1. Indoor Environmental Quality (IEQ)

Similar documents
HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

How To Design A Building In New Delhi

THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM

IEQ-15 Air Distribution System

AG-TQS-IAQ-00 March 4, Application Guide. TQS with IAQ Inlet

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program

ASTACEA4 Inspect complex/central air conditioning systems

Indoor Air Quality Issues for Hotels

HVAC Systems: Overview

Mechanical and Natural Ventilation

Direct Fresh Air Free Cooling of Data Centres

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

INDOOR AIR QUALITY INTRODUCTION WHAT ARE THE SYMPTOMS OF SICK BUILDING SYNDROME? WHEN DID POOR INDOOR AIR QUALITY BECOME A PROBLEM?

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

HVAC Processes. Lecture 7

VENTILATION CHAPTER 4

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

LOCATING AIR INTAKES AND EXHAUSTS

Radford University. Indoor Air Quality Management Plan

Glossary of HVAC Terms

Information paper 20. Prepared by: David Clark. book:

VENTILATION CHAPTER 4

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation The Building Regulations 2010

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

CHAPTER 5 Energy Efficient HVAC Design

IEQ Management Plan. Denver Museum of Nature and Science ECF Addition

Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP

Venice Library Humidity Study. for Williams Building Diagnostics, LLC th Street West Bradenton, FL Report April 13, 2015

Specification. Indoor Air Quality Management

Camfil. Technical Services Bulletin Tools for Schools Filtration for Improved Indoor Air Quality

Indoor Air Quality- What You Need to Know

VENTILATION CHAPTER 4

There are several types of air cleaning devices available, each designed to remove certain types of pollutants.

The Finnish Classification of Indoor Environment and Material Emissions

PEOSH. Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview. Eric Weren, MSIH

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

CHAPTER 4 VENTILATION

CHAPTER 4 VENTILATION

LEED Breadth. Introduction

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone.

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

Glossary of Heating, Ventilation and Air Conditioning Terms

Lesson 36 Selection Of Air Conditioning Systems

BPI Air Conditioning & Heat Pump Professional Training Sample Slides ( ) Agenda

HVAC Basic Science - System Capacity

Integrating Kitchen Exhaust Systems with Building HVAC

LG Electronics AE Company, Commercial Air Conditioning

Energy Efficiency in Industrial HVAC Systems

Educational Performance, Environmental Management, and Cleaning Effectiveness in School Environments

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

ENHANCED LABORATORY HVAC SYSTEM

Comfort Conditioning & Indoor Air Quality

Dedicated Outdoor Air Systems (D.O.A.S.)

Energy Efficiency HOSPITALITY.

Indoor air quality monitoring made easy

Preliminary Final Proposal

USER S INFORMATION MANUAL

INDOOR AIR QUALITY ASSESSMENT INCIDENT RESPONSE. Sgt. William H. Carney Memorial Academy 247 Elm Street New Bedford, Massachusetts

Fan Applications & System Guide

i n d o o r a i r q u a l i t y I AQ EN 13779:2007 European standard Camfil Farr clean air solutions

WHOLE-HOUSE VENTILATION SYSTEMS

"An Office Building Occupant's Guide to Indoor Air Quality"

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

Old Dominion University Mold Management Plan

BUILDING PERFORMANCE METRICS

IAQ - indoor ventilation Air contaminants Molds Requirements for growth Health effects Mold prevention - moisture EH&S mold checks & removal

Walkthrough Inspection Checklist

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

Ventilation Standard For Health Care Facilities

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air. Trevor Wende Vice President, Marketing Advantix Systems, Inc.

ECHO System for Basements

Key energy-efficient features of your new home

HVAC Checklist - Long Form

INDOOR AIR QUALITY ASSESSMENT

Causes and Prevention of Symptom Complaints in Office Buildings: Distilling the Experience of Indoor Environment Quality Investigators

CHAPTER 4 VENTILATION AIR SUPPLY

Hospital Application Guide. Cost-effective climate control for hospitals

What is LEED? Why pursue LEED accreditation? How does LEED accomplish these goals? Sustainable sites Water efficiency Energy and Atmosphere

Indoor Air Quality FILL YOUR HOME WITH AIR THAT IS AS CLEAN AS IT IS COMFORTABLE. READ ONLY

Pool Dehumidification Basics

Flexibility, Efficiency In San Antonio Arena

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

york air-conditioning products Residential & VRF News 2015

Answers to Your Questions from the Webinar

Case Studies: Infrared Heating in Industrial Applications

Ventilation Solutions Fresh Air Solutions for Ductless Heating & Cooling. fantech

