Short Circuit Current Calculations



Similar documents
CHAPTER 2 EXAMPLES AND TABLES

Department of Labor and Industry Electrical Licensing

CONDUCTOR SHORT-CIRCUIT PROTECTION

Electrical Design Training Class Ampacity WSDOT Winter 2008 BZA

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

Guidelines on the Short Circuit Current Rating for Industrial Control Panels

Motor Circuit Protection Tables

Conductor Sizing and the National Electrical Code

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

Motor Protection Voltage Unbalance and Single-Phasing

Rule Fast Track Analysis for National Life Insurance Co.

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Voltage Drop (Single-Phase)

Radial Distribution Test Feeders

BRANCH CIRCUIT AND FEEDER REQUIREMENTS

misconceptions about arc-flash hazard assessments

Cable/Conduit Conversion

Low Voltage Transformer Through-Fault Protection: A System Approach

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

UL 508A Industrial Control Panels Power Distribution and Control. Lunch & Learn Training Eaton Corporation. All rights reserved.

Commercial/Industrial Electricity

Electrical Drawings - Table of Contents

101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer

BASIC NEC CODE RULES AND DESIGN PRACTICE

TRANSFORMERS. Unit 14 OBJECTIVES

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

Part 1 System Modeling & Studies for Existing Systems

The following table shows approximate percentage wise the

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

Buck - Boost Transformers

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

Secondary Unit Substations

Power System Analysis

Voltage Drop. Voltage Drop 1

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity

What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin?

Engineers Edge, LLC PDH & Professional Training

Engineering Series Ratings: Is It Practical?

Fault Characteristics in Electrical Equipment

Fusible Disconnect Switch

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

EARTHING SYSTEM CALCULATION

Mission Critical Data Center Systems

STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

Neutral Currents in Three Phase Wye Systems

Alternate Methods to Short Circuit Breaker Coordination

City of Leesburg, Florida I.T. Data Center APPENDIX A TOSHIBA UPS INFORMATION

A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS

Choosing the Best Solution for Reducing Arc Energy

Hyperlinks are Inactive

How To Choose A Transformer

Chapter 24. Three-Phase Voltage Generation

TOP 10 CHANGES 2013 CALIFORNIA ELECTRICAL CODE 2013 CALIFORNIA ENERGY CODE (ELECTRICAL)

History and Overview. Manual Motor Protectors & Combination Motor Controllers

Rotary Phase Converters

How Much Voltage Drop Is Acceptable?

Application of Four-Pole Circuit Breakers within Data Centers

TERMS AND CONDITIONS

Understanding Arc Flash

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer Electrical Hazards 2/18/2015. Shock.

SURGELOGIC TVSS Surge Protective Devices Enhance System Protection and Reduce Equipment Damage

Joslyn Clark Controls, Inc.

A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software

4.5 Transformer Connections

MOTOR PROTECTION AGAINST SINGLE-PHASING

Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings

Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26

MODEL 5060 USER S GUIDE ELECTRICALC PRO. Set. Stor. Rcl. Off. On/C #THHN #THW VD% Length. DEFuse. ParSz. kilo. WireSz. Grnd. HPth. Watts. Volts.

National Craft Assessment and Certification Program S P E C I F I C A T I O N S

Effective: September 10, 2006 Vermont Attachment 1 to Rule Public Service Board Page 1 of 6

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

Fuseology. Medium Voltage Fuses. Continuous Current-Carrying Capacity. General. Interrupting Rating. Additional Rules.

Requirements for Electrical Installations

City of Riverside Building & Safety Division Phone: (951)

Safety By Design. Strategies for Electrical Contractors

Ground Fault Protection on Ungrounded and High Resistance Grounded Systems

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope

SERVICE ENTRANCE - UNDERGROUND Single & Three Phase 200, & 320/400 Amp

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

Step Voltage Regulators

Transformer Calculations

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.

Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT

IRRIGATION PUMPING Table of Contents - Section 900

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services

7. Reactive energy compensation

THE STABILOY BRAND ADVANTAGE UNLOCKING THE SECRETS OF ALUMINUM A LOOK AT THE ADVANTAGES OF ALUMINUM ALLOY OVER COPPER

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS

Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331)

Transcription:

Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that a short circuit study and a selective coordination study be conducted. These sections include, among others: 0.9 Interrupting Rating 0.0 Component Protection 240. Conductor Protection 250.22 Equipment Grounding Conductor Protection Marked Short-Circuit Current Rating; - 230.82 (3) Meter Disconnect - 409.0 Industrial Control Panels - 440.4(B) Air Conditioning & Refrigeration Equipment - 670.3(A) Industrial Machinery Selective Coordination - 57.7 Health Care Facilities - Selective Coordination - 57.26 Essential Electrical Systems In Healthcare Systems - 620.62 Selective Coordination for Elevator Circuits - 700.27 Emergency Systems - 70.8 Legally Required Standby Systems Compliance with these code sections can best be accomplished by conducting a short circuit study as a start to the analysis. The protection for an electrical system should not only be safe under all service conditions but, to insure continuity of service, it should be selectively coordinated as well. A coordinated system is one where only the faulted circuit is isolated without disturbing any other part of the system. Once the short circuit levels are determined, the engineer can specify proper interrupting rating requirements, selectively coordinate the system and provide component protection. See the various sections of this book for further information on each topic. Low voltage fuses have their interrupting rating expressed in terms of the symmetrical component of short-circuit current. They are given an RMS symmetrical interrupting rating at a specific power factor. This means that the fuse can interrupt the asymmetrical current associated with this rating. Thus only the symmetrical component of short-circuit current need be considered to determine the necessary interrupting rating of a low voltage fuse. For listed low voltage fuses, interrupting rating equals its interrupting capacity. Low voltage molded case circuit breakers also have their interrupting rating expressed in terms of RMS symmetrical amps at a specific power factor. However, it is necessary to determine a molded case circuit breaker s interrupting capacity in order to safely apply it. See the section Interrupting Rating vs. Interrupting Capacity in this book. 0.6 now requires arc-flash hazard warning labeling on certain equipment. A flash hazard analysis is required before a worker approaches electrical parts that have not been put into a safe work condition. To determine the incident energy and flash protection boundary for a flash hazard analysis the short-circuit current is typically the first step. General Comments on Short Circuit Calculations Sources of short-circuit current that are normally taken under consideration include: - Utility Generation - Local Generation - Synchronous Motors - Induction Motors - Alternate Power Sources Short circuit calculations should be done at all critical points in the system. These would include: - Service Entrance - Transfer Switches - Panel Boards - Load Centers - Motor Control Centers - Disconnects - Motor Starters - Motor Starters Normally, short circuit studies involve calculating a bolted 3-phase fault condition. This can be characterized as all 3-phases bolted together to create a zero impedance connection. This establishes a worst case (highest current) condition that results in maximum three phase thermal and mechanical stress in the system. From this calculation, other types of fault conditions can be approximated. This worst case condition should be used for interrupting rating, component protection and selective coordination. However, in doing an arc-flash hazard analysis it is recommended to do the arcflash hazard analysis at the highest bolted 3 phase short circuit condition and at the minimum bolted three-phase short circuit condition. There are several variables in a distribution system that affect calculated bolted 3-phase short-circuit currents. It is important to select the variable values applicable for the specific application analysis. In the Point-to-Point method presented in this section there are several adjustment factors given in Notes and footnotes that can be applied that will affect the outcomes. The variables are utility source short circuit capabilities, motor contribution, transformer percent impedance tolerance, and voltage variance. In most situations, the utility source(s) or on-site energy sources, such as on-site generation, are the major short-circuit current contributors. In the Point-to-Point method presented in the next few pages, the steps and example assume an infinite available short-circuit current from the utility source. Generally this is a good assumption for highest worst case conditions and since the property owner has no control over the utility system and future utility changes. And in many cases a large increase in the utility available does not increase the short-circuit currents a great deal for a building system on the secondary of the service transformer. However, there are cases where the actual utility medium voltage available provides a more accurate short circuit assessment (minimum bolted short-circuit current conditions) that may be desired to assess the arcflash hazard. When there are motors in the system, motor short circuit contribution is also a very important factor that must be included in any short-circuit current analysis. When a short circuit occurs, motor contribution adds to the magnitude of the short-circuit current; running motors contribute 4 to 6 times their normal full load current. In addition, series rated combinations can not be used in specific situations due to motor short circuit contributions (see the section on Series Ratings in this book). For capacitor discharge currents, which are of short time duration, certain IEEE (Institute of Electrical and Electronic Engineers) publications detail how to calculate these currents if they are substantial. Procedures and Methods To determine the fault current at any point in the system, first draw a one-line diagram showing all of the sources of short-circuit current feeding into the fault, as well as the impedances of the circuit components. To begin the study, the system components, including those of the utility system, are represented as impedances in the diagram. The impedance tables include three-phase and single-phase transformers, cable, and busway. These tables can be used if information from the manufacturers is not readily available. It must be understood that short circuit calculations are performed without current-limiting devices in the system. Calculations are done as though these devices are replaced with copper bars, to determine the maximum available short-circuit current. This is necessary to project how the system and the currentlimiting devices will perform. Also, multiple current-limiting devices do not operate in series to produce a compounding current-limiting effect. The downstream, or load side, fuse will operate alone under a short circuit condition if properly coordinated. The application of the point-to-point method permits the determination of available short-circuit currents with a reasonable degree of accuracy at various points for either 3Ø or Ø electrical distribution systems. This method can assume unlimited primary short-circuit current (infinite bus) or it can be used with limited primary available current. 92 2005 Cooper Bussmann

