WaterFurnace/Water Source Heat Pump

Similar documents
HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

Water-Source Heat Pump

Variable Air Volume - VAV


HVAC-32A. Operation Manual. Specifications. Digital Multistage Air Conditioning Controller with inbuilt Outside Air Economy function

TEC Series BACnet MS/TP Network Temperature and Humidity Controllers

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

HEAT HEAT COOL HEAT PUMP COOL

*.ppt 11/2/ :48 PM 1

Programmable Thermostat MODEL XXX With Dehumidify XXX With Out Dehumidify

MicroTech III Unit Controller for Water Source Heat Pump Units

1 For All Non-Programmable Digital Thermostat

CCH/CCW, VFC/VFW, MHC/MHW, LVC/LVW

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art A

All of the above software and firmware are included in the VAV-B Package. Contact Customer Service or Technical Support for this, or for cables.

Corp L6 04/09 Supersedes 06/08

MicroTech III Unit Controller for Water Source Heat Pump Units

T-100-R Installation Guide

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C

Thermostatic Wiring Principles by Bob Scaringe Ph.D., P.E.

Workshop 7 PC Software - Tracker

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

NetworkAIR FM Precision Air Conditioner. Operation and Maintenance

INSTALLATION OPERATING & MAINTENANCE MANUAL

Operational Overview and Controls Guide

DATA AIRE, Inc. MINI DATA ALARM PROCESSOR II

CONTROLS KITS AND ACCESSORIES /2014 Supersedes10/2014

Technical Information

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

PART 11: START-UP PROCEDURES FOR THE INSTALLER

Functional Profile: Heat Pump with Temperature Control

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

Sensi TM. Wi-Fi Programmable Thermostat MANUAL OPERATION. Version: March Emerson Electric Co. All rights reserved.

Application Engineering

Protects against unwanted thermostat controller tampering. Increases occupancy comfort by providing dehumidification.

FX07 Field Controller

GPD 506/P5 Start-up Procedure and Checklist

TECHNICAL APPLICATION AND PROGRAMMING GUIDE

30RB/30RQ. Operation and maintenance instructions

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)

Statement of Work. 3.0 Details of Service Pre Start-up Cooling Start-up Service. Installation Service. Table of Contents. 1.0 Executive Summary

Liebert Deluxe System/3

INSTALLATION MANUAL. Address card EKAC10B

Water Priming Mode Purge air from plumbing system. How do I solve ER-3 WATER PRIME: TIPS ON FILLING SPA IMPORTANT NOTE WARNING

Single Zone LCD Thermostat Operating Instructions

ABB i-bus KNX Fan Coil Controller FC/S 1.1

Mode Switch. Fan Switch Menu button Program button

SMM. Installation Operation Maintenance

Installing the Tracer ZN517 Unitary Controller Ordering number: ,

, User s Manual

Installation Guide. LR-HWLV-HVAC TouchPRO Wireless. System Types

CONTROL STRATEGIES FOR HVAC SYSTEMS

Aurora UPC ZS Zone Sensors User Guide

Electronic Control Devices The European Product Catalogue 2007

INSIDE WDDCMON. User s Guide for the ENVIRO-TEC DDC Control System Windows Based Software

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

English plain text messages with constant backlight that brightens during user interaction. On/Off, Floating, or Proportional 0 to 10 VDC Control

Controller Operator Guide. VariTrac TM Central Control Panel VAV-SVU01A-EN

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

System Manager/Zone Coordinator User s Guide

INSTALLER S & OWNER S MANUAL

Electronic Control Devices The European Product Catalogue 2007

Fossil fuel heating equipment

Installation Owner Diagnostics

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Communicating Wall Control Installation Manual TSTAT0101SC

WHITE-RODGERS COMFORT-SET 90 SERIES

MicroTech Water Source Heat Pump Unit Controller

HVAC Processes. Lecture 7

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-PRESTIGE Date revised: 12/6/10

its ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting.

VARIABLE FREQUENCY DRIVES Revised 4/30/ Mechanical Systems

Fundamentals of HVAC Control Systems

TEC2664Z-3 BACnet MS/TP Rooftop Controller for Stand-Alone and Networked Zoning Systems Part No , Rev.

