HIGH TEMPERATURE HEAT PUMPS TECHNOLOGY FOR GEOTHERMAL DISTRICT HEATING APPLICATIONS



Similar documents
INTRODUCING GEOTHERMAL ENERGY INTO EXISTING DISTRICT HEATING SYSTEMS SUCCESSFUL EXAMPLES FROM SLOVAKIA

District heating and district cooling with large centrifugal chiller - heat pumps

Daikin Altherma hybrid heat pump. The natural combination

Field test of a novel combined solar thermal and heat pump system with an ice store

How Ground/Water Source Heat Pumps Work

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres

The natural ombination

Vitocaldens 222-F Compact Gas-Hybrid appliance

Daikin Altherma. hybrid heat pump. The natural combination

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015

Heating and cooling with wastewater

ROTEX gas hybrid heat pump. A strong team.

Natural geothermal energy.

Energy savings in commercial refrigeration. Low pressure control

UNIT 2 REFRIGERATION CYCLE

Heat Recovery from Data Centers. Guided Tour in Kista, January 21, 2015

Neighbourhood Energy in Vancouver Sewage Heat Recovery within a city-wide strategy

Nordic Heat Pump Product Guide

Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *

Performance Evaluation of a Heat Pump System for Simultaneous Heating and Cooling

Thermal Coupling Of Cooling and Heating Systems

LG Electronics AE Company, Commercial Air Conditioning

Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"

DAikin Altherma low temperature heat pump. end user leaflet

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

Ground Source Heat Pumps The Fundamentals. Southington, Connecticut John F. Sima III P.E.

HVAC Systems: Overview

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

HEAT PUMPS A KEY COMPONENT IN LOW CARBON FUTURE

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Create the right atmosphere with renewables.

Crowne Plaza Copenhagen Towers The world s greenest hotel

Study of a Supercritical CO2 Power Cycle Application in a Cogeneration Power Plant

AQUACIAT2 HYBRID THE COMPACT DUAL-ENERGY SOLUTION HEAT PUMP & GAS BOILER. Cooling and heating capacities of 45 to 80 kw AVAILABLE 2 ND QUARTER OF 2014

25. Fachtagung von GEOTHERMIE.CH

Appendix C. Minimum Equipment Efficiency Standards

Creating Efficient HVAC Systems

How To Use A Water Source Heat Pump

6 18 A steam power plant receives heat from a furnace at a rate of 280 GJ/h. Heat losses to the surrounding air from the steam as it passes through

Typical Cooling Load Profile

Exploitation Tests of Borehole Heat Exchangers in the Laboratory of Renewable Energy Sources in Miekinia Poland

In touch with heat pumps for industry and commerce

Upper Occoquan Service Authority Centreville, Virginia A Case Study

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Our Deep Geothermal Energy Potential: A Case Study in Saskatchewan with Application Throughout the Western Canadian Sedimentary Basin

Federation of European Heating, Ventilation and Air-conditioning Associations

OPTIMAL POLYGEN COOLING CONCEPT FOR ST. OLAVS HOSPITAL IN TRONDHEIM, NORWAY

Mechanical Heat Pumps Using Water as Refrigerant for Ice Production and Air Conditioning. Case studies

PERFORMANCE EVALUATION OF NGCC AND COAL-FIRED STEAM POWER PLANTS WITH INTEGRATED CCS AND ORC SYSTEMS

The natural ombination

COFELY DISTRICT ENERGY DELIVERING LOW CARBON SUSTAINABLE ENERGY SOLUTIONS

Intelligent control system with integrated electronic expansion valves in an air-conditioning system operating at a Telecom telephone exchange

Energy consumption and heat recovery of refrigeration system in modern Arena

Dallas/Fort Worth International Airport District Energy Plant Upgrades Project Making More with Less Sustainable Communities Conference Dallas, TX

GEOTHERMAL HEATING AND COOLING INTRODUCTION

ALONE. small scale solar cooling device Project No TREN FP7EN Project No TREN/FP7EN/ ALONE. small scale solar cooling device

Training in Renewable Energy INFORSE-Europe proposal for implementation of the Renewable Energy Directive Draft 28/

