Roxtec multi-cable transit devices Applications and design practices
|
|
|
- Elinor Gilmore
- 10 years ago
- Views:
Transcription
1 Prepared for: Roxtec International Date: Roxtec multi-cable transit devices Applications and design practices Authors: Allen Gibson, Roxtec Group, P.O Box 17832, United Arab Emirates Allan Bozek, EngWorks Inc, th Avenue SW, Calgary AB T2T 2T7, Canada Bo Millevik, Roxtec Group, Box 540, Karlskrona, Sweden
2 Abstract This is an introduction to applications and an engineering design approach for the proper use of Roxtec multi-cable transit devices within onshore oil, gas and petrochemical facilities. This paper demonstrates improved safety and improved project delivery when cable transit devices are included into owner and EPC design scopes. International standards for cable transit devices and common safety demands are presented, including the use of Roxtec cable transit devices for vapor-tight barriers, blast-rated structures, fire walls, pressurized buildings, and simple ingress protection against environmental elements. Incorporating Roxtec transits into owner-level and engineering-level design standards, is demonstrated to provide project savings that include reducing contractor work-hours, detail design time, and reduced field maintenance time. Proper multi-cable transit design and installations are also shown to increase project safety and operational uptime. Index Terms Multi-cable transit, Cable Transit Device (CTD), Blast-rated wall, Vaportight barrier, Cable entry, Pressurized building, Cable termination, Earthing armored cable 2
3 1. Introduction In the 1950 s, design methods and products were developed to protect against the hazards of water, fire, blast and smoke for shipboard/marine applications. These products became known as multi-cable transits or MCT s. The early adopters for these technologies were primarily naval engineers that required improved methods for sealing cables and pipes that passed through bulkheads and decks of navy vessels. As multicable transits proved their benefits throughout naval fleets and commercial shipyards around the world, the offshore oil and gas industry also began to recognize the safety features and benefits of having a cable transit that can be opened to add, remove and maintain electrical and control system cabling. Today, Roxtec transits for multiple cables and pipes are a standard design practice for many marine and offshore oil and gas projects. However, this same level of standardization for cable entries is lacking within many project designs for onshore projects. This paper focuses on introducing multi-cable transits to electrical, instrumentation and civil design teams working with onshore oil, gas, petrochemical and heavy industrial facilities, reviewing the critical components for design and installation, relevant international standards for use of Roxtec multi-cable transits and providing a recommended work process for proper designs of the transits. 3
4 2. Components and assembly overview for multi-cable transit devices A. Components Multi-cable transits have standardized designs and components. At minimum, each transit includes a frame, modular elastomeric blocks which are commonly called modules or insert blocks, stay plates and a mechanical compression unit, or compression wedge, all as shown in Fig. 1. Also, most Roxtec transit designs require the use of lubricant or assembly gel to aid with the installation of the modules as the design tolerances are very tight and the module materials create friction against themselves during installation Wedge Wedge Clip Frame Stayplate Modules Lubricant 4
5 B. Dimensions and Packing Space The inside dimensions of each single window are most commonly standardized to 120mm width, with varying heights. The interior height range of each single window is variable from 60mm to 240mm. Together, these interior dimensions are known as Packing Space. It should be noted that Packing Space does not include the space allocated to the mechanical compression wedge, only space where cables may be added. Packing space Variable mm Packing space Fixed 120mm Fig. 2 Packing Space in a Roxtec transit C. Combination frames Roxtec transits are often designed as combination frames, where more than one packing window (120mm wide, x-height) are manufactured within the frame as a vertical addition, horizontal addition, or both, as shown in Figs. 3a-c. Fig. 3a Vertical Windows Fig. 3b Horizontal Windows Fig. 3c Combination Windows 5
6 D. Flanged and Non-flanged Frames Manufacturer designs of Roxtec transits also provide the option to have a flange included with the frame to provide increased tolerance for the aperture or cut-out size in the wall or floor, and to enable installation by bolting. Most onshore project designs benefit from flanged frames, Fig. 4a; however in applications where the frame will be welded directly to a steel wall or floor structure, non-flanged frames may be specified, Fig. 4b. Fig.4a Flanged Frame Fig. 4b Non-Flanged Frame E. Frame and Component Materials Selecting proper materials is a critical design element. Roxtec offers frames in different materials to meet specific demand or cost requirements. Some of the most common metallic material types and applications are suggested in TABLE 1, including stainless steel, galvanized and mild steel. For applications without fire rating requirements and when a Roxtec transit will be placed in non-hazardous and non-blast rated applications, a designer may consider composite plastic materials for Roxtec frames to reduce both cost and weight 6
7 F. Aperture Size Most important in early design stages is to accurately size the aperture or cut-out that will be required in a wall or floor to properly install the Roxtec frame. This important dimension is shown as h2 and w2 in Fig. 5. Too often, the aperture dimension is sized incorrectly from the flange dimensions, H and W in Fig. 5. Missing this simple sizing detail has impacted many projects, requiring additional time and expenses to modify structures or to add additional flange plate to the frame to cover the over-sized cut-out. This mistake is easy to avoid by using manufacturer-generated drawings to assure accuracy and communicating early with civil design teams and building contractors. B t1 H h 2 t3 B t2 w2 W D B-B Fig. 5 5 Aperture sizing = h2 and w2 7
8 G. Sealing Modules The modules within a Roxtec transit serve as the seal around the outside diameter, O.D., of the cables. Most modules are manufactured using a halogen-free rubber compound, Roxylon, based on Ethylene-Propylene rubber (EPDM). The material allows for compression from the compression wedge to be applied universally to the modules, creating a mechanical seal around each cable in the transit. Like most onshore oil, gas & petrochemical facilities, which are designed to have an operating life >20 years, Roxtec modules have also proven to be a long-lifecycle product. Roxtec modules consist of two halves which are placed on each side of the cable and then inserted into the frame. Roxtec modules are available with removable layers and center core: one single Roxtec module can seal a cable or pipe over a span of several different diameters simply by peeling layers from the module halves. Typically 6 modules sizes accommodate cable O.D. range from 3mm to 99mm. These modules with center core may be used as spare blocks for future cable additions, due to the fact that when under full mechanical compression, these modules serve as solid blocks. This type of module provides additional flexibility during both design and installations when cable schedules are known to change frequently. H. Mechanical Compression Unit or Compression Wedge It is important that the project design team for Roxtec transits be aware of the specific compression units to match the frame designs. Compression units are not interchangeable among manufacturers; some require additional components to fill voids in the packing space. I. Stay plates or anchor plates The use of stay plates is common to nearly all Roxtec multi-cable transit applications. The metallic plates are installed between each row of modules. On both the front and back side of each stay plate is a raised lip that prevents modules from sliding forward or back within the frame. By design, stay plates provide a significant benefit to increase cable retention and improve integrity of multi-cable transits to withstand pressure from blasts and water. Stay plates also play an important role during horizontal or floor installations. With this raised lip on each side of the stay plates, modules have a place to rest, holding them in place before final compression 8
