newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer



Similar documents
Using Time-of-Day Scheduling To Save Energy

Engineers Newsletter. Understanding Single-Zone VAV Systems. providing insights for today s hvac system designer. volume 42 2

for K-12 School Buildings

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

Air Conditioning Clinic

Air Conditioning Clinic

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

HVAC Systems: Overview

newsletter Let s take a high-level look at airside economizing: what it is, what it requires, and how it s done. How does economizer cooling work?

HVAC Processes. Lecture 7


How Ground/Water Source Heat Pumps Work

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

3/29/2012 INTRODUCTION HVAC BASICS

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

Defining Quality. Building Comfort. Precision. Air Conditioning

Lesson 36 Selection Of Air Conditioning Systems

HEATING, VENTILATION & AIR CONDITIONING

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL

HVAC Simplified Approach Option

The Different Types of Air Conditioning Equipment for IT Environments

The District Energy Manager and Classroom Heating

Commissioning - Construction Documents (Page 1 of 6)

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER

Creating Efficient HVAC Systems

Variable Air Volume - VAV

for Plans Examiners and Building Inspectors

Glossary of Heating, Ventilation and Air Conditioning Terms

Building Re-Tuning Training Guide: AHU Heating and Cooling Control

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

SIMULATION OF RADIANT COOLING PERFORMANCE WITH

Rev. No. 0 January 5, 2009

How a Ground Source Heat Pump Works for a School or College

Building Energy Systems. - HVAC: Heating, Distribution -

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now

How To Use A Water Source Heat Pump

Energy-Saving Strategies for Rooftop VAV Systems

Venice Library Humidity Study. for Williams Building Diagnostics, LLC th Street West Bradenton, FL Report April 13, 2015

GEOTHERMAL HEATING AND COOLING INTRODUCTION

See any red flags? Let s take a look at the problems that occurred on the job and how to avoid making the same mistakes.

Air Conditioning Clinic

Air-Conditioning Buying Guide

HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget

J O U R N A L. Energy Performance for. Proper Specification of Air Terminal Units Future Climate Impacts on Building Design

CONTROL STRATEGIES FOR HVAC SYSTEMS

EnergyPro Building Energy Analysis. Assisted Living Building

Measuring The Right Thing For Humidity Control It s the Dew Point Stupid!

Energy Efficiency in Industrial HVAC Systems

White Paper #10. Energy Efficiency in Computer Data Centers

ENHANCED LABORATORY HVAC SYSTEM

Single Zone LCD Thermostat Operating Instructions

HVAC Costs. Reducing Building. Building owners are caught between two powerful forces the need to lower energy costs. By Stephen J.

Bring the fresh in. Dedicated Outside Air Systems

USER S GUIDE For all Packaged Systems (Air Conditioners and Heat Pumps)

Glossary of HVAC Terms

Indoor Pool Dehumidification

Evaporative Cooling. Terminology. Date: February 28, Concepts

How To Buy A Lennox Power System

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

Product Data Bulletin

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment

1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%

Heat Pumps for Cold Climates?? Yes, Indeed!

Dehumidification Frequently Asked Questions

Pool Dehumidification Basics

C-Bus Application Messages & Behaviour Chapter 25 Air Conditioning

Preliminary Final Proposal

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015

Heating & Cooling Efficiency

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:

Topics for Today. Order of Magnitude Mechanical Estimating. Order of Magnitude Estimate Goal. Project Delivery Methods. Questions for Client

Heating, Ventilation & Air Conditioning Equipment

COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN

Energy Efficiency Analysis for a Multi-Story Commercial Office Building. (LG Multi V Water II Heat Recovery VRF System)

Energy Efficiency. Energy Efficient Home Cooling:

DIABLO VALLEY COLLEGE CATALOG

School HVAC. Design Manual. Application Guide AG Air Cooled Chiller. Chilled Water Pumps. Expansion Tank CHWR CHWS. Make up Water Line Boiler

Comfort you can count on.

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET.

Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *

HEAT RECOVERY FROM CHILLED WATER SYSTEMS. Applications for Heat Reclaim Chillers

HVAC Basic Science - System Capacity

Printing and Publishing Energy Savings Guide

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

How a Ground Source Heat Pump Works for Commercial Buildings

The Only GUY To Call. Why are my utility bills so high? What can I do to lower my energy expenses?

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning)

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air. Trevor Wende Vice President, Marketing Advantix Systems, Inc.

Sustainable Preservation Practices for Managing Storage Environments Webinar: April 3, 2013

ASHRAE Student System Selection Competition New Office Building - Nashville, Tennessee Spring 2009

QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM

Transcription:

engineers volume 36 2 newsletter providing insights for today s hvac system designer energy-saving strategies for Water-Source Heat Pump Systems from the editor... Water-source heat pump (WSHP) systems are often known (unfortunately) as a "low cost" alternative. However, they have the potential to be high-performance systems, reducing operating costs for the building owner and improving occupant comfort. This EN contains a "menu" of cost-effective, system design and control strategies that can be used to save energy in WSHP systems. In general, each section can be read independently, allowing the reader to decide which strategies make sense for a given application. Heat rejected by the units operating in cooling mode is used to offset the heat absorbed by the units in heating mode. In this manner, a WSHP system provides a form of heat recovery and an opportunity to save energy by reducing the need to operate the boiler or cooling tower. For example, if the water temperature stays in the desired range between 60ºF (16ºC) and 90ºF (32ºC) neither the boiler nor the cooling tower need to operate. In applications such as office buildings, heat generated by lights, people, and office equipment often results in the need to provide year-round cooling in the interior zones of the building. In these applications, the benefit of this heat recovery further reduces boiler energy use during the winter months. Equipment/System Configuration Strategies "Hybrid" systems. The WSHP system is often viewed solely as an alternative to other types of HVAC systems. "Hybrid" systems composed of watersource heat pumps and other types of HVAC equipment, however, may be best suited to meet the specific requirements of a given building. WSHP systems are used to provide comfort in a wide range of building types and climates. In this type of system, each zone has a WSHP unit that is controlled to maintain the desired temperature in that zone. All the heat pumps are connected to a common water loop (Figure 1). Also connected to this water loop are a "heat rejecter" (e.g., cooling tower or geothermal ), a "heat adder" (e.g., boiler or geothermal heat exchanger), circulation pumps, and related accessories. Typically, outdoor air is conditioned and delivered by a separate, dedicated ventilation system. During mild weather, such as spring or fall, the heat pumps serving the sunny side and interior of the building often operate in cooling mode and reject heat into the water loop. The heat pumps serving the shady side of the building often operate in heating mode and absorb heat from the water loop. Figure 1. Typical water-source heat pump system horizontal cooling tower boiler pumps rooftop vertical-stack vertical 2007 American Standard All rights reserved 1

Figure 2. "Hybrid" WSHP system horizontal cooling tower boiler pumps self-contained VAV air conditioner Ground-source heat pump systems. A well-known variation of the WSHP system uses the earth as the heat rejecter and heat adder (Figure 3). Ground-source heat-pump (GSHP) systems* do not actually get rid of heat, they store it in the ground for use at a different time. During the summer, the heat pumps extract heat from the building and transfer it to the ground. When the building requires heating, this stored heat can be recaptured from the ground. In a perfectly balanced system, the amount of heat stored over a given period of time would equal the amount of heat retrieved. vertical-stack While there are many possible combinations, the example hybrid system shown in Figure 2 uses variable-air-volume (VAV) self-contained units to serve the interior zones of an office building and water-source heat pumps to serve the perimeter zones. The interior zones in this type of building may have variable loads, but often require cooling year-round. vertical to interior zones These packaged units contain a complete refrigeration circuit with a water-cooled condenser that is connected to the common water loop. The VAV supply fan varies the airflow supplied to the interior zones, resulting in significant part-load fan energy savings, while the condenser heat is rejected to the loop so that it can be absorbed by the heat pumps that are providing heat to the perimeter zones. Ground-source heat pump systems offer the potential for saving energy because they can reduce (or eliminate) the energy needed to operate a cooling tower and/or boiler. Eliminating the cooling tower has architectural and maintenance advantages, and eliminating the boiler frees up floor space in the building. While eliminating both the cooling tower and boiler likely results in the greatest overall energy savings, for most applications it requires the largest (and more expensive) geothermal to account for the imbalance between heat stored and heat extracted. Figure 3. Ground-source heat pump system geothermal pumps For example, in a cooling-dominated climate, a large amount of heat must be rejected to the ground during the cooling season, but a much smaller amount of heat is extracted from the ground during the heating season. This imbalance can cause the temperature of the ground surrounding the geothermal to increase over time. * A 2001 Engineers Newsletter (volume 30-2, "The Three E's of Geothermal Heat Pump Systems") provides more detail on groundsource heat pump systems. 2 Trane Engineers Newsletter volume 36 2 providing insights for today s HVAC system designer