Three-Phase Short Circuits Basic Point-to-Point Calculation Procedure Step. Determine the transformer full load amps (F.L.A.) from either the nameplate, the following formulas or Table : Step 2. Find the transformer multiplier. See Notes and 2 3Ø Faults Multiplier = Ø Line-to-Line (L-L) Faults See Note 5 & Table 3 00 *% Z transformer * Note. Get %Z from nameplate or Table. Transformer impedance (Z) helps to determine what the short circuit current will be at the transformer secondary. Transformer impedance is determined as follows: The transformer secondary is short circuited. Voltage is increased on the primary until full load current flows in the secondary. This applied voltage divided by the rated primary voltage (times 00) is the impedance of the transformer. Example: For a 480 Volt rated primary, if 9.6 volts causes secondary full load current to flow through the shorted secondary, the transformer impedance is 9.6/480 =.02 = 2%Z. * Note 2. In addition, UL (Std. 56) listed transformers 25kVA and larger have a ± 0% impedance tolerance. Short circuit amps can be affected by this tolerance. Therefore, for high end worst case, multiply %Z by.9. For low end of worst case, multiply %Z by.. Transformers constructed to ANSI standards have a ±7.5% impedance tolerance (twowinding construction). Step 3. Determine by formula or Table the transformer letthrough short-circuit current. See Notes 3 and 4. Note 3. Utility voltages may vary ±0% for power and ±5.8% for 20 Volt lighting services. Therefore, for highest short circuit conditions, multiply values as calculated in step 3 by. or.058 respectively. To find the lower end worst case, multiply results in step 3 by.9 or.942 respectively. Note 4. Motor short circuit contribution, if significant, may be added at all fault locations throughout the system. A practical estimate of motor short circuit contribution is to multiply the total motor current in amps by 4. Values of 4 to 6 are commonly accepted. Step 4. Calculate the "f" factor..732 x L x I3Ø f = C x n x E L-L 2 x L x I f = L-L C x n x EL-L Ø Line-to-Neutral (L-N) Faults 2 x L x See Note 5 & Table 3 I f = L-N C x n x EL-N Where: L = length (feet) of conductor to the fault. C = constant from Table 4 of C values for conductors and Table 5 of C values for busway. n = Number of conductors per phase (adjusts C value for parallel runs) I = Available short-circuit current in amperes at beginning of circuit. E = Voltage of circuit. Note 5. The L-N fault current is higher than the L-L fault current at the secondary terminals of a single-phase center-tapped transformer. The short-circuit current available (I) for this case in Step 4 should be adjusted at the transformer terminals as follows: At L-N center tapped transformer terminals, I L-N =.5 x I L-L at Transformer Terminals. At some distance from the terminals, depending upon wire size, the L-N fault current is lower than the L-L fault current. The.5 multiplier is an approximation and will theoretically vary from.33 to.67. These figures are based on change in turns ratio between primary and secondary, infinite source available, zero feet from terminals of transformer, and.2 x %X and.5 x %R for L-N vs. L-L resistance and reactance values. Begin L-N calculations at transformer secondary terminals, then proceed point-to-point. Step 5. Calculate "M" (multiplier) or take from Table 2. Step 6. M = + f Calculate the available short circuit symmetrical RMS current at the point of fault. Add motor contribution, if applicable. I S.C. sym. RMS = I S.C. x M Step 6A. Motor short circuit contribution, if significant, may be added at all fault locations throughout the system. A practical estimate of motor short circuit contribution is to multiply the total motor current in amps by 4. Values of 4 to 6 are commonly accepted. Calculation of Short-Circuit Currents at Second Transformer in System Use the following procedure to calculate the level of fault current at the secondary of a second, downstream transformer in a system when the level of fault current at the transformer primary is known. H.V. UTILITY CONNECTION I S.C. primary MAIN TRANSFORMER I S.C. primary I S.C. secondary 3Ø Transformer (I S.C. primary and f = I S.C. primary x V primary x.73 (%Z) I S.C. secondary are 00,000 x V transformer 3Ø fault values) Ø Transformer (I S.C. primary and I S.C. secondary are Ø fault values: I S.C. secondary is L-L) f = IS.C. primary x V primary x (%Z) 00,000 x V transformer M = + f I S.C. secondary = V primary x M x I S.C. primary V secondary I S.C. secondary Procedure for Second Transformer in System Step A. Calculate the "f" factor (I S.C. primary known) Step B. Step C. Calculate "M" (multiplier). Calculate the short-circuit current at the secondary of the transformer. (See Note under Step 3 of "Basic Point-to- Point Calculation Procedure".) 2005 Cooper Bussmann 93