9 3. Applications for Roxtec cable transit devices in onshore facilities A. Environmental Protection/Ingress Protection In even the simplest applications, Roxtec devices provide excellent protection against the elements and hazards that may be caused by weather (rain, snow, wind, heat, humidity), splashing or hose-down water, sand and/or dust. Standard Roxtec designs have minimum watertight and dust-tight rating equivalent to an Ingress Protection (IP) rating for electrical enclosures of IP 54 as defined by IEC IP 54 provides protection against dust with limited ingress, with no harmful deposit and also protection against splashing from all directions with only limited ingress permitted. Performing at higher levels, Roxtec provides standard products with IP 66 and IP 67 ratings. IP 66 rated products deliver total protection against dust and protection against powerful water jets without harmful effects. IP 67 ratings deliver total protection against dust and protection against immersion into water to a depth of 1 meter. In addition to IP ratings, it is important to understand the capacity of Roxtec devices to prevent the passage of corrosive or potentially explosive gases. Gas tightness is discussed in more detail in Section C Vapor Tight Barrier. Unfortunately, many system failures and safety risks have been created due to poor levels of protection against these routine environmental hazards. A basic Roxtec design and installation protects life, equipment and assets, yet in many projects, it is found that no cable sealing or barrier to the basic environment has been installed. In other cases, the method of sealing the cable entry is simply inadequate. As shown in Fig. 6, a hole remains after the cable sealing installation is complete, compared to Fig. 7, where proper cable sealing is provided in this floor application using a Roxtec seal. Fig. 6 5 Aperture sizing = h2 and w2 Incorrect cable sealing Fig. 7 Correct cable sealing with Roxtec 9
10 B. Blast Rated Structures Due to the potentially explosive environments of many onshore oil, gas and petrochemical facilities, people and operations are at risk of blasts. Many hours of engineering design are involved to correctly design blast rated walls and structures, but the openings where cables pass are not always considered. Most often this oversight is a result of communication breakdowns across project phases and between different engineering disciplines for the project. Roxtec transits should be included in early project designs, with civil and/or structural design teams confirming with Roxtec that the multi-cable transit design provides the required level of blast load protection. Depending on application, Roxtec transits are commonly available to provide protection against blast load to >10 psi for > 60 milliseconds. The ratings for blast rated structures vary widely, but Roxtec can be consulted to provide test reports to the specific project demands. Vapor Tight Barrier During the identification and planning of the hazardous areas for a facility, design considerations must be given to properly separate hazardous areas from unclassified areas. During this hazardous location definition and planning phase, consideration should be given to designing cable entry methods to buildings within these hazardous zones. An unclassified room or building may be installed adjacent to a classified area provided a vapor-tight barrier is placed between the hazardous location and the unclassified area. The design of the vapor barrier is such that it prevents the migration of fugitive emissions from the classified area to the unclassified area under normal ambient pressure conditions. Section 6 of API RP 500 and 505 discuss the use of classifying areas using vapor-tight barriers. The industry currently has vague definition to the term Vapor-Tight ; however the following standards are commonly referenced to address the requirements for vaportight: 1) IEC Construction and Use of Buildings Protected by Pressurization, 2) NFPA 496 Standard for Purged and Pressurized Enclosures for Electrical Equipment, 3) API RP 500 Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class I, Division I and Division 2, and 4) API RP 505 Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class I, Zone 0, and Zone 2 With proper specification, design and installations, Roxtec devices meet or exceed the requirements for vapor-tight barriers. Due to the history of multi-cable transits in 10
11 catastrophic pressure scenarios for harsh marine applications, Roxtec transits have been designed to provide gastight certifications to a pressure of 2.5 bar (~36 psi). For land-based applications, the pressure requirements are much less, where most applications are required to prevent the passage of gases with pressure equal to 25 pa (0.1 inch WC or psi). The onshore project requirement is typically to maintain a pressure slightly positive to atmosphere. Roxtec transits are certainly fit for this purpose. Other methods to create vapor-tight barriers in structures include using concrete or compounds to seal openings around cables. When these methods are used properly, they also provide protection against hazardous vapors. However, when maintenance or addition of cables is required, the effectiveness of these permanent barriers is violated when a new hole or entry is required to the structure. Depending on the structure and location where a new cable entry must be made into these mortar-type cable seals, most often an electrical tool is necessary. This typically requires a hot work permit in addition to partition barriers or operational shutdowns before work may begin. When a properly-specified Roxtec multi-cable transit is used, a simple 13mm wrench provides access to the transit, allowing easy addition or maintenance of cables without the related permitting and downtime required with concrete or compounds as barriers. Recent project reports have also indicated that leakage of corrosive gases into electrical or instrumentation buildings and equipment is a contributing risk to operational reliability and increasing operating costs. Roxtec devices, when specified with noncorrosive components, should be considered for cable entries into buildings and/or equipment in these potentially corrosive environments. D. Earthing, Bonding and EMC Many project designs are using armored cable types for power and control systems, and Roxtec has also improved product designs to meet the requirements specific to these cable types. International and local electrical codes require either bonding or earthing of the armor jacket component in these cable types. Some devices have recently been approved to meet the requirements for bonding or earthing. These Roxtec designs typically include a tin plated copper earthing strap that is embedded into the module, as shown in Fig. 8. Roxtec solutions are also approved to provide equipotential bonding as well as electrical safety protection against lightning strikes, as identified by IEC Fig. 8 Roxtec module with earthing strap embedded for use with armored cables 11
12 Protection against electromagnetic interference (EMI) is also becoming a more frequent discussion for new industrial project designs. The requirements to meet Federal Communications Commission (FCC) regulations in North America and global EMC directives and IEC product standards regarding immunity and emissions are important design criteria. Proper designs to protect against EMI are known to increase uptime reliability and avoid equipment damages caused by electromagnetic Interference. Specific Roxtec devices are approved and fit for these purposes. As interfering signals propagate along cable armor or screens, traditional grounding methods may not provide the most effective ground path for HF signals. Examples of interferences can be surges from lightning strikes, induced currents from variable frequency drives (VFD s) and switched devices. With the Roxtec module design shown in Fig. 8, the electrical safety requirements, and also the industry demands for improved HF grounding methods are considered, giving excellent protection for disturbances conducted by the armor or screen. Other Roxtec module designs are also readily available for shielding purposes giving protection up to 40GHz and more for radiated interference. From an electrical and EMC perspective, Roxtec transits by design, promote good engineering practice in that cables are routed through a single entry plate and not spread around an enclosure or building. This single entry point minimizes the risk of circulating ground currents as all cables are earthed in the same point where the Roxtec frame serves as the bus bar (earthing bar) that encloses all cables. The combination frames discussed in section II.C provide a natural design method for cable segregation where e.g. power cables and sensitive instrumentation cables can be routed through separate openings further reducing the risk for crosstalk and interference. E. Hazardous Locations In addition to using multi-cable transit devices for cable entries to buildings, Roxtec has also developed approved products that meet the major international electrical schemes (IEC, ATEX and AEX) for use of multi-cable transit devices to seal cables entering electrical equipment or enclosures within designated hazardous or classified areas. In these applications, the multi-cable transit device must be an approved device or component to the equipment or enclosure. Where multi-cable transit devices may be installed directly to electrical equipment or enclosures, it may be necessary that a cable entry scheme be certified to a hazardous location standard, e.g. ATEX, IEC or to an accepted engineering practice such as API RP 500/505. These applications must be identified early in the project to ensure that the transit device(s) are properly specified, designed and installed. Roxtec offers hazardous location approved solutions that are labeled for easy visibility and identification by inspector. Including Roxtec early into your project designs can prevent costly inquiries and delays during inspections. 12