INSTALLATION AND OPERATION MANUAL

NX Series Inverters. HVAC Pocket Programming Guide

INSTALLATION INSTRUCTIONS MC95HAE-1 MASTER CONTROLLER

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

5.6 Technical Specification: Premium Efficiency Electric Air Conditioning Equipment

INSTALLATION/PROGRAMMING INSTRUCTIONS E4KP ENTRYCHECK

Controller Automation, Model II+

Installation Guide. VisionPRO. TH8000 Series. Need Help? This manual covers the following models. System Types

VLT 6000 HVAC. Contents

REMOTE CONTROL MANUAL

Technical Support Bulletin Nr. 20 Special AC Functions

Commercial Refrigeration Temperature and Defrost Controls

Installation Instructions. Applications. North American Emissions Compliance. Installation

Engineering Specifications

Installation Instructions

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling

The THERMOSTAT THE EVOLUTION OF CAPABILITIES INTO A PLATFORM FOR ENERGY MANAGEMENT

MANUAL FOR MODEL MP30 ELECTRIC MOTOR DRIVEN LIMITED SERVICE CONTROLLER

Room Controllers. SER8300 Line Voltage Fan Coil Room Controller with SC3000 Relay Pack

HEAT PUMP PROGRAMMABLE THERMOSTAT

14. Troubleshooting Guide

T5000 T000 LCD Digital Fan Coil Thermostat

M&M Refrigeration, Inc. Computer Control System. Screw Compressor Control Sullair Retro Fit Panel

PRODUCT DESIGN. 5. Furnace awaits call from thermostat.

Transcription:

HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 09/04/2003 WaterFurnace/Water Source Heat Pump Water Source Heat Pumps Page 3 Description 3 Sequence of Operation 5 Overview 5 Power Fail Restart 5 Random Start Delay 5 Blower Operation 6 Heating Cycle 6 Cooling Cycle 7 Reversing Valve Operation 7 Compressor Operation 7 Remote Setpoint 7 Occupied Mode 8 Standby Mode 8 Temporary Occupied Mode 8 Auxiliary Heat 8 Emergency Heat 9 Emergency Shutdown 9 Lockout Mode 9 Zone Temperature 9 Fault Signals 10 - Refrigerant System High Pressure 10 - Refrigerant System Low Pressure 10 - Condensate Overflow 10 - Freeze Protection 10 2003 Johnson Controls, Inc. 1 Code No. LIT-6375240

Configuration--Questions and Answers Page 11 Wiring Diagram 18 2 OEM WaterFurnace/Water Source Heat Pump

Water Source Heat Pumps Description The Water Source Heat Pump application is available as a factoryengineered, installed, and tested option. The water source heat pump control system is factory-downloaded and typically requires only a bus connection and address selection in order to network with a Metasys Facility Management System. You can, however, modify factory-installed control strategies, using the HVAC PRO for Windows software tool and a UNT Controller. 1 2 3 4 5 6 7 8 WATER FURNACE SINGLE STAGE CONTROLLER JCI P/N AS-UNT610-1 REV 0 19XX RATINGS: PWR IN:24VAC, CLASS 2, 2A BINARY OUT:24VAC, CLASS 2, 05A PILOT DUTY BASE UNIT: AS-UNT110-1 ANALOG INPUTS 1 2 3 4 5 6 +15VDC BINARY INPUT 1 2 3 4 Z BUS TO ZONE STAT BINARY OUTPUT 1 2 3 4 5 6 7 8 1 2 3 4 5 6 1 2 3 4 5 6 ANALOG INPUTS COMMON +15VDC 24 VAC 24VAC CO M ZBUS REF N2- N2+ 24VAC 24VAC TRACS COMMON COMMON COMMON COMMON COMMON ANALOG INPUTS BINARY IN BINARY OUTPUTS DSI unt110wf Figure 1: Water Source Heat Pump Controller OEM WaterFurnace/Water Source Heat Pump 3

4 OEM WaterFurnace/Water Source Heat Pump

Sequence of Operation Overview The UNT Controller is supplied in a unique preconfigured format where different operating sequences are obtained by performing the question and answer session in the HVAC PRO for Windows software tool. The standard configuration is explained in an itemized printout later in this document. A standard control sequence for a water-to-air heat pump is illustrated below. Increasing Output Commands 100% 0% Supplemental Heat Prop Band Heating Prop Band Heating Setpoints -Occupied -Standby -Unoccupied Cooling Prop Band Cooling Setpoints -Occupied -Standby -Unoccupied Increasing Zone Temperature wshpso Figure 2: Control Sequence for Water-to-Air Heat Pump Power Fail Restart Random Start Delay When the UNT controller is first powered, the outputs are disabled for a random start time delay. This delay is provided to prevent simultaneous starting of multiple heat pumps. Once the timer expires, the controller operates in the occupied mode until commanded to another mode by a facility management system. A random start delay between 20 and 60 seconds is present on the controls. This delay is used after every power failure, as well as the first time the compressor is started after exiting the unoccupied mode or the emergency shutdown mode. OEM WaterFurnace/Water Source Heat Pump 5

