Installation and User Manual GENEREX RCCMD AS400-Client

Size: px
Start display at page:

Download "Installation and User Manual GENEREX RCCMD AS400-Client"

Transcription

1 GENEREX, Author Bodo Radtke Page 1 - November 28, Rel Installation and User Manual GENEREX RCCMD AS400-Client Contents INSTALLATION AND USER MANUAL... 1 GENEREX RCCMD AS400-CLIENT... 1 CONTENTS... 1 DESCRIPTION... 2 A. GENERAL INFORMATION... 2 B. MODULES... 2 C. STEP-BY-STEP INSTALLATION INSTRUCTIONS... 3

2 GENEREX, Author Bodo Radtke Page 2 - November 28, Rel I. Description A. General Information The RCCMD AS400 client is part of the UPSMAN UPS management system that allows the iseries-as400 to act as a client in an UPSMAN managed network. The UPSMAN management module will run on a number of other operating systems ( or on most of the GENEREX standalone network UPS and facility management devices ( Emergency and routine controlled system shutdowns are executed via the network when an authorized UPSMAN manager sends and RCCMD shutdown command to the AS400 running the RCCMD client. The customer defines the shutdown conditions and authorized UPSMAN managers during the setup of the UPS management system. B. Modules 1. Configuration Configuring the AS400 RCCMD client involves setting up a number of parameters which are stored in configuration files. The following file contains the AS400 RCCMD client configuration. a) Configuration file communication 1 rccmdcfg1 This file should hold the IP address of the AS400 which secures the identification of the AS400. This entry must match the entry posted in the IP address found in the configuration of the AS400 if this is not the case see section I.B.2. This entry must also hold the definition of the port that will be used for this program. The default ports is 6003 and if this is not the case please refer to section I.B.2 Default value formation. b) Configuration file communication 2 rccmdcfg2 This file contains information in the form of IP addresses matching the RCCMD senders, that is to say UPSMAN managers or CS121 which manage your UPS. This defines which UPSMAN managers are allowed to send RCCMD messages to the RCCMD AS400 client. These entries act as a filter key for defining authorized UPSMAN managers and should this entry contain no IP addresses see section I.B.2. Default-value formation *all. c) Configuration file SHUTDOWN shutcmd This file contains a predefined shutdown sequence of commands that is enacted when the AS400 RCCMD client receives a valid RCCMD shutdown command. The initial default shutdown file that is written into the system is

3 GENEREX, Author Bodo Radtke Page 3 - November 28, Rel empty. It is the duty of the administrator to define the operations that are to be executed in this file. This may or may not contain actions that are to precede a shutdown such as executing commands, sending messages and safely terminating other processes. (Important: Please see also subject 7! ) The following management program/on-line dialogues for viewing, input, changing and deleting from data records are available: d) Administrative configuration file Communication 1 e) Administrative configuration file Communication 2 f) Administrative configuration file SHUTDOWN C. Step-by-step installation instructions 1. Save/copy the SAVF file from the data media ( or CD ROM). Following we describe this way using FTP. PC FTP commands for use with the iseries: 1. Login in to the iseries as (QSECOFR!!!) 2. Make SAVF file in QGPL: CRTSAVF FILE(QGPL/RCCMD) 3. Backup the SAVF file from mail / CD in the root directory of the hard drive (we recommend to use root C:\!!) 4. On the PC - START->EXECUTE and type in "CMD" and hit ENTER to open a commandshell. 5. Go into the directory containing SAVF (CD \) 6. Start FTP by the following command : "FTP <xxx.xxx.xxx.xxx - IP adress of your iseries> 7. Then enter the following. User (xxx.xxx.x.x:(none)): as400user 31 Enter password. Password: ******** 230 as400user logged on. ftp> binary 200 Representation type is binary IMAGE. ftp> quote site namefmt Now using naming format "1". ftp> put rccmd.savf /qsys.lib/qgpl.lib/rccmd.savf 200 PORT subcommand request successful. 150 Sending file to member RCCMD in file RCCMD in library QGPL. 250 File transfer completed successfully. ftp: bytes sent in 2.43Seconds Kbytes/sec. ftp> quit C:\exit 8. Please backup the files at your iseries library: (At the CD ROM at Directory "OS400/RCCMD") RSTLIB SAVLIB(RCCMD) DEV(*SAVF) SAVF(QGPL/RCCMD) OPTION(*ALL) MBROPT(*ALL) ALWOBJDIF(*ALL)

4 GENEREX, Author Bodo Radtke Page 4 - November 28, Rel INSTALLATION WIZZARD: Please us for the further installation and configuration process the SETUP tool, coming with this software. All following steps described in this documentation are handled through this tool. Start the Setuptool as follows: call xxx/setupmnu, where xxx is the name of the library in which you have saved RCCMD. We recommend to use the name "RCCMD". You may go through all the installation parts step by step, or you may start the installation as complete installation routine. As completet routine use F10 to get to the next step. Follow the instructions on the screen until you get the messge: 'Installation complete'. Finish.'

5 GENEREX, Author Bodo Radtke Page 5 - November 28, Rel make sure that the programm SHUTDWN has the right to execute a shutdown call : CHGOBJOWN OBJ(RCCMD/SHUTDWN) OBJTYPE(*PGM) NEWOWN(QSECOFR) CUROWNAUT(*REVOKE) 2. Enter JOB DESCRIPTION : NOTE: If you have backuped the RCCMD system into any other library than RCCMD (not recommended), you have to change the jobdescription accordingly: CHGJOBD XXX/RCCMD INLLIBL(XXX QGPL QTEMP QUSRSYS) where "XXX" represents the name of the library where you have installed RCCMD. 3. Enter CFGTCP : Selection 1 please note your IP Adress. Here has to be an entry (IP adress) - if this is not the case please check your Networkconfiguration with your Administrator. Mit TCP/IP-Schnittstellen arbeiten System: JCBOCS Auswahl eingeben und Eingabetaste drücken. 1=Hinzufügen 2=Ändern 4=Entfernen 5=Anzeigen 9=Starten 10=Beenden Aus- Internetwahl Adresse Teilnetzmaske Leitungsbeschreibung Leitungsart *LOOPBACK *NONE JCBLIN *ELAN Ende F3=Verlassen F5=Aktualisieren F6=Liste drucken F11=Schnittstellenstatus anzeigen F12=Abbrechen F17=Anfang F18=Ende

