SDSU STANDARD PIPE SCHEDULE

Similar documents
PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT

Copper and Copper Alloy Tube, Pipe and Fittings

SECTION DUCTILE IRON PIPE AND FITTINGS

INDEX. Sec. No. Items Page Nos.

SECTION DUCTILE IRON PIPE AND FITTINGS

A. This Section includes the following for soil, waste, and vent piping inside the building:

ASME/ANSI B Cast Iron Pipe Flanges and Flanged Fittings ASME/ANSI B Malleable Iron Threaded Fittings ASME/ANSI B16.

SECTION FACILITY STORM DRAINAGE PIPING

SECTION GENERAL REQUIREMENTS, MECHANICAL. 1. All piping entering the Shipyard must be controlled per Shipyard Standard Procedure #

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

DISTRIBUTION PIPING MATERIALS: BUILDING HYDRONIC SYSTEM MANAGEMENT. Jim Riley, Texas A&M University February 10, 2015

PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification. 96 B. Riutta

WATER SERVICE 2

STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL Purpose:

All work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition.

Price List January 1, 2015

SECTION SANITARY SEWER PIPE

SECTION SANITARY SEWER AND STORM DRAIN SYSTEMS

B. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation

MS-3/2009 HDPE (High Density Polyethylene) Pipe and Fittings Specification for Buried Potable Water

DIVISION 22 PLUMBING PLUMBING EQUIPMENT Domestic Water Heaters

Facility Operations Physical Safety Guidance Document

Depend-O-Lok FxE Expansion Coupling. System No. Submitted By Spec Sect Para Location Date Approved Date. DEPEND-O-LOK FxE EXPANSION COUPLING

Model Specification 509 DRISCOPLEX 4200 and DRISCOPLEX 4300 Gravity Flow Sanitary Sewer

DESIGN STANDARDS SECTION

PROTECTO 401 Price List

DESIGN AND CONSTRUCTION GUIDELINES AND STANDARDS DIVISION 33 UTILITIES SITE UTILITIES

RMF Engineering

SECTION PIPE HANGERS AND SUPPORTS

SECTION 6 SANITARY SEWER MAIN 6.01 SCOPE

AIR RELEASE, CLEANOUT, AND SEWER MANHOLES

EXHIBIT "A. Technical Specifications for Water and Sewer Service Lines

Specification for Pipe Bursting Gravity Sewer Mains with HDPE Pipe

SANITARY SEWER SPECIFICATIONS

PLUMBING ROUGH IN INSPECTION

DIVISION 4300 STORM DRAINAGE

Section C-1 Pipes and Fittings

SECTION HIGH DENSITY POLYETHYLENE (HDPE) PIPE AND FITTINGS FOR WATER DISTRIBUTION AND TRANSMISSION

SECTION DUCTILE-IRON PIPE AND FITTINGS

PART 7 PLUMBING Section Scope Application Definitions Plumbing Facilities Service Connections

SECTION HIGH DENSITY POLYETHYLENE (HDPE) PIPE AND FITTINGS

SECTION CEMENT-MORTAR LINED AND COATED STEEL PIPE

REGULATORS 175/153 Series

ROOF DRAINS TABLE OF CONTENTS

Guide Specification for Copper and Copper Alloy Building Piping Systems

SECTION POLYVINYL CHLORIDE (PVC) PIPE

Section 3510: Reclaimed water Pipes, Valves, and Appurtenances February 11, 2011

4 of /7/ :51 PM

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.

SAMPLE TEST QUESTIONS STEAMFITTER/PIPEFITTER - ITA WEBSITE

When Should Examination Preparation Begin?

CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements

HERNDON/MUNCEY, INC. Office: (281) INVESTIGATIVE PLUMBING

Replacement of Heating, Ventilation, Air Conditioning (HVAC) Units In Apartments Located at 641 Fifth Avenue. Photo Essay

Engineering Specifications

1. Conductivity < 15 micro ohms/cm 2. ph of 6.0 to Nonvolatile TOC content < 1.0 ppm

SECTION 603 SANITARY SEWER FORCE MAINS

PVC Pipe Restriction Law and Legislation 1) NYS PVC Pipe Restriction Law (Repealed)

Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW

AMERICAN Mechanical Joint Pipe For Water, Sewage or Other Liquids

SECTION GROUND WATER STORAGE TANKS

Welding. Module

SECTION 200: STORM SEWER CONSTRUCTION STANDARDS

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.

