1 D87/D88/D9/D9A/D9E EN Installation Guide Smoke Detector Bases
2 D87/D88/D9/D9A/D9E Installation Guide.0 Overview.0 Overview The D87/D88/D9/D9A/D9E Smoke Detector Bases are designed for use with the D8 Ionization Smoke Detector, D8/D8TH Photoelectric Smoke Detectors, and D0/D0/D0 Heat Detectors. Install these bases according to the National Fire Alarm Code, NFPA 7. Before installing a smoke detector base, read and understand this and the following documents to ensure proper system operation: D8/D8TH Installation Instructions (P/N: 09) D8 Installation Instructions (P/N: 0) D0/D0/D0 Installation Instructions (P/N: 70) NFPA Standard 7 This document covers only the information necessary to mount and wire the bases. Other information is available from: Two-wire compatibility information in the Technical Service Note: Two-Wire Smoke Detector Compatibility (P/N: 8) Installation guidelines in the Technical Service Note: Smoke Detector Installation Considerations (P/N: 7) Information about power requirements, testing, and maintenance in the D8/D8TH Installation Instructions (PN: 09), D8 Installation Instructions (PN: 0), and D0/D0/D0 Installation Instructions (PN: 70). - D87 Base only, two-wire - D88 Base only, two-wire, wide diameter - D9 Base only, four-wire - D9A Base only, four-wire, Form C Auxiliary relay - D9E Base only for power supervision, fourwire, end-of-line (EOL) relay, Normally Open (N/O) auxiliary relay - D9S Base only, four-wire with sounder - D7 EOL supervision module for four-wire systems A is the Underwriters Laboratories, Inc. (UL) compatibility identifier for the D8, D8/D8TH, D0/D0/D0 Smoke Detectors. To determine the identifier used with the D87, refer to the Technical Service Note: Two-Wire Smoke Detector Compatibility (P/N: 8). Detector Power Requirements Standby Voltage: - Two-wire: 8. VDC to.0 VDC - Four-wire: 0 VDC to 0 VDC Alarm Current Two-wire: Dependent on the control panel that must limit the alarm current to 00 ma maximum Four-wire: - D9: ma at VDC; ma at VDC (70 ma maximum at 0 VDC) - D9A: 8 ma at VDC; ma at VDC (7 ma maximum at 0 VDC) - D9E: 8 ma at VDC; 8 ma at VDC (00 ma maximum at 0 VDC) - D9S: ma at VDC; ma at VDC; Sounder ma at VDC, ma at VDC Bosch Security Systems, Inc. /0 F0U
3 D87/D88/D9/D9A/D9E Installation Guide.0 Mounting..0 Mounting. Select mounting locations based on the Technical Service Note: Smoke Detector Installation Considerations (P/N: 7).. Pre-run all system wiring to the base locations.. Mount the base using the two oblong mounting holes.. Tighten the base to the mounting surface.. If mounting to in. (0 cm) square boxes, use the adapter plate. First, mount the adapter plate to the box, then mount the base to the adapter plate and box using the oblong mounting holes. Refer to Figure..0 Two-Wire Detector Wiring Refer to Figure and Table for the D87 and D88 terminal functions. Figure : ( ) (+) D87 Wired in a Two-Wire Configuration Figure : Adapter Plate Connections - Alarm loop negative (-) - Alarm loop positive (+) - End-of-line resistor Table : Two-Wire Terminal Functions Terminal Function Alarm loop positive (+) IN Alarm loop positive (+) OUT Remote LED output Alarm loop negative (-) No connection - Adapter plate mounting holes () - Base to adapter plate mounting holes ()- Depending on local regulations, the bases might be surface mounted using anchors, mollies, or wing nuts. The bases might also be directly mounted to in. (0 cm) octagonal electrical boxes or single gang switch boxes. Ensure the volume of any electrical box you use accommodates the number and size of conductors as specified by the National Electrical Code (NEC) or any local regulations having jurisdiction.. Review Section.0 Two-Wire Detector Wiring, and Section.0 Four-Wire Detector Wiring, page for wiring information. 7. Connect the wiring to the bases. Bosch Security Systems, Inc. /0 F0U