6 GENEREX, Author Bodo Radtke Page 6 - November 28, Rel Selection 10 note the hostname which is linked to your IP adress. Add your noted IP adress (if not already present) and choose a hostname. Mit TCP/IP-Host-Tabelleneinträgen arbeiten System: JCBOCS Auswahl eingeben und Eingabetaste drücken. 1=Hinzufügen 2=Ändern 4=Entfernen 5=Anzeigen 7=Umbenennen Aus- Internetwahl Adresse Host-Name BODO.NET LOOPBACK LOCALHOST JCBOCSSERVER MAIL.BLUEWIN.CH MAIL.BODO AUTH.MAIL.ONLINEHOME.DE Ende F3=Verlassen F5=Aktualisieren F6=Liste drucken F12=Abbrechen F17=Listenanfang bei Selection 12 enter/add (if not already present) the hostname to the Domainname TCP/IP-Domäne ändern (CHGTCPDMN) Auswahl eingeben und Eingabetaste drücken. Host-Name 'JCBOCSSERVER' Domänenname 'JCBOCS.NET' Domänensuchliste *DFT Suchpriorität für Host-Name.. *LOCAL *REMOTE, *LOCAL, *SAME Domain Name Server: Internet-Adresse *NONE Ende F3=Verlassen F4=Bedienerf. F5=Aktualisieren F10=Zusätzl. Parameter F12=Abbrechen F13=Verwendung der Anzeige F24=Weitere Tasten

7 GENEREX, Author Bodo Radtke Page 7 - November 28, Rel If there should be already an entry and your Domainname differs from your hostname, please do not change anything here. 4. Enter ADDLIBLE XXX - where XXX represents the name of the RCCMD library 5. Call the programm RCCMDCFG1 (CALL RCCMDCFG1) Enter, if not already present, your IP adress here. Enter the port number 6003 (default). If you do not not want to use the default port, please change to any other available port and change also the CS121/UPSMAN sender accordingly. Enter here you RCCMD Licensekeycode (see your AS 400 Licensedocument for "RCCMD AS 400 Licensekey")). Finish you setting by pressing F2 and save your settings. Leave the Program with F3. )For deleting your entries use F23.) JCBOCS Kommunikationsdatei Verwalten RCCMDCFG1 00:05:51 Eigene IP Addresse: Lokale Portnummer : Sicherheitscode : 77METRO-PARIS F2=Akzeptiern F3=Verlassen F23=Löschen ATTENTION: If there is no Adress here, so you may add this adress as follows: 1. Enter at CommandLine AS400: UPDDTA RCCMD/RCCMDCFG1 2. Enter your IP 3. Return 4. F3 and Return

8 GENEREX, Author Bodo Radtke Page 8 - November 28, Rel (Alternatively 7.) Call the program RCCMDCFG2 (CALL RCCMDCFG2). Enter here one or more remote IP adresses of your RCCMD server (CS121 or UPSMAN). Every Adress which you enter here has the permisson to transmit an RCCMD shutdown signal, other adresses, not listed here will be refused to send shutdown signals. Please check youre Firewall so that those RCCMD senders can use the Port 6003 to transmit their signal. NOTE: If you do not enter any IP adress here, all RCCMD senders in your network are allowed to send an RCCMD shutdown signal! We recommend to use this feature only while testing, at normal operation we recommend to restrict the number of RCCMD senders. JCBOCS Kommunikationsdatei Verwalten RCCMDCFG2 00:09:13 Ferner IP... : F2=Akzeptiern F3=Verlassen F7=Vorwärts F8=rückwärts F23=Löschen After this please press F2 to save your settings. Leave the program with F3. (Using F23 you can delete youre entries, F7/F8 is to scroll through the page.) 7). (Alternatively 6.) Call the program SHUTCMD (CALL SHUTCMD parm' ') Enter the commands you want to execute when an RCCMD Signal arrives. (your shutdown script). The syntax and commands should be tested before manually so that a simple call of this SHUTCMD has the desired reaction - shutting down your ISeries. The command CALL SHUTCMD parm opens a new screen where you can configure the AS 400 Shutdown Sequence (see page 11, Example to test RCCMD transmission without PWRDWNSYS ). The command CALL SHUTCMD parm can be used without any risk, it does NOT execute any shutdown, it just opens a new configuration screen. Note: If you do not enter anything here, the RCCMD will use per default the command PWRDWNSYS (Power Down System) of your system. If this is the case, please check if the option *cntrld or *immed is active.

9 GENEREX, Author Bodo Radtke Page 9 - November 28, Rel If you want to use any other additional call before the shutdown, please enter as last command PWRDWNSYS *immed - otherwise your System will not do any shutdown! Plesae note that without the *immed parameter the shutdown may take quite long. Tip: You can test your installation without risking a shutdown if you enter here any other comman - without the pwrdwnsys. So the moment you enter any command here which is not pwrdwnsys, you can use this for testing the transmission. Youre CS121 or UPSMAN have in the EVENTS configuration menue "testbutton" to transmit an RCCMD shutdownsignal without making the UPS switch to battery. Picture : UPSMAN Windows Configuration EVENT OVERVIEW Picture: UPSMAN Windows INSERT EVENT RCCMD Shutdown Picture : UPSMAN Windows Configuration RCCMD TEST Button Picture : CS121 EVENTS/ALARMS CONFIGURATION OVERVIEW

10 GENEREX, Author Bodo Radtke Page 10 - November 28, Rel Picture : CS121 EVENTS/ALARMS ADD NEW JOB- SEND RCCMD SHUTDOWN - Test Button If this test is successfull, you can be sure that also a real Shutdown call will also work. In the field "sequence" enter the number of the priority of your commands, eg. 1 for the first command, 2 for the seconds, etc. After you have finished your settings enter F2. Now leave the program with F3. Example to test RCCMD transmission without PWRDWNSYS: Use the following testsequence to check your installation without a real OS 400 shutdown. The test consist of 3 entries: All actions will result in a textmessage to QSECOFR aund QSYSOPR. So to check the successfull transmissions of RCCMD signals, read the logfileentries in the system operator message queue (display message queue SYSOPR). After a successfull test continue with subject 8 (start of RCCMDAS400-Client). Eample ShutDown: JCBOCS Shutdownbefehlsverwaltung SHUTCMD 00:12:02