SECTION VALVES. A. Product Data: Manufacturer s catalog sheets and specifications for each valve type.

Refrigeration Installation 101

Standard Specification for Plastic-Lined Ferrous Metal Pipe, Fittings, and Flanges 1

SECTION ASBESTOS CEMENT PIPE REPAIRS, DEMOLITION, AND DISPOSAL

James M. Pleasants Company

IDENTIFICATION FOR PIPING AND EQUIPMENT

PVC Pipe PVC SCHEDULE 40. Nominal Pipe Size (in.) 1/8. Average I.D. O.D.

What to Expect From the Examination. How to Study the Plumbing Codes

Conduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes

725-R-599 PIPE LINING. (Revised ) SECTION 725, BEGIN LINE 1, INSERT AS FOLLOWS: SECTION 725 SLIP LINING OF EXISTING PIPE

PLUMBING RE-SUBMITTAL

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

Pipe threads for tubes and fittings where pressure-tight joints are not made on the threads. (requires PTFE sealing tape or liquid sealant).

Qualification Guide. BPEC 601/2514/7 - Level 1 Diploma in Plumbing Foundation. BPEC 600/9432/1 - Level 2 Diploma in Plumbing Foundation

DIVISION 22 PLUMBING PLUMBING EQUIPMENT Domestic Water Heaters

STANDARD SPECIFICATION SECTION STEEL PIPE, FUSION-BONDED EPOXY LINED AND COATED

RING JOINT SYSTEMS 207

Defining Quality. Building Comfort. Heating and Cooling Coils

Jay R. Smith Mfg. Co.

B. Reference ASME A17.1 for elevator sumps and sump pump requirements. D. ASSE 1003 Performance Requirements for Water Pressure Reducing Valves.

Corrosion Control & Cathodic Protection for Water & Wastewater Systems

Quality is Our Strength You can count on Oasis Coils

DIVISION 2 - SEWERAGE AND DRAINAGE SECTION STORM DRAIN SYSTEMS PART 1 - GENERAL

ESFR DRY PENDENT SPRINKLER VK502 (K14.0) TECHNICAL DATA

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

SECTION STORM DRAINAGE SYSTEM

Fusion-Tech Pipe Multi-Layer Pipe Safety-Pol Fittings

REVISION RECORD FOR THE STATE OF CALIFORNIA EMERGENCY SUPPLEMENT. January 1, Title 24, Part 5, California Plumbing Code

2006 Codes. Please verify the following before calling for inspection

STANDARD SPECIFICATIONS SECTION METAL FABRICATIONS

FIRING RANGE PHASE 1 DESIGN

CHAPTER 11 STORM DRAINAGE

NFPA31FuelOilPiping 1 Revised

Section 2100-Trenching and Tunneling

Chapter 5 - Aircraft Welding

Transcription:

Service Material 1. SANITARY AND VENT; UNDER GROUND SCHEDULE 40 PVC. SPEC. NO. 7 or Cast iron 2. SANITARY AND VENT, ABOVE GROUND SCHEDULE 40 PVC. SPEC. NO. 7 or Cast iron 3. STORM UNDER GROUND SCHEDULE 40 PVC. SPEC. NO. 7 or Cast iron 4. STORM ABOVE GROUND SCHEDULE 40 PVC. SPEC. NO. 7 or Cast iron 5. POTABLE HOT AND COLD WATER COPPER TUBE, TYPE L. SPEC. NO. 1 6. POTABLE HOT AND COLD WATER UNDERGROUND COPPER TUBE, TYPE K. SPEC. NO. 2 7. HEATING HOT WATER 1 AND UNDER: COPPER TUBE, TYPE L. SPEC. NO. 1 1 ¼ 2 : SCHEDULE 40 STEEL. SPEC. 2 ½ AND OVER: SCHEDULE 40 STEEL. SPEC. SCHEDULE 40 STEEL. SPEC. NO. 18 ALLOWED ONLY UNDER SPECIAL CIRCUMSTANCES 8. CHILLED WATER 1 AND UNDER: COPPER TUBE, TYPE L. SPEC. NO. 1 1 ¼ 2 : SCHEDULE 40 STEEL. SPEC. 2 ½ AND OVER: SCHEDULE 40 STEEL. SPEC. SCHEDULE 40 STEEL. SPEC. NO. 18 ALLOWED ONLY UNDER SPECIAL CIRCUMSTANCES 9. CHILLED WATER UNDERGROUND UTILITY DISTRIBUTION PIPING HDPE. SPEC. NO. 6 DUCTILE IRON. SPEC. NO. 9 SCHEDULE 40 STEEL. SPEC. 10. CONDENSATE DRAIN COPPER TUBE, TYPE L. SPEC. NO. 1 11. STEAM LOW PRESSURE (Fin tube radiation and air coils) 1 AND UNDER: COPPER TUBE, TYPE L. SPEC. NO. 1 1 ¼ 2 : SCHEDULE 40 STEEL. SPEC. 2 ½ AND OVER: SCHEDULE 40 STEEL. SPEC. 1 of 6