Three-Phase Short Circuits System A Available Utility Infinite Assumption 500 KVA Transformer, 480V, 3Ø, 3.5%Z, 3.45%X,.56%R I f.l. =804A 25' - 500kcmil 6 Per Phase Service Entrance Conductors in Steel Conduit 2000A Switch One-Line Diagram Fault X Step. I f.l. = 500 x 000 = 804A 480 x.732 Step 2. Multiplier = 00 = 28.57 3.5 Step 3. I S.C. =804 x 28.57 = 5,540A I S.C. motor contrib = 4 x,804* = 7,26A I total S.C. sym RMS = 5,504 + 7,26 = 58,720A Fault X2 Step 4. Use I S.C.sym RMS @ Fault X to calculate f f =.732 x 50 x 49,803 =.4050 22,85 x 480 Step 5. M = =.77 +.4050 Step 6. I S.C.sym RMS = 49,803 x.77 = 35,445A I sym motor contrib = 4 x,804* = 7,26A KRP-C-2000SP Fuse Step 4. f =.732 x 25 x 5,540 = 0.0349 22,85 x 6 x 480 I total S.C. sym RMS = 35,445 + 7,26 = 42,66A (fault X 2 ) Fault X 400A Switch Step 5. M = =.9663 +.0349 LPS-RK-400SP Fuse Step 6. I S.C.sym RMS = 5,540 x.9663 = 49,803A 50' - 500 kcmil Feeder Cable in Steel Conduit I S.C.motor contrib = 4 x,804* = 7,26A I totals.c. sym RMS = 49,803 + 7,26 = 57,09A (fault X) Fault X 2 Motor Contribution M 2 *Assumes 00% motor load. If 50% of this load was from motors, I S.C. motor contrib. = 4 x,804 x.5 = 3608A System B Available Utility One-Line Diagram Fault X Infinite Assumption Step. 000 KVA Transformer, 480V, 3Ø, 3.5%Z I f.l.= 203A I f.l. = 000 x 000 = 203A 480 x.732 Step 2. Multiplier = 00 = 28.57 3.5 Fault X2 Step 4. f =.732 x 20 x 33,25 =.049 2 x,424 x 480 Step 5. M = =.905 +.049 30-500 kcmil 4 Per Phase Copper in PVC Conduit 600A Switch KRP-C-500SP Fuse Fault X 400A Switch Step 3. I S.C. = 203 x 28.57 = 34,370A Step 4. f =.732 x 30 x 34,370 =.0348 26,706 x 4 x 480 Step 5. M = =.9664 +.0348 Step 6. I S.C.sym RMS = 33,25 x.905 = 30,059A Fault X3 Step A. f = 30,059 x 480 x.732 x.2 =.333 00,000 x 225 Step 6. I S.C.sym RMS = 34,370 x.9664 = 33,25A Step B. M = =.4286 +.333 LPS-RK-350SP Fuse Step C. I S.C. sym RMS = 480 x.4286 x 30,059 = 29,73A 208 20-2/0 2 Per Phase Copper in PVC Conduit Fault X 2 2 225 KVA transformer, 208V, 3Ø.2%Z Fault X 3 3 94 2005 Cooper Bussmann

Single-Phase Short Circuits Short circuit calculations on a single-phase center tapped transformer system require a slightly different procedure than 3Ø faults on 3Ø systems.. It is necessary that the proper impedance be used to represent the primary system. For 3Ø fault calculations, a single primary conductor impedance is only considered from the source to the transformer connection. This is compensated for in the 3Ø short circuit formula by multiplying the single conductor or single-phase impedance by.73. However, for single-phase faults, a primary conductor impedance is considered from the source to the transformer and back to the source. This is compensated in the calculations by multiplying the 3Ø primary source impedance by two. 2. The impedance of the center-tapped transformer must be adjusted for the halfwinding (generally line-to-neutral) fault condition. The diagram at the right illustrates that during line-to-neutral faults, the full primary winding is involved but, only the half-winding on the secondary is involved. Therefore, the actual transformer reactance and resistance of the half-winding condition is different than the actual transformer reactance and resistance of the full winding condition. Thus, adjustment to the %X and %R must be made when considering line-to-neutral faults. The adjustment multipliers generally used for this condition are as follows:.5 times full winding %R on full winding basis..2 times full winding %X on full winding basis. Note: %R and %X multipliers given in Impedance Data for Single Phase Transformers Table may be used, however, calculations must be adjusted to indicate transformer kva/2. 3. The impedance of the cable and two-pole switches on the system must be considered both-ways since the current flows to the fault and then returns to the source. For instance, if a line-to-line fault occurs 50 feet from a transformer, then 00 feet of cable impedance must be included in the calculation. The calculations on the following pages illustrate Ø fault calculations on a singlephase transformer system. Both line-to-line and line-to-neutral faults are considered. Note in these examples: a. The multiplier of 2 for some electrical components to account for the single-phase fault current flow, b. The half-winding transformer %X and %R multipliers for the line-to-neutral fault situation, and c. The kva and voltage bases used in the per-unit calculations. Short Circuit Primary Secondary L 2 N L N 50 Feet Primary Secondary Short Circuit A B C L Short Circuit L 2 2005 Cooper Bussmann 95