11 GENEREX, Author Bodo Radtke Page 11 - November 28, Rel Sequence 1 Befehl SNDMSG MSG('FOLLOWING MESSAGES ARE TESTMESSAGES FROM RCCMDAS400-CLIENT') TOUSR(QSYSOPR) F2=Akzeptiern F3=Verlassen F7=Vorwärts F8=Rückwärts F23=Löschen Press F7, now a new Menue opens: JCBOCS Shutdownbefehlsverwaltung SHUTCMD 00:12:02 Sequence 2 Befehl CALL SETUPTEST1 F2=Akzeptiern F3=Verlassen F7=Vorwärts F8=Rückwärts F23=Löschen etc.... You may also remove the existing entries or add extra entries to this sequence. Please take care that the sequence numbers do not overwrite existing entries. You are still logged in as QSECORF : Enter : CHGMSGQ *USRPRF *break, after this enter : call shutcmd 1st Command to enter: Sequence: 1 Befehl: SNDMSG 'TestShutDownBefehl received' QSECOFR Accept this by F2 and page forward using F7 for te next entry. Return 2nd Comand to enter:

12 GENEREX, Author Bodo Radtke Page 12 - November 28, Rel Sequence: 2 Befehl: SNDMSG 'TEST-RCCMD has been sended' QSYSOPR Accept this by F2 and page forward using F7 for te next entry - or use F8 to return to your previous menue - or use F23 to delete your entries. More entries: Like before, use F3 to leave the program. Here an example with PWRDWNSYS - ideal for testing if you are not allowed to do a real shutdown test of your AS 400.: call shutcmd 1st Command to enter: Sequence: 1 Befehl: SNDMSG 'ShutDownCommand received : System shuts down in 10 Minutesr' QSECOFR Accept this command by F2, page down using F7 for the next command: 2nd Command to enter: Sequence: 2 Befehl: SNDMSG 'RCCMD has been sended, Batterie close to low level' QSYSOPR Accept this command by F2, page down using F7 for another command or go back with F8. To delete your previous entries use F23. 3rd Command to enter: Sequence: 99 Befehl: PWRDWNSYS *IMMED command by F2, or leave the program with F3 In the menue Sequence you define by the sequence number the priority of the commandprocessing. The smallest number has the highest priority and will be executed first. Eg. if you have the sequences 3, 5,1,7,2, than RCCMD will execute your commands in the sequence 1,2,3,5,7. The above shown examples may differ from your system. Please check if the programmed actions are complete to shutdown your AS 400 system, otherwise add extra commands to this sequence. If you have questions please call our hotline service for AS 400 or send us an with your questions. Tip: Use one or more CL-Programs for your individual sequence control

13 GENEREX, Author Bodo Radtke Page 13 - November 28, Rel Start of the AS/400-RCCMD-Client 1. Manual start of the AS/400-RCCMD-Client The Lib RCCMD has to be in the liblist when you start the job. (enter dsplibl). If not present, enter : addlible RCCMD Enter : SBMJOB CMD(CALL PGM(STARTRCCMD) PARM('RCCMD')) JOB(RCCMD) JOBD(RCCMD/SOCKSERV) USER(*JOBD) SYSLIBL(*SYSVAL) CURLIB(*CRTDFT) INLLIBL(*JOBD) And check this by enter: WRKACTJOB JOB(RCCMD) The should be listed now, if not than there might be an error in your installation. Work with active jobs JCBOCS :24:36 CPU %: 0,0 Abgelaufene Zeit: 00:00:00 Aktive Jobs: 163 Auswahl eingeben und Eingabetaste drücken. 2=Ändern 3=Anhalten 4=Beenden 5=Arbeiten mit 6=Freigeben 7=Nachricht anzeigen 8=Mit Spool-Dateien arbeiten 13=Unterbrechen Ausw. Subsystem/Job Benutzer Art CPU % Funktion Status RCCMD BCRADTKE BCH 0,0 PGM-SOCKSERV TIMW Ende Parameter oder Befehl ===> F3=Verlassen F5=Aktualisieren F10=Neubeginn F11=Aufgelaufene Daten F12=Abbrechen F23=Weitere Angaben F24=Weitere Tasten Note. The library RCCMD is the name of the saved library in your As 400. At a restore into any other library, please use this new name accordingly. 2. Automatic programstart at IPL Enter the following command: ADDAJE SBSD(QUSRWRK) JOB(RCCMD) JOBD(RCCMD/SOCKSERV) ** This commands makes RCCMD to start automatically at every System reboot ** At the next Systemstart : please check the autostart entry by entering: WRKACTJOB JOB(RCCMD), the job should be listet now, if not than the installation is incorrect.

14 GENEREX, Author Bodo Radtke Page 14 - November 28, Rel The rccmd-comand is always inside the saved library RCCMD. By entering the librarylist in the jobdescription (see subject 2) you do not need any entry in other jobs or menues. (not needed in systemvalue QUSRLIBL, no need to change manually by "addlibl" or "chglibl"). This is only needed during the installation and the manual start of RCCMD, not at the automatic start) You may also use a differen way to autostart RCCMD: Autostart via subsystem in QSTRUP (SystemstartProgramm from IBM): You may also use the IBM scheduler to start RCCMD. Check if the Objekt library is present in the Liblist. A helpfunction is available for the parameter USER in the command smbjob and/or chgjobd. ** This product is compatible with OS/400-Releases V4R5M0 through V5R3M0 **

Installation and User Manual GENEREX RCCMD AS400-Client

Installation and User Manual GENEREX RCCMD AS400-Client Version: 2012-02-01 Installation and User Manual GENEREX RCCMD AS400-Client Contents INSTALLATION AND USER MANUAL... 1 GENEREX RCCMD AS400-CLIENT... 1 CONTENTS... 1 I. DESCRIPTION... 3 A. GENERAL INFORMATION...