4 D87/D88/D9/D9A/D9E Installation Guide.0 Four-Wire Detector Wiring.0 Four-Wire Detector Wiring. Terminal Connections Do not twist wires or loop the wires around terminals. Cut, strip, and insert the In/Out wires as individual ends for terminal connection.. EOL Resistors Use the EOL resistors supplied or ones specified by the control panel manufacturer. This includes EOL resistors used with the D7 Module.. D7 Power Supervision Relay Refer to Figure for the D7 wiring. Figure : D7 Wiring. Terminal Functions Refer to Table and Figure through Figure for the D9 and D9A terminal functions. Table : Four-Wire Terminal Functions Terminal Function DC power (+) IN (No connection for D9E) DC power (+) OUT (DC power [+] IN for D9E) Remote LED output DC power negative (-) Alarm loop (N/O) Alarm loop (C) When operating the D9, D9A, or D9E in a VDC system, cut the yellow voltage jumpers on each base. (+) ( ) A C B D. D9 Refer to Figure for the D9 wiring. Figure : D9 Wired in a Four-Wire Configuration - Smoke power positive (+) - Smoke power negative (-) - Alarm loop - D7 EOL power supervision module - A = Red wire (+ V) - B = Yellow wire (+ V) (+) ( ) A C B D - C = Black wire (common) - D = Blue wires - End-of-line resistor When using the D7 with VDC systems, connect the red wire to Terminal on the last base in the run. The yellow wire remains unconnected. - Cut loop for VDC - Smoke power positive (+) - Smoke power negative (-) - Alarm loop - D7 EOL power supervision module - A = Red wire (+ V) When using the D7 with VDC systems, connect the yellow wire to Terminal on the last base in the run. The red wire remains unconnected. Use one D7 per loop with the D9 and D9A. - B = Yellow wire (+ V) - C = Black wire (common) - D = Blue wires - End-of-line resistor The D9 is the standard smoke detector base used in four-wire configurations. The Alarm Loop relay (Terminals and ) is a N/O relay rated at 0. A at 00 VDC. The relay closes on alarm. Bosch Security Systems, Inc. /0 F0U
5 . D87/D88/D9/D9A/D9E Installation Guide.0 Four-Wire Detector Wiring. D9A Refer to Figure for the D9A wiring..7 D9E Power Supervision Base Refer to Figure for the D9E wiring. Figure : D9 Auxiliary/Alarm Contact Wiring Figure : D9 Power Supervision Base N/C 9 C 8 - Form C auxiliary - N/O alarm N/O 7 The D9A provides a N/O Alarm Loop relay and an auxiliary set of Form C (NC/C/NO) contacts. The contacts are rated at 0. A at VAC and at.0 A at 0 VDC for resistive loads. Do not use the D9A with inductive or capacitive loads. ( ) (+) - Cut loop for VDC - Smoke power negative (-) - Smoke power positive (+) - N/O auxiliary contacts - Alarm loop - End-of-line resistor The D9E provides a set of N/O alarm loop contacts and an auxiliary set of N/O contacts. The contacts are rated at 0. A at VAC, and at.0 A at 0 VDC for resistive loads. Do not use the D9E with inductive or capacitive loads. The D9E also provides EOL power supervision using a built-in relay. This eliminates the need for separate power supervision devices such as the D7. Only use one D9E base per zone run; it must be the last base on the run. The EOL relay is rated at 0. A at 00 VDC for resistive loads. Bosch Security Systems, Inc. /0 F0U
