Energy Efficient Renovations of Storm Damaged Residences - Florida Case Studies



Similar documents
PERFORMANCE OF SIDE-BY-SIDE SOUTH TEXAS HOMES Isolating the Contribution of Spray Polyurethane Foam Insulation

FLORIDA SOLAR ENERGY CENTER

Home Energy Evaluation Report

First Time Home Buyers Energy Efficiency Workshop Guide

Advancing Residential Energy Retrofits

THE IC Y N E N E AD V A N T A G E

Potential of Energy Efficiency and Renewable Energy Savings To Impact Florida s Projected Energy Use in 2014

Inspecting to a higher standard.

energy-saving checklist a guide for rental property owners

TechPractices: Home Front Homes:

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN Fax: Re-Roofing: Asphalt Shingles

Home Performance with ENERGY STAR. Evaluation Report

Facts About Home Cooling

Existing Housing Stock

Before You Start an Energy Efficiency Retrofit The Building Envelope

Energy Analysis for Internal and External Window Film Applications for Existing Homes in Florida

Sustainable Design and Energy-Efficient Building Techniques for Existing Housing

Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen

2014 British Columbia Building Code Changes

Current Programs available to Limited Income Customers. Residential and Multifamily

research highlight Highly Energy Efficient Building Envelope Retrofits for Houses

Inspection Item COMMENTS

Cost-Effective, Energy-Efficient Home Improvements for Florida Homes August 8, 2012

William Zoeller, R.A.

The Only GUY To Call. Why are my utility bills so high? What can I do to lower my energy expenses?

TABLE OF CONTENTS" SECTION 3: Comparing Standing Seam Metal to Other Metal Roofs PAGE 7"

Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes

Key energy-efficient features of your new home

Energy Efficiency for the Homeowner

Rehab Inspection Report Page 1

Chapter 8. Duct Design and Sealing

Category Measure Minimum Efficiency / Certification Requirements

Direct Energy Home Energy Audit Audit Report

bout your HOUSE before you start Renovating Your Basement Moisture Problems

ENERGY STAR Certified Homes, Version 3 Cost & Savings Estimates

#1) BEFORE Purchasing Land Here Is A Checklist Of Things You Should Check

PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES

Energy Star Case Study on Blue Hills. Introduction

Glossary of Heating, Ventilation and Air Conditioning Terms

ROOFS, SNOW AND ICE DAMS

Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls

bout your house before you start Renovating Your Basement Moisture Problems

Maintenance Matters. Window and Door Replacement

Final inspections are completed by site visit only. Access to fenced yards shall be planned.

Below are detailed instructions for using the EMS load calculator.

air conditioners how to choose a cooling system

Air-Conditioning Buying Guide

HVAC INSTALLATION SUCCESS WITH 2012 IECC DELAWARE. for Builders & Trades. Recommended Practices for Optimized Energy Savings

HVAC INSTALLATION. Success with 2015 IECC Northeast & Mid-Atlantic. Checklist for Builders & Trades

This report presents the findings and recommendations of the assessment of energy use and

Energy-Saving Tips. Energy Saving Tips

BUILDING ASSESSMENT QUESTIONNAIRE. B. TENANTS Is there more than one tenant in the building? YES

Larry Haight's Residential Roofing Co, Inc NE 95th Street Redmond, Washington Phone: (425) Fax: (425)

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

Shingle Roofing: What s below the surface is important

In the Fall 2002 issue of HHE News I examined

EarthCents (DSM) Program Summary

PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES

Your Personal Home Energy Action Plan

Attic condensation during winter can

APPENDIX C FORMS 2010 FLORIDA BUILDING CODE ENERGY CONSERVATION C.1

) SIGNIFICANT CHANGES INCLUDING CODE COMMENTARY

Asphalt Shingle Application Requirements

HomeSpec REPORT SUMMARY

CLOSED CRAWLSPACES. Have you ever been in your crawlspace? If not, have you ever even

Residential Roofing Guide

Preventing Ice Dams on Roofs

Energy Efficiency. Energy Efficient Home Cooling:

Water Damage & Repair

Sample Customer 123 Conservation Way TAMPA FL Tracking Number:

Points of Construction

Economics of Passive Solar and Zero Energy Homes

I NI NP R Inspected Items

Home Inspection Report

Residential HVAC System Sizing

Attachment #23 Health Safety Table. Client Education Inform issue and document. How to clean & maintain gutters. How to adjust sprinklers

Dehumidification Frequently Asked Questions

Low Cost Interior Duct Systems for High Performance Homes in Hot Climates

Measured Energy and Peak Demand Reduction from High Efficiency Air Conditioner Replacement

SAVE ENERGY AT HOME INSULATE AND AIR SEAL

ROOF CONDENSATION: A COSTLY PROBLEM

October 5, 2015 Dear Client,

Exhibit B. Property Acquisition and Disposition Division Residential Design & Performance Standards

Basic B.S. (building science) insights for. Spray Foam, HVAC and Moisture

Designing Schools To Reduce On-Going And Future Maintenance and Repair Costs

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

FLORIDA SOLAR ENERGY CENTER

Energy Upgrade California TM Incentive Reservation Form

Your Guide to Buying an Energy-Efficient Central Air Conditioner

System Interactions in Forced-Air Heating and Cooling Systems, Part II: Continuous Fan Operation

about your house Before You Start Renovating Your Basement Moisture Problems Figure 1 Moisture problems to solve

Contract for Weatherization Management Address City & State

ROOF INSPECTION REPORT

Does Wall Township require an inspection by the building department on resale of a home?

