Selecting Fiberglass, Rock and Slag Wool Insulation for Fire Safety and Code Compliance. By North American Insulation Manufacturers Association

Similar documents
Building Envelope Design by Roxul (BEDR ) FireWall and Roxul Plus MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings

Building Envelope Design using ROXUL. FIREWALL and ROXUL PLUS MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings

fire & soundproofing Insulation Roxul Safe n Sound Fire and Soundproofing Insulation for Interior Partition Walls and Floors

INSULATION FOR PRE-ENGINEERED METAL BUILDINGS. ROXUL SAFE 55 & 65 and ROXUL PLUS MB. Insulation for Pre-Engineered Metal Buildings

Fire & Soundproofing Insulation. Roxul SAFE N SOUND. Fire and Soundproofing Insulation for Interior Partition Walls and Floors.

B. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation

Underwriters Laboratories Testing Information

Fiberglas, Exterior Wall Thermal Insulation

Terms and Definitions In Canada

LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.

Safe Operating Procedure

ROXUL Board Insulation Section Master Guide Specification (CAVITYROCK ) Page 1 April 2016

Tremco Fire Protection Systems Group Technical Bulletin

Tsawwassen BC Arena Before & After installation of the Low-E ceiling

Twiga Insul. India's Leading Thermal and Acoustic Insulation. Insulating India

Building Code Clarifications - 7. Fire Resistance

EcoTouch Insulation with PureFiber Technology

SECTION PRE-ENGINEERED BUILDING BLANKET INSULATION

Meeting the Fire Code with Continuous Foam Plastic Insulation

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

FIRESTOPPING & SMOKE SEALS

THERMAL INSULATION MATERIALS TEST METHOD SELECTION LIST

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600

Composite Panel Firewall Systems

4 Installation Requirements

FIRE-RESISTANCE-RATED CONSTRUCTION

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

Energy Efficiency HOSPITALITY.

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in

Insulating Basements: Part 3 Basement Wall Systems

Mechanical insulation to increase building efficiency. Saving money, energy and the planet.

Value Engineering Considerations for Cast Iron Soil Pipe and PVC in Commercial Sanitary and Storm Drainage Applications

Contract for Weatherization Management Address City & State

Fire Preventive and Fireproof Performance Test and Evaluation Procedure Manual

CHAPTER 6 DUCT SYSTEMS

Why was asbestos used?

RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS

FIRE AND SMOKE PROTECTION FEATURES

Fire Testing of Recycled Materials for Building Applications

FIRE-RESISTANCE-RATED CONSTRUCTION

Environmental Education Associates. Asbestos in Construction

INTERNATIONAL FIRE PROTECTION

SECTION HVAC INSULATION. A. All work specified in this Section is subject to the provisions of Section

Energy Efficiency. Bars & RestauRants.

Fire-Rated Glass and Glazing START

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings

ROCK WOOL Preformed Pipe Section

Excerpts from the Canadian National Building Code (NBC)

Name Of Occupancy Date. Yes No Describe

Lightweight Partition Design for Residential and Commercial Buildings

2014 British Columbia Building Code Changes

Decree of the Ministry of the Environment on fire safety of ventilation systems

ASBESTOS BACKGROUND INFORMATION

Asbestos Management POLICY

Medicine Hat Fire Department. Special Event Requirements. medicinehat.ca/fire. August 2012

FLAMMABLE AND COMBUSTIBLE LIQUIDS

Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**

Roxul Board Insulation Section Master Guide Specification (CAVITYROCK DD) Page 1 October 2013

HOOVER TREATED WOOD PRODUCTS, INC. TECHNICAL NOTE FOR ADDITIONAL INFORMATION: TEC-WOOD ( )

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.

Marine Exhaust Insulation

St. John s University

CONDENSATION IN REFRIDGERATED BUILDINGS

Residential HVAC Load Sizing Training October 14, David Kaiser Green Code Plan Reviewer

B. Types of mechanical insulation specified in this section include the following:

DUCT SYSTEMS CHAPTER 6

Roof Insulation Building. Energy. Environment friendly e-library

Whether your pocketbook

energy-saving checklist a guide for rental property owners

Cannon T4 Modular Data Centres. For Outside Deployment & Challenging Environments

STENCA PIPE. High quality pipe insulation.