Blower Operation Heating Cycle The setup software can be used to define the blower as continuous operation or cycled operation. If the cycled option is selected, the blower runs only on a call for heating or cooling while in the occupied, standby, or unoccupied mode. If the continuous option is selected, the blower runs continuously while in the standby or occupied modes, and can be cycled based on the call for heating or cooling in the unoccupied mode. The blower does not operate during the emergency shutdown mode. Continuous operation is the factory-programmed selection. During the heating cycle, the reversing valve turns off immediately. On a call for heating, the blower enable output turns on immediately after the Blower Minimum Off Time and/or random start delay timers are satisfied--whichever occurs last. The compressor turns on after the Fixed Compressor On Delay, following the blower enable output. When heating is no longer required, the compressor output is turned off immediately after the Compressor Minimum On Time is satisfied. The blower enable output is turned off after the Blower Off Delay (Fan Purge Delay). After the compressor output is turned off, it remains off for at least the Compressor Minimum Off Time. If the dual compressor option is selected, the compressors are sequenced to maintain the zone heating setpoint. As the temperature drops below the heating setpoint and begins to operate in the heating proportional band, the first stage compressor is activated. If the first stage compressor is not able to satisfy the heating demand, the second stage compressor activates. If the zone temperature drops below the heating proportional band and begins to operate in the supplemental heating proportional band, then the auxiliary heating output(s) are energized in sequence. A supplemental heat delay ensures that the outputs remain off following the transition to the occupied, standby, or unoccupied mode. This allows the heat pump compressor(s) time to deal with a call for heat. The UNT Controller is allowed to operate the heat pump in the heating mode regardless of the outdoor air temperature. 6 OEM WaterFurnace/Water Source Heat Pump

Cooling Cycle Reversing Valve Operation Compressor Operation Remote Setpoint During the cooling cycle, the reversing valve turns on immediately. On a call for cooling, the blower enable output turns on immediately after the Blower Minimum Off Time and/or random start delay timers are satisfied--whichever occurs last. The compressor turns on after the Fixed Compressor On Delay following the blower enable output. When cooling is no longer required, the compressor output is turns off immediately after the Compressor Minimum On Time has been satisfied. The blower enable output is turns off after the Blower Off Delay. After the compressor output is turned off, it remains off for at least the Compressor Minimum Off Time. If the dual compressor option is selected, the compressors are sequenced to maintain the zone cooling setpoint. As the temperature rises above the cooling setpoint and begins to operate in the cooling proportional band, the first stage compressor is activated. If the first stage compressor is unable to satisfy the cooling demand, the second stage compressor is activated. The UNT Controller is allowed to operate the heat pump in the cooling mode regardless of the outdoor air temperature. The reversing valve energizes when the zone temperature increases above the cooling setpoint. The output de-energizes when the zone temperature drops below the heating setpoint. The output remains in the last commanded state when the zone temperature is in the deadband of operation (between heating and cooling setpoints). A six second delay is in affect after the reversing valve, or valves, are commanded from one state to the other, before allowing the compressor to turn on. The compressor runs on a call for heating or cooling. The blower enable output must be on before the compressor is turned on. The compressor output activates after the Fixed Compressor On Delay following the blower enable output. When heating or cooling is no longer required, the compressor output de-activates after the Compressor Minimum On Time. After the compressor output is turned off, it remains off for at least the Compressor Minimum Off Time. If the dual compressor option is selected, the compressor is sequenced to maintain the zone occupied/unoccupied setpoint. As the cooling/heating demand increases, the first stage compressor is activated. If the first stage compressor is not able to satisfy the demand, then the second stage compressor is activated. A single warmer/cooler adjustment from a room thermostat is used to increase or decrease the zone setpoints (defined in HVAC PRO for Windows) for all modes of operation. No adjustment is made to the setpoints if the warmer/cooler input goes unreliable. OEM WaterFurnace/Water Source Heat Pump 7