12. STEAM LOW PRESSURE (Branches and Mains, including steam traps) 2 AND UNDER: SCHEDULE 40 STEEL. SPEC. 2 ½ AND OVER: SCHEDULE 40 STEEL-- SEAMLESS. SPEC. 13. STEAM HIGH PRESSURE 2 AND UNDER: SCHEDULE 40 STEEL. SPEC. 2 ½ AND OVER: SCHEDULE 40 STEEL SEAMLESS. SPEC. 14. STEAM CONDENSATE RETURN BLACK STEEL PIPE, SCHEDULE 80 STEEL. SPEC. NO. 4 15. PURE WATER POLYPROPYLENE FUSION. SPEC. NO. 10 HDPE. SPEC NO. 6 16. NATURAL GAS BLACK STEEL PIPE, SCHEDULE 40. SPEC. NO. 3 17. ACID WASTE AND VENT INCLUDING TRAPS POLYPROPYLENE SPEC. NO. 10 18. COMPRESSED AIR GENERAL COPPER TUBE, TYPE L. SPEC. NO. 1 BLACK STEEL PIPE, SCHEDULE 40. SPEC. NO. 3 19. COMPRESSED AIR MEDICAL AND LAB COPPER TUBE, TYPE L. SPEC. NO. 16 20. VACUUM COPPER TUBE, TYPE L. SPEC. NO. 16 21. SPRINKLER WET PIPE 2 AND UNDER: BLACK STEEL PIPE, SCHEDULE 40. SPEC. 2 ½ AND OVER: BLACK STEEL PIPE, SCHEDULE 10. SPEC. NO. 15 22. SPRINKLER DRY PIPE GALVANIZED STEEL PIPE, SCHEDULE 40. SPEC. NO. 14 23. CONDENSER WATER PIPING SCHEDULE 80 PVC. SPEC. NO. 5 BLACK STEEL PIPE, SCHEDULE 40 STEEL. SPEC. FIBERGLASS. SPEC. NO. 12. COPPER TUBE, TYPE L. SPEC. NO. 1 HDPE. SPEC. NO. 6 24. REFRIGERANT PIPING COPPER TUBE, TYPE L. SPEC. NO. 25 25. DOMESTIC WATER UNDERGROUND UTILITY DISTRIBUTION PIPING DUCTILE IRON PIPE. SPEC. NO. 9 COPPER TUBE, TYPE K. SPEC. NO. 2 2 of 6