More information

CREATE!FORM SERVER FOR ISERIES V6R1 INSTALLATION

CREATE!FORM SERVER FOR ISERIES V6R1 INSTALLATION T ECHNICAL NOTE Product: Create!form Server 2.8 Last modified: February 2, 2009 5:49 pm Created by: Development Inside this note: Installing Create!form Server 2.8 CREATE!FORM SERVER FOR ISERIES V6R1 INSTALLATION

More information

Textura CMS Interface Setup Manual. Version 1.1

Textura CMS Interface Setup Manual. Version 1.1 Textura CMS Interface Setup Manual Version 1.1 January 4, 2007 This user manual contains confidential information of Textura, LLC and is protected by all applicable patents, copyright, trademark trade

More information

Installation of TMKSVR as part of the SAPINST environment

Installation of TMKSVR as part of the SAPINST environment SAP TMKSVR tools for the iseries Installation of TMKSVR as part of the SAPINST environment Installation of TMKSVR as part of the SAPINST environment Installation 1.1. Prerequisites 1.2. Start installation

More information

Digital Certificate Manager Setup

Digital Certificate Manager Setup Digital Certificate Manager Setup Contents Pre-configuration 3 Sample control scripts 3 Server Requirements 3 Prerequisites 3 Technical documents available online at 3 Firewall Considerations 4 Introduction

More information

Users Guide. FTP/400 File Transfer API and Remote Command Server Version 1.00. By RJS Software Systems, Inc.

Users Guide. FTP/400 File Transfer API and Remote Command Server Version 1.00. By RJS Software Systems, Inc. FTP/400 File Transfer API and Remote Command Server Version 1.00 Users Guide By RJS Software Systems, Inc. RJS Software Systems P.O. Box 19408 Minneapolis, MN 55419 (612) 822-0412 Voice (612) 822-1364

More information

www.orati-systems.com

www.orati-systems.com www.orati-systems.com Table of Contents Summary Features Requirements Installation and configuration Rebuild and deploy Java Debugging Summary isftp is an open source toolset developed by Orati Systems

More information

Installation guideline. ConTool

Installation guideline. ConTool Installation guideline ConTool Updated: 06.04 04.20.2011 Created by: consolut international ag Ebnatstrasse 65c CH-8200 Schaffhausen fon: +41 (0) 525 33833 10 fax: +41 (0) 525 33833 2 info@consolut.com

More information

UPS SNMP Watch User manual

UPS SNMP Watch User manual Version: 2010-12-15 UPS SNMP Watch User manual Copyright Statement for Intellectual Property and Confidential Information The information contained in this manual is non-conditional and may be changed

More information

Table of contents Introduction. 11-About it. 12-Prerequisites. 13-Installation

Table of contents Introduction. 11-About it. 12-Prerequisites. 13-Installation by Giovanni B. Perotti (Italy) 1. 2. 3. 4. 5. Table of contents Introduction 11. About it 12. Prerequisites 13. Installation Set up 21. Defining an image catalog 22. Defining a virtual tape drive 23. Loading

More information

Remote Software Facility

Remote Software Facility Remote Software Facility Copyright 1994, 2010 All Rights Reserved Release 8.6 (October 2010) Bug Busters Software Engineering, Inc. 2208 NW Market St Suite 512 Seattle, WA 98107 Voice: (206) 633-1187 Fax:

More information

TANDBERG MANAGEMENT SUITE 10.0

TANDBERG MANAGEMENT SUITE 10.0 TANDBERG MANAGEMENT SUITE 10.0 Installation Manual Getting Started D12786 Rev.16 This document is not to be reproduced in whole or in part without permission in writing from: Contents INTRODUCTION 3 REQUIREMENTS

More information

LogLogic IBM i5/os Collector Guide

LogLogic IBM i5/os Collector Guide LogLogic IBM i5/os Collector Guide Software Release: 1.0 Document Release: December 2010 Part Number: LL600020-00EI5010001 This manual supports LogLogic IBM i5/os Collector Release 1.0 and later, and LogLogic

More information

Restoring KeyesMail from a CD or Save File onto your iseries or AS/400

Restoring KeyesMail from a CD or Save File onto your iseries or AS/400 Existing Installations Only KeyesMail Version 9 - Update Instructions The following instructions can be used to install an update to an existing KeyesMail system. During the update, objects in your original

More information

Manual Password Depot Server 8

Manual Password Depot Server 8 Manual Password Depot Server 8 Table of Contents Introduction 4 Installation and running 6 Installation as Windows service or as Windows application... 6 Control Panel... 6 Control Panel 8 Control Panel...

More information

Installation and Administration Guide

Installation and Administration Guide Installation and Administration Guide Product Version: 2.5.0 Publication date: 7/21/2011 Copyright 2008-2011, LINOMA SOFTWARE LINOMA SOFTWARE is a division of LINOMA GROUP, Inc. Table of Contents Introduction...

More information

Setting Up Specify to use a Shared Workstation as a Database Server

Setting Up Specify to use a Shared Workstation as a Database Server Specify Software Project www.specifysoftware.org Setting Up Specify to use a Shared Workstation as a Database Server This installation documentation is intended for workstations that include an installation

More information

HP ProLiant ML150 System Monitor User Guide

HP ProLiant ML150 System Monitor User Guide HP ProLiant ML150 System Monitor User Guide November 2003 Contents Introduction... 1 MSM Features...1 Installing MSM... 3 Installing MSM Server on the Server...3 Installing MSM Console on a Client PC...3

More information

UPS MONITORING SOFTWARE USER MANUAL

UPS MONITORING SOFTWARE USER MANUAL UPS MONITORING SOFTWARE USER MANUAL Emily For Linux Table of Contents 1 Installation...2 1.1. Note...2 1.2. Install Instructions...2 1.3 Uninstall Instructions...2 2 Function Explanations...3 2.1 Function

More information

Setting Up the Device and Domain Administration

Setting Up the Device and Domain Administration Setting Up the Device and Domain Administration Install a Host Support Program on your Computer A NetVault7.1 program must be installed on the computer(s) used by the administrator(s) of your backup service.

More information

AXIGEN Mail Server. Quick Installation and Configuration Guide. Product version: 6.1 Document version: 1.0

AXIGEN Mail Server. Quick Installation and Configuration Guide. Product version: 6.1 Document version: 1.0 AXIGEN Mail Server Quick Installation and Configuration Guide Product version: 6.1 Document version: 1.0 Last Updated on: May 28, 2008 Chapter 1: Introduction... 3 Welcome... 3 Purpose of this document...

More information

VTLBackup4i. Backup your IBM i data to remote location automatically. Quick Reference and Tutorial. Version 02.00

VTLBackup4i. Backup your IBM i data to remote location automatically. Quick Reference and Tutorial. Version 02.00 VTLBackup4i Backup your IBM i data to remote location automatically Quick Reference and Tutorial Version 02.00 Manufacture and distributed by VRTech.Biz LTD Last Update:16.9.2013 Contents 1. About VTLBackup4i...