Conversely, in a heating-dominated climate, a relatively small amount of heat is rejected to the ground during the cooling season, but a much larger amount of heat must be extracted back out of the ground during the heating season. In this case, the temperature of the ground can decrease over time. In either case, future operation of the heat pumps is compromised by this change in ground temperature. Figure 4. "Hybrid" GSHP system geothermal cooling tower (or dry cooler) pumps In many areas of the country, this imbalance requires the geothermal to be larger to prevent the ground temperature from changing over time. The first cost to install such a large often dissuades people from considering this approach. Using a "hybrid" approach, however, can often make GSHP systems more economical, opening up the possibility to reap the potential energy savings. This "hybrid" approach involves adding a small cooling tower or dry cooler to the loop for a system that is installed in a cooling-dominated climate (Figure 4), or adding a small boiler to a system in a heating-dominated climate. In either case, the geothermal is sized based on the smaller of the two loads: for the total heat absorbed in a cooling-dominated climate or the total heat rejected in a heating-dominated climate. Then, a small cooling tower (or boiler) is added to reject (or add) the remaining heat. This approach reduces the required size of the geothermal by avoiding the imbalance described previously. While the overall energy savings may not be as great as in a system with a larger, this approach often results in a more acceptable return on investment. bypass valve Variable-flow pumping. The watercirculating pumps can be either constant- or variable-flow pumps. Constant-flow pumps operate whenever the system is on, delivering a constant flow of water throughout the loop, and consuming a constant amount of energy. Variable-flow pumps take advantage of the fact that all heat pumps in the system are not always operating at the same time. For example, when a zone needs neither cooling nor heating the compressor turns off. When the compressor turns off, a motorized, two-position valve shuts off water flow to that heat pump, so less total water flow is required in the loop. A variablefrequency drive (VFD) on the circulating pump allows the pump to unload, saving energy by delivering only the amount of water required by the operating heat pumps. In a variable-flow system, consider installing an automatic balancing valve for each heat pump. This device helps ensure proper water flow through the heat pump (when the compressor is operating) as the system flow rate changes. In addition, a diverting valve and bypass pipe can be added to a ground-source heat pump system to bypass the geothermal heat exchanger whenever the temperature of the loop falls within a desired range (see Figure 4). This reduces the pressure drop that the circulating pump must overcome, and saves pumping energy. providing insights for today s HVAC system designer Trane Engineers Newsletter volume 36 2 3