13 F. Cable Terminations With the increase in modular building packages for substations, control centers and analyzer buildings, Roxtec devices are becoming more common in designs with floor entries for cables to enter directly below electrical equipment. In these cases, the Roxtec frame is either welded or bolted to the floor at strategic locations to the cable termination in the equipment. The cables are then pulled through the Roxtec frame, sealed with the modules and compressed. The Roxtec device provides cable retention in addition to an approved barrier against environment, fire, gases, blast, and rodents. With proper component selection, Roxtec devices also provide earthing and bonding safety as well as protection against EMI as discussed in section III.D. Internal Building Cable Tray Internal Power Connections Internal Control Connections Control Panel LV SWGR MCC Field Control Cables Field Cable Tray Field Power Connections Field Motor Connections Using Roxtec devices as the cable entry method into substations, control rooms and analyzer buildings offers several advantages including the following: 1. Efficiency: A Roxtec multi-cable transit device allows multiple cables to be pulled at the same time into the opening. The design of Roxtec transits provides for a high quantity and high density of cables to be installed within a very small footprint, making a very time and cost-efficient installation. 2. Integrity: The frame of the Roxtec multi-cable transit maintains the structural and environmental integrity of the floor or structure. In contrast, when foams and other alternatives for cable sealing are used, the integrity of the structure is most often compromised. 3. Future Expansion: By design, Roxtec devices are easily opened to maintain or add new cables. As discussed in more detail later, it is important that the design includes spare capacity of modules. 4. Cable Bend Radius: Using Roxtec devices for cable entries to floors provides additional room below the building floor and equipment. The standard depth for Roxtec devices is 60mm, but the manufacturer can provide deeper extension frames that are designed to a depth equal to or less than the height of the 13
14 structural steel. This additional working space assists with the restrictive bend radius of larger armored cables and allows for proper alignment of cables with equipment configurations. 5. Single entry point for earthing to minimize risks of circulating ground currents as discussed in section III.D. G. Cable Retention and Pull Force The design and materials of Roxtec devices provide high levels of cable retention for both vertical installations (walls) and horizontal installations (floors). The latest Roxtec designs are tested for cable retention to perform to the same requirements as traditional metallic cable glands, as defined in EN for Type B cable glands, IEC 62444, and also as stated as the minimum Pull Force in UL 514B, Table 27. As an example, for 50mm O.D. cables, Roxtec devices have tested to provide cable retention >2000 NM (~450 pound-force). In general, multi-cable transit devices used within hazardous areas should comply with IEC , where it is stated to secure cables for fixed installations without slippage with a force applied to the cable equal to 5 times the value in millimeters of the cable diameter in Newtons (1 Newton = lbs.-force) for round cables. Roxtec can be consulted to provide documentation for cable retention requirements for the project demands or to comply with the applicable standard. In most multi-cable transit applications, including cable entries into floors (horizontal frame installation), the system delivers approved cable retention and cable support. See Section 8.L.1 for additional information about cable support requirements. H. Fire Barrier Roxtec devices have a long and proven history of providing protection against fire. One of the most efficient applications for Roxtec multi-cable transit devices is when a design must provide fire protection, but also has demand(s) to provide protection against water, smoke, blast, rodents or other hazards. Stated in another way, if the only design concern is fire, there may be less sophisticated and lower cost methods to provide fireonly protection. However, when a complete risk assessment is included with project design, most often the risk of fire is compounded with the risks of casualty or damage from the hazards of smoke, water, or blast that are directly or indirectly related to the fire. In these cases where risks beyond fire-only are present, Roxtec devices should be considered by project owners, engineers and operators. I. Rodent and Insect Barrier Although often overlooked, rodent and insect infestations have caused operational upsets to many onshore processing plants. From the arctic conditions of the Canadian oil sands to the hot and harsh conditions of Saudi Arabian deserts, rodents and insects search for nesting, breeding and eating locations within the most favorable 14
15 conditions. Typically, these locations are buildings or cabinets that shelter electrical and control equipment. Unfortunately, when these pests seek refuge within electrical or control equipment, they often destroy the sensitive cables, connections or wiring within the buildings and cabinets, causing downtime and costly repairs or replacement of equipment. Preventing entry of these pests can be aided by using Roxtec devices where cables enter/exit buildings. Roxtec can provide you with test reports that demonstrate their system ability to serve as a barrier to these pests. J. Extreme Environments Many of today s largest projects are being constructed in the most harsh and hazardous environments that our world has to offer. These projects are demanded to perform at the same or higher levels of safety when compared to projects in the more mild climates. The history of Roxtec multi-cable transit devices through the hazards and harsh environments of shipboard and offshore oil and gas applications has proven the ability of the system to endure to these extreme conditions. When designing for such extreme environments, temperature and variations of temperatures are a primary consideration. Roxtec devices are available to perform with an operating temperature range from -40 C to +80 C with standard materials, and some solutions are certified for arctic conditions with temperature ratings to -60 C. Roxtec should be consulted to confirm the tested performance of the specified multicable transit device. For applications which demand operating performance requirements beyond the standard Roxtec product range, higher performing materials are available. However, it should be noted that when non-standard products are required, that either an engineering judgment and/or additional product testing may be required to confirm other certifications that are represented with standard materials. This can impact delivery timing and costs, so it is most important to have these discussions with Roxtec very early in project design. K. Vibration and noise dampening The components of Roxtec devices which are in direct contact with and around cables are made of elastomeric polymers which provide vibration and noise dampening performance. Owners and operators of skid mounted turbine equipment, generators, motors, mining equipment and cranes commonly specify Roxtec devices, with vibration and noise dampening often cited as one of the benefits to protect their systems. L. Retrofit for Existing Cables Many existing, or brownfield, facilities are operating today with either no original attempt to seal cable entries into buildings or have attempted to seal these entries using sub-standard methods. Roxtec devices are available with bolt-together frames 15
16 that can be installed around existing cables. These retrofit solutions provide brownfield projects with the possibility to improve safety and reliability by installing Roxtec transit devices to properly seal existing openings into buildings and equipment. The potential risks and costs associated with water, gases, rodents or blast entering control rooms or substations should be considered. Is it recommended to leave a fire or blast-rated door open in an operating facility? No. Is it wise to leave a window open with blowing rain? No. In fact, most project owners and EPC firms have adopted specification standards and safety requirements for fire and blast rated doors. Yet in many of these same buildings, the opening for cable entries remains open. These instances can be solved with Roxtec retrofit frames. 16