Occupied Mode Standby Mode Temporary Occupied Mode Auxiliary Heat An occupied binary data point is provided for a facility management system or a zone terminal. If communication loss with the supervisory device occurs, the controller maintains the last commanded state for ten minutes. The default state for the occupied data point is on. While the controller is in the occupied mode, it controls the heating and cooling stages to maintain the occupied mode setpoints. When the controller is in unoccupied mode (night setback), the blower cycles based on the unoccupied mode setpoints and the zone temperature. The first time the compressor starts after the controller exits the unoccupied mode, there is a random start delay present. A standby binary data point is provided for a facility management system or zone terminal. The standby mode is an unoccupied strategy and does not affect when the controller when it is in the occupied mode. If communication is lost with the facility management system, the controller maintains the last commanded state for ten minutes. The standby data point default state is off. While the controller is in the standby mode, it controls the heating and cooling stages to maintain the standby mode setpoints. Temporary occupancy places the controller in the occupied mode for a user-defined time period. Temporary occupancy is initiated by pressing a button on the Metastat zone sensor resulting in a momentary short across AI-1. The timer is reset every time the button is pressed. Two auxiliary heating stages are optionally available. Auxiliary or supplemental heating is activated when the zone temperature drops below the heating proportional band and begins operating in the supplemental heating proportional band. This insures that the heat pump compressor is fully loaded. The user has the ability to define the command percentage (between 0-100%) that stage one energizes. A supplemental heat delay insures the output remains off following a transition from shutdown mode, allowing the heat pump compressor time to deal with a call for heat. Supplemental heat will be available during the occupied, standby, unoccupied, and lockout mode. While in emergency shutdown mode, the heating output(s) are turned off. 8 OEM WaterFurnace/Water Source Heat Pump

Emergency Heat Emergency Shutdown Lockout Mode Zone Temperature The emergency heating mode is initiated through a binary data point by a facility management system or zone terminal. When the emergency heating mode is activated, only the blower enable output and the auxiliary heat output is available for control. The compressor is not allowed to operate. On a demand for heating, the auxiliary heating output is sequenced to maintain the occupied, standby, or unoccupied mode setpoints. When the emergency heating mode is de-activated, the compressor output is re-enabled and the controller resumes normal operation. The shutdown mode can be activated by a command from a facility management system or a closed contact on BI-3. If communication loss with the supervisory device occurs, the controller maintains the last commanded state for ten minutes. The default state for the emergency shutdown data point is off. When the emergency shutdown mode is activated, the blower, compressor, and auxiliary heating output is turned off immediately and remains off until the emergency shutdown mode is de-activated. The first time the compressor starts after the emergency shutdown mode has been de-activated, there is a random start delay present. Lockout mode can be activated by any of the following fault signals: refrigerant system high pressure, refrigerant system low pressure, freeze protection, and condensate overflow. When any valid fault signal remains continuously active for the length of its recognition delay, the controller goes into fault retry mode, which turns off the compressor. After the Compressor Minimum Off Time, the compressor attempts to operate once again. If three consecutive faults are recognized during a single heating or cooling demand, the unit goes into lockout mode and turns off the compressor until the controller is reset. If a fault occurs on a dual compressor unit, the other compressor continues to operate based on the heating or cooling demand. If one of the compressors on a dual compressor unit locks out, the controller goes into lockout mode and turns off both compressors until the unit is reset. The lockout condition can be reset by powering down the controller or by a command from the facility management system. Lockout mode does not prevent the auxiliary heating from being activated to satisfy heating demand. The average zone temperature is calculated by taking the average of zone temperature sensor 1 (AI-1) and zone temperature sensor 2 (AI-4). If either sensor is unreliable or not present, the controller uses the reliable sensor. If both sensors are unreliable, all controller outputs are turned off. OEM WaterFurnace/Water Source Heat Pump 9

Fault Signals Refrigerant System High Pressure Refrigerant System Low Pressure Condensate Overflow Freeze Protection The refrigerant system high pressure safety switch monitors the refrigerant pressure. The normally closed high pressure switch is wired in series with the low pressure switch and the compressor contactor and opens when the high pressure limit is reached. If the controller attempts to start the compressor and it fails to detect the compressor starter voltage three times in a row, then the unit becomes locked out. Refer to the Lockout Mode section of this document. The refrigerant system low pressure safety switch monitors the refrigerant pressure. The normally closed low pressure switch is wired in series with the high pressure switch and the compressor contactor and opens when the low pressure limit is reached. If the controller attempts to start the compressor and it fails to detect the compressor starter voltage three times in a row, then the unit becomes locked out. Refer to the Lockout Mode section of this document. The condensate overflow sensing circuit monitors the condensate level and provides a voltage signal input to AI-3. If the condensate water level rises, resulting in the input signal dropping below 6.0 VDC for the recognition delay period, the condition is recognized as a fault. The freeze protection temperature sensor monitors the water source temperature. If the temperature drops below the freeze protection trip point (default 30 F) for the recognition delay period, the condition is recognized as a fault. The freeze protection fault condition is bypassed at normal compressor startup to allow the refrigeration circuit to stabilize. When the UNT Controller is starting the compressor during the fault retry mode, the freeze protection fault is not bypassed. The fault setting is adjustable during the configuration process, but not adjustable in the commissioning mode of HVAC PRO for Windows, nor is it adjustable by a facility management system. 10 OEM WaterFurnace/Water Source Heat Pump