Building Condition Assessment Report

The Potential for Energy Retrofits within the City of Sacramento s Rental Housing Inspection Program

Why is my air conditioner dripping on my customers?

BPC Green Builders. Green building for new and existing homes. Health Comfort Energy

Detached accessory structures that contain no conditioned floor area are exempt.

Energy Efficient Homes: Air Conditioning 1

Transcription:

CONTRACT REPORT Energy Efficient Renovations of Storm Damaged Residences - Florida Case Studies FSEC-CR-1648-06 September 8, 2006 Submitted to: U.S. Department of Energy Cooperative Agreement No. DE-FC26-99GO10478 Submitted by: Dave Chasar, P.E. Neil Moyer Eric Martin 1

Abstract This study documents the energy impact of retrofit options performed on four Central Florida homes suffering damage from hurricanes in the summer of 2004. Case studies are presented to show the costs and benefits of various retrofit strategies, including the potential to enhance comfort and durability. Results are based on pre- and post-retrofit home performance testing as well as analysis of simulated and actual energy savings. Whole house energy savings resulting from the retrofits is estimated to be between 1% and 27%, while cooling savings ranged between 3% and 45%. Executive Summary Storm-damaged homes offer the opportunity for repairs that reduce energy use, improve comfort and enhance resistance to future storms. Case studies of four Florida homes damaged in the summer of 2004 were documented to show the costs and benefits of various retrofit strategies. All four homes required roof replacement and each took advantage of roof cladding with higher reflectance than the original a proven means of reducing cooling energy use. Two of the case studies included improvements to attic insulation, tightening of the envelope and/or duct system and improved efficiency equipment and lighting. Energy savings attributable to storm repairs were estimated through detailed computer simulation and in one case savings were directly measured in a before/after fashion. Whole-home energy savings estimates derived by computer simulation ranged from a high 27%, in the home requiring the greatest amount of renovation, to a low of 1% in the home with a lightcolored shingle roof replacement. Cooling energy savings was also analyzed as it typically makes up the largest single subset of whole-home energy use in Central Florida. Cooling savings derived from the computer model ranged from 3% to 45% and, as in the case of whole home energy, was directly impacted by the level of home repair. Measured data obtained from one home showed a 19% reduction in cooling energy use after the dark shingle roof was replaced with white metal. This fell roughly in line with computer estimated cooling savings of 16%.

Table of Contents Abstract... 2 Executive Summary... 2 Table of Contents... 3 1.0 Introduction... 4 1.1 Home Performance Testing... 4 1.2 Simulated Energy Use and Savings Analysis... 5 2.0 Case Study Examination... 5 2.1 Home A... 6 2.1.1 Post-retrofit Energy Savings... 7 2.1.2 Material Costs... 8 2.1.3 Opportunities For Enhanced Comfort... 8 2.1.4 Assessment Of Indoor Air Quality... 9 2.2 Home B... 10 2.2.1 Post-retrofit Energy Savings... 10 2.2.2 Material Costs... 12 2.2.3 Economic and Other Benefits... 12 2.2.4 Installation... 13 2.2.5 Opportunities for Enhanced Comfort... 13 2.2.6 Assessment of Indoor Air Quality... 13 2.3 Home C... 13 2.3.1 Post-retrofit Energy Savings... 14 2.3.2 Material Costs... 14 2.3.3 Opportunities For Enhanced Comfort... 14 2.3.4 Assessment Of Indoor Air Quality... 15 2.4 Home D... 15 2.4.1 Post-retrofit Energy Savings... 16 2.4.2 Opportunities For Enhanced Comfort... 17 2.4.3 Assessment Of Indoor Air Quality... 18 3.0 Conclusions... 18 4.0 References/Resources... 19 5.0 Acknowledgement... 19 6.0 Disclaimer... 19 Appendix A: Utility Bill Comparison... 20 Page 3