A knowledge-based system for Waste Heat Recovery. Richard Law

Food industry Prosecc industry Heat & power (Production of district heating & cooling) Food industry Process industry Logistic centres Sport arenas

Hybrid heat pumps. saving energy and reducing carbon emissions

A NEW DESICCANT EVAPORATIVE COOLING CYCLE FOR SOLAR AIR CONDITIONING AND HOT WATER HEATING

HEAT PUMPING AND REVERSIBLE AIR CONDITIONING; RETROFIT OPPORTUNITIES IN A LABORATORY BUILDING. Campus du Sart Tilman, B49, B-4000 Liège, Belgium

HEAT RECOVERY FROM CHILLED WATER SYSTEMS. Applications for Heat Reclaim Chillers

How To Calculate The Performance Of A Refrigerator And Heat Pump

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE

Three main techniques are used to exploit the heat available: geothermal aquifers, hot dry rocks and ground-source heat pumps.

GAS HEATING IN COMMERCIAL PREMISES

AdSORPTION CHILLER NAK

New technical solutions for energy efficient buildings

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now

Geothermal. . To reduce the CO 2 emissions a lot of effort is put in the development of large scale application of sustainable energy.

Lesson 36 Selection Of Air Conditioning Systems

Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle

Hybrid system. Energy-efficient and environmentally friendly

HEAT PUMP FOR DISTRICT COOLING AND HEATING AT OSLO AIRPORT, GARDERMOEN

Continuous flow direct water heating for potable hot water

ECOCIAT. Domestic hot water heat recovery unit

COMPARISON CONCERNING TO THE COGENERATION SYSTEMS DEVELOPMENT

Increasing the evaporation temperature with the help of an internal heat exchanger

English version. Manual for Determination of Combined Heat and Power (CHP)

Ambient Energy Fraction of a Heat Pump

Top Technology for Industry, Agriculture, Business and Communities

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

The Second Law of Thermodynamics

Three-years operation experience of a ground source heat pump system in Northern Greece

Condensing Economizers Workshop Enbridge Gas, Toronto. MENEX Boiler Plant Heat Recovery Technologies. Prepared by: Jozo Martinovic, M A Sc, P Eng

Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions

High Pressure Ammonia Systems New Opportunities

Small-Scale Solar Heating and Cooling Systems

DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description

The Central Solar Heating Plant with Aquifer Thermal Energy Store in Rostock - Results after four years of operation

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

CGC s Hybrid System Loop Control

ARP Food Industry, Portugal

Sea Water Heat Pump Project

In the compression-refrigeration loop (air conditioning), which is likely to be warmer? 1. Condenser coil 2. Evaporator coil

Transcription:

Leszek WOJTAN FRIOTHERM AG Zürcherstrasse 12 8401 Winterthur, Switzerland leszek.wojtan@friotherm.com Technika Poszukiwañ Geologicznych Geotermia, Zrównowa ony Rozwój nr 1/2013 HIGH TEMPERATURE HEAT PUMPS TECHNOLOGY FOR GEOTHERMAL DISTRICT HEATING APPLICATIONS ABSTRACT Already since more than three decades high capacity centrifugal heat pumps are reducing CO 2 emissions and are supplying hot water up to 90 C to district heating systems. In most cases the heat is recovered from low temperature heat sources like waste, river and sea water. However, with the centrifugal heat pump technology energy can also be exploited from high temperature heat sources like geothermal water. With an intelligent heat pump system the district heating return temperature can be boosted and at the same time the exploitation of the geothermal heat source can be increased. In this paper four examples of large centrifugal heat pumps in district heating applications using ground, water from the Neocomian and Dogger aquifers will be presented. The heating capacity of presented examples ranges from 5'000 to 8'650 kw. KEY WORDS High temperature heat pumps, district heating, centrifugal compressor, ground water, geothermal water, Neocomian aquifer, Dogger aquifer * * * 1. GROUND WATER Ground water with the mean temperature of 14 C is the most cost-effective heat source from the investment point of view. In contrary to river or lake water the temperature of ground water is almost constant even in the winter period. In summer, ground water can be used for cooling of heat pumps in chiller-mode and rejected heat may be stored underground for reuse during the heating season. With a 2-stage unit heat may be lifted up to 90 C. Direct use of ground water as a heat source requires a special design of evaporator. However, installations with an intermediate heat exchanger between ground water and clean chilled water are also widely used. Even if there is an additional water loop and pump this 161

