructions Control Panel D9412GV4/D7412GV4 v2.03 en UL Installation Instructions Control Panel Table of Contents en 3 Table of contents 1 Introduction 5 1.1 About documentation 5 1.2 Bosch Security Systems, Inc.

More information

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY

More information

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual PART 8: FIELD WIRING A. INSTALLATION MUST COMPLY WITH: 1. National Electrical Code and any other national, state, provincial or local codes or regulations. 2. In Canada, CSA C22.1 Canadian Electrical Code

More information

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,

More information

INTRODUCTION. The data provided is for The Standard Products and any variation will be dealt with at the end of this manual.

INTRODUCTION. The data provided is for The Standard Products and any variation will be dealt with at the end of this manual. INTRODUCTION The information provided herein covers the range of products known as the 'Sensor 901' series. The range of equipment is designed to meet the requirements of BS 5839 parts 1 & 4 1988. The

More information

SHUTTER STARZ TABLETOP COMPLETE PHOTO STUDIO KIT

SHUTTER STARZ TABLETOP COMPLETE PHOTO STUDIO KIT SHUTTR STARZ TABLTOP COMPLT PHOTO STUIO KIT TX Internationa 2012 A B H C G I SS150 SHUTTR STARZ PROSSIONAL PHOTOGRAPHY STUIO LIGHTING UMBRLLA KIT A B C G H I Qty. 1 32 Professiona Light Tent Qty. 1 13

More information

Method of Build KOMFORT. Polar 100

Method of Build KOMFORT. Polar 100 Poar 100 - a seamess (tape and fiied or skimmed) soid partition and frameess gazed dry or siicon jointed system Poar 100 Method of Buid Love the space you re in. March 2013 Poar-100 - partitioning system

More information

What to do before, during and after a flood

What to do before, during and after a flood Suffok Food Risk Management Partnership What to do before, during and after a food Practica advice on what to do to protect yoursef and your property "Over 5.5 miion properties in Engand and Waes are at

More information

HERNANDO COUNTY FIRE ALARM GUIDELINES

HERNANDO COUNTY FIRE ALARM GUIDELINES HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a

More information

User Guide for the DS7060 Control/Communicator

User Guide for the DS7060 Control/Communicator DS7060 User Guide Copyright 1996-97 Detection Systems, Inc. User Guide for the DS7060 Control/Communicator Copyright 1996-97 Detection Systems, Inc. Detection Systems, Inc., 130 Perinton Parkway, Fairport,

More information

XP-600 Programming Instructions

XP-600 Programming Instructions Hexadecimal Data Entry To Enter a hexadecimal digit enter the following A= A1 D= A4 B= A2 E= A5 C= A3 F= A6 XP-600 Programming Instructions Note These Programming Instructions are intended to be used in

More information

TABLE OF CONTENTS FEATURES

TABLE OF CONTENTS FEATURES TABLE OF CONTENTS FEATURES 2 Keypad Programmable... 2 EEPROM Memory... 2 Static/Lightning Protection... 2 Supervision... 2 Operation... 2 SPECIFICATIONS 2 PC1550 Control Panel... 2 PC1500RK Keypad... 2

More information

ZUP SERIES. Model naming method. Features. Applications. Conformity to RoHS Directive. Product Line up ZUP36-12. Programmable CVCC 200W 800W 19Model

ZUP SERIES. Model naming method. Features. Applications. Conformity to RoHS Directive. Product Line up ZUP36-12. Programmable CVCC 200W 800W 19Model SERIES Programmabe CVCC 200W 800W 19Mode Features 800W Constant Votage/Constant Current uit-in RS232 & RS485 Interface An embedded Microprocessor controer Digita Encoder Knob Software Caibration Last Setting

More information

FLEET. Management. Innovative Tools for. Telematics for the Working Fleet

FLEET. Management. Innovative Tools for. Telematics for the Working Fleet Innovative Toos for FLEET Management Teematics for the Working Feet Track driver performance Compare drivers and vehices Retrieve vehice info wireessy DAVIS INSTRUMENTS CATALOG What s Inside? DriveRight

More information

Reference & Installation Manual

Reference & Installation Manual & Versions 4.4 (728ULT) & 4.1 (738ULT) 728ULT 738ULT Reference & Installation Manual Table of Contents Introduction... 1 About This Manual... 1 New Features... 1 Main Features... 1 Specifications... 1

More information

Early access to FAS payments for members in poor health

Early access to FAS payments for members in poor health Financia Assistance Scheme Eary access to FAS payments for members in poor heath Pension Protection Fund Protecting Peope s Futures The Financia Assistance Scheme is administered by the Pension Protection

More information

STEALTH I DC MANUAL TECH SUPPORT 1-888-588-4506.WEB www.stealth1charging.com BLACK UNIT IS 24/36 ONLY

STEALTH I DC MANUAL TECH SUPPORT 1-888-588-4506.WEB www.stealth1charging.com BLACK UNIT IS 24/36 ONLY STEALTH I DC MANUAL TECH SUPPORT 1-888-588-4506.WEB www.stealth1charging.com BLACK UNIT IS 24/36 ONLY PLEASE READ AND UNDERSTAND YOUR NEW PRODUCT IMPORTANT MESSAGE: Before installing your newly purchased

More information