1.0 Introduction The hurricane season of 2004 was one of the most active in recent history and hit the Central Florida region especially hard with three major storms out of the 14 named weather events. One storm, Frances, took a path rarely taken by previous hurricanes; making landfall in Melbourne area and heading west-northwest across the state, turning north on the western coast and moving northward through the Tallahassee region (Fig 1). Many homes in east central Florida suffered serious damage from three hurricanes in the summer of 2004. This study documents the energy impact of retrofit options performed on four homes damaged Figure 1 Path of Hurricane Frances 2004 primarily by wind and wind-driven rain. Measured and predicted energy use data are presented as well as installed costs as reported by the homeowners. These homes offer a range of retrofit options providing data on costs and benefits of effective retrofit strategies for hot-humid climates. Envelope and duct tightness tests were performed both before and after renovations to improve energy evaluations and show any impact the retrofits may have had on these important home performance measurements. Post-retrofit testing, and in some cases monitoring, helped determine the final performance level of each home. Test results, in conjunction with a home audit, provided the information needed for an energy analysis performed with hourly simulation software (Energy Gauge USA). 1.1 Home Performance Testing Blower door and duct blaster tests were performed to establish airtightness levels. Where hurricane renovations were expected to impact leakage levels, testing was performed both before and after retrofits. Test results provided supportive inputs to the Energy Gauge USA energy analysis software for improved energy use and savings predictions. Tests of the building envelope and duct system assist in the determination of air-transported moisture that can cause damage to building components, increase energy consumption and decrease occupant comfort. Three tests using a blower door and duct blaster were performed. The first test employs the blower door and establishes a leakage rate for the house at a specific pressure (air changes per hour at 50 pascals or ACH50). (250 Pascals is equal to 1 inch water column). The next two tests use the duct blaster and yield the leakage rate of the duct system in a similar manner (cubic feet per minute of air leakage at 25 pascals or CFM25). One test measures the total leakage from the duct system to the interior and exterior of the building (CFM25total) and the second test measures leakage to the exterior of the building only (CFM25out). Page 4

1.2 Simulated Energy Use and Savings Analysis The U.S. Department of Energy (DOE) Residential Buildings Program developed the Building America Research Benchmark (Hendron, 2005) to track progress toward whole-house energy savings goals of 40-70% and onsite power production of up to 30%. The Benchmark is generally consistent with mid-1990s standard practice, as reflected in the Home Energy Rating System (HERS) Technical Guidelines (RESNET, 2002), with additional definitions for residential enduses. A series of user profiles, intended to represent the behavior of a standard set of occupants, was created for use in conjunction with the Benchmark. Energy Gauge USA software was used to determine performance of storm damaged homes relative to the Building America benchmark. In addition to whole-house energy, cooling energy was separately analyzed due to the high impact on this end-use afforded by the retrofit measures. Repairs on each case study home included roof cladding with cooler colors than were present before storm damage and in many cases improved attic insulation and/or sealing. Table 1 Predicted Annual Total Energy Comparison House BA Benchmark Pre-retrofit Post-retrofit kwh (Therms)* kwh (Therms)* Benchmark Savings kwh (Therms)* Benchmark Savings Overall Savings A 18,578 15,106 19% 13,234 29% 10% B 20,223 17,414 14% 16,487 19% 5% C 15,082 (339) 13,305 (309) 11% 13,171 (312) 12% 1% D 13,681 (267) 13,940 (368) -7% 14,040 20% 27% *Homes C & D had gas heating and hot water prior to retrofit. House D converted to all electric at during remodeling. Table 2 Predicted Annual Cooling Energy Comparison House Pre-retrofit (kwh) Post-retrofit (kwh) Cooling Savings A 4,294 3,372 21% B 6,854 5,746 16% C 5,005 4,870 3% D 6,930 3,805 45% 2.0 Case Study Examination Each home was evaluated to determine its relative performance in each of three areas: energy savings, comfort and indoor air quality. The four homes are presented here with a table describing the relevant pre-retrofit and post-retrofit construction details and homeownerprovided repair costs. Up to three years of utility bills were collected for each home to provide additional documentation of energy use. These are presented as plots in Appendix A along with cooling degree day weather profiles. Multiple factors presented complications in using the utility data, thus no formal analysis was performed. Some of these factors included: All Homes experienced storm-related power outages during the months of August and September in 2004 with up to one third of the billing cycle being lost. Page 5