solution offers a very good flexibility. Figures 1a and 1b show simplified schemas of two-stage heat pump with the heating capacity of 5'000 kw designed for a project in the region Île-de-France. In winter and intermediate season the heat pump produces hot water at 80 C and chilled water at 5 C simultaneously. As the cooling demand especially in winter is reduced, the required heat source capacity may be completed from the ground water by means of an intermediate heat exchanger. As shown in Figure 1a, the compressors are connected in series producing very high isentropic lift. The coefficient of performance (COP) for heating is 3.0 and if the complete cooling capacity of 3'350 kw may be used, the total COP for heating and cooling rises up to 5.0. a) b) Fig. 1. Simplified schema of heat pump UNITOP 23/22 (project Île-de-France): a) in 2-stage operation for hot water production at 80 C, b) in 1-stage operation. Compressors in parallel Rys. 1. Uproszczony schemat pompy ciep³a UNITOP 23/22 dla projektu Île-de-France: a) dwustopniowy tryb pracy do wytwarzania wody o temperaturze 80 C. Sprê arki po³¹czone szeregowo, b) jednostopniowy tryb pracy. Sprê arki po³¹czone równolegle The cooling demand rises in summer and at the same time the need of heat production for sanitary water heating is limited. As shown in Figure 1b, the compressors may be connected during the summer period in parallel to increase the cooling capacity of the heat pump up to 6'200 kw. Both compressors may be operated simultaneously or individually, what offers very effective partial load regulation. The condenser is cooled indirectly by the geothermal water pumped back to the geothermal well at 30 C. The switching from 2-stage (compressors in series) to 1-stage operation (compressors in parallel) is performed fully automatically by the combination of valves. 162

The performance data of the heat pump for both operating modes are shown in Table 1. It may be seen that in summer mode, the value of COP for cooling in 1-stage operation rises up to 5.1. Table 1 Performance data of UNITOP 23/22 Tabela 1 Dane techniczne pompy ciep³a UNITOP 23/22 Winter mode Summer mode Cooling capacity 3 350kW 6 200kW Evaporator regime 12/5 C 15/5 C Heating capacity 5 000kW 7 400kW Condenser regime 50/80 C 16/32 C COP cooling 2.0 5.1 COP heating 3.0 COP total 5.0 Figure 2 shows a general arrangement of UNITOP 23/22. The unit with the dimensions 3'800 9'000 3'200 may be delivered as a complete package ready for the installation on site. Thanks to the possibility of operation in different modes, very effective partial load conditions and the heat source balancing with geothermal water in winter, the heat pump adapts to very various operating conditions and can be operated all-the-year with the highest efficiency. Fig. 2. General arrangement of 2-stage heat pump UNITOP 23/22 for hot water production at 80 C Rys. 2. Rysunek z³o eniowy 2-stopniowej pompy ciep³a UNITOP 23/22 do wytwarzania wody ciep³owniczej o temperaturze do 80 C 163

2. WATER FROM THE NEOCOMIAN AQUIFER In February 2013 DALKIA FRANCE commissioned the first geothermal installation using water from the Neocomian aquifer, which provides heat to 3'500 accommodations and two large public buildings in the commune Le Plessis-Robinson in the southwestern suburbs of Paris. The heat source is water at 39 C with the volumetric flow of 200m3/h exploited from a 900 m deep geothermal well. Between geothermal and evaporator water an intermediate heat exchanger with a temperature gap of 1 C has been installed. The geothermal water is cooled down to 15 C and injected into a geothermal well. The extracted heat is then upgraded to 70 C by means of heat pumps. After the long study the solution with two FRIOTHERM's 1-stage heat pumps type UNITOP 22 has been chosen. As shown in Figure 3, the evaporators and condensers are connected counter-currently in series. This arrangement allows equalising of compressors isentropic lifts and increases significantly the COP value. The return temperature from district heating network varies between 40 and 50 C. The technical data of heat pumps are shown in Table 2. Fig. 3. Heat pumps arrangement (project Le Plessis-Robinson) Rys. 3. Uk³ad pomp ciep³a w projekcie Le Plessis-Robinson Figure 4 shows the annual heat duration curve for the district heating network of commune Le Plessis-Robinson. The maximum heating capacity of installed heat pumps of 6'850 kw with the partial load operation covers more than 78% of the annual heating demand. During the coldest days the complementary heat is produced by means of gas boilers. It is very important to design the heat pumps for the basic load of the district heating, what maintain the maximal number of operating hours with the highest heat pump/-s performance. 164