6 D87/D88/D9/D9A/D9E Installation Guide.0 Four-Wire Detector Wiring.8 Remote Alarm Indicator Using the SMK-RA Alarm Indicator, connect the positive (Item in Figure 7) lead to Terminal and the negative lead (Item in Figure 7) to Terminal. Figure 7: SMK-RA Remote Alarm Indicator Wiring - Red wire - SMK-RA Annunciator - Alarm indicator - White wire - Two-wire detector base Bosch Security Systems, Inc. /0 F0U
7 . D87/D88/D9/D9A/D9E Installation Guide Notes Notes Bosch Security Systems, Inc. /0 F0U
8 Bosch Security Systems, Inc. 0 Perinton Parkway Fairport, NY 0 USA Bosch Security Systems, Inc., 00
D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors
D7050/D7050TH EN Installation Instructions Multiplex Photoelectric Smoke Detectors D7050/D7050TH Installation Instructions.0 Description Notices These instructions cover the installation of the D7050/D7050TH
More informationconventional system operation
conventional system operation detection line operation Conventional detection systems normally operate on a 24VDC line. In the standby condition, the detectors will draw a low current, typically less than
More informationDetector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases
Detector Color Detector transparent with Color Inserts FAA 500 TR W Trim Ring FAA 500 TR P Trim Ring transparent with Color Inserts FAA 500 BB Ceiling Mount Back Box FCA 500 / FCA 500 E Detector Bases
More informationD9412GV3/D7412GV3. Approved Applications Compliance Guide. Control Panels
D9412GV3/D7412GV3 EN Approved Applications Compliance Guide Control Panels D9412GV3/D7412GV3 Approved Applications Compliance Guide Listings and Approvals Listings and Approvals Fire UL The D9412GV3 and
More informationControl Panels D9412GV3/D7412GV3/D7212GV3. UL Installation Instructions
Control Panels D9412GV3/D7412GV3/D7212GV3 en UL Installation Instructions Control Panels Table of Contents en 3 Table of Contents 1 Installation 4 1.1 Installation Preparation 4 1.2 Enclosure Options
More information2.0 Installation 1. Remove the cover using a small flat blade screwdriver. Figure 2: Cover Removal
O N DS160/DS161 Installation Guide High Performance Request-to-Exit Sensors 1.0 Description The DS160/161 is a passive-infrared (PIR) detector designed for Request to Exit (REX) interior applications.
More informationHM-W536 Install Guide
HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.
More informationSmoke Detectors Ordering Information DS230 DS230 Series Heat Detectors DS230F DS233F Peripheral Accessories EOL200 TP280 Bases Features
Smoke Detectors DS230 Series Heat Detectors DS230, DS230F and DS233F Heat Detectors 2-wire: See Tech Service Note P/N: 26979. 4-wire: Compatible with all UL Listed 4-wire control panels. Ordering Information
More informationSECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
More informationMODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE
DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000
More informationSECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS
SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment
More informationDORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
More informationSFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description
SFC-200 SERIES FIRE ALARM CONTROL PANELS SFC-200 Series Fire Alarm Control Panels Description Summit s SFC-200 Series fire alarm control panels consist of six and twelve zone models which are equipped
More informationControl Panel. D9412GV4/D7412GV4 v2.03. en UL Installation Instructions
Control Panel D9412GV4/D7412GV4 v2.03 en UL Installation Instructions Control Panel Table of Contents en 3 Table of contents 1 Introduction 5 1.1 About documentation 5 1.2 Bosch Security Systems, Inc.
More informationHONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12)
HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) UL864 (Commercial Fire) Compliance General Requirements The VISTA-128FBPT/VISTA250FBPT
More informationCM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems
CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way
More informationSILENT KNIGHT MODEL 5207
SILENT KNIGHT MODEL 5207 Fire Control / Communicator Installation, Programming, and Operation Manual Part Number 150865 Rev. C, 04/03 Contents Section 1 Introduction.......................................................................1-1
More informationExpansion Modules & Accessories
HONEYWELL SECURITY & CUSTOM ELECTRONICS Expansion Modules & Accessories Honeywell s wide range of expansion modules and accessories enable you to configure a system to meet any installation challenge and
More informationrpsa FIRE PROTECTION ENGINEERS
R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Sample Fire Alarm System Calculations 1. A fire alarm manufacturer specifies
More informationFire Alarm Control/Communicator
Operation and Installation Guide Addendum Fire Alarm Control/Communicator This addendum (P/N: 41740) is intended to replace pages 5, 10, 11, 12, 20, 22, 52, 66, and 78 through 81 of the D7024 Reference
More informationOperating the DS9400 Fire Alarm Control/Communicator
TM 255 DETECTION SYSTEMS Power Alarm Troubl Silenced Supervised TM 255 DS9400 FIRE CONTROL/COMMUNICATOR Operating the DS9400 Fire Alarm Control/Communicator Outline I. Description II. Features III. Installation
More informationFC-72 SERIES FIRE ALARM SYSTEM
FC-72 SERIES FIRE ALARM SYSTEM INSTRUCTION/OPERATING MANUAL Copyright 1988 Part Number: 9000-0007 Published in the U.S.A. Version 5.1 All rights reserved Serial Number 301 2nd Ave. Waltham, MA 02451-1133
More informationFire Alarm System Accessories
Approved by APPROVED Fire Alarm System Accessories FM Approved* Intrinsically Safe Devices Single and Dual Channel Isolated Barrier Modules Features Single or dual channel intrinsically safe, transformer
More informationCB200W Water Leak Detection Panel Application Guide
Checked by: AJC Approved by: JBJ Contents CB200W Water Leak Detection Panel Application Guide 1. Cabinet Specifications... 2 2. Panel Hardware Specifications... 3 3. Panel Configuration... 4 4. Technical
More informationAM100 SECURITY SYSTEM INSTALLATION INSTRUCTIONS
AM100 SECURITY SYSTEM INSTALLATION INSTRUCTIONS N7526-3V1 Rev B 4/99 Ref: 20AMTE RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations For The Location Of Fire And Burglary Detection Devices
More informationCLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline
More informationSECTION 13850 DETECTION AND ALARM
SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring
More information4-Wire Air Duct Smoke Detector. Protection Systems. A UTC Fire & Security Company. Models DH-60 FEATURES APPLICATION DESCRIPTION SAMPLING TUBES
4-Wire Air Duct Smoke Detector Models DH-60 F-70.05 FEATURES Approvals/Listing UL 268A Listed File S1064 Factory Mutual Approved CSFM Listed #3240-1076:121 NYC MEA Listed #134-95-E City of Los Angeles
More informationFire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need?
5/2/2014 Fire Alarm FAQs Question Answer Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? A: The size of a fire alarm panel is determined by a number of factors,
More informationPC4020CF v3.0 and higher Commercial Fire Installation Guide DLS-3 v1.3
PC4020CF v3.0 and higher Commercial Fire Installation Guide DLS-3 v1.3 Table of Contents Section 1: Introduction 1 1.1 Introduction...1 1.2 Hardware Description and Specifications...1 Section 2: Fire Zone
More informationHolder/Release Devices with Integral Door Closers DORMA EMF/ EMR
Holder/Release Devices with Integral Door Closers DORMA EMF/ EMR DORMA EMR Holder/Release Device with Integral Detector The DORMA EMR Series holder/release device incorporates a photoelectric detector
More informationFire detection equipment
PRODUCT CATALOG Fire detection equipment www.apollo-fire.com Apollo Fire Detectors is one of the world s largest manufacturers of fire detectors, modules and notification devices. Established in 1980,
More informationSmall Building Life Safety Solutions. GE Security. Affordable FireShield Conventional Fire Alarm Control Panels. imagination at work
GE Security Small Building Life Safety Solutions Affordable FireShield Conventional Fire Alarm Control Panels imagination at work cost Location: Environment: Solution: Flower shop Finely decorated, gentle
More informationINTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description
INTELLIGENT FIRE ALARM CONTROL PANELS MR-2100/MR-2200 Intelligent Fire Alarm Control Panels Description MR-2100/MR-2200 Intelligent Fire Alarm Control Panel (shown with optional LED modules) Secutron's
More informationEQUIPMENT SPECIFICATIONS
EQUIPMENT SPECIFICATIONS IC-1600 Intelligent Controller The IC-1600 Intelligent Controller is a fully intelligent panel that has a complete database on board. It operates in conjunction with the Access
More informationEMF/EMR. Holder/Release Devices with Integral Door Closers
EMF/EMR Holder/Release Devices with Integral Door Closers EMR TECHNICAL DETAILS DORMA EMR SERIESHOLDER/RELEASE DEVICE The DORMA EMR Series holder/ release device incorporates a photoelectric detector and
More informationFPD-7024. Fire Alarm Control Panel. Operation and Installation Guide BOSCH FIRE CONTROL/COMMUNICATOR. Trouble Silenced.