17 4. WORK PROCESS AND DESIGN APPROACH FOR ROXTEC DEVICES Taking a very early and very clear decision path in all project designs is important. Selecting an overall project design method for cable entries should be no different. Today it is most common in the marine and offshore oil/gas industries that project owners make the design decision related to cable entry methods for decks and bulkheads. However, for onshore projects, this decision has most often been left to an electrical contractor on the job site. With lack of standardization, many unapproved methods have been deployed at the last minute to attempt to seal openings for cable entries, or the cable entries are never sealed. To improve project designs for safety, delivery timing, maintenance and costs, project owners should consider taking a decision to standardize their methods for sealing cable entries and push this engineering decision forward to all stages of engineering design and construction throughout a project. Although the overall costs to properly seal cable entries is nominal within the scope of project budgets, when this decision is not taken as a design method or standard practice, then the related costs and delays begin to rise quickly near the completion stage of a project. As an example, if civil designs do not properly size apertures in concrete walls, or worse, omit openings for cable entries, the cost to customize product sizing or to modify the opening sizes not only adds costs, but also creates project delays. The following section will provide a simple and effective design method for project owners, engineering and construction firms to approach cable entry designs. A. Owner level Owner-level decision to adopt and standardize on a proper method for sealing cable entries is critical to improve project safety, reduce design risks and costs, and to simplify long-term maintenance and expansions for cabling. Regardless of the design method chosen for cable entries, it is critical that this decision be clearly and routinely included in the related project documents and communications. B. Front End Engineering Design (FEED) Owner-level decisions to standardize on multi-cable transit devices for cable entries should be communicated to the FEED stage of a project and the selected device manufacturer should be consulted for the best methods and early design recommendations. At this stage, Roxtec will be able to provide preliminary drawings 17
18 and budgetary quotes based on the earliest cable schedule data. At this stage the combined requirements such as area classification, tightness, fire, blast, and the earthing strategy should be assessed as this will drive some of the requirements for wall or floor design, and cable and multi-cable transit system type selection. C. Project Management Contractor (PMC) At the time the PMC is selected by the owner, the PMC becomes responsible for communicating owner-level design standards, and cable entry methods should be included. To optimize project standardization and efficiency, the same design method for cable entries should be employed across the full scope of the project. This standardization certainly improves design and construction efficiencies, but more importantly for the lifecycle of the project, it provides the operating owner and/or maintenance teams with a standardized platform to simplify maintenance which reduces total cost of ownership. D. Detail Design For electrical and controls teams during this project stage, the first requirement is to accurately size the aperture for all multi-cable transit devices. This can be easily completed by providing Roxtec with preliminary cable schedules. Roxtec is able to provide the design service for all multi-cable transit devices, and even cable transit design software which the project team may elect to utilize. This software system provides significant time savings when designing multi-cable transits when compared with traditional CAD designs. To properly size apertures, only basic cable data is required as follows. Roxtec can provide a template to provide this information. 1) Cable O.D. for each cable 2) Cable type (power, control, telecom, etc.) 3) Spare capacity as a percentage (%), it is important to factor in design changes to add equipment and technology to the project scope as well as consideration for future expansions or upgrades that my require additional cables to be added to the transit. A minimum 30% spare capacity within a multi-cable transit design is recommended, and many projects will add 100% spare capacity, as they have learned that Roxtec transits which are properly designed and installed during original construction reduce costs when compared to installing additional transit devices within an operating facility. Modifications to cable schedules are ongoing with all projects, and cable transit designs should be frequently updated throughout the project design, as often as cable schedules are updated. With the Roxtec Transit Designer software and consultation, these modifications are relatively simple and quick, and provide updated engineering drawings, bill of materials, delivery timings and budgetary quotes. Again, all involved engineering disciplines should be included in these updates. 18
19 E. Civil Engineering Civil design teams should be included at this time, if not earlier. Before any doorways or window openings are finalized, cut or cast into a building, it is critical to have accurate sizing. Aperture sizing for multi-cable transit devices is no different. To provide the most cost-effective and the safest solutions using multi-cable transits aperture sizing for them should be precise, just as other openings in buildings. As frames should be connected to an earthing system, proper methods to connect the frame to earth must to be established. This is especially important for frames cast into concrete structures where it can be difficult to arrange for such earthing arrangements after casting is complete. Roxtec has specific earth stud arrangements on their frames to simplify this. F. Construction Contractors (Buildings) As early as possible, contractors for building construction should receive engineering detail drawings produced by Roxtec, but controlled and communicated by the PMC or EPC teams. At the same time that the construction contractor is sizing doorways and windows, they should also be sizing multi-cable transit apertures. G. Electrical Contractors In many projects, it is often several months between the time that civil construction is complete with Roxtec frames installed and the time when cabling is pulled into buildings and equipment. It is important that the onsite electrical contractor team has received training to properly use Roxtec devices to seal cables and cable entries using the owner and manufacturer-approved cable transit design. It is most important that the Installation Detail Drawings for multi-cable transit devices include a note requiring that the onsite electrical contractor contact the manufacturer for training. Roxtec provides onsite, hands-on training, and web-based or video training is also available. A proper installation of Roxtec transit devices is not complicated, but it is different for many contractors, and training should be defined within the work process. H. Maintenance Teams Onsite electrical and instrumentation maintenance teams should also be included as early as possible in the communications and training for Roxtec multi-cable transit devices. These teams will be responsible for safely and cost-effectively maintaining facilities for the extended life cycle. 19
20 5. DETAILS REQUIRED FOR PROPER SPECIFICATION OF ROXTEC DEVICES To accurately and efficiently specify, design, install and maintain Roxtec devices, the following details should be considered early in the project and carried forward in routine communications throughout the project: A. Environmental Demands 1) IP requirements 2) Vapor-tight requirements B. Blast Load Demands 1) Peak overpressure requirements (mbar or psi) 2) Duration (ms) C. Operating Temperature Demands D. Cable Retention or Pull Force Demands E. Material Requirements for Frame and Hardware Proper selection of frame materials is a required engineering specification, as is the material specification for the hardware and components within a multi-cable transit. TABLE 1 provides a general selection guide for frame materials. For hardware and metallic multi-cable transit components, stainless steel should be specified when stainless frames are specified. When other frame materials are specified, galvanized hardware and metallic components are generally fit for purpose. 20
21 Table 1 Materail Selection Guide for roxtec frames 316L SS - Painted 316L, 316, or 304 SS Galvanized Mild Steel Mild Steel - Painted Continuous exposure to corrosive atmosphere X Potential or occasional exposure to corrosive atmosphere X X Indoor and/or non-corrosive atmosphere X X Fire rating Blast rating X X X X Hazardous Area (EXe) X X X X For use with earthing armored cables 1 X 2 X X X 2 1 Requires approved Roxtec components (modules and compression) for use with armo red cables. 2 Interior of frame must not be painted, to provide direct contact with earthing strap for modules used with armored cables F. Surface Treatments 1) Hot dip galvanized 2) Paint or coating specification G. Method of Installation 1) Bolting 2) Casting 3) Welding H. Structure Material thickness of material should be stated with the material type 1) Concrete - block 2) Concrete poured 3) Steel 4) Gypsum 5) Brick - masonry 6) Insulated panel or sandwich construction I. Fire Demands Unlike many other electrical and building standards, fire ratings are typically more regionalized or sometimes even localized, and the authority having jurisdiction should 21