Configuration-- Questions and Answers The Water Source Heat Pump comes factory-configured. Changes to the default settings can be accomplished, however, by responding to programmed sequence of questions using HVAC PRO for Windows. The flowchart below explains the order of the questions. Start HVAC PRO for Windows Select File, New, OEM, WaterFurnace Number of compressors / reversing valves: 1 Stage 2 Stages Freeze protection low limit 30 degrees F - Open loop 20 degrees F - Closed loop 15 degrees F - Closed loop Blower operation: Continuous - Blower on during occupied Cycled - Blower cycles during occupied Number of stages of auxiliary heating: None 1 Stage 2 Stages Accessory output operation: None Cycled with blower Cycled with compressor STOP flow Figure 3: Question and Answer Flowchart OEM WaterFurnace/Water Source Heat Pump 11

The following is a printout documenting the HVAC PRO for Windows question and answer session including inputs, outputs, and parameters with point types and addresses for mapping into a Metasys Facility Management System. The printouts listed are default settings for a WaterFurnace/Johnson Controls OEM application. STANDARD CONFIGURATION PRINT - LONG FORM PROJECT INFORMATION HVAC PRO Version : 5.10 Configuration File : c:\winpro5\files\*.cfg Configuration date : 08/0l/94 Operator Name : Paul Stewart Job Name : Contract Number : Frequency : 60 Hz Engineering Units : English (Degrees F) Device Group : UNT Device Name : UNT110-1 Application Group : OEM Applications Application Name : WaterFurnace Configuration History : QUESTION AND ANSWER SESSION Number of compressors / reversing valves: 1 Stage Degrees protection low limit 30 degrees F - Open loop Blower operation: Continuous - Blower on during occupied Number of stages of auxiliary heating: None Accessory output operation: Cycled with compressor SIDELOOP DEFINITION (NONE) ANALOG INPUTS (* Denotes OPERATOR-DEFINED AI) AI 1 SHORT NAME : ZoneTmpl LONG NAME : Zone Temp 1 LOW INPUT : 0.0 HIGH INPUT : 0.0 LOW OUTPUT : -50.0 HIGH OUTPUT : 250.0 LOW WARNING : -50.0 HIGH WARNING : 250.0 LOW ALARM : -50.0 HIGH ALARM : 250.0 SENSOR TYPE : R-NI FILTER VALUE : 1 : Deg F AI 2 SHORT NAME : WmCl Adj LONG NAME : Warm/Cool Adjust LOW INPUT : 0.0 HIGH INPUT : 1500.0 LOW OUTPUT : -2.0 HIGH OUTPUT : 2.0 LOW WARNING : -5.0 HIGH WARNING : 5.0 LOW ALARM : -5.0 HIGH ALARM : 5.0 SENSOR TYPE : R-POT FILTER VALUE : 1 : Deg F AI 3 SHORT NAME : CondLevl LONG NAME : Condensate Level LOW INPUT : 0.0 HIGH INPUT : 10.0 LOW OUTPUT : 0.0 HIGH OUTPUT : 10.0 LOW WARNING : 0.0 HIGH WARNING : 10.0 LOW ALARM : 0.0 HIGH ALARM : 10.0 SENSOR TYPE : V FILTER VALUE : 1 : VDC 12 OEM WaterFurnace/Water Source Heat Pump

AI 4 SHORT NAME : ZoneTmp2 LONG NAME : Zone Temp 2 LOW INPUT : 0.0 HIGH INPUT : 0.0 LOW OUTPUT : -50.0 HIGH OUTPUT : 250.0 LOW WARNING : -50.0 HIGH WARNING : 250.0 LOW ALARM : -50.0 HIGH ALARM : 250.0 SENSOR TYPE : R-NI FILTER VALUE : 1 : Deg F AI 5 SHORT NAME : FrzTmpC1 LONG NAME : Comp 1 Freeze LOW INPUT : 0.0 HIGH INPUT : 0.0 LOW OUTPUT : -50.0 HIGH OUTPUT : 250.0 LOW WARNING : -50.0 HIGH WARNING : 250.0 LOW ALARM : -50.0 HIGH ALARM : 250.0 SENSOR TYPE : R-NI FILTER VALUE : 1 : Deg F BINARY INPUTS (* Denotes OPERATOR-DEFINED BI) BI 1 SHORT NAME : Occupied LONG NAME : Occupied ENABLE COS : N NORMAL COND : Unocc STATE 0 : Unocc STATE 1 : Occ BI 2 SHORT NAME : Shutdown LONG NAME : Shutdown ENABLE COS : N NORMAL COND : Off BI 3 SHORT NAME : PrsCmpl LONG NAME : Cmp 1 H\L press ENABLE COS : N NORMAL COND : Off ANALOG OUTPUTS (* Denotes OPERATOR-DEFINED AO) (NONE) BINARY OUTPUTS (* Denotes OPERATOR-DEFINED BO) BO1 SHORT NAME : Fan LONG NAME : Fan CONTROL TYPE : Individual PULSE TYPE : Maintained MIN ON TIME : 1.00 MIN OFF TIME : 1.00 BO 2 SHORT NAME : Compl LONG NAME : Compressor 1 CONTROL TYPE : Staged PULSE TYPE : Maintained MIN ON TIME : 1.00 MIN OFF TIME : 5.00 CYCLFS/HOUR : 12 BO 3 SHORT NAME : RevVlvl LONG NAME : Reversing Vlv 1 CONTROL TYPE : Individual PULSE TYPE : Maintained MIN ON TIME : 0.00 MIN OFF TIME : 0.00 STATE 0 : Htg STATE 1 : Clg BO 8 SHORT NAME : AuxOut LONG NAME : Accessory Output CONTROL TYPE : Individual PULSE TYPE : Maintained MIN ON TIME : 1.00 MIN OFF TIME : 1.00 OEM WaterFurnace/Water Source Heat Pump 13