FPD-7024 Power Alarm Trouble Silenced BOSCH FIRE CONTROL/COMMUNICATOR EN Operation and Installation Guide Fire Alarm Control Panel FPD-7024 Operation and Installation Guide FCC Compliance Notice FCC Compliance
More informationESL 1500 Series Fire Alarm Control Panel Installation and Operations Manual
g GE Security ESL 1500 Series Fire Alarm Control Panel Installation and Operations Manual Table of Contents Precautions and Warnings... 1 System Overview... 1 Panel Listing...1 Panel Description... 2
More informationFire Fighter Phone System Installation Instructions
Fire Fighter Phone System Installation Instructions Introduction This publication describes the installation procedure for the Fire Fighter s Phone on a 4100U or a 4100ES Fire Alarm Control Panel (FACP).
More informationFIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10
TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified
More informationRelease Control Fire Alarm Systems
SYSTEM ABORT PUSH AND HOLD COIL SUPERVISION MODULE (2 AMP) 2081-9046 RED INSTALLATION INSTRUCTIONS 574-437 REV YEL NAC+ MAINTAIN 1/4" SEPARATION BETWEEN POW ER LIMITED (RED/) AND NONPOWER S LIMITED (YEL/)
More informationAdvanced Intelligent Modules. Overview. Description
Overview Features M200XE Short Circuit Isolator Module M201E Single Output Module M210E Single Input Module M210E CZ Conventional Zone Module M220E Dual Input Module M221E Dual Input Single Output Module
More informationWD-AMX Water Detection Controllers
Page 1 of 5 WD-AMX Water Detection Controllers Features: Benefit: LED Status of leak status VFC output Audible alarm Auto or manual reset alarm output Uses an isolated AC signal which prevents oxidation
More informationSECTION 16721 FIRE ALARM AND DETECTION SYSTEM
1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this
More informationProtection Systems. A UTC Fire & Security Company F-73-01. Linear Heat Detector FEATURES DESCRIPTION APPLICATIONS BENEFITS
Effective: May 2007 AlarmLine TM R Protection Systems Linear Heat Detector A UTC Fire & Security Company F-73-01 FEATURES Integrating Type Linear Heat Detector Analog Sensing Field Adjustable Alarm Set
More informationDUCT SMOKE DETECTOR D4120
Purpose/Application National and local safety standards and codes recognize the ability of air duct systems to transfer smoke, toxic gases, and flame from area to area. Sometimes smoke can be of such quantity
More informationFire & Security DETECTORS
Fire & Security DETECTORS Smoke Sensitivity 0.98 ~.0%/ft Obscuration Ceiling Spacing 50 foot rating for heat sensor Temperature Range 10ºC to 50ºC Humidity 0 to 95% RH, no condensation or icing Dimensions
More informationFireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual
FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual P/N 315-049403-1 Siemens Building Technologies Fire Safety Table Of Contents Introduction...1 The Access levels...1 User Level...1 Maintenance
More information4100U/4100ES to TFX Fire Fighter Phone System Installation Instructions
4100U/4100ES to TFX Fire Fighter Phone System Installation Instructions Introduction This publication describes the installation procedure for the 4100U/4100ES to TFX Fire Fighter s Phone card used to
More informationFire Detection Product Range
Fire Detection Product Range World Leading Fire Detection Products from the NITTAN group Issue 1.0 Business Overview The Nittan Group has been at the forefront of the fire protection industry since 1954
More informationComprehensive Security with one Powerful System. G Series integrated security, fire and access control panels
Comprehensive Security with one Powerful System G Series integrated security, fire and access control panels 2 3 Designed for Flexibility Bosch s G Series panels provide the ultimate in security controls
More informationVOT-320. VOT-320V0xxL VOT-320V0xxH. Quick Installation Guide