Single-Phase Short Circuits 96 2005 Cooper Bussmann

Impedance & Reactance Data Transformers Table. Short-Circuit Currents Available from Various Size Transformers (Based upon actual field nameplate data or from utility transformer worst case impedance) Voltage Full % Short and Load Impedance Circuit Phase kva Amps (Nameplate) Amps 25 04.5 275 37.5 56.5 808 20/240 50 208.5 23706 ph.* 75 33.5 34639 00 47.6 42472 67 696.6 66644 45 25.0 3879 75 208.0 2332 2.5 32. 3259 50 46.07 43237 20/208 225 625.2 6960 3 ph.** 300 833. 83357 500 388.24 24364 750 2082 3.50 6609 000 2776 3.50 882 500 464 3.50 328 2000 5552 4.00 542 2500 6940 4.00 92764 75 90.00 0035 2.5 35.00 5053 50 8.20 6726 225 27.20 25088 300 36.20 3345 277/480 500 602.30 5463 3 ph.** 750 903 3.50 28672 000 204 3.50 38230 500 806 3.50 57345 2000 2408 4.00 66902 2500 30 4.00 83628 * Single-phase values are L-N values at transformer terminals. These figures are based on change in turns ratio between primary and secondary, 00,000 KVA primary, zero feet from terminals of transformer,.2 (%X) and.5 (%R) multipliers for L-N vs. L-L reactance and resistance values and transformer X/R ratio = 3. ** Three-phase short-circuit currents based on infinite primary. UL listed transformers 25 KVA or greater have a ±0% impedance toler - ance. Short-circuit amps shown in Table reflect 0% condition. Transformers constructed to ANSI standards have a ±7.5% impedance tolerance (two-winding construction). Fluctuations in system voltage will affect the available short-circuit current. For example, a 0% increase in system voltage will result in a 0% greater available short-circuit currents than as shown in Table. Impedance Data for Single-Phase Transformers Suggested Normal Range Impedance Multipliers** X/R Ratio of Percent For Line-to-Neutral kva for Impedance (%Z)* Faults Ø Calculation for %X for %R 25.0..2 6.0 0.6 0.75 37.5.4.2 6.5 0.6 0.75 50.0.6.2 6.4 0.6 0.75 75.0.8.2 6.6 0.6 0.75 00.0 2.0.3 5.7 0.6 0.75 67.0 2.5.4 6..0 0.75 250.0 3.6.9 6.8.0 0.75 333.0 4.7 2.4 6.0.0 0.75 500.0 5.5 2.2 5.4.0 0.75 * National standards do not specify %Z for single-phase transformers. Consult manufacturer for values to use in calculation. ** Based on rated current of the winding (one half nameplate kva divided by secondary line-to-neutral voltage). Note: UL Listed transformers 25 kva and greater have a ± 0% tolerance on their impedance nameplate. This table has been reprinted from IEEE Std 242-986 (R99), IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems, Copyright 986 by the Institute of Electrical and Electronics Engineers, Inc. with the permission of the IEEE Standards Department.. Impedance Data for Single-Phase and Three-Phase Transformers- Supplement kva Suggested Ø 3Ø %Z X/R Ratio for Calculation 0.2. 5.3. 75..5 50.07.5 225.2.5 300..5 333.9 4.7 500.24.5 500 2. 5.5 These represent actual transformer nameplate ratings taken from field installations. Note: UL Listed transformers 25kVA and greater have a ±0% tolerance on their impedance nameplate. 2005 Cooper Bussmann 97

Conductors & Busways "C" Values Table 4. C Values for Conductors Copper AWG Three Single Conductors Three-Conductor Cable or Conduit Conduit kcmil Steel Nonmagnetic Steel Nonmagnetic 600V 5kV 5kV 600V 5kV 5kV 600V 5kV 5kV 600V 5kV 5kV 4 389 - - 389 - - 389 - - 389 - - 2 67 - - 67 - - 67 - - 67 - - 0 98 - - 982 - - 982 - - 982 - - 8 557 55-559 555-559 557-560 558-6 2425 2406 2389 2430 248 2407 243 2425 245 2433 2428 242 4 3806 375 3696 3826 3789 3753 3830 382 3779 3838 3823 3798 3 4774 4674 4577 48 4745 4679 4820 4785 4726 4833 4803 4762 2 5907 5736 5574 6044 5926 5809 5989 5930 5828 6087 6023 5958 7293 7029 6759 7493 7307 709 7454 7365 789 7579 7507 7364 /0 8925 8544 7973 937 9034 8590 920 9086 8708 9473 9373 9053 2/0 0755 0062 9390 424 0878 039 245 045 0500 703 529 053 3/0 2844 804 022 3923 3048 2360 3656 3333 263 440 49 3462 4/0 5082 3606 2543 6673 535 4347 6392 5890 483 7483 7020 603 250 6483 4925 3644 8594 72 5866 83 785 6466 9779 9352 800 300 877 6293 4769 20868 8975 7409 2067 20052 839 22525 2938 2063 350 9704 7385 5678 22737 20526 8672 22646 294 982 24904 2426 2982 400 20566 8235 6366 24297 2786 973 24253 23372 2042 2696 26044 2358 500 2285 972 7492 26706 23277 2330 26980 25449 2326 30096 2872 2596 600 22965 20567 7962 28033 25204 22097 28752 27975 24897 3254 3258 27766 750 2437 2387 8889 29735 26453 23408 305 30024 26933 34605 3335 29735,000 25278 22539 9923 349 28083 24887 33864 32689 29320 3797 35749 3959 Aluminum 4 237 - - 237 - - 237 - - 237 - - 2 376 - - 376 - - 376 - - 376 - - 0 599 - - 599 - - 599 - - 599 - - 8 95 950-952 95-952 95-952 952-6 48 476 472 482 479 476 482 480 478 482 48 479 4 2346 2333 239 2350 2342 2333 235 2347 2339 2353 2350 2344 3 2952 2928 2904 296 2945 2929 2963 2955 294 2966 2959 2949 2 373 3670 3626 3730 3702 3673 3734 379 3693 3740 3725 3709 4645 4575 4498 4678 4632 4580 4686 4664 468 4699 4682 4646 /0 5777 5670 5493 5838 5766 5646 5852 5820 577 5876 5852 577 2/0 787 6968 6733 730 753 6986 7327 727 709 7373 7329 7202 3/0 8826 8467 863 90 885 8627 9077 898 875 9243 964 8977 4/0 074 067 9700 74 0749 0387 85 022 0642 409 277 0969 250 222 460 0849 2862 2343 847 2797 2636 25 3236 306 266 300 390 3009 293 4923 483 3492 497 4698 3973 5495 5300 4659 350 5484 4280 3288 683 5858 4955 6795 6490 554 7635 7352 650 400 667 5355 488 8506 732 6234 8462 8064 692 9588 9244 854 500 8756 6828 5657 239 9503 835 2395 20607 934 2308 2238 20978 600 20093 8428 6484 2345 278 9635 23633 2396 2349 25708 25244 23295 750 2766 9685 7686 25976 23702 2437 26432 25790 23750 29036 28262 25976,000 23478 2235 9006 28779 2609 23482 29865 29049 26608 32938 3920 2935 Note: These values are equal to one over the impedance per foot and based upon resistance and reactance values found in IEEE Std 24-990 (Gray Book), IEEE Recommended Practice for Electric Power Systems in Commerical Buildings & IEEE Std 242-986 (Buff Book), IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems. Where resistance and reactance values differ or are not available, the Buff Book values have been used. The values for reactance in determining the C Value at 5 KV & 5 KV are from the Gray Book only (Values for 4-0 AWG at 5 kv and 4-8 AWG at 5 kv are not available and values for 3 AWG have been approximated). Table 5. C Values for Busway Ampacity Busway Plug-In Feeder High Impedance Copper Aluminum Copper Aluminum Copper 225 28700 23000 8700 2000 400 38900 34700 23900 2300 600 4000 38300 36500 3300 800 4600 57500 49300 4400 000 69400 89300 62900 56200 5600 200 94300 9700 76900 69900 600 350 9000 04200 9000 84000 7500 600 29900 20500 0000 90900 9200 2000 42900 3500 34200 25000 20400 2500 43800 56300 80500 66700 2700 3000 44900 75400 20400 88700 23800 4000 277800 256400 Note: These values are equal to one over the impedance per foot for impedance in a survey of industry. 98 2005 Cooper Bussmann