Dedicated ventilation system. In most WSHP systems, the outdoor air is conditioned by a separate, dedicated ventilation system. This conditioned outdoor air is typically delivered to the zones in one of two ways (Figure 5). The first approach is to duct the outdoor air directly to the intake of each heat pump, where it mixes with return air from the zone. The second approach is to duct the conditioned outdoor air directly to each zone. A variation on this second approach (bottom configuration in Figure 5) is to duct the outdoor air to the supply-side of each WSHP, where it mixes with supply air from the heat pump before being delivered to the zone. Figure 6: Sensible cooling is a byproduct of 'cold-coil' dehumidification sensible cooling space DH dehumidification Figure 5: Dedicated ventilation system configurations OA OA OA dedicated OA unit to intake of each WSHP to supply-side of each WSHP WSHP direct to each zone Depending on the climate, the dedicated OA unit may be used to cool, dehumidify, heat, and/or humidify the outdoor air. This approach allows the heat pumps to handle only the zone cooling and heating loads, not the ventilation load. Many dedicated outdoor-air systems are designed to dehumidify the outdoor air so it is at least as dry as the space, and then reheat it to approximately space temperature (neutral). However, when a chilledwater or DX cooling coil is used for dehumidification, a byproduct of that process is that the dry-bulb temperature of the air leaving the coil is colder than the space (Figure 6). If the dehumidified outdoor air (DH) is reheated to neutral (), the sensible cooling performed by the dedicated OA unit is wasted. If the dedicated outdoor-air system delivers air directly to the individual zones, the dehumidified outdoor air (DH) can be delivered "cold," rather than reheated to neutral. The low drybulb temperature of the conditioned OA offsets part of the sensible cooling load in the zones, reducing the cooling energy used by the heat pumps. At design conditions, this means that the heat pumps can be sized for less airflow and less cooling capacity than in a neutral-air system.** Compared to a neutral-air system, a dedicated outdoor-air system that delivers cold air directly to the zones (or to the supply-side of each WSHP): Requires less overall cooling capacity. The required cooling capacity of each heat pump is less than in a neutral-air system, and the required capacity of the dedicated OA unit is the same for both configurations. Requires less overall cooling energy for much of the year. By taking advantage of the sensible cooling already done by the dedicated OA unit, the cold-air system requires less cooling energy at each heat pump. The neutral-air system throws away this sensible cooling benefit by reheating the air to approximately space temperature. Requires less overall fan airflow and, therefore, less fan energy. For those zones that require seasonal cooling and heating, the supply airflow delivered by the heat pump is less than in a neutral-air ** A 2006 ASHE Journal article (Murphy, J. "Smart Dedicated Outdoor-Air Systems." July 2006. available at www.ashrae.org or www.trane.com) further discusses the impact of delivering the conditioned OA "cold" versus "neutral." 4 Trane Engineers Newsletter volume 36 2 providing insights for today s HVAC system designer

system, and the airflow delivered by the dedicated OA unit is the same for both configurations. (For zones that require year-round cooling, the supply airflow may need to be sized based on the warmest temperature to be delivered by the dedicated OA unit.) While the conditioned outdoor air should be delivered cold whenever possible, as the space sensible cooling load decreases due to changes in outdoor conditions and internal loads it is possible that the cold, conditioned outdoor air may provide more sensible cooling than the space requires. As a result the space dry-bulb temperature drops and the WSHP operates in the heating mode. While this may appear strange to the building operator, the few heat pumps that are operating in the heating mode absorb heat from the loop, reducing the amount of heat that needs to be rejected by the cooling tower. This likely improves system efficiency, rather than degrading it. In addition, the remaining zones continue to benefit from the sensible cooling due to the cold, conditioned outdoor air. During the heating season, however, it may be desirable to heat the outdoor air to a temperature near the desired space temperature before delivering it directly to the zones. Finally, if the outdoor air is delivered directly to each zone (center configuration in Figure 5), the fan inside the heat pump is no longer required to operate in order to ventilate the zone. This affords the opportunity to cycle the local fan on and off along with the compressor, saving fan energy at part-load conditions. Exhaust-air energy recovery. A centralized ventilation system often makes it more feasible to implement exhaust-air energy recovery, if exhaust air from the building can be routed back to the dedicated OA unit. Figure 7. Exhaust-air energy recovery outdoor air As an example, Figure 7 shows a totalenergy wheel used to precondition the outdoor air. During the cooling season, this desiccant-coated wheel revolves between the outdoor and exhaust airstreams, removing both sensible heat and moisture from the entering outdoor air and rejecting it to the exhaust air. During the heating season, the wheel recovers both sensible heat and moisture from the exhaust air, and transfers it to the outdoor air being brought into the building for ventilation. In many climates and building types, exhaust-air energy recovery is an effective means of reducing the energy required to cool, dehumidify, heat, or humidify the entering outdoor air. It also reduces the required cooling and heating capacity of the dedicated outdoor-air unit. Waterside economizer. During cold weather, the heat pumps serving perimeter zones often operate in heating mode and absorb heat from the water loop, which lowers the loop Figure 8. Waterside economizer exhaust air air temperature. If the loop water temperature is allowed to drift down further than normal to 45 F (7 C), for example a waterside economizer coil can be used to provide "free cooling" for interior zones. When the loop water is cool enough, a three-way valve diverts the water through the waterside economizer coil to cool the entering air, reducing (or avoiding) the need to operate the compressor (Figure 8). The three-way valve allows the economizer coil to be bypassed when not in use, saving pump energy. And, unlike other systems, no cooling tower energy is used to create the colder water; just the heat pumps serving the perimeter zones that are already operating in the heating mode. Hot gas reheat for humidity control. Because a water-source heat pump typically uses a constant-speed fan with a cycling compressor, it can be susceptible to high relative-humidity levels in the zone at part-load conditions. One approach to improve part-load dehumidification in WSHP systems is to use the dedicated outdoor-air system to dehumidify the outdoor air so that it is drier than the space. But in some buildings, it may not be practical to serve every zone with the dedicated outdoor-air system. refrigerant-to-water waterside economizer coil three-way valve providing insights for today s HVAC system designer Trane Engineers Newsletter volume 36 2 5