VOT-320 VOT-320V0xxL VOT-320V0xxH en Quick Installation Guide VOT-320 Table of Contents en 3 Table of Contents 1 General information 4 2 Parts included 5 3 Unpacking 6 4 Installing and connecting 7 4.1
More informationFLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
More informationLife Alarm Fire Alarm Controls
FIRE SUPERVISORY SUPV SILENCED SILENCE AC POWER RESET UL, ULC Listed FM Approved MEA Approved* Life Alarm Fire Alarm Controls Fire Alarm Controls 4005 Series Fire Alarm Control Panels Eight through Thirty-Six
More informationSection 1: About Your ORBIT-Pro
Section 1: About Your ORBIT-Pro Introduction to this Manual This ORBIT-Pro Installation and Programming Manual is designed to take you through the required steps so you can successfully install the ORBIT-Pro
More informationBARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell
Data, installation, operation and maintenance 4 & 8 Zone Fire Panels Zircon range BARDIC by Honeywell LED flashing LED Continuous FAULT DISABLE/TEST Power General Fault Sounder Fault/ Disable System Fault
More informationVISTA-20SE INSTALLATION INSTRUCTIONS 2-PARTITIONED SECURITY SYSTEM
VISTA-20SE 2-PARTITIONED SECURITY SYSTEM INSTALLATION INSTRUCTIONS Principal changes between the VISTA-20SE and the former VISTA-20 are indicated by margin lines. N7526V4 8/97 RECOMMENDATIONS FOR PROPER
More informationwww.sebury.com.cn Digital Keypad Use s Manual
K3 K4 www.sebury.com.cn Digital Keypad Use s Manual Contents Introduction Introduction Specifications Intramural Interface Circuit 3 Mounting 3 Wiring 5 Power UP 7 Engineer Programming Mode 7 The K3/K4
More informationPowerCode Wireless. Fully supervised wireless system. Features
PowerCode Wireless WIRELESS Fully supervised wireless system Features technology Fully supervised Attractive, elegant design Reporting of tamper and RF signal jamming Transmitter inactivity and low battery
More informationFIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
More informationFire Pump Controllers Remote Alarm Panels
Fire Pump Controllers Remote Alarm Panels Remote Alarm Panels 1.8 Remote Alarm Panels FDAP-M Electric... DFDAP-M Diesel... Product Specifications... 2 6 9 Features 1-1 DFDAP-M / FDAP-M Remote Alarm Panel
More informationSECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM
KNOXVILLE, TENNESSEE SECTION 28 31 11 PAGE 1 PART 1 - GENERAL 1.01 DESCRIPTION OF WORK SECTION 28 31 11 A. Extent of fire alarm and detection system work shall be as described in this specification, as
More informationFire Alarm System Plans Submittal Guidelines For New and Existing Systems
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,
More informationSP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE
SP4LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE INSTALLATION AND OPERATION MANUAL MASS NOTIFICATION SYSTEM Part Number: P84767 Rev. A Copyright 2006 Cooper Wheelock, Inc. All rights reserved.
More information16720S01 - FIRE ALARM SYSTEM (HARDWIRED), MANUAL AND AUTOMATIC
1. GENERAL 1. Fire alarm system shall be manufactured by Simplex, Autocall or Edwards. Simplex part numbers are provided in this spec for clarification only and do not exclude equivalent part numbers of
More informationPLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
More informationNetworX Series. NX-216E Zone Expander Module Installation and Startup
NetworX Series NX-E Zone Expander Module Installation and Startup 00 GE Security All rights reserved. These instructions do not purport to cover all details or variations in equipment nor to provide every
More informationD4120 Duct Smoke Detector D4S Sensor Component D4P120 Power Board Component
INSTALLATION AND MAINTENANCE INSTRUCTIONS D Duct Smoke Detector DS Sensor Component DP Power Board Component Ohio Avenue, St. Charles, Illinois 0-00-SENSOR, FAX: 0-- www.systemsensor.com NOTE: The D duct
More informationARCHITECT AND ENGINEER SPECIFICATION SECTION 13850 DETECTION AND ALARM SECURITY ACCESS AND SURVEILLANCE. DSC MAXSYS PC4020 V3.
