Noby-420 User Operating Manual & Log Book Rev.2 Page 1 of 12. Fire Control Panel. User Operating Manual & Log Book

Similar documents
BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

SECURIT 800L+ CONTROL PANEL

CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL. user manual & log book. Approved Document No. DFU Rev 1

FIREDEX Conventional Fire Panels

User Guide Premier Elite 24/48/88/168/640

Using your LED Plus keypad

CONTENTS 4. HOW TO UNSET THE PANEL...7

Matrix 424/832/832+ ICON & LCD User Manual. Software Version 5 RINS EN Security Grade 2 Environmental Class 2

NetworX Series. NX- 4/8 Code Pad. User Manual (Australian Version)

FIRE ALARM PANEL & SYSTEM OPERATION ID50 SYSTEM. The Fire Alarm System can be activated in the following ways :~

XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL. user manual and log book. Approved Document No. DFU Rev 1

IMPORTANT USER INFORMATION

9452/9453 Installation and User Guide

Understanding the Code Pad lights...4. Code Pad tones...5. Fully arming the system On MODE...6. Fully arming the system - Quick Arm MODE...

HARDWIRED CONTROL PANELS

FA-300 Series. LCD Fire Alarm Control Panel. User Guide. LT-954 Rev. 0.1 February FA-300 SERIES Fire Alarm Control Panel

XR1. Intruder alarm system Operating Instructions. Unset system indications. Set System indication

SmartLine. Conventional Fire Detection Control Panel. Extinguishant system Control Panel. User's Manual. GameOver

GST301. (Single Protection Zone) Operation Manual

Master User Guide Premier Elite Series

How To Set A Timer On A Gg System

SYSTEM 7000 IRIS+ USER MANUAL

INTRODUCTION. The data provided is for The Standard Products and any variation will be dealt with at the end of this manual.

SECURITY SYSTEM NOTES. EMERGENCY ACTIVATION KEYS (check if enabled) PROGRAMMED FUNCTIONS

User Guide Veritas 8/Veritas 8Compact/Veritas R8 INS036-5

NetworX NX-6V2. LED Keypad User Manual

ICP-CP500. User's Guide ICP-CP500 Codepads

2 4PI175 issue 1_6/01. How to unset system in alarm. Programs 1, 2 and 3. Access codes. How to operate Personal Attack

TS590. Intruder Alarm Control Panel. SYSTEM OPEN 17:30 01 Jan ENT 0 ESC

USER GUIDE SERIES 4250 AUDIO ALARM CONFIRMATION SYSTEM CONTROL UNIT

Product Data Sheet. User Manual. User Manual MX-4100, MX-4200, MX-4400, Mx-4400/LE & Mx-4800 Fire Alarm Control Panels

SECURITY SYSTEM NOTES

SECURITY SYSTEM NOTES

SPECIAL CODES AUXILIARY CODES SYSTEM NOTES

HILLS Series LED Code Pad User Manual

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

HILLS Series LED Code Pad User Manual

EDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual

Conventional Fire Detection and Extinguishant Control System Specification

ACTIVE 5 ENGINEERING MANUAL

Control/Communicator Installation Manual

Master User Guide Premier Elite 24/48/88/168/640

GE Concord 4 Quick User Guide

USER GUIDE HARDWIRED CONTROL UNIT

SECURITY SYSTEM NOTES SPECIAL CODES AUXILIARY ARM / DISARM CODES ENTRY / EXIT DELAY TIMES ZONE DESCRIPTIONS

FIRST ALERT INSTRUCTION MANUAL FOR FA 270 KEYPADS SECURITY SYSTEM

User s Information Guide R1A

MONITOR ISM / AFx Multi-Tenant Security System User Guide V1.3

SECURITY SYSTEM NOTES SPECIAL CODES ENTRY / EXIT DELAY TIMES ARM / DISARM CODES

Security System. User Guide for the LED Command Center

FA701 Series. User s Guide. K6249-2V2 5/09 Rev. A

User.QXD 09/05/00 14:47 Page 1 Gardtec /582 User Instructions

Secure Keypads for access control

Fire System. User's Guide

SECURITY SYSTEM NOTES SPECIAL CODES. Security System Configuration

IDS. Users Guide to Keypad Functions S E C U R I T Y MANUAL NO B ISSUED AUG 2002 VERSION 1.18