Table 2 Performance data of UNITOPs 22 Tabela 2 Dane techniczne pompy ciep³a UNITOP 22 HP2 HP1 Cooling capacity 2 600 kw 2 950 kw Evaporator regime 25/14 C 38/25 C Heating capacity 3 250 kw 3 600 kw Condenser regime 45/57 C 57/70 C COP heating 4.50 5.00 COP total 4.75 Fig. 4. Annual heat load duration curve for Le Plessis-Robinson (DALKIA France) Rys. 4. Wykres uporz¹dkowany rocznego zapotrzebowania na moc ciepln¹ dla projektu Le Plessis-Robinson (DALKIA France) Figure 5 shows a general arrangement of 1-stage heat pump UNITOP 22 designed for Le Plesssis-Robinson project. The dimensions of heat pump are 5'400 x 2'000 x 3'000. The units have been designed to fit in the existing room of heating plant. 3. WATER FROM THE DOGGER AQUIFER As found by Michard G. et al. (1988), waters from the Dogger formation of the Paris basin utilized for heating, have a chlorinity in the range 0.07 0.6 mole/litre and a temperature in the range 48 80 C. However, most of the Dogger geothermal wells provide water at 165

Fig. 5. General arrangement of 1-stage heat pump UNITOP 22 for hot water production at 70 C (project Le Plessis-Robinson) Rys. 5. Rysunek z³o eniowy 1-stopniowej pompy ciep³a UNITOP 22 do wytwarzania wody ciep³owniczej o temperaturze do 70 C (projekt Le Plessis-Robinson) temperatures around 70 C, what allows a direct use of geothermal heat transferred into a district heating network in the intermediate heat exchangers. The flows of geothermal water from the Dogger nappe of the Paris basin are in the range of 250 m3/h. Figure 6 shows titanium heat exchangers of a geothermal installation with Dogger water in the region Île-de-France. The volumetric flow of Dogger water is 280 m3/h and the Fig. 6. Titanium heat exchangers of a geothermal installation with Dogger water Rys. 6. Tytanowy wymiennik ciep³a instalacji geotermalnej z wod¹ ze zbiornika utworu jurajskiego doggeru 166

temperature oscillates around 76 C. Depending on the network return temperatures, the thermal power transferred into a district heating varies between 6'300 and 11'000 kw. The utilisation of geothermal heat in the most of district heating systems is limited by the high return temperature from the network. This effect in magnified especially during the winter time, when the return temperatures in some installations may increase even up to 60 C. As a consequence, geothermal water with a relatively high temperature has to be injected into a geothermal well. An excellent solution to boost the geothermal wells' exploitation even at high return temperatures is offered by centrifugal heat pumps. The most efficient way of implementation, is the installation of heat pump for the cooling of district heating water before entering into a geothermal heat exchanger. Reduced district heating water temperature allows to recuperate more heat from geothermal water. Figure 7 depicts such type of arrangement for the mentioned before installation in the region Île-de-France. The district heating water is cooled in the heat pump's evaporator from 55 to 37.5 C, then is reheated in two stages firstly by the geothermal water up to 67.2 C and finally in the condenser up to 89 C. In this case, the use of heat pump increases the exploitation of heat from geothermal water by 5'550 kw. Fig. 7. Heat pump arrangement for boosting of geothermal well exploitation Rys. 7. Uk³ad pompy ciep³a zwiêkszaj¹cy eksploatacjê energii z odwiertu geotermalnego Depending on the customer's needs, different heat pumps arrangement may be proposed. Figure 8 presents a very effective use of the heat pump for a boosting of geothermal well exploitation in the district heating network with higher volumetric flow. The return flow is split into two streams. The evaporator gets the same volumetric flow as the flow of geothermal water and the rest flows through the condenser. The evaporator water is cooled down by 10.3 C and then is reheated by the Dogger water up to 71 C. The extracted heat in the evaporator is rejected by the heat pump into the condenser water, lifting its temperature 167