Home A: while there was a noticeable energy reduction in 2005 over the previous two years this included the removal of an unknown amount of pool pumping energy (a potentially large energy end use). Home D: extensive damage in this home caused electric utility service to be shut down after the storm and not restored until June of 2006. 2.1 Home A Predicted Annual Savings Against BA Benchmark Pre-retrofit Post-retrofit 19% 29% This home was constructed in 1963, and had concrete block walls enclosing approximately 1100 square feet of conditioned space. The roof over conditioned space was sloped at a 3:12 pitch and covered with shingles, while the garage had a flat roof covered with roll roofing. A previous owner added on to the home using wood frame construction to increase the conditioned space to 1740 square feet. Approximately 300 square feet of these additions were added with flat roofs. The current residents purchased the home in 2001, and did some minor remodeling including replacement of the home s air conditioning/heating system. Most of the damage caused to the home during Hurricane Frances was due to failure of the roof covering subject to high winds, and subsequent rainwater intrusion. One flat roof section was stripped bare to the plywood decking, and there were a large amount of damaged and missing shingles. Extensive water stains were apparent on the ceiling drywall in every room when the homeowners regained access to the home after the storm. In two rooms, large holes eventually formed in the ceiling as the heavy, wet drywall failed under its own weight. A number of recessed can light fixtures and ceiling fans were also damaged due to the water. In addition, some of the water that leaked through the roof flowed down the trusses to where they meet the exterior concrete block walls, and flowed down behind the drywall where it pooled on the floor, ruining carpet and baseboards. After an inspection by an insurance adjuster, the original plan was to replace the entire roof covering, any damaged roof decking, and to cut out and patch damaged areas of the ceiling and wall board. The long lead time encountered to get the roof replaced led to additional mold growth on the ceiling drywall. As a result, the owner decided to replace entire ceiling. Old blown in fiberglass and fiberglass batts were removed and the owner took advantage of this opportunity to converted the attic to an unvented type using BioBased foam. Rather than replace the roof covering with shingles that only have a life expectancy of 15-25 years, the owner decided to utilize white standing seam metal on pitched areas of the roof with a 50 year life expectancy. For the flat roof areas, rather than using a roll roofing, built up covering, or bituminous covering with a life expectancy of 5 years, the owner used a 10-year system that includes 1 of closed cell foam sprayed on the exterior of the flat roof decking which was then Page 6

covered by reflective silver colored, spray applied, coating to protect the foam from UV deterioration. In addition, 85% of the existing incandescent lighting was converted to fluorescent by removing all recessed can lights and installing Energy Star Gossamer Wind ceiling fans with light kits and other Energy Star fixtures and bulbs. Damaged carpet was replaced with laminate cork flooring. The small, 4000 gallon swimming pool received some damage from the storm debris and, with the owners expecting a new baby and lack of previous use, decided to remove the pool. Therefore there was little to no energy used for pool pumping from 9/04 on. Table 3 Home A Construction Details Pre-Retrofit Post-Retrofit Construction date 1963 Construction type Concrete block (and 2x4 frame) Floor type / Area (ft 2 ) Slab-on-grade / 1,740 Attic / Roof type Vented / Grey shingle Sealed / White metal / Silver foam Window type Single-pane / Clear / Aluminum Glass/Floor Area 33% Insulation attic/wall/floor R16 / R4 (R11) / R0 R-20 / R-4 (R11) / R-0 Exterior wall cladding stucco Air Conditioner 3-ton, 14 SEER, heat pump Thermostat Programmable Ventilation type/amount none OA duct installed not connected Water heater Electric, 50 gal, EF 0.88 Other appliances Refrigerator, Dishwasher, Clothes dryer, Clothes Washer Fluorescent lighting 5% 85% Occupancy 2 3 (as of 9/05) Infiltration (ACH50) 9.9 6.0 Duct leakage (CFM25, total/out) 164/124 80/58 Pool pumping 240 V None 2.1.1 Post-retrofit Energy Savings Primary improvements expected to result in energy savings include the choice of a more reflective, roof covering, creation of an unvented attic that brought the ductwork inside conditioned space, and use of primarily fluorescent rather than incandescent lighting. Removal of the swimming pool was also expected to result in some energy savings. These improvements are reflected in the utility bill history plot for Home A in the appendix when comparing the postretrofit energy use in 2005 with the pre-retrofit numbers. A formal analysis of utility bill data was not performed due to the removal of unknown pool pumping energy (potentially large energy user). Page 7

2.1.2 Material Costs The roof was supplied and installed by a roofing contractor. The standing seam metal panels were 16 wide galvalume coated with a Fluoroceram coating containing 70% Kynar 500 or Hylar 5000 PVDF resin. The coating has a 20 year warranty. The metal was installed over 1x2 battens and synthetic underlayment was used. A self-adhering underlayment was used on a portion of the deck. The flat roof covering consisted of 1 of polyurethane closed cell spray foam covered with a thin layer of an elastomeric acrylic coating for UV resistance. Table 4 Home A Contractor Installed Roofing Costs Remove existing roof; install underlayment, battens, drip edge, flashings, Price not boots, vent & ridge cap; install metal roof on pitched areas broken down Install foam roof system on flat areas Total $ 14,025 The homeowner obtained several other roofing estimates from different contractors for a similar overall scope with varying materials. Table 5 Home A Roofing Estimates 30 year dimensional shingles and mod-bit granulated for flat $8,440 Aluminum standing seam metal and Bidimit for flat $16,448 30 year dimensional shingles and mod-bit granulated for flat $11,300 Standing seam metal and mod-bit granulated for flat $16,500 5-vee metal and mod-bit granulated for flat $15,300 A single vendor was used for installation of spray foam to create an unvented attic. Table 6 Home A Contractor Installed Insulation Costs 5 ½ inches (R-22) BioBased foam under pitched roof ($1.65/sqft) 1,925 3 ½ inches (R-14) BioBased foam under flat roof ($1.40/sqft) 433 3 ½ inches (R-14) BioBased foam under flat roof ($1.40/sqft) 135 Total $ 2,493 Some spray foam was also used to replace damaged insulation in wood frame exterior walls. The homeowners purchased their own ceiling fans and lights and utilized an electrician to rewire for lighting location changes and install the fans and fixtures. Table 7 Home A Lighting Costs Electrical labor $622 7 Gossamer Wind Ceiling fans with fluorescent light kits $1183 Other fluorescent fixtures and bulbs $150 Total $ 1,955 2.1.3 Opportunities For Enhanced Comfort The homeowners report a slight improvement in overall comfort after the retrofit and slightly better humidity control. It is expected that this is experienced as a result of the unvented attic providing more even temperature distribution throughout this older home, and reducing uncontrolled air infiltration, as demonstrated by pre and post envelope testing. The white metal Page 8