Vectren Commercial/Industrial New Construction Incentive Application

VENTILATION RATES AND IAQ IN EUROPEAN STANDARDS AND NATIONAL REGULATIONS

A Breath of Poor Air: Inspecting Indoor Air Quality in the Classroom Ashley Schopieray

Liabilities of Vented Crawl Spaces And Their Impacts on Indoor Air Quality in Southeastern U.S. Homes

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air

DESERT RESEARCH INSTITUTE MOLD ASSESSMENT AND REMEDIATEION PROCEDURE

Building and Grounds Maintenance Checklist

SECTION HVAC AIR-DISTRIBUTION SYSTEM CLEANING

Ductless Mini-Split Systems. Comfort... where you need it, when you need it

Mold and Mildew Mold and mildew can be detected by sight, smell and touch.

Transcription:

INDOOR AIR QUALITY : INDOOR AIR QUALITY TO MAXIMISE PRODUCTIVITY By: Ir. Ng Yong Kong 26 TH March 2013 1. Indoor Environmental Quality (IEQ) Primary areas of concern in IEQ Air Quality and Ventilation Thermal Comfort: Design & Controllability of Systems Lighting and Visual Perception Acoustic and Noise Comfort 1

1. Indoor Environmental Quality (IEQ) More than just Indoor Air Quality (IAQ) HVAC system provides a comfortable environment for building occupants and contributes significantly to Indoor Health Environment IAQ Definitions by WHO - The physical and chemical nature of indoor air, as delivered to the breathing zone of building occupants, which produces a complete state of mental, physical and social well-being of the occupants, and not merely the absence of disease or infirmity. Good IAQ may be defined as air with no known contaminants at harmful concentrations. Common contaminants or pollutants include gaseous pollutants, such as carbon dioxide (produced by occupants and from combustion appliances), volatile organic compounds (released by carpet glue and other materials), odours and particulates. Good IAQ is essential to ensure the health and comfort of occupants. 2

Factors that increase our exposure to indoor air pollutants Reduced ventilation rates to conserve energy The use of synthetic building materials and furnishings The use of chemically formulated personal care products, pesticides, printing inks, and household cleaners. Pollutant Sources Indoor sources Combustion sources Building materials and furnishings Asbestos-containing insulation Household cleaning products HVAC systems Occupants and activities Outdoor sources Radon Pesticides Outdoor air pollution 3

Why do we air-condition our buildings? Control Temperature Control Humidity/Moisture Control Air Movement Control Air Quality Control Noise and glare Control the environment increase productivity and comfort Pollutants Types Sick building syndrome (SBS) Sick building syndrome (SBS) is a condition that may be experience by occupants of the buildings. The symptoms include headaches, eye strain and lung irritation. Usually the symptoms disappear when the affected person leaves the mal-functioning building and are of short duration. Sick building syndrome occurs in the buildings which may have a number of defects, including inadequate ventilation, low light levels and /or flickering light fittings, excessive odours, high ambient noise levels, lack of local controls and other factors. 4

Pollutants Types Sick building syndrome (SBS) Typically inadequate ventilation may be due to insufficient supplies of fresh air, excessive recirculation of air, poorly maintained air handling units (i.e. filters not replace when needed) or a poorly designed and / or installed ductwork system. Low light levels are the result of light fittings not being replaced, the wrong type of fitting being used, poor lighting controls and / or insufficient numbers of light fittings being installed. Poor levels of daylighting can have the same effect. Pollutants Types Sick building syndrome (SBS) Excessive odours may be due to a poorly designed/installed kitchen ventilation system and inadequate ventilation rates. High noise levels may be present due to the proximity of a space to and adjacent busy road and / or a plant room, insufficient sound insulation and lack of sound absorption materials used on wall and ceiling surfaces. No local controls may be available for an occupant not adjacent to an openable window or window or an adjustable thermostat (in many cases local thermostats may be disabled to prevent excessive adjustment by occupants). 5