More information

RCCMD Multiple Server Shutdown Software

RCCMD Multiple Server Shutdown Software Version: 2012-11-30 RCCMD Multiple Server Shutdown Software User manual Version: 2012-11-30 Copyright Statement for Intellectual Property and Confidential Information The information contained in this

More information

SequeLink Server Installation Instructions for the iseries

SequeLink Server Installation Instructions for the iseries SequeLink Server Installation Instructions for the iseries Requirements This document describes installation of SequeLink Server for the iseries. Throughout this document, the term iseries refers to the

More information

You re probably already familiar with using a File Transfer Protocol (FTP)

You re probably already familiar with using a File Transfer Protocol (FTP) 6 FTP, File Transfer, and More You re probably already familiar with using a File Transfer Protocol (FTP) client for downloading files from the Internet. What you may not know is that you can do a lot

More information

Email Setup, Management & Troubleshooting Version V6R1M0

Email Setup, Management & Troubleshooting Version V6R1M0 Email Setup, Management & Troubleshooting Version V6R1M0 CoolSpools Email Setup V6R1 Page: 1 IMPORTANT This document is only applicable if you wish to configure CoolSpools Email to use IBM Mail Server

More information

Create a New Account Contents

Create a New Account Contents Create a New Account Contents Goals...2 Create a New Domain Account...2 Domain Information...3 Package...4 Settings...5 Reseller Settings...6 DNS Settings...6 Mail Routing Settings...7 Conclusion...7 1

More information

Installation Instruction STATISTICA Enterprise Server

Installation Instruction STATISTICA Enterprise Server Installation Instruction STATISTICA Enterprise Server Notes: ❶ The installation of STATISTICA Enterprise Server entails two parts: a) a server installation, and b) workstation installations on each of

More information

How to export a spool file from an AS/400 and export to a Windows PC

How to export a spool file from an AS/400 and export to a Windows PC How to export a spool file from an AS/400 and export to a Windows PC This instruction manual is intended for customers working with AS/400 host systems and Lexmark printers capable of printing from an

More information

Backup & Restore Guide

Backup & Restore Guide The email Integrity Company Sendio Email Security Platform Appliance Backup & Restore Guide Sendio, Inc. 4911 Birch St. Suite 150 Newport Beach, CA 92660 USA +1.949.274.4375 www.sendio.com 2010 Sendio,

More information

Application Note: FTP Server Setup on computers running Windows-7 For use with 2500P-ACP1

Application Note: FTP Server Setup on computers running Windows-7 For use with 2500P-ACP1 Application Note: FTP Server Setup on computers running Windows-7 For use with 2500P-ACP1 The CTI 2500P-ACP1 is capable of transferring data files to a remote FTP Server. This document provides information

More information

TIBCO MFT Platform Server for IBM i User Guide. Software Release 7.1.0 April 2013

TIBCO MFT Platform Server for IBM i User Guide. Software Release 7.1.0 April 2013 TIBCO MFT Platform Server for IBM i User Guide Software Release 7.1.0 April 2013 Important Information SOME TIBCO SOFTWARE EMBEDS OR BUNDLES OTHER TIBCO SOFTWARE. USE OF SUCH EMBEDDED OR BUNDLED TIBCO

More information

Kollaborate Server Installation Guide!! 1. Kollaborate Server! Installation Guide!

Kollaborate Server Installation Guide!! 1. Kollaborate Server! Installation Guide! Kollaborate Server Installation Guide 1 Kollaborate Server Installation Guide Kollaborate Server is a local implementation of the Kollaborate cloud workflow system that allows you to run the service in-house

More information

BestSync Tutorial. Synchronize with a FTP Server. This tutorial demonstrates how to setup a task to synchronize with a folder in FTP server.

BestSync Tutorial. Synchronize with a FTP Server. This tutorial demonstrates how to setup a task to synchronize with a folder in FTP server. BestSync Tutorial Synchronize with a FTP Server This tutorial demonstrates how to setup a task to synchronize with a folder in FTP server. 1. On the main windows, press the Add task button ( ) to add a

More information

XStream Remote Control: Configuring DCOM Connectivity

XStream Remote Control: Configuring DCOM Connectivity XStream Remote Control: Configuring DCOM Connectivity APPLICATION BRIEF March 2009 Summary The application running the graphical user interface of LeCroy Windows-based oscilloscopes is a COM Automation

More information

User s Manual PowerPanel Shutdown Service Graceful Shutdown and Notification service to ensure power protection of your computer

User s Manual PowerPanel Shutdown Service Graceful Shutdown and Notification service to ensure power protection of your computer User s Manual PowerPanel Shutdown Service Graceful Shutdown and Notification service to ensure power protection of your computer Revision 1.1 TABLE OF CONTENTS INTRODUCTION... 1 INSTALLATION GUIDE... 2

More information

Quick Installation and Setup for WinPower Software

Quick Installation and Setup for WinPower Software Quick Installation and Setup for WinPower Software A. On the WinPower Installation menu, simply follow on-screen instructions and key in the software serial number. The installation will be automatically

More information

Tera Term Telnet. Introduction

Tera Term Telnet. Introduction Tera Term Telnet Introduction Starting Telnet Tera Term is a terminal emulation program that enables you to log in to a remote computer, provided you have a registered account on that machine. To start

More information

Installation Guide for WebSphere Application Server (WAS) and its Fix Packs on AIX V5.3L

Installation Guide for WebSphere Application Server (WAS) and its Fix Packs on AIX V5.3L Installation Guide for WebSphere Application Server (WAS) and its Fix Packs on AIX V5.3L Introduction: This guide is written to help any person with little knowledge in AIX V5.3L to prepare the P Server

More information

Installation and Administration Guide

Installation and Administration Guide Installation and Administration Guide Product Version: 4.0.0 Publication date: 11/29/2011 Copyright 2007-2011, LINOMA SOFTWARE LINOMA SOFTWARE is a division of LINOMA GROUP, Inc. Table of Contents Introduction...