roof and unvented attic also provide for lower indoor air temperatures during spring and fall, reducing reliance on air conditioning. 2.1.4 Assessment Of Indoor Air Quality It is expected, although not quantified, that indoor air quality in this home post retrofit is better than pre-retrofit. The homeowners have reported less dust present in the home, presumably from the unvented attic reducing uncontrolled air flow. Although no duct sealing was conducted, the unvented attic brings the ductwork within the home s air and thermal boundaries and reduces the effect of existing duct leakage on space depressurization and subsequent uncontrolled air infiltration. In addition, the use of hard surface flooring in place of carpet is likely to reduce the presence of dust and dust mites. Lastly, the entire home needed to be repainted, the homeowners used paint classified as containing low and zero volatile organic compounds (VOC). The use of the unvented attic which reduced the Air Changes Per Hour at 50 pascals (ACH50) from 10 down to 6 has caused the homeowner to consider adding mechanical ventilation for better perceived indoor air quality. The owner has also been considering the addition of supplemental dehumidification for enhanced comfort. Spot ventilation is present via bath fans, windows, and exterior vented kitchen range hood to remove intermittent sources of humidity, but it is rarely used. The owner has purchased equipment and installed necessary ductwork to implement the mechanical ventilation / supplemental dehumidification scheme shown in the following figure, but has not yet made the scheme operational. Table 8 Home A Mechanical Ventilation / Supplemental Dehumidification Costs 50 pint per day dehumidifier 180 6 flex duct 25 feet 41 10 x 10 ductboard box 12 10 x 10 filter back grill w/pleated filter 21 6 duct collar with manual damper 8 homeowner purchased Total $ 262 Figure 2 Dehumidified Return Plenum w/aircycler Control Page 9

2.2 Home B Predicted Annual Savings Against BA Benchmark Pre-retrofit Post-retrofit 14% 19% This 1,700 square foot home in Cocoa, Florida was damaged by hurricanes Frances and Jeanne. A white metal roof was chosen to replace the damaged shingles to reflect summer heat and thereby reduce cooling energy use. The shingles were not removed but left in place below the newly installed metal. Table 9 Home B Construction and Testing Details Pre-Retrofit Post-Retrofit Construction date 1991 Construction type Wood-frame Floor type / Area (ft 2 ) Slab-on-grade / 1,710 Attic / Roof type Vented / Dark shingle Vented / White metal Window type Single-pane / Clear / Aluminum Glass/Floor Area 16% Insulation attic/wall/floor R19 / R11 / R0 Exterior wall cladding Natural cedar (med-dark) Air Conditioner 3-ton, 9 SEER, heat pump Thermostat Standard Ventilation None Water heater Active Solar, electric backup Energy Star appliances H-axis Clothes washer Other appliances Refrigerator, Dishwasher, Clothes dryer Fluorescent lighting 30% Occupancy 6 Infiltration (ACH50) 7.0 Duct leakage (CFM25, total/out) 250/180 2.2.1 Post-retrofit Energy Savings A before/after energy comparison was made possible with monitored data collected at the home in 2004 and 2005. Indoor, outdoor and attic temperatures along with air conditioner energy use and runtime were analyzed to assess performance. Table 10 Home B Measured 9-Week Performance Highlights (June 25 August 31) Dark Shingle 2004 White Metal 2005 Reduction % Savings Cooling Energy (kwh) 2,170 1,749 420 Cooling Cost (@ $0.10/kWh) $217 $175 $42 19% Avg. Peak Attic Temp ( F) 111 F 96 F 15 F Avg. Peak Ambient Temp ( F) 89.4 F 88.6 F 0.8 F Notes: Energy estimate based on linear fit accounting for ambient temperature difference Page 10

A nine-week period in the summer of 2005 show the white metal roof providing a 19% savings in air conditioner energy over the same period in 2004 when shingles were in place. Similar savings were seen in a more rigorous 2002 study comparing side-by-side homes in Ft. Myers, Florida. (Parker, Sonne, and Sherwin 2002) Figure 3 shows the effect on cooling energy use by plotting daily air conditioner energy against the difference in indoor and outdoor temperature. This approach helps account for the difference in average outdoor temperature between 2004 (79.5 F) and 2005 (82.5 F). The average-day plot (figure 4) illustrates the effect of the white roof on attic temperature and cooling power. In this plot, average values of Figure 3 Shingle vs. White Metal temperature and power for each hour over the 9-week data period result in an average 24 hour profile. The attic is noticeably cooler under the white metal roof (15 F at peak) during the day but is actually warmer at night, due to the warmer nighttime temperatures in 2005. Figure 4 Average Summer Conditions Page 11