Pollutants Types Sick building syndrome (SBS) The existence and extent of SBS may be established using questionnaires. Occupants are asked to score their satisfaction level for ambient variables including air temperature, perceived humidity level, local (fresh) air flow, noise, task lighting, glare and odours, and their ability to control some of these values. Pollutants Types Sick building syndrome (SBS) Analysis is then performed on the data to determine whether conditions are satisfactory for the occupants in each assessed area. Results should indicate what modifications might be required to achieve acceptable thermal, lighting and acoustic conditions. In relation to ventilation, this may include increased fresh air flow rates, adjustment of diffusers, more frequent maintenance of ventilation plant and improved occupant access to controls. 6

Pollutants Types External (outdoor) air pollution Poor outdoor air quality will have significant impact on indoor air quality. External pollutants include vehicle exhausts, discharges from combustion appliances, industrial process and power station exhausts. Fungal spores and pollen from vegetation may also cause air quality problems. Vehicle exhausts include CO, CO 2, NO x and SO 2, particulates (especially from diesel engines) and VOCs (e.g from petrol and oil). Pollutants Types External (outdoor) air pollution Ozone is generated by the action of sunlight on nitrous oxides (present in vehicle exhausts). Power station release the same pollutants to vehicles, but are usually located in rural or semi-rural areas, so the impact of their pollutants is much reduced. In urban areas, traffic is a significant contributor to external pollution, with additional pollutant emissions coming from building exhausts and industrial processes. 7

Outdoor Air Quality Motorists passed a highway toll gate covered by thick haze in Kuala Lumpur, Malaysia, Thursday, Aug. 11, 2005. The ominous haze that has shrouded parts of Southeast Asia this month is just one visible element of a much larger problem that is choking hundreds of thousands to death every year across the region, the World Health Organization said. (AP Photo/Andy Wong) What Are OA Intake Restrictions? Significant contaminated exhaust Noxious or dangerous exhaust Chimneys and flues Truck loading area Driveway, street Thoroughfare w/high traffic Garbage dumpster Cooling tower 8

RNC/NRNC - Air Cool Split Units It basically comprises an indoor unit with the evaporator and blower and an outdoor unit with the compressor, condenser coil and fan coupled with refrigeration piping. The indoor units is often known as Fan Coil Units ( FCUs )and the outdoor units known as Condensing Units.( C.U.) As a whole, they are known as the Air Cooled Split Units. (ACSUs) Air Cooled Split Units Warm air (recirculating) Fan Coil Unit Cool air Outdoor air Condensing Unit 9

Air Cooled Split Units (ACSUs) Inverter type Both indoor and outdoor units are housed in robust casings. The outdoor unit is basically the same construction for all the various types of indoor units. The difference lies in the type of indoor unit. Cassette Wall Mounted Floor Standing Ceiling Exposed Air Cooled Split Units Many Business Establishments are housed in Small Premises using ACSUs. Office Restaurant 10

ACSUs ( incld. Inverter type ) : Fresh Air Intake? The wall mounted, floor standing and under ceiling split system has no provision for intake of outdoor air and/or exhaust of stale room. air. Room air is just filtered and recirculated. Can you consider this for large buildings? 11

Ducted Systems Introducing OA IAQ Definitions Building-Related Illness (BRI) is a term referring to illness brought on by exposure to the building air, where symptoms of diagnosable illness are identified and can be directly attributed to environmental agents in the air. Eg. of BRI is Legionnaires Disease commonly found in aquatic environment. 12

CODES and STANDARDS FOR IAQ PERFORMNCE AND THERMAL COMFORT EQ1: Minimum IAQ Performance Meet the minimum requirements of ventilation rate in ASHRAE Standard 62.1:2010 or the local building code whichever is the more stringent. 13

ASHRAE STD 62.1-2010 Ventilation For Acceptable For Indoor Air Quality Ventilation is the key to Sustainable IAQ and ASHRAE Std 62.1 is the most widely recognised Standard Internationally by most countries and HVAC Engineers in the world. EQ1: Minimum IAQ Performance MS 1525:2007 8. Air Conditioning and Mechanical Ventilation (ACMV) System Indoor Design Condition Recommended Design DB Temperature 23-26ºC (73.4 78.8 F ) Minimum DB Temperature 22ºC Recommended Design RH 55% - 70% Recommended Air Movement 0.15 m/s 0.50m/s Maximum Air Movement 0.7 m/s Outdoor Design Conditions Recommended Outdoor Design 33.3ºC / 27.2ºC Conditions DB / WB ( 92 F/ 81 F ) 14