SUGGESTED SPECIFICATION EXHAUST SYSTEM SILENCER, FLEX CONNECTOR, INSULATION BLANKETS, WALL / ROOF THIMBLES

Wood use in Type I and II (noncombustible) construction

A Code Review for Emergency Generators and Indoor Use of Portable Generators

COMMERCIAL BUILDING APPLICATIONS

ROCKWOOL Rigid, Semi-rigid and Flexible Slabs are high quality resin bonded slabs that can be used for thermal, acoustic and fire insulation.

Fire-Retardant-Treated (FRT) Plywood

The soot and scale problems

PLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW

BRIEFING TO THE UN STAFF

WATER. Water Management Protect your building from water damage. Intent. Information & Tips

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

HOT WORK PERMIT PROGRAM TRAINING. John Braun

Cold Room & Refrigeration System (Casserole Assembly) No of units: 1

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

Fire-resistant barriers: background on requirements and determination method. Reading guide for test reports.

Product Guide Specification

H-Stud Area Separation Wall System

How To Test For Premer Retardant

Basics of HVAC Cleaning

Fire Barrier Duct Wrap 15A

1 DESCRIPTION OF THE APPLIANCE

Building Codes Update: The 2009 International Fire Code and the Apartment Industry

Asbestos WHAT TO DO? Studies of people who were exposed to high levels of asbestos in factories and shipyards, are at increased risk of:

Glossary of HVAC Terms

Water Vapor Permeance of Wood Structural Panels and Wood Wall Construction

Edition: Export Published: 09/2010. Product catalogue. Technical and industrial insulation. Lapinus

READ AND SAVE THESE INSTRUCTIONS

ENGINEERING SPECIFICATION PULTRUDED DYNARAIL FIBERGLASS LADDER & LADDER CAGES

Transcription:

Selecting Fiberglass, Rock and Slag Wool Insulation for Fire Safety and Code Compliance By North American Insulation Manufacturers Association (Note: The following article is of a general informational nature and is based upon a current technical understanding of the matters discussed. It does not comprise complete information about specific situations. NAIMA makes no warranty of any kind, expressed or implied, or regarding fitness for any particular purpose, in connection with the general information supplied. Specific information on insulation fire performance characteristics should be obtained directly from the manufacturer.) The high cost of energy today makes insulation a primary consideration in building design and a critical component in reducing a building s energy use and lifetime operating costs. Whether constructing a new building or renovating an existing structure, insulation s primary function is to reduce heat loss and heat gain. In addition, insulating with fiberglass, rock and slag wool insulations to recommended thickness levels helps control condensation, bar unwanted noise and improve indoor comfort. These insulations are also an integral component in some fire- resistant constructions. However, choosing the right insulation for a particular application can be a challenge as each insulation type has different properties and application recommendations. When designing, building or renovating structures, designers, specifiers and builders must ask several key questions about the insulation. n What are the thermal require- NAIMA members provide insulation products for thermal, acoustical, airdistribution and fire safety applications for all building and industrial applications. ments needed to meet codes or design specifications? n How can the insulation selected best help the owner reduce operating expenses and energy costs? n Does the insulation system meet OSHA s workplace acoustical standards and should additional insulation be considered where acoustical comfort is critical to the building occupants? n Is the insulation selected of the 16 November 1993/Construction Dimensions

type and density to provide at least the minimum required fire rating for the assembly? n Will the overall insulation system provide the fire properties required? Insulation Materials Fiberglass has been commercially manufactured and marketed for more than 50 years. Designers and engineers are most familiar with fiberglass as a thermal insulation in building thermal envelopes, but a variety of products has been developed for sound-control applications and as thermal insulation for air ducts, pipes, automobiles, mobile homes, aircraft, refrigerators, cooking appliances and a variety of other appliances and equipment. While it is not designed principally for fire protection, fiberglass insulation does have some fire-resistant attributes: glass wool is inorganic and, therefore, inherently noncombustible. With the proper mix of binder levels and density, fiberglass can be used in certain applications of While it is not designed principally for fire protection, fiberglass insulation does have some fireresistant attributes: glass wool is inorganic and, therefore, inherently non-combustible. up to 1,000 degrees Fahrenheit. Of course, the product manufacturer s specifications must be consulted in any proposed high-temperature applications. Similarly, rock wool and slag wool insulation are used in products such as ceiling tiles, wall and roof insulation, pipe and process insulations, insulation for ships, mobile homes, cooking appliances and other products used for sound attenuation and fire protection. Rock and slag wool are also inherently non-combustible. They maintain their performance in higher temperatures and are used in certain continuous applications and fire protection assemblies at up to 2,000 degrees. Again, consult specific manufacturer s specifications in any proposed high-temperature applications. Insulation Types Today, there are four basic types of fiberglass, rock and slag wool insulations commonly used in commercial and industrial building applications: Flexible Blanket Insulations. These are commonly used for insu- Construction Dimensions/November 1993 17