2.2.2 Material Costs The new roof was purchased and installed by the homeowner. A three foot wide, exposed fastener, steel panel proved the most economical choice that included galvalume substrate and Kynar paint finish. Galvalume is an aluminum-zinc alloy that has shown improved performance over galvanized roofing in tests conducted by BIEC International. Kynar is a fluoropolymer paint available through many manufacturers and reputed to outlast siliconized polyester based paints. Warranties were found to be generally longer on Galvalume and Kynar products than with typical galvanized metal panels. The product purchased for this project came with a 40-year warranty on the finish. Table 11 Home B Metal Roofing Costs Material Only 26 ga, 3 ft, exposed fastener, Galvalume panel w/ Kynar paint 4,100 sqft $ 6,300 (includes flashing, gutters and screws) Synthetic Underlayment (5-1,000 sqft rolls) 5,000 sqft $ 750 Skylight Flashing 2 $ 150 Caulk & Pipe Boots $ 200 homeowner purchased Total $ 7,400 The shingle replacement estimate provided by the insurance adjuster included all material and labor costs with a 29% profit margin and special increases associated with post-disaster market conditions. Table 12 Home B Estimated Shingle Replacement Cost Material + Labor (includes special market conditions increase) Dimensional Shingle 3,900 sqft $ 6,500 30lb Felt Underlayment $ 550 Miscellaneous flashing/boots $ 700 Labor (including shingle removal) $ 4,200 Total $11,950 The cost comparison shown here is an isolated example in a local market impacted by conditions following unusual hurricane activity. Material and labor price instability are expected under such circumstances and will certainly vary from one situation to another but are presented here for comparison purposes. 2.2.3 Economic and Other Benefits While metal and shingle roofing costs vary with choice of material and difficulty of installation, metal roofing is generally more expensive than shingles. The energy savings shown here would take many years to offset the increased cost of metal but other benefits to consider include: Lasts about 3 time longer (50 yrs vs. 17 yrs) Resists harsh weather, wind and fire Possible insurance discounts to homeowners (none in this case) Minimum 25% recycled content (as high as 50%) 100% recyclable at end of useful life Sources: http://www.metalroofing.com/ (Metal Roofing Alliance) http://www.wbdg.org (National Institute of Building Science) Page 12

2.2.4 Installation Codes in many jurisdictions allow for at least two layers of roofing material before removal of existing cladding is required. The determining factor for removal is the weight of material and metal roofing meets the requirements with less difficulty as it is far lighter than shingles on a per square foot basis. Shingle removal is labor intensive and the material must be hauled away. The existing shingles, in this case, were left in place since damage was limited to individual shingle tabs and there was no major exposure of underlayment or roof decking. Two options were considered for installing metal over shingles: (1) install 1x4 purlins or battens over the shingles prior to affixing the metal, and (2) install new underlayment over the shingles and then affix the metal panels directly to the shingles. In either case, manufacturer s recommendations should be followed as some products are designed for installation over solid decking while others can be installed on open framing. For this project, 5-foot wide synthetic underlayment was nailed to the shingles followed by fastening of the metal panels. The major drawback of this approach was a marked increase in oil-canning, a common imperfection in metal roofing related to wrinkling of the panels upon installation. While some amount of oilcanning can be expected in any installation its presence does not generally influence performance. 2.2.5 Opportunities for Enhanced Comfort An average peak attic temperature 15 F lower than before the retrofit is expected to provide cooler peak interior temperatures during future power outages when air conditioning is unavailable. 2.2.6 Assessment of Indoor Air Quality The retrofit is expected to have little or no impact on indoor air quality. 2.3 Home C Predicted Annual Savings Against BA Benchmark Pre-retrofit Post-retrofit 11% 12% This 1, 960 square foot home in Rockledge, Florida was the least damaged of the four houses chosen in this evaluation. There were loss of shingles, but only a small amount of water actually came through to the ceiling. The damage to the ceiling was slight and when allowed to dry, only needed to be repainted. The fiberglass insulation in the attic was not affected either. The replacement roof for this home was purchased and installed by the homeowner. The original dark, 3-tab asphalt shingles were removed and replaced with white ones. Page 13