More information

GWAVA 5. Migration Guide for Netware GWAVA 4 to Linux GWAVA 5

GWAVA 5. Migration Guide for Netware GWAVA 4 to Linux GWAVA 5 GWAVA 5 Migration Guide for Netware GWAVA 4 to Linux GWAVA 5 Copyright 2010 GWAVA, Inc. All rights reserved. Content may not be reproduced without permission. http://www.gwava.com Overview While GWAVA

More information

µtasker Document FTP Client

µtasker Document FTP Client Embedding it better... µtasker Document FTP Client utaskerftp_client.doc/1.01 Copyright 2012 M.J.Butcher Consulting Table of Contents 1. Introduction...3 2. FTP Log-In...4 3. FTP Operation Modes...4 4.

More information

RCCMD Multiple Server Shutdown Software

RCCMD Multiple Server Shutdown Software Version: 2014-08-07 RCCMD Multiple Server Shutdown Software User manual Version: 2014-08-07 Copyright Statement for Intellectual Property and Confidential Information The information contained in this

More information

S OF T WAR E. DirectClock. Keeping the right time on your iseries and PCs with DirectClock (FunkUhr) User Manual

S OF T WAR E. DirectClock. Keeping the right time on your iseries and PCs with DirectClock (FunkUhr) User Manual DirectClock Keeping the right time on your iseries and PCs with DirectClock (FunkUhr) User Manual TOOLMAKER S OF T WAR E iseries & Toolmaker - Quality Combined Sales in: Germany: TOOLMAKER SOFTWARE GMBH

More information

Software Version: 9.8

Software Version: 9.8 X - A n a l y s i s Installation & Upgrade Guide Software Version: 9.8 T h i s p r o d u c t r e q u i r e s a s e c u r i t y c o d e t o a c t i v a t e i t. F o r S e c u r i t y C o d e, p l e a s

More information

STIDistrict Server Replacement

STIDistrict Server Replacement STIDistrict Server Replacement Major Steps Defined This document addresses how to migrate data and applications from an existing STIDistrict (SQL) Server to a new machine. There will be 8 major steps:

More information

How To Set Up Dataprotect

How To Set Up Dataprotect How To Set Up Dataprotect This document will show you how to install and configure your computer for a Typical installation. If you have questions about configuring a Custom installation please contact

More information

Technical Support Information

Technical Support Information Technical Support Information Broadband Module/Broadband Module Plus Configuration Guidance Setting up Remote Access to a Network Device (Mail/File Server/Camera Etc) connected to the LAN port of the Broadband

More information

DISASTER STRIKES. Are you ready?

DISASTER STRIKES. Are you ready? DISASTER STRIKES Are you ready? 1 Your Goal Complete OS/400 restoration Complete application restoration Bring back the most current information Protect your job 2 Your AS/400 just lost all of its data!

More information

Symantec ESM agent for IBM AS/400

Symantec ESM agent for IBM AS/400 Symantec ESM agent for IBM AS/400 Version 6.5 Installation Guide 1 Legal Notice Copyright 2009 Symantec Corporation. All rights reserved. Symantec, the Symantec Logo, LiveUpdate, Symantec Enterprise Security

More information

Acronis Backup & Recovery 11.5 Quick Start Guide

Acronis Backup & Recovery 11.5 Quick Start Guide Acronis Backup & Recovery 11.5 Quick Start Guide Applies to the following editions: Advanced Server for Windows Virtual Edition Advanced Server SBS Edition Advanced Workstation Server for Linux Server

More information

EZblue BusinessServer The All - In - One Server For Your Home And Business

EZblue BusinessServer The All - In - One Server For Your Home And Business EZblue BusinessServer The All - In - One Server For Your Home And Business Quick Start Guide Version 3.11 1 2 3 EZblue Server Overview EZblue Server Installation EZblue Server Configuration 4 EZblue Magellan

More information

+27O.557+! RM Auditor Additions - Web Monitor. Contents

+27O.557+! RM Auditor Additions - Web Monitor. Contents RM Auditor Additions - Web Monitor Contents RM Auditor Additions - Web Monitor... 1 Introduction... 2 Installing Web Monitor... 2 Overview... 2 Pre-requisites for installation... 2 Server installation...

More information

Senomix Timesheets for Mac OS X

Senomix Timesheets for Mac OS X for Mac OS X Self-Installed Server Installation Guide v5.1 2015 Senomix Software Inc. www.senomix.com Table of Contents 1.0 - Introduction... 1 2.0 - System Overview... 2 3.0 - Timesheets Server Installation

More information

ilaw Installation Procedure

ilaw Installation Procedure ilaw Installation Procedure This guide will provide a reference for a full installation of ilaw Case Management Software. Contents ilaw Overview How ilaw works Installing ilaw Server on a PC Installing

More information

DBMoto 7 Setup Guide for IBM DB2 for i Transactional Replications

DBMoto 7 Setup Guide for IBM DB2 for i Transactional Replications DBMoto 7 Setup Guide for IBM DB2 for i Transactional Replications Copyright This document is copyrighted and protected by worldwide copyright laws and treaty provisions. No portion of this documentation

More information

10 STEPS TO YOUR FIRST QNX PROGRAM. QUICKSTART GUIDE Second Edition

10 STEPS TO YOUR FIRST QNX PROGRAM. QUICKSTART GUIDE Second Edition 10 STEPS TO YOUR FIRST QNX PROGRAM QUICKSTART GUIDE Second Edition QNX QUICKSTART GUIDE A guide to help you install and configure the QNX Momentics tools and the QNX Neutrino operating system, so you can

More information

Browser Client 2.0 Admin Guide

Browser Client 2.0 Admin Guide Browser Client is a web-based application that allows users to point their browser at a URL and view live video from a set of Intellex units. Browser Client 2.0 is compatible with Intellex 3.2 software.