22 always be recognized. The following fire demands are common for onshore facilities; however it is most important that the project design team specifies the fire rating requirements for each wall, floor or rooftop where Roxtec devices will be installed minutes 2. 1 hour 3. 2 hours 4. 3 hours 5. 4 hours Further, the prevailing fire code or fire standards should be communicated in the specification and must be communicated with Roxtec, i.e. UL 1479, 1 hour rating for poured concrete wall. J. Cable Type To properly specify and design Roxtec devices, it is critical to identify the cable type that will pass through the Roxtec device. The following basic categories will typically provide sufficient information to Roxtec to assist with proper specification of the multicable transit system. 1. Armored Cable i. Steel wire armor (SWA) ii. Metal clad (MC), including TECK cable iii. Braided, (Copper, Steel, ) 2. Non-armored cable or Tray Cable 3. Circular or non-circular cable Armored cable types may require the use of a Roxtec transit that is approved to provide bonding, earthing or grounding of the cable armor, depending on the application and electrical code of the authority having jurisdiction. If the project design is using cables that are non-circular, Roxtec should be consulted in detail to review systems approved for the non-circular cables with the specified demands. K. Bonding, Grounding, and EMC Requirements Does the location, surrounding environment or nearby electrical, instrumentation or other potentially sensitive equipment require protection from electromagnetic interference (EMI)? Will your project use armored cables which must have the armor earthed? Either way, Roxtec should be consulted to provide recommendations to meet your EMC demands. The following general information should be provided. 1. Type of protection required a. Bonding & Grounding b. Conducted interference c. Radiated interference d. Both conducted and radiated interference 22
23 2. Relative details of environment or equipment to be protected a. Frequency range b. Required protection levels L. Installation Details 1. Cable Fixing Point - While a Roxtec device provides robust cable support and a defined fixing point, industry standards require that cables should be supported in additional methods when the cable runs vertical, or is not laid on top of horizontal cable trays or supports, according to Offshore Standard DNV-OS-D201, April Additionally, BS 7671, EC60364-series and other standards require the intervals between cable supports to be such that cables do not suffer mechanical damage or strain, and provide the guide as shown in TABLE Entry all cables should be installed to enter a multi-cable transit frame at a 90 angle. 3. Cable length should be measured to the termination point and enough slack or surplus should be left to allow for lifting and placement of the cable into the multicable transit frame and modules. Table 2 BS 7671 ARMORED CABLE MAXIMUM SUPPORT SPACING Cable O.D (mm) Horizontal (mm) Vertical (mm) >9, but >15, but >20, but
24 6. CONCLUSIONS Roxtec multi-cable transit devices are innovative technologies that have proven their safety record throughout some of the harshest conditions within offshore oil/gas and marine projects. As onshore projects strive for improved safety, increased efficiency for project deliveries, and lower total costs of ownership, Roxtec devices should be considered for inclusion into owner-level approvals, standards and specifications for cable entries. Taking a decision to standardize on a cable entry method is not complicated or time consuming. However, it is proven across many mega-projects, that by not taking a formal decision at the project owner level, that creative and non-approved methods are commonly utilized, and in too many cases, no cable sealing method is applied. Roxtec devices are standardized in the design. The standard width of each window within a frame is 120mm and the standard depth is 60mm, although many other sizing options and configurations are available for both frames and components. Roxtec frames can be designed in small single windows, or larger combination frames with multiple windows with different orientations to meet differing project demands. Although Roxtec frames and apertures sizing are mostly standardized, the specialized components, e.g. earthing armored cables, and the product certifications for fire, blast and operating temperatures can vary. It is important to be in close communication on these details early in project scopes. Complete multi-cable transit engineering design services, onsite installation training and project support are also provided by Roxtec. Since multi-cable transits are a relatively new technology to many onshore designers and installers, it is important to select a provider that is resourced to support the project requirements with the most efficiency, from FEED through long-term project maintenance. Specifying Roxtec devices is simple when a design team includes the vendor early in project discussions. To obtain the highest levels of safety and reduced project risks (design, installation, and maintenance) Roxtec devices should be considered by project owners to be included within company engineering standards for the electrical, control and civil disciplines. When people and assets require protection from the risks of weather, harmful gases, blast, fire, rodents and/or EMI, Roxtec multi-cable transits are a proven, certified and cost-effective solution. 24
25 7. REFERENCES 1. American Society of Civil Engineers Design of Blast Resistant Buildings in Petrochemical Facilities 2. Army TM ; Structures to Resist the Effects of Accidental Explosion 3. Process Industries Practices PIP ELSGL01 Electrical Construction Specification 4. Alan Bozek, Hazardous Area Classification Tutorial Presentation IEEE PCIC New Orleans NFPA 496 Standard for Purged and Pressurized Enclosures for Electrical Equipment, 2008 Edition, Quincy, MA: NFPA 6. General Cable, Cable Installation Manual for Power and Control Cables, Highland Heights, KY USA: General Cable Technologies Corporation, Ninth Edition, September IEC Construction and Use of Buildings Protected by Pressurization, 8. NFPA 496 Standard for Purged and Pressurized Enclosures for Electrical Equipment, 9. API RP 500 Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class I, Division I and Division 2, and 10. BS 7671 Requirements for Electrical Installations 11. API RP 505 Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class I, Zone 0, and Zone IEC Low Voltage Electrical Installations, Section
26 8. VITA Allen Gibson is a graduate of Oklahoma State University and since 1990, has worked for international oil and gas companies in both technical and commercial roles, and served as President/CEO of a US-based LPG company. He is a member of the IEEE Industrial Applications Society and a member of the PCIC Middle East Local Committee. Since 2007 he has worked for Roxtec Group and serves as the Global Segment Manager for Process Industries. [email protected] Allan Bozek has over 24 years experience in the design, construction and maintenance of oil and gas facilities. He is an industry recognized expert in Hazardous Area Classification and Hazardous Location Protection and Wiring Methods. The scope of his experience includes upstream production, downstream refinery and upgrader facilities, offshore, heavy oil SAGD, and a number of international projects. He is a member of the IEEE Industrial Applications Society, a committee member of the Canadian Electrical Code Section 18 (Hazardous Locations) and is a Registered Professional Engineer in Canada. [email protected] Bo Millevik is an Electrical Engineer in Sweden with more than 30 years of combined experience at Ericsson and Flextronics in electronic designs, testing and electronic manufacturing, with a focus on EMC solutions. Bo has worked at Roxtec since 2009 developing Roxtec products for EMC applications. Bo is active with IEEE EMC Sweden Chapter and the Industrial Applications Society. [email protected] Roxtec is the world leader in modular-based cable and pipe penetration seals. Roxtec transits are used worldwide in a wide range of projects and industries to ensure safety, efficiency and operational reliability. The Roxtec sealing system protects against, for example, fire, gas and water, and includes solutions for electrical safety. 26
27 Roxtec International AB Box 540, Karlskrona, SWEDEN PHONE , FAX BRO ver_1.0/en/1405/anant Roxtec and Multidiameter are registered trademarks of Roxtec in Sweden and/or other countries.