Voltage Drop Calculations Ratings of Conductors and Tables to Determine Volt Loss With larger loads on new installations, it is extremely important to consider volt loss in mind, otherwise some very unsatisfactory problems are likely to be encountered. The actual conductor used must also meet the other sizing requirements such as full-load current, ambient temperature, number in a raceway, etc. How to Figure Volt Loss Multiply distance (length in feet of one wire) by the current (expressed in amps) by the figure shown in table for the kind of current and the size of wire to be used, by one over the number of conductors per phase. Then, put a decimal point in front of the last 6 digits you have the volt loss to be expected on that circuit. Example 6 AWG copper wire in 80 feet of iron conduit 3 phase, 40 amp load at 80% power factor. Multiply feet by amperes: 80 x 40 = 7200 Multiply this number by number from table for 6 AWG wire threephase at 80% power factor: 7200 x 745 = 5364000 Multiply by 5364000 x = 5364000 #/phase Place decimal point 6 places to left. This gives volt loss to be expected: 5.364V (For a 240V circuit the % voltage drop is 5.364 x 00 or 2.23%). 240 These Tables take into consideration reactance on AC circuits as well as resistance of the wire. Remember on short runs to check to see that the size and type of wire indicated has sufficient ampere capacity. How to Select Size of Wire Multiply distance (length in feet of one wire) by the current (expressed in amps), by one over the number of conductors per phase. Divide that figure into the permissible volt loss multiplied by,000,000. Look under the column applying to the type of current and power factor for the figure nearest, but not above your result you have the size of wire needed. Example Copper in 80 feet of steel conduit 3 phase, 40 amp Ioad at 80% power factor Volt loss from local code equals 5.5 volts. Multiply feet by amperes by 80 x 40 x = 7200. #/phase Divide permissible volt loss multiplied by,000,000 by this number: 5.5 x,000,000 = 764. 7200 Select number from Table, three-phase at 80% power factor, that is nearest but not greater than 764. This number is 745 which indicates the size of wire needed: 6 AWG. Line-to-Neutral For line to neutral voltage drop on a 3 phase system, divide the three phase value by.73. For line to neutral voltage drop on a single phase system, divide single phase value by 2. Open Wiring The volt loss for open wiring installations depends on the separation between conductors. The volt loss is approximately equal to that for conductors in nonmagnetic conduit. 30.5 offers a method to calculate conductor ampacity. Installation in Conduit, Cable or Raceway NEC Tables 30.6 through 30.9 give allowable ampacities (currentcarrying capacities) for not more than three conductors in a conduit, cable, or raceway. Where the number of conductors exceeds three the allowable ampacity of each conductor must be reduced as shown in the following tables: Installation in Conduit, Cable or Raceway per 30.5(B)(2)(a) The Number of Percentage of Values Conductors In One In Tables 30.6 And Conduit, Raceway 30.8 Or Cable 4 to 6 80% 7 to 9 70% 0 to 20 50% 2 to 30 45% 3 to 40 40% 4 and over 35% Conditions Causing Higher Volt Loss The voltage loss is increased when a conductor is operated at a higher temperature because the resistance increases. If type RH, RHW, THW, or THWN wire (75 C wire) is loaded to near its full rating, or if room temperature is 5 C higher than normal, add the following percentages to get the volt loss. Conditions Causing Higher Volt Loss Direct Single Or Three Phase Power Factor Wire Size Current 00% 90% 80% 70% 60% 4 to 4 AWG 5.0% 5.0% 4.8% 4.7% 4.7% 4.6% 2 to 3/0 AWG 5.0% 5.0% 4.2% 3.8% 3 5% 3.3% 4/0 AWG to 500 kcmil 5.0% 5.0% 3.% 2.6% 2.4% 2.0% 600 kcmil to 000 kcmil 5.0% 5.0% 2.5% 2.2%.6%.3% If type RHH, THHN or XHHW wire (90 C. wire) is loaded to near its full rating or if room temperature is 30 C higher than normal, add twice the above percentages to get the volt loss. Room Temperature Affects Ratings The ampacities (carrying capacities) of conductors are based on a room temperature of 86 F or 30 C. If room temperature is higher, the ampacities are reduced by using the following multipliers; (for 0-2000 volt, insulated conductors not more than 3 conductors in raceway or direct buried, Table 30.6). Room Temperature Affects Ratings Room Ampacity Multiplier Temperature TW THW, THWN THHN, XHHW* C F (60 C Wire) (75 C Wire) (90 C Wire) 3-35 87-95.9.94.96 36-40 96-04.82.88.9 4-45 05-3.7.82.87 46-50 4-22.58.75.82 5-55 23-3.4.67.76 56-60 32-40.58.7 6-70 4-58.33.58 7-80 59-76.4 2005 Cooper Bussmann 99