INSTALLATION MANUAL CONTENTS

SECURIT 800L+ CONTROL PANEL

SECURITY SYSTEM NOTES. Security System Configuration

THANK YOU FOR VOTING TEXECOM MASTER USER MANUAL. Security Control Panels with Integrated Communicator. Issue 6

Installation and Operation Manual

Security System User's Guide

Intruder alarm system Operating Instructions

CS450. User Manual

TS510 & TS500. Installation & User Guide. Compatible Equipment

P/N Rev D

BS5839 Part 1:2002 Overview

VISTA-128FBP VISTA-250FBP Commercial Fire and Burglary Partitioned Security Systems with Scheduling

Fire Log Book. Provided by Norfolk Fire & Rescue Service. Name and address of premises:...

Users Guide to Keypad Functions

LPCB APPROVED CFP 2/4/8 ZONE FIRE ALARM CONTROL PANEL. installation & maintenance manual. Approved Document No. DFU Rev 1

Fire Alarm Control Panel. Family. Operating Manual

SECURITY SYSTEM NOTES AREA LISTINGS SPECIAL CODES ENTRY / EXIT DELAY TIMES ARM / DISARM CODES ZONE DESCRIPTIONS

ALARM SYSTEM USER GUIDE

AMI MARINE (UK) LTD BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM (BNWAS) Operation Manual KW810

SPR-5 FOUR SECTOR COMPOS I TE CONTROL UN I T.

Galaxy 2 Series. User Guide. Honeywell Security

conventional system operation

A.1. a Division of Pittway Corporation. Documento: M MGAS-ENG. Edizione: 01/1997 Rev.:

Gen4 Intruder Alarm Panels SIMPLY SECURE. For Residential & Small Commercial Applications

SFC-200 SERIES LCD FIRE ALARM PANEL

510 / 511 Cardiorespiratory Monitor Preventative Maintenance Test Procedure

NetworX Series. NX-148E LCD Keypad. User Manual

FIRE SAFETY RECORD OF TESTS LOGBOOK

FIRE. 4100U Fire Alarm. Operator s Manual. Operator's Manual. Operator s Manual. LT0395 Iss 1.0

GARDINER TECHNOLOGY. Gardtec Speech Dialler UG4100 Rev1.0. The Gardtec Speech Dialler Step by Step User Guide

FIRE SAFETY PRECAUTIONS

D24 ALARM CONTROL PANEL USER S MANUAL REVISION 1.1 A$12.00 INC GST

EURO User Manual. Castle Care-Tech 2012 (RINS1531) Issue 2. Page 1

User Guide. RX-406 LED Keypad For CAPTAIN-I Ver.5.5 & up

BREEAM CRITERIA WATER LEAK DETECTION SYSTEM Type WG2 - CONTROL PANEL CONNECTIONS

Feel Secure Your Guide to Home Safety

D1260/D1260B. Keypad. National Security Systems Inc (800) Owner's Manual

INSTRUCTION MANUAL LCD-6OO SECURITY STATION

9448 Installation and User Guide

LD2 One & Two Zone Water Detection Alarm Installation and Operation Manual

VR8. User Guide Intruder Alarm System

Accenta/Optima. User Guide. Servicing Organisation (Installer) name: Telephone Number: Date of Installation: Account Number: Honeywell Security

25 Years of Manufacturing Excellence INFINITY. The Intelligent 2 Wire Fire Detection System for Professionals

EKP1 LED KEYPAD. Owner's Manual. Use with AV9000 & SC800/1600 Series Control panel

Transcription:

Noby-420 User Operating Manual & Log Book Rev.2 Page 1 of 12 Fire Control Panel User Operating Manual & Log Book TABLE OF CONTENTS Page Introduction 1 Keypad Operation 2 LED Indications 3 What to do in the event of a fire alarm? 3 Routine Testing 4 Contact Details 5 Installation Details 6 Log: Event Log 7 Log: Test Log 9 Log: Engineer Service Log 12 Introduction This document is primarily aimed at the end-user of the Noby-420 Fire Control Panel, to be handed over to a Responsible Person on completion of the installation work. The Responsible Person is the person at the site who would normally: prepare Fire Alarm Procedures for the premises ensure that all personnel are familiar with the Fire Alarm Procedures ensure that persons likely to operate the Fire Control Panel are familiar with its operation, and know where the User Operating Manual is stored. ensure that all detectors and call-points remain free from obstruction routinely test the Fire Alarm System contact the Installation/Service Company in the event of a fire, system fault or false alarms ensure that the Fire Alarm System is regularly serviced maintain a log book of all activities related to the Fire Alarm System

Noby-420 User Operating Manual & Log Book Rev.2 Page 2 of 12 KEYPAD OPERATION General Each of the following functions of the fire control panel must be preceded by the 4 digit Access Code [3][6][3][6]. Successful entry of the Access Code is confirmed by the red Function LED. Pressing [5] to Quit at any time will cause the system to revert back to normal standby mode, otherwise the system will automatically revert back after 10 seconds of inactivity. Mute Sounders [3][6][3][6] [1] Main external sounders switched off. Mute Panel [3][6][3][6] [4] Panel internal sounders (piezos) switched off. System Reset [3][6][3][6] [5] All LEDs are tested for 3 seconds. Quick Reset [3][6][3][6] [1] [4] [5] A Quick Reset is an amalgamation of the first three operations above. Note : Main sounders & Panel sounders MUST be individually muted before a reset can be accepted. Reset is acknowledged by a 3 second LED test. Evacuate [3][6][3][6] [2] Main sounders, Panel sounders and Fire Relay are activated (provided they have not been isolated). Zone_Isolate & Relay_Isolate [3][6][3][6] [3] This function is used to Isolate zones and/or the Fire Alarm Relay. The current isolation status is displayed by any flashing yellow zone LED s and/or the Relay_Isolate LED. Note that scrolling down automatically wipes any pre-existing isolation status LEDs, and that it is therefore advisable to check the whole isolation suite prior to exiting this procedure. Key [1] to Scroll-Down and highlight the desired yellow zone LED (or the Relay_Isolate LED) for selection. Key [3] to Toggle the selected zone (or the relay) on or off the LED flashes when isolation is active. Key [4] to Accept and update the current isolation status and then revert back to normal standby mode...or Key [5] to Quit and revert back to normal standby mode without updating the displayed isolation status. Once back in normal standby mode any isolated zone (or relay) is confirmed by a flashing zone fault LED (and/or Relay_Isolate LED). Zone_Isolate and/or Relay_Isolate operations should only be performed or authorised by the Installation/Service Company). Test [3][6][3][6] [6] This function is used to one-man test the system. Key [1] to Scroll-Down and highlight the zone for test. Key [6] to Toggle the zone selected for test on or off the yellow zone LED will flash when in test mode. It is now possible to trigger each detector in turn on the selected zone. The sounders are activated momentarily (provided they are not isolated) and the Zone Fire LED is latched. The Fire Alarm Relay is not activated. Key [5] to Quit to revert back to normal standby mode. The system will revert back to normal standby mode after 90 seconds of panel inactivity (i.e. no keypad operations or zone activations). Any fire alarm generated from a non-test zone will cause the system to abort the test and give the appropriate fire response.