Fig. 2 Option 1 Integrated Design using Physical Separation. Fig. 1 Standard Modular Process Skid Design Concept
Modular Integration of Process Equipment Packages for Oil and Gas Facilities Copyright Material PCIC Europe Paper No. PCIC Europe XXXX Allan Bozek EngWorks, Inc. 1620 49 th Avenue, SW Calgary, AB T2T 2T7
Whitepaper Modular Integration of Process Equipment Packages for Oil and Gas Facilities
Whitepaper Modular Integration of Process Equipment Packages for Oil and Gas Facilities Author: Allan Bozek P.Eng, MBA, EngWorks Inc, Calgary, Canada Abstract An integrated design approach to a modular
Whitepaper. Modular Substation Cable Termination Design. Author: Allan Bozek P.Eng, MBA, EngWorks Inc, Calgary, Canada
Whitepaper Modular Substation Cable Termination Design Author: Allan Bozek P.Eng, MBA, EngWorks Inc, Calgary, Canada Abstract The methods for cable penetrations into modular industrial substations are
David O Brien, CMP Products ([email protected])
David O Brien, CMP Products ([email protected]) 1) Main Function of Cable Glands 2) Common Issues with Cable Glands 3) Compliance / Standards, changing times 4) How do we select Cable Glands?
Stainless Steel and Mild Steel Enclosures. Stainless Steel and Mild Steel Enclosures
SX 8 The SX range comprises 14 sizes of enclosure manufactured in either stainless steel or mild steel. 11 sizes are available in depths of 140 or 200mm and 8 sizes are available in depths of 140, 200
Embedded Parts Introduction - Anchors
In the plant construction or process plants such as chemical, petrochemical, gas or power plants various disciplines are brought into contact and built on each other. Civil, mechanical, electro technical
Session 14 Cable Support Systems
Session 14 Cable Support Systems Cable Support Systems in the IEC World A new IEC Standard, IEC61537 2001 has been developed If full details of the cabling layout are available then the likely cable load
Electrical Classification
Electrical Classification Using NFPA 70 and NFPA 499 to Classify Hazardous Locations Electrical classifications are established in accordance with the National Electrical Code, NFPA 70, also referred to
PAINT BOOTH LIGHTING
PAINT BOOTH LIGHTING PAINT BOOTH LIGHTING Lighting is comprised of many components that need to be considered when selecting the appropriate fixtures and lamps to accomplish a specific task. Selecting
EX-TECH SAS CP/PB 150 EXPLOSIONPROOF MANUAL CALL POINT/ PUSH BOTTON TECHNICAL MANUAL
PRODUCT NAME: CP/PB -150- EXPLOSION-PROOF-MANUAL CALL POINT/ PUSH BOTTON DOC NO.: EX-TECH SAS-12-CP-PB150-TM REV01 EXPLOSION-PROOF MANUAL CALL POINT/ PUSH BOTTON II 2GD EPL Gb, Db Ex d IIC T6, IP66 Ex
HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12
SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications
Cable and pipe transits
Cable and pipe transits FOR ONSHORE OIL, GAS AND PETROCHEMICAL APPLICATIONS ABOUT ROXTEC The world s leading provider of multi-cable and pipe transits Founded in Sweden in 1990 Inventor of Multidiameter
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
D-13. temporary / mobile power. for harsh & hazardous (classfied) locations. Construction Demolition Maintenance Turnarounds Shutdowns
for harsh & hazardous (classfied) locations Construction Demolition Maintenance Turnarounds Shutdowns D-13 temporary / mobile power Temporary power products are used on industrial and construction sites
James M. Pleasants Company
James M. Pleasants Company SUBMITTAL DATA GAINESVILLE MECHANICAL DECEMBER 20, 2013 PROJECT: GSU: J-183 HUMANITIES LAW BLDG. QUOTE NO:12116 ENGINEER: STEVENS & WILKINSON GASKETED PLATE HEAT EXCHANGER Tag:
4 Installation Requirements
4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming
ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.
POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,
SECTION 22 LIGHTNING PROTECTION SYSTEM
SECTION 22 LIGHTNING PROTECTION SYSTEM 22.01 SCOPE: A. These Specifications shall form a part of the Contract Documents and shall govern construction work for all buildings to be built or modified for
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
Explosion proof enclosures
1 of 7 Explosion proof enclosures DE8 C 2 of 7 The Ex d enclosures are rugged and designed for harsh environment like: Oil and gas industry Chemical industry Pharmaceutical industry Agribusiness Without
Stilling Well Recommendations
White Paper June 24, 2009 Stilling Well Recommendations This document describes general requirements for stilling wells used for radar tank gauging applications. Automation solutions for oil & gas, defense
Safety instructions VEGAFLEX FX8*(*).FC/ O****A/H*****
Safety instructions VEGAFLEX FX8*(*).FC/ O****A/H***** FM 3046039 Class I Div 1, Groups A, B, C and D Class II Div 1, Groups E, F and G; Class III Class I, Zone 0, AEx ia IIC Ga, Ga/Gb, Gb Document ID:
Comparative study for cables and busbars
Comparative study for cables and busbars Preliminary considerations To compare the prices of two categories of product as different as traditional cables and busbars, it is necessary to make some preliminary
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
WHY CABLE TRAY? BECAUSE A CABLE TRAY WIRING SYSTEM PROVIDES SAFE AND DEPENDABLE WAYS TO SAVE NOW AND LATER
Large numbers of electrical engineers have limited detail knowledge concerning wiring systems. There is the tendency by engineers to avoid becoming involved in the details of wiring systems, leaving the
The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables
The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing
8146/5 Series Breaker Panelboards
8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial
SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design
SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design Ideal installation for; Offices Branch Offices Schools Computer Aided Classes Government Offices Hotels
necessary for years of satisfactory service. SmartBlock insulating form concrete walls share the
Chapter 7 PLUMBING AND ELECTRICAL 7.1 Introduction to Plumbing and Electrical Consideration of support services such as plumbing and electrical systems from the preliminary schematics phase through final
Securing your electrical installations Prisma,
Securing your electrical installations Prisma, an optimised solution for type tested low voltage switchboards up to 3200 A Table of contents Developing installation safety 4 Prisma P * Electrical switchboards