Voltage Drop Calculations Copper Conductors Ratings & Volt Loss Conduit Wire Ampacity Direct Volt Loss (See explanation prior page.) Size Type Type Type Current Three-Phase Single-Phase T, TW RH, RHH, (60 Cycle, Lagging Power Factor.) (60 Cycle, Lagging Power Factor.) (60 C THWN, THHN, 00% 90% 80% 70% 60% 00% 90% 80% 70% 60% Wire) RHW, XHHW THW (90 C (75 C Wire) Wire) Steel 4 20* 20* 25* 640 5369 4887 437 3848 3322 6200 5643 5047 4444 3836 Conduit 2 25* 25* 30* 3860 3464 369 284 2508 272 4000 3659 328 2897 2508 0 30 35* 40* 2420 2078 98 728 532 334 2400 224 995 769 540 8 40 50 55 528 350 264 48 026 900 560 460 326 84 040 6 55 65 75 982 848 82 745 673 597 980 937 860 777 690 4 70 85 95 66 536 528 49 450 405 620 60 568 59 468 3 85 00 0 490 433 434 407 376 34 500 50 470 434 394 2 95 5 30 388 346 354 336 32 286 400 409 388 36 33 0 30 50 308 277 292 280 264 245 320 337 324 305 283 0 25 50 70 244 207 228 223 23 200 240 263 258 246 232 00 45 75 95 93 73 96 94 88 78 200 227 224 27 206 000 65 200 225 53 36 62 63 60 54 58 87 88 84 78 0000 95 230 260 22 09 36 40 39 36 26 57 62 6 57 250 25 255 290 03 93 23 28 29 28 08 42 48 49 48 300 240 285 320 86 77 08 5 7 7 90 25 33 35 35 350 260 30 350 73 67 98 06 09 09 78 3 22 26 26 400 280 335 380 64 60 9 99 03 04 70 05 4 8 20 500 320 380 430 52 50 8 90 94 96 58 94 04 09 600 335 420 475 43 43 75 84 89 92 50 86 97 03 06 750 400 475 535 34 36 68 78 84 88 42 79 9 97 02 000 455 545 65 26 3 62 72 78 82 36 72 84 90 95 Non- 4 20* 20* 25* 640 5369 4876 4355 3830 330 6200 5630 5029 4422 382 Magnetic 2 25* 25* 30* 3464 3464 358 2827 249 253 4000 3647 3264 2877 2486 Conduit 0 30 35* 40* 2420 2078 908 74 56 36 2400 2203 980 75 520 (Lead 8 40 50 55 528 350 255 34 00 882 560 449 30 66 09 Covered 6 55 65 75 982 848 802 73 657 579 980 926 845 758 669 Cables or 4 70 85 95 66 536 59 479 435 388 620 599 553 502 448 Installation 3 85 00 0 470 433 425 395 36 324 500 490 456 47 375 in Fibre or 2 95 5 30 388 329 330 30 286 259 380 38 358 330 300 Other 0 30 50 308 259 268 255 238 29 300 30 295 275 253 Non- 0 25 50 70 244 207 220 22 99 85 240 254 244 230 24 Magnetic 00 45 75 95 93 73 88 83 74 63 200 27 2 20 88 Conduit, 000 65 200 225 53 33 5 50 45 38 54 75 73 67 59 Etc.) 0000 95 230 260 22 07 27 28 25 2 24 47 48 45 40 250 25 255 290 03 90 2 4 3 0 04 29 32 3 28 300 240 285 320 86 76 99 03 04 02 88 4 9 20 8 350 260 30 350 73 65 89 94 95 94 76 03 08 0 09 400 280 335 380 64 57 8 87 89 89 66 94 00 03 03 500 320 380 430 52 46 7 77 80 82 54 82 90 93 94 600 335 420 475 43 39 65 72 76 77 46 75 83 87 90 750 400 475 535 34 32 58 65 70 72 38 67 76 80 83 000 455 545 65 26 25 5 59 63 66 30 59 68 73 77 * The overcurrent protection for conductor types marked with an (*) shall not exceed 5 amperes for 4 AWG, 20 amperes for 2 AWG, and 30 amperes for 0 AWG copper; or 5 amperes for 2 AWG and 25 amperes for 0 AWG aluminum and copper-clad aluminum after any correction factors for ambient temperature and number of conductors have been applied. Figures are L-L for both single-phase and three-phase. Three-phase figures are average for the three-phase. 200 2005 Cooper Bussmann