More information

Installation Instruction STATISTICA Enterprise Small Business

Installation Instruction STATISTICA Enterprise Small Business Installation Instruction STATISTICA Enterprise Small Business Notes: ❶ The installation of STATISTICA Enterprise Small Business entails two parts: a) a server installation, and b) workstation installations

More information

How To Install And Run Cesview Iii 1.3.3 (For New Users)

How To Install And Run Cesview Iii 1.3.3 (For New Users) Cesview IIi 1.3 Installation and Automation Guide Contents: New ser Quick Guide Cesview IIi asic Installation o Additional Server Installation Notes o Additional rowser Only (Client) Installation Notes

More information

Using Symantec NetBackup with Symantec Security Information Manager 4.5

Using Symantec NetBackup with Symantec Security Information Manager 4.5 Using Symantec NetBackup with Symantec Security Information Manager 4.5 Using Symantec NetBackup with Symantec Security Information Manager Legal Notice Copyright 2007 Symantec Corporation. All rights

More information

How to install Magellan 6

How to install Magellan 6 Information sheet Magellan S T Ü B E R How to install Magellan 6 Updated: 03.11.2014 All statements made in this document represent the current status of products - errors reserved and can be revised in

More information

- 1 - SmartStor Cloud Web Admin Manual

- 1 - SmartStor Cloud Web Admin Manual - 1 - SmartStor Cloud Web Admin Manual Administrator Full language manuals are available in product disc or website. The SmartStor Cloud Administrator web site is used to control, setup, monitor, and manage

More information

Quick Start Guide for VMware and Windows 7

Quick Start Guide for VMware and Windows 7 PROPALMS VDI Version 2.1 Quick Start Guide for VMware and Windows 7 Rev. 1.1 Published: JULY-2011 1999-2011 Propalms Ltd. All rights reserved. The information contained in this document represents the

More information

How to output SpoolFlex files directly to your Windows server

How to output SpoolFlex files directly to your Windows server How to output SpoolFlex files directly to your Windows server This document will quickly cover how to setup your AS/400 or iseries system to communicate with a Windows based file server. Under normal circumstances

More information

Configure your ewon using FTP

Configure your ewon using FTP Configure your ewon using FTP When you need to configure several ewons at the same time or make a repeated action you can use the ewon web interface. But you can also make changes on your ewon using FTP.

More information

Training module 2 Installing VMware View

Training module 2 Installing VMware View Training module 2 Installing VMware View In this second module we ll install VMware View for an End User Computing environment. We ll install all necessary parts such as VMware View Connection Server and

More information

Install / Users Guide

Install / Users Guide Remote shutdown program for network Install / Users Guide Windows Vista 7 Server 2008 Windows NT4.0 2000 XP Server 2003 Windows 98 Me INR-HF51881e LICENSE AGREEMENT USE OF THIS SOFTWARE IS SUBJECT TO LICENSE

More information

Moxa Device Manager 2.3 User s Manual

Moxa Device Manager 2.3 User s Manual User s Manual Third Edition, March 2011 www.moxa.com/product 2011 Moxa Inc. All rights reserved. User s Manual The software described in this manual is furnished under a license agreement and may be used

More information

Customer Tips. How to Upgrade, Patch or Clone Xerox Multifunction Devices. for the user. Purpose. Upgrade / Patch / Clone Process Overview

Customer Tips. How to Upgrade, Patch or Clone Xerox Multifunction Devices. for the user. Purpose. Upgrade / Patch / Clone Process Overview Xerox Multifunction Devices Customer Tips January 27, 2009 This document applies to the Xerox products indicated in the table below. For some products, it is assumed that your device is equipped with the

More information

Quick Installation and Setup for WinPower Software

Quick Installation and Setup for WinPower Software Quick Installation and Setup for WinPower Software A. On the WinPower Installation menu, simply follow on-screen instructions. The installation will be automatically proceeded. B. The software will start

More information

Direct Storage Access Using NetApp SnapDrive. Installation & Administration Guide

Direct Storage Access Using NetApp SnapDrive. Installation & Administration Guide Direct Storage Access Using NetApp SnapDrive Installation & Administration Guide SnapDrive overview... 3 What SnapDrive does... 3 What SnapDrive does not do... 3 Recommendations for using SnapDrive...

More information

Q N X S O F T W A R E D E V E L O P M E N T P L A T F O R M v 6. 4. 10 Steps to Developing a QNX Program Quickstart Guide

Q N X S O F T W A R E D E V E L O P M E N T P L A T F O R M v 6. 4. 10 Steps to Developing a QNX Program Quickstart Guide Q N X S O F T W A R E D E V E L O P M E N T P L A T F O R M v 6. 4 10 Steps to Developing a QNX Program Quickstart Guide 2008, QNX Software Systems GmbH & Co. KG. A Harman International Company. All rights

More information

CONNECTING TO DEPARTMENT OF COMPUTER SCIENCE SERVERS BOTH FROM ON AND OFF CAMPUS USING TUNNELING, PuTTY, AND VNC Client Utilities

CONNECTING TO DEPARTMENT OF COMPUTER SCIENCE SERVERS BOTH FROM ON AND OFF CAMPUS USING TUNNELING, PuTTY, AND VNC Client Utilities CONNECTING TO DEPARTMENT OF COMPUTER SCIENCE SERVERS BOTH FROM ON AND OFF CAMPUS USING TUNNELING, PuTTY, AND VNC Client Utilities DNS name: turing.cs.montclair.edu -This server is the Departmental Server

More information

Bitrix Site Manager ASP.NET. Installation Guide

Bitrix Site Manager ASP.NET. Installation Guide Bitrix Site Manager ASP.NET Installation Guide Contents Introduction... 4 Chapter 1. Checking for IIS Installation... 5 Chapter 2. Using An Archive File to Install Bitrix Site Manager ASP.NET... 7 Preliminary

More information

F-SECURE MESSAGING SECURITY GATEWAY

F-SECURE MESSAGING SECURITY GATEWAY F-SECURE MESSAGING SECURITY GATEWAY DEFAULT SETUP GUIDE This guide describes how to set up and configure the F-Secure Messaging Security Gateway appliance in a basic e-mail server environment. AN EXAMPLE

More information

Level 2 systemsoperationssuite v4.2

Level 2 systemsoperationssuite v4.2 Level 2 systemsoperationssuite v4.2 Installation, Upgrade & Getting Started Copyright Copyright 2009-2013 Halcyon Software Limited. All rights reserved. IBM, iseries, Power/System i, IBM i, OS/400 and

More information

Local Caching Servers (LCS): User Manual

Local Caching Servers (LCS): User Manual Local Caching Servers (LCS): User Manual Table of Contents Local Caching Servers... 1 Supported Browsers... 1 Getting Help... 1 System Requirements... 2 Macintosh... 2 Windows... 2 Linux... 2 Downloading

More information

Remote Client Program... 3. Web Client... 39

Remote Client Program... 3. Web Client... 39 Remote Client / Web Client USER MANUAL T Series Digital Video Recorder Remote Client Program... 3 Remote Client Program Installation... 4 Remote Client... 6 Main Window... 6 Site Registration... 7 Group

More information

UPS Management Software

UPS Management Software UPS Software UPSMAN/UPSMON, RCCMD and UNMS Comprehensive UPS Administration Description The Software is a collection of client/server modules for networks and local workstations for monitoring the status

More information

Kaseya 2. Installation guide. Version 7.0. English

Kaseya 2. Installation guide. Version 7.0. English Kaseya 2 Kaseya Server Setup Installation guide Version 7.0 English September 4, 2014 Agreement The purchase and use of all Software and Services is subject to the Agreement as defined in Kaseya s Click-Accept

More information

NS Series Programmable Terminal FTP Function

NS Series Programmable Terminal FTP Function NS Series Programmable Terminal FTP Function Created by OMRON HMI Contents 1. FTP on the NS Series... 3 1.1. Intended Purpose... 3 1.2. Models... 3 2. External Interfaces... 3 2.1. Data Storage Location...