SPEC. NO. 1 TYPE L HARD TEMPER COPPER, ASTM B88 SOLDER TYPE WITH 95/5 SOLDER WROUGHT COPPER SOLDER JOINT, ANSI B16.22 SPEC. NO. 2 TYPE K SOFT TEMPER COPPER, ASTM B88 SOLDER TYPE WITH SIL-FOS, OR FLARED TYPE WROUGHT COPPER SOLDER JOINT, ANSI B16.22, OR BRASS FLARED FITTINGS, ANSI B16.26 SPEC. SCHEDULE 40 BLACK STEEL, ASTM A106 GRADE B 2 AND UNDER: SCREWED 2 ½ AND OVER: WELDED AND FLANGED 2 AND UNDER: CAST IRON SCREWED FITTINGS, ANSI B16.3, 125 LB. (S) 175 LB. (WOG) 2 ½ AND OVER: BUTT WELD SCHEDULE 40 STEEL FITTINGS, ANSI B16.9 UNIONS: 2 AND UNDER, CAST IRON GROUND JOINT WITH BRASS SEAT, 250 LB. (S) 500 LB. (WOG) FLANGES: 2 ½ AND OVER: FORGED STEEL WELDING NECK OR SLIPON, 150 PSIG, ANSI B16.5 SPEC. NO. 4 SCHEDULE 80 BLACK STEEL, ASTM A106 GRADE B 2 AND UNDER: SCREWED. 2 ½ AND OVER: WELDED AND FLANGED. 2 AND UNDER: CAST IRON SCREWED FITTINGS, ANSI B16.3, 125 LB. (S) 500 LB. (WOG). 2 ½ AND OVER: BUTT WELD SCHEDULE 80 STEEL FITTINGS, ANSI B16.9 UNIONS: 2 AND UNDER: CAST IRON GROUND JOINT WITH BRASS SEAT, 250 LB. (S) 500 LB. (WOG) FLANGES: 2 ½ AND OVER: FORGED STEEL WELDING NECK OR SLIP-ON, 150 PSIG, ANSI B16.5 SPEC. NO. 5 SPEC. NO. 6 SCHEDULE 80 PVC SOLVENT WELDED WITH SOLVENT CEMENT RATED FOR APPLICATION PVC MATERIAL AND RATED FOR PRESSURE REQUIREMENTS AND APPLICATION HIGH DENSITY POLYETHYLENE (HDPE) SOCKET TYPE TO MATCH PIPING HDPE SPEC. NO. 7 SCHEDULE 40 PVC, ASTM D 2665 SOLVENT WELDED, WITH ASTM D 2564 SOLVENT CEMENT PVC 3 of 6

SPEC. NO. 9 SPEC. NO. 10 SPEC. NO. 12 DUCTILE IRON PIPE ANSI/AWWA A21.51/C151 WALL THICKNESS CLASS SHALL BE SELECTED PER AWWA C600. PROVIDED WITH EXTERIOR TAR COATING AND CEMENT LINING PER ANSI/AWWA A21.4/C104. JOINTS SHALL BE ANSI/AWWA A21.11/C111 PUSH ON TYPE. MECHANICAL JOINT 250 PSIG GRAY CAST IRON PER ANSI/AWWA C110/A21.10. PROVIDE WITH CEMENT LINIING PER ANSI/AWWA A21.4/C104 AND RETAINING GLANDS FOR EACH FITTING. POLYPROPYLENE FLAME RETARDANT PIPE, SCHEDULE 40, FUSEAL OR EQUAL. ELECTRICAL FUSION TYPE SOCKET TYPE TO MATCH PIPING. FIBERGLASS BELL AND SPIGOT SPEC. NO. 14 FLANGED: GROOVED: SCHEDULE 40 STEEL, GALVANIZED, ASTM A53/A53M. 1 ½ AND UNDER: SCREWED. 2 AND OVER: FLANGED, OR CUT GROOVED. SCREWED: CAST IRON, GALVANIZED 125 LB. CLASS, ANSI B16.4 AND ASTM A123/A123M. CAST IRON, GALVANIZED, 125 LB. CLASS, ANSI B16.1 AND ASTM A123/A123M DUCTILE IRON, GALVANIZED, ASTM A133 AND A536, UL LISTED AND FM APPROVED. FURNISH COUPLINGS AND FITTINGS BY SAME MANUFACTURER. NOTE: 1. PLAIN END FITTINGS AND COUPLINGS ARE NOT ALLOWED. 2. NO FIELD WELDING PER NFPA 13. SPEC. NO. 15 SCHEDULE 10 BLACK STEEL, ASTM A53/A53M. 2 AND OVER: FLANGED, OR CUT GROOVED. FLANGED: CAST IRON 125 LB. CLASS, ANSI B16.1 GROOVED: DUCTILE IRON, ASTM A133 AND A536, UL LISTED AND FM APPROVED. FURNISH COUPLINGS AND FITTINGS BY SAME MANUFACTURER. NOTE: 1. PLAIN END FITTINGS AND COUPLINGS ARE NOT APPROVED. 2. NO FIELD WELDING PER NFPA 13. SPEC. NO. 16 UNIONS: TYPE L HARD TEMPER COPPER, ASTM B88 MEDICAL GRADE BRAZED WITH MINIMUM 15% SILVER BRAZING ROD BRAZED WITH MINIMUM 15% SILVER BRAZING ROD SPEC. NO. 17 CAST IRON SOIL PIPE, SERVICE WEIGHT, COATED INSIDE AND OUT, NO HUB NEOPRENE SEALING SLEAVE WITH TYPE 301 STAINLESS STEEL SHIELD AND SCREW 4 of 6