up to 61.6 C. After that, both hot water streams flow together producing hot water at 67.5 C. The use of heat pump in this application increases the thermal power extracted from geothermal water by 3'000 kw. As the required temperature lift is not high, the COP of the heat pump gives very high value of 6.3. Fig. 8. Heat pump arrangement for boosting of geothermal well exploitation for district heating network with higher volumetric flow Rys. 8. Uk³ad pompy ciep³a zwiêkszaj¹cy eksploatacjê energii z odwiertu geotermalnego dla sieci ciep³owniczych o wiêkszych przep³ywach wolumetrycznych It is obvious that volumetric flow and return temperature in district heating networks vary continuously. Thus, it is of crucial importance in the heat pump design to take into account all possible operating conditions. Figure 9 shows the picture of the FRIOTHERM's heat pump type UNITOP 33C widely used in the high temperature geothermal applications. Fig. 9. Heat pump UNITOP 33C designed for boosting of geothermal well exploitation with Dogger water Rys. 9. Pompa ciep³a UNITOP 33C zaprojektowana do zwiêkszenia eksploatacji ciep³a z odwiertu geotermalnego z wod¹ ze zbiornika 168

CONCLUSIONS The presented high temperature centrifugal heat pump technology has been developed over the last 35 years and offers mature solutions for geothermal installations. It enables the exploitation of heat from ground and waters from the Neocomian aquifer by upgrading it to the temperature levels required by the district heating networks. Furthermore, the heat pumps may significantly increase the exploitation of heat from water hosted by the Dogger aquifer with very high COP values. As presented above, very different heat pumps arrangements are possible. Their design depends on heat source temperatures, heat source volumetric flow, condenser outlet temperature, volumetric flow and return temperature of district heating water, partial load conditions and so on. Each geothermal project requires an individual study to optimise heat pump design and its hydraulic implementation for the operation in all possible district heating conditions with the highest performance. REFERENCES MICHARD G., BASTIDE J.-P., 1988 Etude geochimique de la nappe du dogger du Basin Parisien. Journal of Vulcanology and Geothermal Research, Volume 35, issues 1 2, September, (1988), 151 163. TECHNOLOGIA WYSOKOTEMPERATUROWYCH POMP CIEP A DLA CIEP OWNICTWA SIECIOWEGO W ZASTOSOWANIACH GEOTERMALNYCH STRESZCZENIE Ju od ponad trzech dziesiêcioleci odœrodkowe pompy ciep³a zasilaj¹ sieci ciep³ownicze wod¹ o temperaturach do 90 C, przyczyniaj¹c siê do znacznej redukcji emisji CO 2. W wiêkszoœci przypadków do odzysku ciep³a u ywane s¹ niskotemperaturowe Ÿród³a ciep³a, takie jak œcieki, woda rzeczna b¹dÿ morska. Jednak e przy u yciu technologii odœrodkowych pomp ciep³a mog¹ byæ równie eksploatowane inne dolne Ÿród³a ciep³a, takie jak woda geotermalna. Zastosowanie inteligentnego systemu pompy ciep³a umo liwia podwy szenie temperatury powrotu sieci ciep³owniczej do wymaganego poziomu przy jednoczesnym zwiêkszeniu eksploatacji Ÿród³a geotermalnego. Artyku³ prezentuje cztery przyk³ady zastosowañ odœrodkowych pomp ciep³a du ej mocy w aplikacjach ciep³owniczych u ywaj¹cych wody gruntowej ze zbiorników w utworach jurajskich (neokomu i doggeru). Moc cieplna u ytych urz¹dzeñ waha siê w zakresie od 5 000 do 8 650 kw. 169

S OWA KLUCZOWE Wysokotemperaturowe pompy ciep³a, ciep³ownictwo sieciowe, odœrodkowe sprê arkowe pompy ciep³a, woda gruntowa, woda geotermalna, zbiornik wodonoœny neokomu, zbiornik wodonoœny doggeru