Voltage Drop Calculations Aluminum Conductors Ratings & Volt Loss Conduit Wire Ampacity Direct Volt Loss (See explanation two pages prior.) Size Type Type Type Current Three-Phase Single-Phase T, TW RH, RHH, (60 Cycle, Lagging Power Factor.) (60 Cycle, Lagging Power Factor.) (60 C THWN, THHN, 00% 90% 80% 70% 60% 00% 90% 80% 70% 60% Wire) RHW, XHHW THW (90 C (75 C Wire) Wire) Steel 2 20* 20* 25* 6360 5542 5039 4504 3963 349 6400 589 520 4577 3948 Conduit 0 25 30* 35* 4000 3464 365 2836 2502 265 4000 3654 3275 2889 2500 8 30 40 45 2520 225 2075 868 656 44 2600 2396 258 92 663 6 40 50 60 66 402 30 88 06 930 620 53 372 225 074 4 55 65 75 06 883 840 769 692 63 020 970 888 799 708 3 65 75 85 796 692 668 65 557 497 800 77 70 644 574 2 75 90 00 638 554 54 502 458 4 640 625 580 529 475 85 00 5 506 433 432 405 373 338 500 499 468 43 39 0 00 20 35 402 346 353 334 30 284 400 407 386 358 328 00 5 35 50 38 277 290 277 260 24 320 335 320 30 278 000 30 55 75 259 225 24 234 22 207 260 279 270 256 239 0000 50 80 205 200 73 94 9 84 74 200 224 22 22 20 250 70 205 230 69 48 73 73 68 6 72 200 200 94 86 300 90 230 255 4 24 50 52 50 45 44 74 76 73 68 350 20 250 280 2 09 35 39 38 34 26 56 60 59 55 400 225 270 305 06 95 22 27 27 25 0 4 46 46 44 500 260 30 350 85 77 06 2 3 3 90 22 29 3 30 600 285 340 385 7 65 95 02 05 06 76 0 8 2 22 750 320 385 435 56 53 84 92 96 98 62 97 07 4 000 375 445 500 42 43 73 82 87 89 50 85 95 00 03 Non- 2 20* 20* 25* 6360 5542 5029 4490 3946 3400 6400 5807 584 4557 3926 Magnetic 0 25 30* 35* 4000 3464 355 2823 2486 247 4000 3643 3260 287 2480 Conduit 8 30 40 45 2520 225 2065 855 640 423 2600 2385 242 894 643 (Lead 6 40 50 60 66 402 30 75 045 92 620 502 357 206 053 Covered 4 55 65 75 06 883 83 756 677 596 020 959 873 782 668 Cables or 3 65 75 85 796 692 659 603 543 480 800 760 696 627 555 Installation 2 75 90 00 638 554 532 490 443 394 640 65 566 52 456 in Fibre or 85 00 5 506 433 424 394 360 323 500 490 455 45 373 Other 0 00 20 35 402 346 344 322 296 268 400 398 372 342 30 Non- 00 5 35 50 38 277 28 266 247 225 320 325 307 285 260 Magnetic 000 30 55 75 252 225 234 223 209 93 260 270 258 24 223 Conduit, 0000 50 80 205 200 73 86 8 7 60 200 25 209 98 85 Etc.) 250 70 205 230 69 47 63 60 53 45 70 88 85 77 67 300 90 230 255 4 22 4 40 36 30 42 63 62 57 50 350 20 250 280 2 05 25 25 23 8 22 44 45 42 37 400 225 270 305 06 93 4 6 4 08 32 34 32 28 500 260 30 350 85 74 96 00 00 98 86 5 5 4 600 285 340 385 7 62 85 90 9 9 72 98 04 06 05 750 320 385 435 56 50 73 79 82 82 58 85 92 94 95 000 375 445 500 42 39 63 70 73 75 46 73 8 85 86 * The overcurrent protection for conductor types marked with an (*) shall not exceed 5 amperes for 4 AWG, 20 amperes for 2 AWG, and 30 amperes for 0 AWG copper; or 5 amperes for 2 AWG and 25 amperes for 0 AWG aluminum and copper-clad aluminum after any correction factors for ambient temperature and number of conductors have been applied. Figures are L-L for both single-phase and three-phase. Three-phase figures are average for the three-phase. 2005 Cooper Bussmann 20