Industry Code of Practice on Indoor Air Quality 2010 DOSH Malaysia* Ministry of Human Resources Table 1: List of Indoor Air Contaminants and the Maximum Limits Acceptable Range for Specific Physical Parameters 2010 Parameter Acceptable range (a) (b) (c) Air temperature Relative humidity Air movement 23.0 26.0 ºC 40 70% 0.15 0.50 15

List of Indoor Air Contaminants and acceptable limits Indoor Air Contaminants Eight-hours time-weighted average airborne concentration ppm mg/m³ cfu/m³ Chemical contaminants (a) Carbon dioxide (b) Carbon monoxide (c) Formaldehyde (d) Ozone (e) Respirable particulates (f) Total volatile organic compounds (TVOC) C1000 10 0.1 0.05-3 - - - - 0.15 - - - - - - - Biological contaminants (a) Total bacterial counts (b) Total fungal counts - - - - 500 1000 ASHRAE Standard 55-2010 Specifies conditions likely to be thermally acceptable to at least 80% of the adult occupants in a space 16

Indoor Environmental Quality Thermal Comfort (EQ6) Design to ASHRAE 55-2010 : Thermal Environmental Conditions for Human Occupancy in conjunction with relevant localised parameters as listed in MS 1525:2007 Specifies Conditions likely to be thermally acceptable to at least 80% of the adult occupants in a space 6 Primary factors that must be addressed when defining conditions for thermal comfort are: 1.) Metabolic rate 2.) Clothing insulation 3.) Air temperature 4.) Radiant temperature 5.) Air speed 6.) Humidity 17

1.) Factors affecting comfort and Indoor Air Quality (IAQ) Space Temperature Relative Humidity Air Velocity Noise and Acoustic Level Ventilation - Supply of Acceptable Air & removal of Unacceptable Air Lack of Maintenance of ACMV ( HVAC ) system ( eg. Filters not cleaned or replace regularly ) What are the IAQ Problems in Buildings? IAQ during design and construction Lack of Commissioning Moisture in Building Assemblies Poor Outdoor Air Quality Moisture and Dirt in Ventilation Indoor Contaminant Sources Contaminants from Indoor Equipment and Activities Inadequate Ventilation Rates Ineffective Filtration and Air Cleaning 18

Minimum IAQ Performance *EQ1: Minimum IAQ Performance Meet the minimum requirements of ventilation rate in ASHRAE Standard 62.1:2007 or the local building code whichever is the more stringent. MS 1525:2007 Section 8.1.4 Ventilation Outdoor Air-Ventilation Rates should comply with Third Schedule (By Law 41) Article 12 (1) of Uniform Building By Laws, 1984 ( UBBL ) 19

Building code requirements Extract from Third Schedule (By-law 41) ASHRAE Comfort Zone 20

ASHRAE STD 62.1-2010 Ventilation For Acceptable For Indoor Air Quality Ventilation is the key to Sustainable IAQ and ASHRAE Std 62.1 is the Leading Standard adopted by most Local Authorities and HVAC Engineers in the world. EQ1: Minimum IAQ Performance ASHRAE Std 62.1-2010 Ventilation For Acceptable Indoor Air Quality 1.) Ventilation Rate Procedure ( VRP ) 2.) Indoor Air Quality Procedure ( IAQ ) 3.) Natural Ventilation permitted to be used in conjunction with Mechanical Ventilation. 21

Acceptable Indoor Air Quality is defined as air in which there are no known Contaminants at harmful Concentrations as determined by Cognizant Authorities and with which a substantial majority ( 80% or more ) of the people exposed do not express dissatisfaction. 1.) Ventilation Rate Procedure ( VRP ) is a prescriptive procedure with a table of minimum required outdoor airflow rates per occupant for a variety of nonresidential occupancies. The airflow rate per square foot of building floor area is basedon the design occupancy density and the required flow rate per person, adjusted to reflect the air distribution system used. 1.) Ventilation Rate Procedure ( VRP ) V bz = R p.p z + R A.A Z ( PEOPLE + AREA COMPONENT ) Where V bz = Design outdoor airflow required in the breathing zone of the occupied space or spaces in a zone,i.e the breathing zone outdoor air flow A z = Zone floor area: the net occupiable floor area of the zone m 2 ( ft 2 ) P z = zone population: the largest number of people expected to occupy the zone during typical usage. R p = outdoor airflow rate required per person as determined from Table 6-1 R a = outdoor airflow rate required per unit area as determined from Table 6-1 22