ORAY PREFABRICATED GSM SHELTER CONTAINERS TECHNICAL SPECIFICATIONS
GSM SHELTER CONTAINERS TECHNICAL SPECIFICATIONS ~GSM SHELTER CONTAINERS ARE PROCUDED ACCORDING TO THE DEMANDED SIZE.~ (W x L x H) Page1 GENERAL FEAUTURES Environmental Conditions : Maximum outdoor temperature
Chapter 3 Pre-Installation, Foundations and Piers
Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory
R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0
FieldBarrier Features Assembly 8... 12 outputs Ex ia IIC, FISCO and Entity Advanced fault isolation and diagnostics at the spur FieldBarrier in Zone 1/Div. 2 Instruments in Zone 0...1/Div. 1 For FOUNDATION
Loss Prevention Standard
Loss Prevention Standard : ISSUE 3.0 Requirements for the LPCB Approval and Listing of Companies Undertaking the Maintenance and Repair of Doorsets, Shutters, and Active Smoke/Fire Barriers This standard
ELEVATOR TRAVELING CABLE - DESIGN EVOLUTION
ELEVATOR TRAVELING CABLE - DESIGN EVOLUTION by Richard Laney Introduction Elevator traveling cable is a vital link between the elevator car and controller. In conventional elevators, all power and signal
Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description
Worldwide Contacts www.tyco-fire.com Model F thru F3 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description The Mulsifyre Nozzles are open (nonautomatic) nozzles and they are designed
CERTIFICATE OF APPROVAL No CF 5055 ARABIAN VERMICULITE INDUSTRIES
CERTIFICATE OF APPROVAL No CF 5055 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of 1 st Industrial Area,
100% EMI Emission Containment
100% EMI Emission Containment Designed for Longer Service Life Highly Flexible for Easier Handling and Faster Installation Authorized Distributor Industrial VFD Cables Index n Variable Frequency Drive
NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)
NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:
CLASSIFICATION NOTES
CLASSIFICATION NOTES Type Approval, Installation and Testing of Water Level Detectors on Bulk Carriers and Single Hold Cargo Ships other than Bulk Carriers General Information This edition of the classification
Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC
TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection
Blast Resistant Building BP Refinery Rotterdam
Blast Resistant Building BP Refinery Rotterdam 14 May, 2008 1 1 Contents Presentation Introduction KCI Functional Specification Blast Resistant Building Basis for design Blast & impact loading Design modeling
How To Use A Ds340 (Dsp)
Ideal for monitoring dust levels in the exhaust gas of industrial combustion or air filtration processes. Innovative Dynamic Detection Principle (DDP) measurement technique Immune to gradual reductions
SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)
APPLICATIONS Process Industry Weak Acids Alkalies Compressed Air Pulp & Paper MODELS ASM - Flanged Connection OPTIONS Control Rods Oil & Gas Water & Waste Pump suction & discharge Sea water Chemical lines
Operating Instructions
Operating Instructions Cable Glands Ex d and Ex e with Compound > Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Safety Information...3 4 Designated Use...4 5 Technical Data...4
Cooktop Low-Profile Ventilation Hoods
INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............
GK Packing System Welding Instructions
GK Packing System Welding Instructions Roxtec GmbH Neuer Höltigbaum 1-3, 22143 Hamburg GERMANY Tel +49 (040) 657398-0, Fax +49 (040) 657398-50 EMAIL [email protected], www.roxtec.de Welding instructions
Office of the State Fire Marshal. Fire Rated Doors
Office of the State Fire Marshal Fire Rated Doors Fire Rated Doors These doors serve a purpose. They are manufactured in a way that is to help reduce the spread of fire and smoke. Fire rated doors allow
Terminal Boxes Series 8146
Series > Enclosures in shock-resistant glass fibre reinforced polyester resin > basic enclosure sizes various heights > Fitted according to the customer's requirements > For terminals up to max. 00 mm
INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP
INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES Interpretations of the FTP CONTENTS FTP1 Adhesives used in A or B class divisions (FTP Code 3.1, Res A.754 para. 3.2.3) June 2000 FTP2 Pipe and duct
SnoTrace KSR Surface Snow and Ice Melting INSTALLATION PROCEDURES
SnoTrace Surface Snow and Ice Melting INSTALLATION PROCEDURES SnoTrace INSTALLATION PROCEDURES Refer to the SnoTrace Cable Testing Report for required recording of test data and circuit information. Upon
www.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT
Cabinets 101: Configuring A Network Or Server Cabinet
Cabinets 101: Configuring A Network Or Server Cabinet North, South and Central America White Paper May 2012 www.commscope.com Contents Background Information 3 What is a network or server cabinet? 3 What
Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS
Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS STANDARD & ECONOMICAL BasicRack A complete low-cost, high-quality basic equipment management system. Design Six web channel holes per side allow
Mark Cramer Inspection Services, Inc.
Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction
Pressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection
GE Oil & Gas. Air cooled heat exchangers Robust and reliable for all loads and applications
GE Oil & Gas Air cooled heat exchangers Robust and reliable for all loads and applications What it is Air cooled heat exchangers are commonly used in industrial applications where a reliable source of
INTERNATIONAL STANDARD
IEC 61892-7 INTERNATIONAL STANDARD Edition 2.0 2007-11 Mobile and fixed offshore units Electrical installations Part 7: Hazardous areas INTERNATIONAL ELECTROTECHNICAL COMMISSION PRICE CODE XA ICS 47.020.60
Instrumentation Cable...14-17. Power Cable...2-11. Assembly Solutions...32
Severe Cold Durability Exceeds CSA Cold Bend / Cold Impact (-0 C/-35 C) Drilling Mud Resistant Flame Retardant Certified to IEC 9-3 (33-3A) and IEEE 580 Oil Resistant Assemblies...3-33 Ester Based Mud
Waveguide Access Point WGA631. Product Guide
Waveguide Access Point Product Guide Waveguide Access Point Contents 1. Description............................ 3 2. Application............................ 3 3. Technical data... 4 4. Physical interfaces......................