Noby-420 User Operating Manual & Log Book Rev.2 Page 3 of 12 LED Indications LED Indications Continuous Flashing 2 Zone Fire LED s Zones alarmed First to alarm (winking) Common Fire LED One or more zones in fire condition N/A 2 Zone Fault LED s Zone/s in fault Zone/s isolated (slow flash) Head Removed (intermittent winking ) Common Fault LED Any zone fault or system fault Fault Input terminal active, non-latching Sounder Fault LED Sounder fault Sounders Isolated PSU Fault LED Low voltage (< 21 volts), non-latching Fuses F1 or F4, or Low Volts (latched). CPU Fault LED N/A CPU watchdog warning Power LED Primary supply (mains) OK. Off=mains fail Mains restored Relay Isolate LED N/A Relay isolated Function LED Access code successfully entered N/A Isolate LED N/A One or more zones isolated Test LED N/A 7 day fire test reminder WHAT TO DO IN THE EVENT OF A FIRE ALARM? User responsibilities The Responsible Person for the fire alarm should devise written procedures for the action to be taken in the event of a fire alarm and ensure that all other users have received sufficient training on how to operate the system properly and that they are familiar with these procedures. In the event of a fire In the event of a fire alarm the fire control panel will: activate the Main Sounders and internal Panel Sounder. activate the Alarm Relay which may trigger any connected ancillary equipment. the LED display will indicate: o Common Fire LED o one or more Zone LEDs indicating the location of the fire (the first zone to alarm is distinguishable by a winking Zone Fire LED) When the alarm sounds CARRY OUT THE PRESCRIBED FIRE ALARM PROCEDURE Silencing the panel Only after the prescribed Fire Alarm Procedures have been carried out should you silence the audible sounders. Mute Sounders [3][6][3][6] [1 Mute Sndrs] Mute Panel [3][6][3][6] [4 Mute Panel] To re-sound the alarm Once silenced the sounders can be manually re-activated: Evacuate [3][6][3][6] [2 Evacuate] Resetting the system Only perform a System Reset once the cause of the alarm has been established. Quick Reset [3][6][3][6] [1] [4] [5] If the original cause of the alarm still exists or has not cleared then the alarm will immediately re-sound.

Noby-420 User Operating Manual & Log Book Rev.2 Page 4 of 12 ROUTINE TESTING The Fire Alarm System should be periodically tested by the Responsible Person to ensure that it remains fully functional at all times. Daily Check the panel for normal operation. The green Power LED should be lit. The Isolate LED may be flashing in which case one or more yellow zone fault LEDs will also be flashing. ** The Relay_Isolate LED may be flashing.** Any other fault indication should be recorded in the Event Log and the Installation/Service Company informed. ** Zone_Isolate and/or Relay_Isolate operations should only be performed or authorised by the Installation/ Service Company). Weekly Operate at least one manual call point or detector to ensure correct operation of the Noby-420 Control Panel. If possible, choose a different device to trigger the Fire Alarm System each week, by rotation, such that the whole system is eventually tested over a period of time. A record of the test should be kept in the Test Log. The Installation/Service Company may have configured a Weekly Test Reminder option, which will flash the Test LED and sound an intermittent bleep when a test is due. This reminder will be automatically reset after a test has been carried out. Quarterly Every three months the Installation/Service Company should check the Fire Alarm System: Check the log book entries and confirm that any remedial action has been taken. Check the battery and its connections. Remove mains supply and check that the battery is capable of supplying the alarm sounders. Operate at least one call point or detector in each zone to test the fire alarm as per above. Perform a visual inspection of the fire alarm system for any alterations or obstructions. Issue a certificate of testing. Annually Every twelve months the Installation/Service Company should check the Fire Alarm System. This check is similar to the quarterly check except that every device on the system should be checked for operation

Noby-420 User Operating Manual & Log Book Rev.2 Page 5 of 12 CONTACT DETAILS Site Name Site Address Responsible Person Installer Name Installer Address Tel No Fax No Emergency Contact Office Hours 24 Hour

Noby-420 User Operating Manual & Log Book Rev.2 Page 6 of 12 INSTALLATION DETAILS Zone Circuit Details Location Detectors Type Qty Call Points Comments 1 2 Sounder Circuit Details Location Sounders Type Qty Comments 1 2

Noby-420 User Operating Manual & Log Book Rev.2 Page 7 of 12 EVENT LOG Date Zone / Device Event Action Signature

Noby-420 User Operating Manual & Log Book Rev.2 Page 8 of 12 EVENT LOG Date Zone / Device Event Action Signature

Noby-420 User Operating Manual & Log Book Rev.2 Page 9 of 12 TEST LOG Date Zone / Device Comment Signature

Noby-420 User Operating Manual & Log Book Rev.2 Page 10 of 12 TEST LOG Date Zone / Device Comment Signature

Noby-420 User Operating Manual & Log Book Rev.2 Page 11 of 12 TEST LOG Date Zone / Device Comment Signature

Noby-420 User Operating Manual & Log Book Rev.2 Page 12 of 12 ENGINEER SERVICE LOG Date Inspection / Work Done Signed