TABLE 6-1 MINIMUM VENTILATION RATES IN BREATHING ZONE People Outdoor Area Outdoor Default Values Occupancy Air Rate Air Rate Category R p Ra Office Buildings cfm/ person COPY L/s person cfm/ft ² L/s m² Occupant Density #1000 ft² cfm/ or #100 m² person Combined Outdoor Air Rate L/s person Office Space 5 2.5 0.06 0.3 5 17 8.5 Reception areas 5 2.5 0.06 0.3 30 7 3.5 TABLE 6-1 MINIMUM VENTILATION RATES IN BREATHING ZONE Hotels, Motels, Resort, Dormitories Bedroom / living room 5 2.5 0.06 0.3 10 11 5.5 Barracks sleeping areas 5 2.5 0.06 0.3 20 8 4.0 Laundry rooms, central 5 2.5 0.12 0.6 10 17 8.5 Laundry rooms within 5 2.5 0.12 0.6 10 17 8.5 dwelling units Lobbies / pre-function 7.5 3.8 0.06 0.3 30 10 4.8 Multipurpose assembly 5 2.5 0.06 0.3 120 6 2.8 23

ASHRAE Std 62.1-2007 Ventilation For Acceptable Indoor Air Qualy 1.) Example : Ventilation Rate Procedure ( VRP ) V bz = R p.p z + R a.a z Where V bz = Design outdoor airflow required A z = floor area = 1,000 sq. ft., P z = population = 5 people (20m2/person ) R p = outdoor airflow rate required per person as determined from Table 6-1 = 5 cfm/person R a = outdoor airflow rate required per unit area as determined from Table 6-1 = 0.06 cfm/ft2 V bz = R p.p z + R a.a z = 5 x 5 + 0.06 x 1,000 = 85 cfm i.e 17cfm/person ASHRAE Std 62.1-2007 Ventilation For Acceptable Indoor Air Qualy 2.) Example : Ventilation Rate Procedure ( VRP ) V bz = R p.p z + R a.a z Where V bz = Design outdoor airflow required A z = floor area = 10,000 sq. ft., P z = population = 100 people R p = outdoor airflow rate required per person as determined from Table 6-1 = 5 cfm/person R a = outdoor airflow rate required per unit area as determined from Table 6-1 = 0.06 cfm/ft2 V bz = R p.p z + R a.a z = 5 x 100 + 0.06 x 10,000 = 1,100 cfm i.e 11cfm/person 24

ASHRAE Std 62.1-2007 Ventilation For Acceptable Indoor Air Quality Ventilation Rate Procedure ( VRP ) V bz = R p.p z + R a.a z Where V bz = Design outdoor airflow required Eg. 2 Banks or bank lobbies ( Default Values ) A z = floor area = 100 m2, P z = population = 15 people R p = outdoor airflow rate required per person as determined from Table 6-1 = 3.8 L/s.person R a = outdoor airflow rate required per unit area as determined from Table 6-1 = 0.3 L/s.m2 V bz = R p.p z + R a.a z = 3.8 x 15 + 0.3 x 100 = 57 + 30 = 87 L/s = 6.0 L/s.person MINIMUM VENTILATION RATES IN BREATHING ZONE Occupancy People Outdoor Area Outdoor Design Values Air Rate Air Rate Occupant Density Combined Outdoor Category R p Ra Air Rate cfm/ person L/s person cfm/ft ² L/s m² #1000 ft² cfm/ or #100 m² person L/s person Office Buildings Office Space 5 2.5 0.06 0.3 Banks or Bank lobbies 7.5 3.8 0.06 0.3 10ft2/person 10 17 8.5 50ft2/person 15 12 6.0 25