ModuSec. Secure and efficient IT room solutions. Turnkey Modular Construction Fast clean build to any size or shape
ModuSec Secure and efficient IT room solutions Turnkey Modular Construction Fast clean build to any size or shape Room in room Standalone external build Transportable Modusec SR Options Modusec SR Options
A World Class Manufacturer of Induction Bends
A World Class Manufacturer of Induction Bends COFELY FABRICOM BENDING A leading position in bending High Flexibility and Close Tolerances As a world leading manufacturer of pipe bends, produced by induction
Microcor Wireless Transmitter (MWT)
Rohrback Cosasco Systems, Inc. Microcor Wireless Transmitter (MWT) Features: Highly Secure and Reliable Self Organizing Wireless Mesh Network High Resolution Metal Loss Measurement for all process environments
Decree of the Ministry of the Environment on fire safety of ventilation systems
THE NATIONAL BUILDING CODE OF FINLAND MINISTRY OF THE ENVIRONMENT Housing and Building Department Decree of the Ministry of the Environment on fire safety of ventilation systems Adopted in Helsinki, 18
Section: R100 Bulletin: R100.51 Date: 07/13 Supersedes: New TRUST. Your Water Level. Steam you can depend on, 24/7. Boiler Level Indication System
Section: R100 Bulletin: R100.51 Date: 07/13 Supersedes: New TRUST Your Water Level Steam you can depend on, 24/7 Boiler Level Indication System Boiler Level Indication System Where s your water? For over
STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM
Chapter 9 STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM 9.1 BACKGROUND Steel is widely used in the construction of multi-storey buildings. However, steel construction is seldom used and is traditionally
Enclosures 1-866-338-0988. DuraSystems Barriers, Inc. www.durasystems.com Email: [email protected]. The Passive Fire Protection Specialists
Enclosures Sturdy single and double wall fire protection construction Impact resistant Fast & easy installation Pre-manufactured and modular Available in galvanized, stainless steel & other specialty metals
Foxboro Evo Process Automation System
Foxboro Evo Process Automation System Product Specifications PSS 31H-2Z32 FBM232 Field Device System Integrator Module, 10/100 Mbps Ethernet, Single The FBM232 Field Device System Integrator (FDSI) module
How To Safely Dig For Natural Gas
PNG DIAL B4-U-DIG book_final_nu 5/1/05 3:24 PM Page 2 Phoenix Natural Gas,197 Airport Road West, Belfast BT3 9ED. Tel. 08454 55 55 55. www.phoenix-natural-gas.com PNG DIAL B4-U-DIG book_final_nu 5/1/05
Protecting YOUR NEW HOME FROM Wind Damage
Protecting YOUR NEW HOME FROM Wind Damage Blueprint for Safety... A Blueprint for Life When severe weather threatens, protecting life and property automatically becomes top priority for millions of Florida
Guide for SOLID CONCRETE BLOCK SEALS
Guide for SOLID CONCRETE BLOCK SEALS July, 2006 Mine Safety and Health Administration SOLID CONCRETE BLOCK SEAL Formersection 30 CFR 75.335(a)(1) specifies requirements for seals constructed using solid
Blast Proof Occupied Buildings
Blast Proof Occupied Buildings 1 1 Contents Presentation References Functional Specification Blast Resistant Building Basis for design Blast & impact loading Design modeling & analyses Preliminary design
Verizon NEBS TM Compliance: Data Center Equipment NEBS Requirements Verizon Technical Purchasing Requirements VZ.TPR.9703 Issue 2, March 2012
Verizon NEBS TM Compliance: Data Center Equipment NEBS Requirements Verizon Technical Purchasing Requirements VZ.TPR.9703 Issue 2, March 2012 CHANGE CONTROL RECORD: Version Date Action* Reason for Revision
Micro Motion 3098 Gas Specific Gravity Meter
Product Data Sheet PS-001161, Rev. D April 2013 Micro Motion 3098 Gas Specific Gravity Meter Micro Motion density and concentration meters are built to tackle the most demanding process and fiscal applications.
12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting
12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.
Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time
Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to
Select Radiators Installation Guide
Select Radiators Installation Guide Table of Contents Informational Symbols...3 Before You Begin...4 Select Rough-In... 5 Connection Installation...6 Optional Piping Arrangements...7 Conventional Wall
know-how Giant in distributing electricity for industry Prisma GK
Prisma GK Giant know-how in distributing electricity for industry Installation system up to 630A for electrical power distribution and circuit control. Prisma GK: technology and innovation for an IP55
The MC Cable Revolution is Gaining Ground REMKE
The MC Cable Revolution is Gaining Ground June 2014 MC Cable Installation Continues to Improve with Advances in Materials and Fittings As the use of Metal Clad Cable grows, contractors are demanding better
AN IN-DEPTH LOOK AT 2011 NEC ARTICLE 392 - CABLE TRAY. (The following code explanations are to be used with a copy of the 2011 NEC.
AN IN-DEPTH LOOK AT 2011 NEC ARTICLE 392 - CABLE TRAY (The following code explanations are to be used with a copy of the 2011 NEC.) To obtain a copy of the NEC contact: National Fire Protection Association
RPV - RP - RA air handling units
APPLICATIONS Heating, ventilation, cooling >> FACTORIES >> WAREHOUSES >> HALLS >> DISTRIBUTION CENTRES >> COMMERCIAL PREMISES >> PLACES OF WORSHIP RPV - RP - RA air handling units www.reznor.eu RPV - RP
DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT. User Manual. SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium
DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT User Manual SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium +32 (0)9/321.91.12 - Fax +32 (0)9/321.91.13 - e-mail: [email protected]
0845 0098 980 www.nicholsonsts.com
0845 0098 980 www.nicholsonsts.com ROOFTRAK The IFP is revolutionising the way we fix things to roofs. Technical Director of a leading UK roofing system manufacturer The ROOFTRAK-IFP A revolutionary solution
Installation. Smart-UPS VT MGE Galaxy 3500. Maintenance Bypass Panel. 10-40 kva 400 V
Installation Smart-UPS VT MGE Galaxy 3500 Maintenance Bypass Panel 10-40 kva 400 V Contents Safety.................................................. 1 Save these instructions...................................
CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements
16600 Underground Electrical Duct Bank This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications
TPM 006/99 Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER
Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER PSUM These technical specifications determinate a range of manufactured sizes and models of fire shutters (further only shutters)
SEISMIC VELOCITY TRANSDUCER T1-40
SEISMIC VELOCITY TRANSDUCER T1-40 Measurement of Omnidirectional Absolute Vibrations Certified according to ATEX 94/9/CE directive OPERATION Transducer T1-40 serves for seismic measurement of the absolute
INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1
City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included
Tremco Fire Protection Systems Group Technical Bulletin
Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,
CIR. Index. Gexol. Standard CIR UL Listed Type TC-ER. Crush and Impact Resistant Without External Armoring. Arctic CIR UL Listed Type TC-ER-HL*
Gexol CIR Crush and Impact Resistant Without External Armoring Passes the same stringent crush and impact testing required by UL 2225 for Type MC-HL n Available in Standard and Arctic Grade Jackets n Highly
Residential Deck Safety, Construction, and Repair
Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the
60.12. Depend-O-Lok FxE Expansion Coupling. System No. Submitted By Spec Sect Para Location Date Approved Date. DEPEND-O-LOK FxE EXPANSION COUPLING
60.1 D-O-L FxE expansion couplings are a bolted, split-sleeve design that provides for expansion and contraction at the coupled joint. These couplings are furnished with restraint rings that, when affixed
e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN
e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN We create ideas with power! ELEKTROMETAL ENERGETYKA SA is a new Polish company providing solutions for electrical power engineering. Our services
Low Voltage Switchboards The Best Technical Solution for Your Ship
The Best Technical Solution for Your Ship Wärtsilä SAM Electronics Optimal Power Distribution The uninterrupted supply of power to systems and consumers onboard modern ships is an extremly important matter.
Storage Store the siding in a dry and ventilated area. Do not place it directly on the ground. Always cover the siding after a day s work.
Installation Guide Before you begin, take the time to read this entire guide to clearly understand the requirements and steps to follow for proper installation. Warning Do not install defective material.