More information

Question: 1 Which associated object must be restored on the system prior to restoring a logical file?

Question: 1 Which associated object must be restored on the system prior to restoring a logical file? Question: 1 Which associated object must be restored on the system prior to restoring a logical file? A. The access path B. The physical file C. The field reference file D. The user profile that created

More information

Setting Up Scan to SMB on TaskALFA series MFP s.

Setting Up Scan to SMB on TaskALFA series MFP s. Setting Up Scan to SMB on TaskALFA series MFP s. There are three steps necessary to set up a new Scan to SMB function button on the TaskALFA series color MFP. 1. A folder must be created on the PC and

More information

Configuring Virtual Blades

Configuring Virtual Blades CHAPTER 14 This chapter describes how to configure virtual blades, which are computer emulators that reside in a WAE or WAVE device. A virtual blade allows you to allocate WAE system resources for use

More information

For keyboard and touchscreen BlackBerry devices User manual

For keyboard and touchscreen BlackBerry devices User manual TSMobiles Terminal Service client for Mobiles For keyboard and touchscreen BlackBerry devices User manual Introduction... 3 System Requirements... 3 1. Configuring Remote Desktop on computer... 4 2. Installation...

More information

CS 326e F2002 Lab 1. Basic Network Setup & Ethereal Time: 2 hrs

CS 326e F2002 Lab 1. Basic Network Setup & Ethereal Time: 2 hrs CS 326e F2002 Lab 1. Basic Network Setup & Ethereal Time: 2 hrs Tasks: 1 (10 min) Verify that TCP/IP is installed on each of the computers 2 (10 min) Connect the computers together via a switch 3 (10 min)

More information

Web Service for SKF @ptitude Observer. Installation Manual. Part No. 32179700 Revision A

Web Service for SKF @ptitude Observer. Installation Manual. Part No. 32179700 Revision A Web Service for SKF @ptitude Observer Part No. 32179700 Revision A Copyright 2009 by SKF Reliability Systems All rights reserved. Aurorum 30, 977 75 Luleå Sweden Telephone: +46 (0) 920 758 00, Fax: +46

More information

Changing Your Cameleon Server IP

Changing Your Cameleon Server IP 1.1 Overview Technical Note Cameleon requires that you have a static IP address defined for the server PC the Cameleon server application runs on. Even if the server PC has a static IP address, you may

More information

NETWORK ADMINISTRATION

NETWORK ADMINISTRATION NETWORK ADMINISTRATION INTRODUCTION The PressureMAP software provides users who have access to an Ethernet network supporting TCP/IP with the ability to remotely log into the MAP System via a network connection,

More information

Print/Scan System (U)

Print/Scan System (U) Print/Scan System (U) KM-3035/4035/5035 Network Scanner Operation Guide ALWAYS read this Operation Guide thoroughly before use. After reading, maintain it in good condition and keep it

More information

EMC Data Domain Management Center

EMC Data Domain Management Center EMC Data Domain Management Center Version 1.1 Initial Configuration Guide 302-000-071 REV 04 Copyright 2012-2015 EMC Corporation. All rights reserved. Published in USA. Published June, 2015 EMC believes

More information

HowTo. Planning table online

HowTo. Planning table online HowTo Project: Description: Planning table online Installation Version: 1.0 Date: 04.09.2008 Short description: With this document you will get information how to install the online planning table on your

More information

System Operator s Guide. MaddenCo Inc. Revised August 2003. Copyright 2003 by MaddenCo, Inc All rights reserved.

System Operator s Guide. MaddenCo Inc. Revised August 2003. Copyright 2003 by MaddenCo, Inc All rights reserved. System Operator s Guide MaddenCo Inc. Revised August 2003 Copyright 2003 by MaddenCo, Inc All rights reserved. 1 Please understand that MaddenCo has expended substantial sums in developing and maintaining

More information

Quick Start Guide for Parallels Virtuozzo

Quick Start Guide for Parallels Virtuozzo PROPALMS VDI Version 2.1 Quick Start Guide for Parallels Virtuozzo Rev. 1.1 Published: JULY-2011 1999-2011 Propalms Ltd. All rights reserved. The information contained in this document represents the current

More information

GUARD1 PLUS SE Administrator's Manual

GUARD1 PLUS SE Administrator's Manual GUARD1 PLUS SE Administrator's Manual Version 4.4 30700 Bainbridge Road Solon, Ohio 44139 Phone 216-595-0890 Fax 216-595-0991 info@guard1.com www.guard1.com i 2010 TimeKeeping Systems, Inc. GUARD1 PLUS

More information

Installing LearningBay Enterprise Part 2

Installing LearningBay Enterprise Part 2 Installing LearningBay Enterprise Part 2 Support Document Copyright 2012 Axiom. All Rights Reserved. Page 1 Please note that this document is one of three that details the process for installing LearningBay

More information

System Management. What are my options for deploying System Management on remote computers?

System Management. What are my options for deploying System Management on remote computers? Getting Started, page 1 Managing Assets, page 2 Distributing Software, page 3 Distributing Patches, page 4 Backing Up Assets, page 5 Using Virus Protection, page 6 Security, page 7 Getting Started What

More information

Installation of IEXL

Installation of IEXL Installation of IEXL IEXL Software License Agreement idata Development Ltd ( IDD Ltd ) License IDD Ltd grants to the purchaser, license to use the software product on the specified serial number and processor

More information

Customer Control Panel Manual

Customer Control Panel Manual Customer Control Panel Manual Contents Introduction... 2 Before you begin... 2 Logging in to the Control Panel... 2 Resetting your Control Panel password.... 3 Managing FTP... 4 FTP details for your website...

More information