PARAMETERS (* Denotes MONITOR ONLY Parameters) TYPE ADDRESS LONG NAME SHORT NAME VALUE Modes * ADF 28 Restart Delay RstrtDel 0.0 Minute * BD 21 Restart Status Res Stat **** BD 228 Standby Command Stby Cmd **** BD 229 Shutdown Command Shutdown **** BD 227 Occupied Command Occ Cmd **** * BD 22 Occupied Status Occ Stat **** ADF 174 Occ Ovrd Time Occ Time 60.0 Minute * BD 14 Temp Occ Status TOccStat **** BD 225 Emergency Heat Emer Htg **** * BD 23 Shutdown Status ShutStat **** Zone Cooling Set Points ADF 129 Occ Clg Setpt Occ Clg 74.0 Deg F ADF 130 Stby Clg Setpt Stby Clg 77.0 Deg F ADF 131 Unocc Clg Setpt Unoc Clg 80.0 Deg F ADF 132 Clg Prop Band Clg PB 3.0 Deg F ADF 133 Clg Integ Time Clg Int 0.0 * ADF 21 Actual Clg Setpt ActClgSP **** AO 8 Cooling Command CoolCmd **** ADF 189 Cooling Failsoft CoolFail 0.0 % Zone Heating Set Points ADF 134 Occ Htg Setpt Occ Htg 70.0 Deg F ADF 135 Stby Htg Setpt Stby Htg 66.0 Deg F ADF 136 Unocc Htg Setpt Unoc Htg 62.0 Deg F ADF 137 Htg Prop Band Htg PB -3.0 Deg F ADF 139 Htg Integ Time Htg Int 0.0 * ADF 20 Actual Htg Setpt ActHtgSP **** AO 7 Heating Command HeatCmd **** ADF 190 Heating Failsoft HeatFail 0.0 % Fan Operation ADF 163 Fan Purge Time FanPurge 0.5 Minute Heat Pump Output ADF 164 Comp Stage 1 Percent CmpStgl% 5 % A0 5 Compressor Command CompCmd **** Freeze Sensor Fault ADE 195 Freeze Bypass Const1 2.0 Minute ADF 191 Freeze Tmp DelaY Const2 0.5 Minute ADF 180 Freeze Tmp Diff Fr2TeDif **** ADE 181 Freeze Tmp Limit FrzTeLim **** Condensate Fault ADF 192 Condensate Delay Constl 0.5 Minute ADF 193 Condensate Limit Constl 6.0 VDC ADF 194 Condensate Diff Constl 0.5 VDC Lockout Points * ADF 22 Fault Count Cmp 1 Constl 0 * BD 25 Fault Mode Cmp 1 Failsoft 0 Off * BD 26 Lockout Status Failsoft 0 Off BD 231 Lockout Release Failsoft 0 Off Average Zone Temp * ADF 24 Zone Temp ZoneTemp 0.0 Deg F Reversing Valve BD 226 Rev Vlv Htg Pos RVlvPos 0 Off 14 OEM WaterFurnace/Water Source Heat Pump