MINIMUM VENTILATION RATES IN BREATHING ZONE Occupancy Category People Outdoor Area Outdoor Design Values Air Rate R p Air Rate Ra Occupant Density Combined Outdoor Air Rate cfm/ person L/s person cfm/ft² L/s m² #1000 ft² or #100 m² cfm/ person L/s person Hotels, Motels, Resort, Dormitories Places of religious worship 5 2.5 0.06 0.3 5ft2/person 200 5.3 2.7 Libraries 5 2.5 0.12 0.6 50ft2/person 20 11 5.5 Retail Mall common areas 7.5 3.8 0.06 0.3 20ft2/person 50 9 4.5 Lecture Classroom 7.5 3.8 0.06 0.3 10ft2/person 100 8 4.0 MINIMUM VENTILATION RATES IN BREATHING ZONE Occupancy Category People Outdoor Area Outdoor Design Values Air Rate R p Air Rate Ra Occupant Density Combined Outdoor Air Rate cfm/ person L/s person cfm/ft² L/s m² #1000 ft² or #100 m² cfm/ person L/s person Hotels, Motels, Resort, Dormitories Lobbies/ prefunction Multi purpose assembly Educational Facilities Computer lab 10 5 0.12 0.6 Restaurant Dining rooms 7.5 3.8 0.06 0.3 5 2.5 0.06 0.3 7.5 3.8 0.18 0.9 20ft2/person 50 6.7ft2/person 150 20ft2/person 50 10ft2/person 100 9 4.5 5.4 2.7 12.4 6.2 9.3 4.7 26

Air Classification and Recirculation Class 1: Air with low contaminant concentration, low sensory-irritation intensity, and inoffensive odor. Class 2: Air with moderate contaminant concentration, mild sensory-irritation intensity, or mildly offensive odors. Class 2 air also includes air that is not necessarily harmful or objectionable but that is inappropriate for transfer or recirculation to spaces used for different purposes. 27

28

Variable Refrigerant System ( VRS )/ Variable Refrigerant Flow ( VRF ) On a single refrigerant pipe, many indoor units can be connected. Many Fan Coil Units ( up to 60 units) Remedial measures- 1.HVAC Specifying engineers Cassette unit with fan, filter and ducting for outdoor air Ashrae Malaysia Chapter one day seminar April 2008 58 29

Remedial measures-1.hvac Specifying engineers Cassette unit with fan, filter and ducting for outdoor air Ashrae Malaysia Chapter one day seminar April 2008 59 ASHRAE Std 62.1-2007 Ventilation For Acceptable Indoor Air Quality 2.) Indoor Air Quality Procedure ( IAQ ) is a performance based design approach in which the building and its ventilation system are designed to maintain the concentrations of specific contaminants at or below certain limits identified during the building design and to achieve the design target level of perceived IAQ acceptability by occupants. 30

ASHRAE Std 62.1-2007 Ventilation For Acceptable Indoor Air Quality 2.) Indoor Air Quality Procedure ( IAQ ) It provides an engineered approach to an acceptable IAQ in a building :- i) identify contaminants of concern ii) likely rates of generation and acceptable levels of these contaminants iii) defining a system and outdoor ventilation rate that together will maintain the contaminants concentration below maximum acceptable level Air Purification to remove some or all of the contaminants of concern can be part of the system ASHRAE Standard 62.1-2007, Ventilation for Acceptable Indoor Air Quality, specifies minimum ventilation rates and indoor air quality that will be acceptable to the human occupants of a building. Considers chemical, physical, and biological contaminants. Table 6-1 Minimum Ventilation Rates in Breathing Zone (PEOPLE COMPONENT ONLY ) Rp, Flow rate per person or per unit area (ASHRAE 62.1-2010) e.g. Office space 5cfm/person Mall & supermarket 7.5 cfm/person Restaurant & Café 7.5 cfm/person Lecture hall 7.5 Cfm/person Games arcade / Casino 7.5 Cfm/person Computer & Science Lab 10 Cfm/person Disco & Aerobics room 20 Cfm/person 31

COST OF USING HIGH FA At Ambient of 92 F DB/81 FWB (33.3 C/ 27.2 C) 174.3 Cfm ( 300 M³/Hr) of FA Requires 1 Ton ( 3.517KW ) of AC Load High use of Fresh Air Results in High Capital Cost High Operating Cost (Energy & Water Cost) 63 ASHRAE STANDARDS 62 Ventilation for Acceptable Indoor Air Quality LOCATION OFFICE SPACE OA REQUIRMENTS FOR VENTILATION CFM/Person (62-1989,1999 & 2001) CFM/PERSON 20 MIN.VENTILATION RATES IN BREATHING ZONE (62.1-2004 & 2007) CFM/Person 5 CONFERENCE ROOM CFM/PERSON 20 CFM/Person 5 64 32