Another option for controlling humidity is to reheat the dehumidified supply air with heat recovered from the refrigeration circuit in the heat pump. This is sometimes referred to as hotgas reheat. In this configuration, the air is first cooled and dehumidified by the refrigerant-to-air, then reheated by the reheat coil to control not only the dry-bulb temperature, but also the relative humidity in the zone (Figure 9). Figure 9. Hot gas reheat for humidity control reheat coil air water loop compressor As long as the zone relative humidity is less than the desired upper limit (60% for example), the heat pump operates in the standard cooling mode and the compressor cycles on and off to maintain zone temperature. When the humidity sensor indicates that the zone relative humidity is too high, but the zone temperature is at setpoint, the reheat valve diverts hot refrigerant vapor from the compressor through the reheat coil. This allows the compressor to keep operating to dehumidify the air, while warming the supply air to avoid overcooling the zone. Although ASHE Standard 90.1-2004, Energy Standard for Buildings Except Low-Rise Residential Buildings, limits the use of reheat using "new" energy, it allows unlimited reheat for the purpose of humidity control if site-recovered energy (such as heat recovery from the refrigeration circuit) is used as the source of heat. Optimized Control Strategies Night setback. To lower installed costs, some WSHP systems use simple, residential-style thermostats with no system-level controls. A nonprogrammable thermostat causes the heat pump to maintain the same temperature, whether the zone is occupied or not. Use of programmable thermostats allows each zone to vary the temperature setpoint based on time of day and day of the week. But they also allow occupants to override these setpoints or ignore the schedule altogether (by using the "hold" feature of the thermostat), thus thwarting any potential for energy savings. Figure 10. Energy-saving potential of night setback HVAC energy consumption, % of base refrigerant-to-air refrigerant-to-water 100 80 60 40 20 0 Atlanta without night setback Louisville A more sustainable approach is to equip each heat pump with a DDC controller that is connected to a zone temperature sensor, and then use a system-level controller that coordinates the operation of all components of the system. This system-level controller contains a timeof-day schedule that defines when the building is expected to be unoccupied. During these times, the system is shut off and the temperature in each zone is allowed to drift away from the occupied setpoint. Allowing the indoor temperature to drift during unoccupied periods saves energy by avoiding the need to operate heating, cooling, and ventilation equipment. Figure 10 shows the potential energy savings of using night setback in an example office building that has a typical WSHP system. Minneapolis with night setback reversing valve reheat valve 6 Trane Engineers Newsletter volume 36 2 providing insights for today s HVAC system designer