STANDARD CONFIGURATION PRINT - LONG FORM PROJECT INFORMATION HVAC PRO Version : 5.10 Configuration File : C:\WINPRO5\FILES\*.cfg Configuration date : 08/12/94 Operator Name : Paul Stewart Job Name : Contract Number : Frequency : 60 Hz Engineering Units : English (Degrees F) Device Group : UNT Device Name : UNT110-1 Application Group : OEM Applications Application Name : WaterFurnace Configuration History : QUESTION AND ANSWER SESSION Number of compressors / reversing valves: 2 Stage Freeze protection low limit 30 degrees F - Open loop Blower operation: Continuous - Blower on during occupied Number of stages of auxiliary heating: None Accessory output operation: Cycled with compressor SIDELOOP DEFINITION (NONE) ANALOG INPUTS (* Denotes OPERATOR-DEFINED AI) AI 1 SHORT NAME : ZoneTmpl LONG NAME : Zone Temp 1 LOW INPUT : 0.0 HIGH INPUT : 0.0 LOW OUTPUT : -50.0 HIGH OUTPUT : 250.0 LOW WARNING : -50.0 HIGH WARNING : 250.0 LOW ALARM : -50.0 HIGH ALARM : 250.0 SENSOR TYPE : R-NI FILTER VALUE : 1 : Deg F AI 2 SHORT NAME : WmCl Adj LONG NAME : Warm/Cool Adjust LOW INPUT : 0.0 HIGH INPUT : 1500.0 LOW OUTPUT : -2.0 HIGH OUTPUT : 2.0 LOW WARNING : -5.0 HIGH WARNING : 5.0 LOW ALARM : -5.0 HIGH ALARM : 5.0 SENSOR TYPE : R-POT FILTER VALUE : 1 : Deg F AI 3 SHORT NAME : CondLevl LONG NAME : Condensate Level LOW INPUT : 0.0 HIGH INPUT : 10.0 LOW OUTPUT : 0 0 HIGH OUTPUT : 10.0 LOW WARNING : 0 0 HIGH WARNING : 10.0 LOW ALARM : 0.0 HIGH ALARM : 10.0 SENSOR TYPE : V FILTER VALUE : 1 : VDC AI 4 SHORT NAME : ZoneTmp2 LONG NAME : Zone Temp 2 LOW INPUT : 0.0 HIGH INPUT : 0.0 LOW OUTPUT : -50.0 HIGH OUTPUT : 250.0 LOW WARNING : -50.0 HIGH WARNING : 250.0 LOW ALARM : -50.0 HIGH ALARM : 250.0 SENSOR TYPE : R-NI FILTER VALUE : 1 : Deg F OEM WaterFurnace/Water Source Heat Pump 15

AI 5 SHORT NAME : FrzTmpC1 LONG NAME : Comp 1 Freeze LOW INPUT : 0.0 HIGH INPUT : 0.0 LOW OUTPUT : -50.0 HIGH OUTPUT : 250.0 LOW WARNING : -50.0 HIGH WARNING : 250.0 LOW ALARM : -50.0 HIGH ALARM : 250.0 SENSOR TYPE : R-NI FILTER VALUE : 1 : Deg F AI 6 SHORT NAME : FrzTmpC2 LONG NAME : Comp 2 Freeze LOW INPUT : 0.0 HIGH INPUT : 0.0 LOW OUTPUT : -50.0 HIGH OUTPUT : 250.0 LOW WARNING : -50.0 HIGH WARNING : 250.0 LOW ALARM : -50.0 HIGH ALARM : 250.0 SENSOR TYPE : R-NI FILTER VALUE : 1 : Deg F BINARY INPUTS (* Denotes OPERATOR-DEFINED BI) BI 1 SHORT NAME : Occupied LONG NAME : Occupied ENABLE COS : N NORMAL COND : Unocc STATE 0 : Unocc STATE 1 : Occ BI 2 SHORT NAME : Shutdown LONG NAME : Shutdown ENABLE COS : N NORMAL COND : Off BI 3 SHORT NAME : PrsCmpl LONG NAME : Cmp 1 H\L press ENABLE COS : N NORMAL COND : Off BI 4 SHORT NAME : PrsCmp2 LONG NAME : Cmp 2 H\L press ENABLE COS : N NORMAL COND : Off ANALOG OUTPUTS (* Denotes OPERATOR-DEFINED AO) (NONE) BINARY OUTPUTS (* Denotes OPERATOR-DEFINED BO) BO 1 SHORT NAME : Fan LONG NAME : Fan CONTROL TYPE : Individual PULSE TYPE : Maintained MIN ON TIME : 1.00 MIN OFF TIME : 1.00 BO 2 SHORT NAME : Compl LONG NAME : Compressor 1 CONTROL TYPE : Staged PULSE TYPE : Maintained MIN ON TIME : 1.00 MIN OFF TIME : 5.00 CYCLES/HOUR : 12 BO 3 SHORT NAME : RevVlvl LONG NAME : Reversing Vlv 1 CONTROL TYPE : Individual PULSE TYPE : Maintained MIN ON TIME : 0.00 MIN OFF TIME : 0.00 STATE 0 : Htg STATE 1 : Clg BO 4 SHORT NAME : Comp2 LONG NAME : Compressor 2 CONTROL TYPE : Staged PULSE TYPE : Maintained MIN ON TIME : 1.00 MIN OFF TIME : 5.00 CYCLES/HOUR : 12 BO 5 SHORT NAME :RevVlv2 LONG NAME : Reversing Vlv 2 CONTROL TYPE :Individual PULSE TYPE : Maintained MIN ON TIME :0.00 MIN OFF TIME : 0.00 STATE 0 :Htg STATE 1 : Clg BO 8 SHORT NAME : AuxOut LONG NAME : Accessory Output CONTROL TYPE : Individual PULSE TYPE : Maintained MIN ON TIME : 1.00 MIN OFF TIME : 1.00 16 OEM WaterFurnace/Water Source Heat Pump