Table 13 Home C Construction Details Pre-Retrofit Post-Retrofit Construction date 1987 Construction type Wood-frame Floor type / Area (ft 2 ) Slab-on-grade / 1,960 Attic / Roof type Vented / Dark shingle Vented / White shingles Window type Single-pane / Clear / Aluminum Glass/Floor Area 10% Insulation attic/wall/floor R19 / R4 / R0 Exterior wall cladding Stucco Air Conditioner 4-ton, 10SEER, straight cool Heating 0.67 AFUE Natural gas furnace Thermostat Standard Ventilation None Water heater 34KBtu Natural gas 40 gallon (tank) Other appliances Refrigerator, Dishwasher Fluorescent lighting 10% Occupancy 2 to 3 Infiltration (ACH50) 6.0 Duct leakage (CFM25, total/out) 233 /199 2.3.1 Post-retrofit Energy Savings A small amount of energy savings are expected as a direct result of replacing the dark asphalt shingles with lighter colored ones. Payback on such a measure is immediate however, as this is considered a no-cost upgrade. An estimated 3% of annual cooling costs will be saved with this retrofit measure. Similar savings were seen in a more rigorous 2002 study comparing side-byside homes in Ft. Myers, Florida. (Parker, Sonne, and Sherwin 2002) 2.3.2 Material Costs The following cost breakdown was provided by the homeowner who purchased and installed the new roof. Table 14 Home C Shingle Roofing Costs Material Only 3-tab Asphalt Shingles (White) 3,000 sqft $ 1,410 15# Felt Underlayment 3,000 sqft $ 255 Delivery & Taxes $ 350 Other Material $ 1,350 Day Labor $ 1,170 homeowner purchased Total $ 4,535 2.3.3 Opportunities For Enhanced Comfort Slightly lower attic temperatures are expected with the white shingle roof installed. The average maximum attic temperature was 6.6 F lower than the dark shingle base case in the Ft. Myers study mentioned above. During future power outages this may translate into cooler interior peak temperatures while air conditioning is unavailable. Page 14

2.3.4 Assessment Of Indoor Air Quality The retrofit is expected to have little or no impact on indoor air quality. 2.4 Home D Predicted Annual Savings Against BA Benchmark Pre-retrofit Post-retrofit -7.5% 20% This home was the most severely damaged of the four buildings in the analysis. A section of the rear portion of the roof was destroyed allowing water to enter into the dwelling which resulted in severe damage to the interior. As a result, the interior had to be completely demolished and rebuilt per recommendations. This retrofit included light roof color, unvented or sealed attic, sealed air distribution system, higher efficient heating and cooling system and double pane low-e windows. In addition, the gas water heater that was located within the conditioned space was replaced by an electric unit (there were 2 primary reasons for the replacement -1) age of the unit and 2) the electric unit did not require combustion/dilution air). Table 15 Home D Construction Details Pre-Retrofit Post-Retrofit Construction date 1966 Construction type Concrete block Floor type / Area (ft 2 ) Slab-on-grade / 1,440 Slab-on-grade / 1590 Attic / Roof type Vented / Dark fiberglass composite panel Sealed / Light fiberglass composite panel Window type Single / Clear / Aluminum Dbl-pane / Clear / Aluminum Glass/Floor Area 12% Insulation attic/wall/floor R11 / R0 / R0 R20 / R0 / R0 Exterior wall cladding Painted block Air Conditioner 2.5-ton, 8SEER, straight-cool 3-ton, 13SEER, heat pump Thermostat Standard programmable Ventilation None Water heater 40 gal Natural gas 40 gal Electric Other appliances Refrigerator, Dishwasher, Clothes dryer Fluorescent lighting 10% Occupancy 2 Infiltration (ACH50) 7.5 estimated 5.0 Duct leakage (CFM25, total/out) 220/175 estimated 32/0 Page 15

The homeowner opted to slightly increase the conditioned floor space by incorporating the small storage area (part of the original attached garage) in the front of house as part of the living area. This was an increase of approximately 150 square feet (1500 cubic feet of volume). 2.4.1 Post-retrofit Energy Savings As a result of considering opportunities for energy efficiency during the retrofit process, the owners expected to experience lower utility bills as a result of their repair decisions. Primary improvements that were expected to result in energy savings include the choice of a more reflective, energy efficient roof covering, creation of an unvented attic that brought the ductwork inside conditioned space, and increased heating and air conditioned equipment efficiency. Table 16 Home D Contractor Installed Roofing Costs Remove existing roof Price not broken down Apply synthetic underlayment Apply batten system Install drip edge, flashings, boots, kitchen vent and ridge cap Install light fiberglass composite panel roof Total (approximate) $ 15,000 Figure 5 Finished light colored composite roof panels installed Table 17 Home D Contractor Installed Insulation Costs 5 ½ inches (R-22) Icynene foam under pitched roof (~$2/sqft) $3180 Total $ NC Material and labor costs were donated by Icynene to research post retrofit energy consumption Page 16

Figure 6 Sealed attic with spray foam insulation (Icynene ). Note the duct work is below the insulation, which places it within the air & thermal boundaries. Table 18 Home D Contractor Installed HVAC Costs Remove existing system Price not broken down New sealed air distribution system New heat pump Total (approximate) $ 6000 Table 19 Home D Contractor Installed Envelope and Other Improvement Costs New electric water heater 500 Interior renovation (walls, floors and cabinets) 6000 New windows (dbl pane clear) 3,500 Total (approximate) $ 9,500 2.4.2 Opportunities For Enhanced Comfort This home is in the final stages of remodeling. The homeowners have had a long uphill battle with insurance issues, finances and contractors. It is hoped that by late summer or early fall of 2006, the home will finally be finished (at the time of this report, the drywall has been hung and taped). Comfort enhancements will include some sound control with the Figure 7 www.soundproofwindows.com/comparison.html installation of the double pane windows (figure 7) and a slight increase in the thermal losses, especially in the winter months. Page 17