ASHRAE STANDARDS 62.1 Ventilation for Acceptable Indoor Air Quality LOCATION AUDITORIUM CLASS ROOM OA REQUIRMENTS FOR VENTILATION CFM/Person (62-1989,1999 & 2001) CFM/PERSON 20 CFM/PERSON 20 MIN.VENTILATION RATES IN BREATHING ZONE (62.1-2004,2007 & 2010 ) CFM/Person 5 ( People Component) CFM/Person 7.5 (People Component) 65 CALCULATION FOR ENERGY SAVINGS WITH REDUCTION OF OUTDOOR AIR 66 33

ASHRAE 62 2001 2010 (Cfm/person) (Cfm/person) OFFICE 20 5 (15) 67 DB WB ENTHALPY F F Btu/lb of dry air OUTDOOR AIR 92 81 44.78 DESIGN TEMP. 75 64 29.31 15.47 68 34

FOR AN OFFICE WITH 200 PERSONS Savings = 4.45 x CFM x Enthaply = 4.45 x (200 x 15) x 15.47 = 17.2 tons (60.5kw) 69 No of People Savings in Chiller Tonnage 100 8.6 ton (30.3KW) 200 17.2 ton (60.5KW) 500 43.0 ton (151.3KW) 1,000 86.1 ton (302.6KW) 2,000 172.1 ton (605.3KW) 70 35

36

37

38

CO2 Monitoring and Demand Control Ventilation ( EQ3) Ventilation Is Fixed Question: How could we ventilate the space more efficiently? Answers: Measure Ventilation In The Space Like Temperature Vary Ventilation Based On Occupancy Zone Control Ventilation With CO 2 39

The effect of CO 2 on man 8,0% Convulsions, immediate paralysis and death Main alarm 3,0% Muscular pain, unconsciousness, convulsions and risk of death Pre alarm 1,50% 0,50% 0,10% 0,04% Shortness of breath and increased heart frequency Hygienic limit value Recommended indoor limit value Fresh air Carbon Dioxide and DCV. Humans are the main indoor source of CO2. Indoor carbon dioxide concentrations can be used to indicate specific and limited aspects of indoor air quality but are not an overall indicator of the quality of indoor air. Demand Control Ventilation adjusts ventilation air based on the number of occupants and the ventilation demands that the occupants create. 40

Carbon Dioxide and DCV (2) CO 2 -based DCV has the most energy savings potential in buildings where occupancy fluctuates & when ventilation is over designed. Office buildings, government facilities, retail stores and shopping malls, airports, theaters, auditoriums, conference or lecture halls, entertainment areas are good candidates for DCV CO 2 Demand Controlled Ventilation Examples: Assuming a Conference room with Max. capacity of = 200 people If Designed Ventilation rate = 7 l/s/ person The Amount of ventilation required = 1,400 l/s Now if the Conference room is not fully occupied, say with No. of People = 70 If Ventilation rate is maintained at 7 l/s/ person Amount of ventilation = 490 l/s DCV uses CO2 measurement to indirectly determine level of occupancy and thus ventilation 41

Typical Installation AHU Room Return Air CO2 sensor AHU Room AHU Supply Air Fresh Air Fresh air damper Damper Actuator Typical Installation AHU Room Return Air CO 2 sensor AHU Room Return Air AHU Supply Air CO 2 sensor PLC Fresh Air Fresh air damper Damper Actuator 42

Carbon Dioxide (CO 2 ) Sensors/Controllers Wall Mount Application Duct Mount Application Great potential for Energy savings when: i.) the space has less than maximum occupancy ii.) the space has variable occupancy pattern iii.) the ventilation is over designed Sensors are recommended to be verified every 3 years n = # of sensors R = terminating resistor 500 n Ω R 2-10 V input 4 20 ma Com - + 24V G+ G 0 I 0 G+ G 0 I 0 CO 2 sensor CO 2 sensor 3ph Supply Variable Speed Drive G+ G 0 I 0 CO 2 sensor G+ G 0 I 0 CO 2 sensor FAN Averaging CO 2 Sensor Monitoring & Control using VSD G+ G 0 I 0 CO 2 sensor 43

IAQ Before and During Occupancy All ventilation air filters will be changed after the flush-out Pressure sensor to detect filter blockage Purging to eliminate bad odors and improve air quality especially for building space that does not have adequate openable windows Ventilation of the encapsulation, hood or extraction type should be provided so that the spread of contaminants is prevented Building materials and surface finishes should not contain any substances that emit chemicals, bacteria or fungi THANK YOU By: Ir. Ng Yong Kong, (email : nyk@nyk.com.my h/p no. +6012-201 9319 ) and others. 26 th March 2013 44