PARAMETERS (* Denotes MONITOR ONLY Parameters) TYPE ADDRESS LONG NAME SHORT NAME VALUE Modes * ADF 28 Restart Delay RstrtDel 0.0 Minute * BD 21 Restart Status Res Stat **** BD 228 Standby Command Stby Cmd **** BD 229 Shutdown Command Shutdown **** BD 227 Occupied Command Occ Cmd **** * BD 22 Occupied Status Occ Stat **** ADF 174 Occ Ovrd Time Occ Time 60.0 Minute * BD 14 Temp Occ Status TOccStat **** BD 225 Emergency Heat Emer Htg **** * BD 23 Shutdown Status ShutStat **** Zone Cooling Set Points ADF 129 Occ Clg Setpt Occ Clg 74.0 Deg F ADF 130 Stby Clg Setpt Stby Clg 77.0 Deg F ADF 131 Unocc Clg Setpt Unoc Clg 80.0 Deg F ADF 132 Clg Prop Band Clg PB 3.0 Deg F ADF 133 Clg Integ Time Clg Int 0.0 * ADF 21 Actual Clg Setpt ActClgSP **** AO 8 Cooling Command CoolCmd **** ADF 189 Cooling Failsoft CoolFail 0.0 % Zone Heating Set Points ADF 134 Occ Htg Setpt Occ Htg 70.0 Deg F ADF 135 Stby Htg Setpt Stby Htg 66.0 Deg F ADF 136 Unocc Htg Setpt Unoc Htg 62.0 Deg F ADF 137 Htg Prop Band Htg PB -3.0 Deg F ADF 139 Htg Integ Time Htg Int 0.0 * ADF 20 Actual Htg Setpt ActHtgSP **** AO 7 Heating Command HeatCmd **** ADF 190 Heating Failsoft HeatFail 0.0 % Heat Pump Output ADF 162 Interstage On IntStgOn 1.0 Minute ADF 164 Comp Stage 1 Percent CmpStgl% 5 % ADF 161 Interstage Off IntStgOf 0.5 Minute AO 5 Compressor Command CompCmd **** Fan Operation ADF 163 Fan Purge Time FanPurge 0.5 Minute Freeze Sensor Fault ADF 195 Freeze Bypass Constl 2.0 Minute ADF 191 Freeze Tmp Delay Const2 0.5 Minute ADF 180 Freeze Tmp Diff FrzTeDif **** ADF 181 Freeze Tmp Limit FrzTeLim **** Condensate Fault ADF 192 Condensate Delay Constl 0.5 Minute ADF 193 Condensate Limit Constl 6.0 VDC ADF 194 Condensate Diff Constl 0.5 VDC Lockout Points * ADF 22 Fault Count Cmp 1 Constl 0 * BD 25 Fault Mode Cmp 1 Failsoft 0 Off * ADF 23 Fault Count Cmp 2 Constl 0 * BD 27 Fault Mode Cmp 2 Failsoft 0 Off * BD 26 Lockout Status Failsoft 0 Off BD 231 Lockout Release Failsoft 0 Off Average Zone Temp * ADF 24 Zone Temp ZoneTemp 0.0 Deg F Reversing Valve BD 226 Rev Vlv Htg Pos RVlvPos 0 Off OEM WaterFurnace/Water Source Heat Pump 17

Wiring Diagram Figure 4: WaterFurnace International/Johnson Controls Water Source Heat Pump Wiring Diagram 18 OEM WaterFurnace/Water Source Heat Pump

Notes OEM WaterFurnace/Water Source Heat Pump 19

Notes Controls Group FAN 637.5 507 E. Michigan Street HVAC PRO for Windows User s Manual P.O. Box 423 Printed in U.S.A. Milwaukee, WI 53201 20 OEM WaterFurnace/Water Source Heat Pump