The new heat pump and tight duct work should provide more uniform temperature and humidity control throughout the house. The new system is now totally within the thermal and air boundaries of the building. The coolest air no longer needs to pass through the hottest portion of the house (attic) as it is delivered to the rooms. In addition, there appeared to be a fairly large return side leak to the air handler in the old system. The air associated with that leak was pulled directly from the attic space. (The system was not tested because of water damage to the structure.) Slightly lower attic temperatures are expected with the white shingle roof installed. The average maximum attic temperature was 6.6 F lower than the dark shingle base case in the Ft. Myers study mentioned above. During future power outages this may translate into cooler interior peak temperatures while air conditioning is unavailable. 2.4.3 Assessment Of Indoor Air Quality The removal of the gas appliances from within the conditioned space and converting the vented attic space to an unvented attic eliminates the sources of potential pollutants (combustion gases, moisture, insulation particles, and various dust particles. Also, there should be enhanced humidity control since the new unit is not able to pull hot humid attic air into the return air stream. 3.0 Conclusions Home repairs necessitated by storm damage offer an excellent opportunity to reduce energy use, improve comfort and enhance resistance to future storms. An excellent example is reroofing, a repair required by each of the case study homes. This is a common post-hurricane repair that, with the right material choice, can reduce summertime cooling costs as well as improve indoor conditions during future power outages. A decade of research at the Florida Solar Energy Center clearly shows that a white reflective tile or metal roof can reduce space-cooling loads by 20% or more. Each case study home took advantage of roof cladding with a higher reflectance than the original. Energy savings from storm repairs on four homes were estimated through detailed computer simulation and in one case measured directly in a before/after fashion. Computer-derived Wholehome energy savings ranged from a high of 27%, in the most extensively renovated home, to a low of 1% in the home with a light-colored shingle roof replacement. Cooling energy was also analyzed as it typically makes up the largest single end use of whole-home energy consumption in Central Florida. Cooling savings derived from the computer model ranged from 3% to 45% and, as in the case of whole home energy, was directly impacted by the level of home repair. Measured data obtained from one home showed a 19% reduction in cooling energy use after the dark shingle roof was replaced with white metal. This fell roughly in line with computer estimated cooling savings of 16%. Up to three years of utility bills were collected for each home to provide additional documentation of energy use. These are presented as plots in Appendix A along with cooling degree day weather profiles. Multiple factors presented complications in using the utility data, thus no formal analysis was performed. Page 18

4.0 References/Resources Parker, D., Sonne, J., Sherwin, J., "Comparative Evaluation of the Impact of Roofing Systems on Residential Cooling Energy Demand in Florida," Proceedings of ACEEE 2002 Summer Study, American Council for an Energy Efficient Economy, Washington, DC, August 2002. (http://www.fsec.ucf.edu/bldg/pubs/coolroof/) http://www.eere.energy.gov/buildings/disaster_recovery/dr_consumers.html http://www.homeenergy.org/katrina.html Operation Fresh Start is a project of the National Center for Appropriate Technology (NCAT). It began in 1997 with support from the Department of Energy's Office of Energy Efficiency and Renewable Energy (EERE) in response to 1997 flooding in Red River, North Dakota. http://freshstart.ncat.org/rebuild.htm Hendron, R. (2005). Building America Research Benchmark Definition, Version 3.1, Updated July 14, 2004. 40 pp.; NREL/TP-550-36429. Residential Energy Services Network (RESNET). 2002. Mortgage Industry National Home Energy Rating Systems Accreditation Standards. Chapter 3, pp. 29-54. San Diego, CA: RESNET. 5.0 Acknowledgement This work is sponsored, in large part, by the US Department of Energy (DOE), Office of Energy Efficiency and Renewable Energy, Buildings Technologies Program under cooperative agreement number DE-FC26-99GO10478. This support does not constitute an endorsement by DOE of the views expressed in this report. The authors appreciate the encouragement and support from the homeowners who provided their homes and Mr.Terry Logee, Mr. George James, Mr. Ed Pollock, and Mr. William Haslebacher of the US Dept of Energy. 6.0 Disclaimer This report was prepared as an account of work sponsored by an agency of the United States government. Neither the United States government nor any agency thereof, nor any of their employees, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe privately owned rights. Reference herein to any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise does not necessarily constitute or imply its endorsement, recommendation, or favoring by the United States government or any agency thereof. The views and opinions of authors expressed herein do not necessarily state or reflect those of the United States government or any agency thereof. Page 19

Appendix A: Utility Bill Comparison Page 20

Page 21