SPEC. NO. 18 SPEC. NO. 25 TYPE CLAMPS. CAST IRON SCHEDULE 40 BLACK STEEL, ASTM A120 BOLTED CLAMP TYPE COUPLING WITH GROOVED END LOCK. VICTAULIC OR EQUAL. BLACK MALLEABLE IRON, GROOVED ENDS, ASTM-A47 TYPE L SOFT COPPER SOLDER TYPE WITH SIL-FOS, OR FLARED TYPE ON DISSIMILAR METALS. BRAZED CONNECTIONS WITH 15% SILVER BRAZING ROD FOR ALL OTHER JOINTS. PURGE JOINT WITH DRY NITROGEN WHILE BRAZING OR SOLDERING GENERAL NOTES: A. This information is given as a general guide only. The Professional Consultant is responsible that pipe, fittings, etc. are suitable for service intended. B. All welding shall conform to workmanship, testing and general requirements of welding section ANSI B31.1 Power Piping. C. Grooved joint piping SPEC. NO. 18 shall not be used on hydronic heating or cooling systems. Exceptions may be allowed only for final connection to equipment that is not available with flanged or threaded connections. D. PVC pipe fitting pressure ratings decrease as pipe diameter increases. Ensure both piping and fittings meet specified pressure ratings, especially when large diameter piping is used. E. Copper Piping: 1. Do not allow T-drill fittings or similar products that extrude a branch from a main line. 2. Do not allow mechanical crimp connections such as Pro-Press except for an emergency tiein to an existing system that has poor isolation. Obtain prior approval with owner. TESTING REQUIREMENTS: A. COPPER PIPING 1. Specifications shall include language that allows the Owner to perform destructive testing of soldered or brazed joints at Owner s discretion and expense. 2. When Owner elects to perform destructive testing, fabricated joints will be tested as follows: a. Test will ensure joints are minimum 80% penetrated around the full circumference of the joint and free of voids. Any joints exhibiting less than 80% penetration of the filler material will be considered to have failed the test. b. Owner shall pay for initial testing of the selected joints. The joint will be sliced and peeled apart (not heated) for inspection purposes. 5 of 6

c. If the joint passes inspection, the Owner will pay for the reconstruction of the joint. d. If any of the joints fail, the contractor is responsible for the repair and subsequent destructive testing. The owner shall select two more joints at random (any size or location) to be tested at the contractor s expense for every failed joint. e. Owner or engineer reserves the right to test any additional joints they deem suspect at owner s expense. Reworking of any failed joints will be at contractor s expense. 3. Specify the following procedure and requirements. a. Piping underground and in chases and walls shall be tested before piping is concealed. b. Test piping before insulation is applied. 1) If insulation is applied before pipe testing and a leak occurs which ruins the insulation, specify damaged insulation is replaced with new insulation by the Contractor at no cost to the Owner. c. Specify a test pressure of 150 psig water pressure. d. Hold test pressure for minimum 4 hours. e. Specify the test is witnessed by the Owner s Representative. f. If more than 3 solder joints leak within the one year warranty, the contractor shall extend the original warranty to a period of 2 years from the date of substantial completion. Warranty shall cover material and labor on all solder joints within original scope of project along with all damages to the building that result from a leak. B. WELDED STEEL PIPING 1. Specifications shall include nondestructive testing of welded joints, a. Include testing of both shop and field fabricated welds b. Test ten percent of all welds making sure to include all welders work. c. Clearly describe Owner pays for initial testing and additional testing in the event of a failure will be paid for by the contractor. d. Clearly indicate what ASME specification to test to. e. Owner or engineer reserves the right to test any additional welds they deem suspect at owner s expense, any rework or retesting will be at contractor s expense. C. SANITARY, STORM, AND ACID WASTE AND VENT PIPING 1. Specify the following procedure and requirements: a. Test piping with water to prove tight. b. Test piping before insulation is applied. c. Hydrostatically test soil, waste, and vent piping inside the building with 15 feet of water and allow to stand for 1 hour for inspection before connecting fixtures. 1) If a leak appears, repair and repeat test. d. Hydrostatically test interior downspouts with 15 feet head of water and allow the water to stand for 1 hour with no leak. e. Water test force mains at a pressure equal to 1.5 times the operating pump discharge pressure. f. Owner s representative shall witness test. 6 of 6