ARCHITECT AND ENGINEER SPECIFICATION SECTION 13850 DETECTION AND ALARM SECURITY ACCESS AND SURVEILLANCE DSC MAXSYS PC4020 V3.5 Rev0x2 Digital Security Controls 3301 Langstaff Rd., Concord, ON Canada L4K
More informationAccess Control Interface Module D9210C. Program Entry Guide
Access Control Interface Module D9210C en Program Entry Guide Access Control Interface Module Table of Contents en 3 Table of Contents 1 Trademarks 4 2 Door Profile 5 3 Strike Profile 9 4 Event Profile
More informationSECTION 16721 FIRE ALARM AND DETECTION SYSTEMS
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat
More informationISW-D8125CW-V2. Installation and Operation Guide. Inovonics Echostream Interface Module
ISW-D8125CW-V2 EN Installation and Operation Guide Inovonics Echostream Interface Module ISW-D8125CW-V2 Installation and Operation Guide Contents Contents 1.0 Overview...3 1.1 FCC Compliance Notice, Part
More informationPFC-6030 Fire Alarm Control Panel
PFC-6030 Fire Alarm Control Panel Installation, Operation & Programming Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax:
More informationSmoke Detector PSD 2 & 4 Wire Units
Smoke Detector PSD 2 & 4 Wire Units Advanced Photoelectric Smoke Detectors Models PSD-7157 and PSD-7157D F-70.02 FEATURES Approvals/Listing US and Canadian UL Listed (culus) FM Approved CSFM Approved NYC
More information8900 EMR (WITH DETECTOR)
00 EMR (WITH ) GENERAL DESCRIPTION Each 00 EMR series unit contains a door closer, hold open electromagnet and smoke detector. The unit can be used as a single installation or as a series of singles powered
More informationInstallation Instructions & Owner s Operation Manual for Two to Eight Zone 2400 Series Fire Alarm Control Panels
Installation Instructions & Owner s Operation Manual for Two to Eight Zone 2400 Series Fire Alarm Control Panels P/N 46000-1320, Rev. 1.6 Edwards This product has been designed to meet the requirements
More informationHow To Make A Commercial Detector
Detection delivered. Reliability assured. Commercial Series Motion Detectors Detection is the first step to protecting a home or business and the people and property within its walls. Instant responses
More informationHOME AUTOMATION, INC. Control & Security System. Installation Manual
HOME AUTOMATION, INC. Control & Security System Installation Manual Document Number 20I00-2 Rev. 2.4 May, 2003 Home Automation, Inc. Installation Manual Document Number 20I00-2 Rev. 2.4 May, 2003 Copyright!
More information(68.52) X. June 2000 Supercedes February 2000. xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we look @ business differently
(68.52) X June 2000 Supercedes February 2000 xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM.... we look @ business differently XENEX SYSTEM ARCHITECTURE Note: This schematic is for guidance only please
More informationTrueAlarm Fire Alarm Systems
TrueAlarm Systems UL, ULC, CSFM Listed; FM Approved* Network Annunciators; es Features Provides a dedicated local area network (LAN) for connection of a TrueSite workstation server to remote clients: es
More informationAC-115 Compact Networked Single Door Controller. Installation and User Manual
AC-115 Compact Networked Single Controller Installation and User Manual December 2007 Table of Contents Table of Contents 1. Introduction...5 1.1 Key Features... 6 1.2 Technical Specifications... 7 2.
More informationDesign and Construction Standards SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS
SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES: A. Fire alarm and smoke detection systems. 1.2 REFERENCES 1.3 NFPA 72 1.4 NFPA 101 1.5 REGULATORY REQUIREMENTS
More informationConettix C900V2. Installation Guide. Dialer Capture Ethernet Module
Conettix C900V2 EN Installation Guide Dialer Capture Ethernet Module Conettix C900V2 Installation Guide Trademarks Trademarks Altronix is a registered trademark of Altronix Corporation. Phillips is a registered
More informationABLOY DA60 SWING DOOR OPERATOR Installation and commissioning manual Abloy Oy An ASSA ABLOY Group company APPROVALS / STANDARDS Low Voltage directive 7//EEC as amended by the directive 9/68/EEC EMC directive
More informationE-PDD Duct Smoke Detector Installation Sheet
E-PDD Duct Smoke Installation Sheet Operation The duct smoke detector's primary purpose is to provide early warning of an impending fire and shut down the HVAC unit in order to prevent smoke from circulating
More informationDISCONTINUED PRODUCT. Infrastructure Management & Monitoring For Business-Critical Continuity. Liebert icom-do. User Manual
Infrastructure Management & Monitoring For Business-Critical Continuity Liebert icom-do User Manual TABLE OF CONTENTS 1.0 INTRODUCTION............................... 1 2.0 INSTALLATION...............................
More informationINSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930
INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................
More informationC. Conform to requirements of Americans with Disabilities Act (ADA).
SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National
More informationA.1. a Division of Pittway Corporation. Documento: M-010.1-MGAS-ENG. Edizione: 01/1997 Rev.:
Documento: M-010.1-MGAS-ENG Edizione: 01/1997 Rev.: A.1 a Division of Pittway Corporation FRONT PANEL & VISUAL INDICATIONS GENERAL TROUBLE GENERAL PROGRAMMING IN PROGRESS ENABLE/ALARM/TROUBLE (ZONE 1 ALARM
More informationCarbon Monoxide (CO) Detection PRODUCTS. Accessories Conventional Detectors
Carbon Monoxide (CO) Detection PRODUCTS Accessories Conventional Detectors 2 Complete CO Detection The system-connected CO1224T and CO1224TR CO detectors with RealTest provide early warning by using reliable
More informationPN 15153:G1 ECN 02-539. Fire Alarm Control Panel MS-4424. Instruction Manual. Document 15153 10/22/2002 Rev: G
PN 15153:G1 ECN 02-539 Fire Alarm Control Panel MS-4424 Instruction Manual Document 15153 10/22/2002 Rev: G Fire Alarm System Limitations An automatic fire alarm system typically made up of smoke detectors,
More informationSPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi addressable detection and control system.
More informationCARBON MONOXIDE MONITORING AND SHUTDOWN SYSTEM MODEL 12V Installation And User Manual (Rev. 102804NP) QUICK INSTALLATION TIPS AND TROUBLESHOOTING GUIDES ARE LOCATED ON THE BACK OF THE MANUAL Dear New UltraGuard
More informationSignaling Lights. LH Series Surface Mount Indicators. Part Numbers. Jumbo Dome (one color) Jumbo Dome (two color)
Innovative indicators in a slim & stylish design. uces installation space. LH Series Surface Mount Indicators Key features of the LH series include: Direct mounting on surfaces such as panels, aluminum
More informationALARMLINE ANALOGUE Linear Heat Detection System
ALARMLINE ANALOGUE Alarmline Analogue sensor cable senses temperature variations by continuously monitoring the resistance of specially doped N.T.C. polymeric insulation. A change in temperature produces
More informationControl Panels D9412G/D7412G/D7212G. Installation & Troubleshooting Quick Reference Guide
Control Panels D9412G/D7412G/D7212G Installation & Troubleshooting Quick Reference Guide D9412G/D7412G/D7212G Installation & Troubleshooting Quick Reference Guide Page 2 2004 Bosch Security Systems, Inc.
More informationAdvantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
More informationQS4 Fire Alarm Control Panel
QS4 Fire Alarm Control Panel Technical Reference Manual P/N 3100186 Rev 2.0 12JUL01 Compliance Statement Limitation of Liability Fire Alarm System Limitations FCC Compliance Statement The QS4, hereinafter
More informationAlarmSense 2-wire detection and alarm system. Product Guide
AlarmSense 2-wire detection and alarm system Product Guide Contents What is AlarmSense? 2 The purpose of AlarmSense 4 How AlarmSense works 4 Alarmsense Features 5 Detector removal monitoring 5 Priority/non-priority
More informationPN: 50066:D2 ECN 02-606. Fire Control Communicator MS-5024/MS-5024E. Document #50066 12/03/02 Rev.
PN: 50066:D2 ECN 02-606 Fire Control Communicator MS-5024/MS-5024E Document #50066 12/03/02 Rev. D Fire Alarm System Limitations An automatic fire alarm system typically made up of smoke detectors, heat
More information