Night setback reduced the overall HVAC energy use by 10% to 15% for this example building. Optimal start. In those systems that use a time-of-day schedule to start and stop the HVAC system, the time at which the system starts in the morning is typically set to ensure that the indoor temperature reaches the desired occupied setpoint on either the coldest or warmest day of the year. The result is that, for most days, the system starts much earlier than it needs to. This increases the number of operating hours and increases system energy use. An alternative approach is to use a strategy called optimal start. The system-level controller is used to determine the length of time required to bring each zone from the current temperature to the occupied setpoint temperature. Then, the controller waits as long as possible before starting the system, so that the temperature in each zone reaches occupied setpoint just in time for occupancy. This optimal start strategy reduces the number of hours that the system needs to operate, and saves energy by avoiding the need to maintain the indoor temperature at occupied setpoint even though the building is unoccupied. Loop temperature optimization. A system-level controller should be used to operate the water circulation pumps and coordinate cooling tower and boiler operation. To maximize the energyrelated benefits of a WSHP system, the loop water temperature should be allowed to float across a wide range between 60ºF (16ºC) and 90ºF (32ºC), for example. Further, communicating system-level controls offer the opportunity to optimize the loop water temperature in an effort to minimize overall system energy consumption. In the cooling mode, the compressor in the watersource heat pump is more efficient if the entering water temperature is cooler. However, making cooler water often requires the cooling tower to use more energy. A smart, system-level controller can reset the loop temperature setpoint to minimize the combined energy consumed by the heat pumps and cooling tower under the current operating conditions. Summary The impact of any energy-saving strategy on the operating cost of a specific building depends on climate, building usage, and utility costs. Building analysis tools (like TCE 700) can be used to analyze these strategies and convert energy savings to real operating cost dollars that can be used to make financial decisions. Figure 11 shows the potential energy savings of using several of these strategies in an example office building with a WSHP system. The "base" WSHP system complies with ASHE 90.1-2004, so it includes night setback control, variable-flow pumping with a VFD, and a total-energy wheel on the dedicated outdoor-air unit. The optimized system adds optimal start and loop temperature optimization to the system-level controls, and the conditioned outdoor air is ducted directly to each zone (rather than to the inlet of each heat pump). Delivering the OA directly to each zone allows it to be delivered "cold" (rather than reheated to neutral) during the cooling season, and allows the fan in each heat pump to cycle off with the compressor when that zone does not require either cooling or heating. Figure 11. Energy-saving potential in WSHP systems 100 HVAC energy consumption, % of base 80 60 40 20 The optimized WSHP system reduced the overall HVAC energy use by about 20% for this example office building in Atlanta, by 15% in Louisville, and by 8% in Minneapolis. If the system is converted to a ground-source heat pump system, the energy savings increases to 37% in Atlanta, 40% in Louisville, and 24% in Minneapolis. There is a real potential to create highperformance WSHP systems, which reduce operating costs for the building owner and improve occupant comfort. 0 Atlanta Louisville Minneapolis 90.1-compliant WSHP system optimized WSHP system By John Murphy, applications engineer, Trane. You can find this and previous issues of the Engineers Newsletter at www.trane.com/ engineersnewsletter. To comment, e-mail us at comfort@trane.com. optimized GSHP system providing insights for today s HVAC system designer Trane Engineers Newsletter volume 36 2 7

Trane A business of American Standard Companies www.trane.com For more information, contact your local Trane office or e-mail us at comfort@trane.com TCE 700 Join Trane in celebrating 35 years of TCE. Introduced into the HVAC industry in 1972, the HVAC design and analysis program was the first of its kind and quickly became a de facto industry standard. It continues to grow with the industry meeting requirements for ASHE Standard 140*, ASHE 90.1, and LEED Green Building Rating System and recently approved by the IRS to certify energy savings for building owners. Find out more, visit www.trane.com 5 31 9 7 2 TCE 2 0 0 7 *ASHE Standard 140, Standard Method of Test for Evaluation of Building Energy Analysis Computer Programs. Trane believes the facts and suggestions presented here to be accurate. However, final design and application decisions are your responsibility. Trane disclaims any responsibility for actions taken on the material presented. 8 Trane Engineers Newsletter volume 36 2 ADM-APN024-EN (May 2007)