lating walls, ducts, ceilings and roofs for thermal and acoustical control. Board Insulations. Semi-rigid to rigid pre-formed insulation boards are commonly used in partitions for sound control, curtain wall applications, ceiling boards, boiler walls, hot and cold ducts, tanks and breechings. In addition, some of these board insulations are used in firerated insulation assemblies. Preformed Pipe Insulations. These are used for insulating domes tic hot and chilled water pipe lines and distributions systems, low- and high-pressure steam lines and power and process lines. Spray Fireproofing. This is used for thermal, acoustical and fire-protective applications on structural steel members, concrete pan joists, steel roof and floor sections, walls and partitions. Combined, these products meet the needs of a variety of thermal, acoustical and fire applications and are manufactured and engineered with building codes, occupant safety and fire protection in mind. Fire-Performance Testing In industrial, commercial and residential buildings, insulation and other building materials must meet fire-resistance levels established by local, state and federal building codes. These codes typically are based on tests developed by the American Society for Testing and Materials and include ASTM E-136, Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 degrees Centigrade, to be classified non-combustible and To put the heat of a an ordinary oven in a 550-degrees-Fahrenheit A self-cleaning mo 800 degrees during A typical two-hour fire te more than double the generated by a s ASTM E-84, Standard Test Method of Surface Burning Characteristics of Building Materials. ASTM E-84 measures surface burning characteristics such as flame spread and smoke developed. To determine flame spread, the insulation is subjected to a controlled flame in a test apparatus called the Steiner Tunnel. Smoke developed is determined through the use of photometers that detect the 18 November 1993/Construction Dimensions

opacity of the smoke generated by the insulation in the fire test. Although acceptable parameters for both flame spread and smoke developed are established within individual building codes and thus may vary between jurisdictions, the standard usually is 25/50 (always, however, consult the specific building code in the applicable jurisdiction). This means an insulation must not have a flame-spread rating of greater than 25 or a smoke developed rating greater than 50. Another important fire-test standard for commercial construction in ASTM E-119, Standard Method of Fire Tests of Building Construction fire into perspective, home features up to a baking temperature. del will heat up to the cleaning cycle. st rating is 1,800 degrees maximum temperature elf-cleaning oven. and Materials, which tests for fire endurance levels and gives results in rating of one-, two-, or three-hours. Fire endurance is especially critical in specific commercial applications where building codes typically mandate fire barriers to prevent the spread of fire, maintain structural integrity and allow time for people to safely exit the building. To put the heat of a fire into perspective, an ordinary oven in a home Construction Dimensions/November 1993 19

features up to a 550-degrees-Fahrenheit baking temperature. A selfcleaning model will heat up to 800 degrees during the cleaning cycle. A typical two-hour fire test rating is 1,800 degrees more than double the maximum temperature generated by a self-cleaning oven. An excellent method of decreasing the risk to people and property during a fire is by using an insulation assembly built expressly for this purpose. In these assemblies, the insulation and its other components work together to keep the cold side from getting too hot, and maintaining the total integrity of the structure by not allowing flames to pass through or spread to other parts of the building. Rock and slag wool insulation is also subjected to ASTM E-814, Standard Test Method for Fire Tests of Through Penetration Fire Stops. Fiberglass, rock wool and slag wool insulations for commercial construction are engineered to meet the fire-performance requirements of today s rigorous building codes. In addition, they provide valuable energy savings, and thermal and acoustical benefits. These insulation products come in many shapes and sizes to meet every design application challenge found in residential, commercial and industrial construction. When properly selected and installed in accordance with manufacturers specifications, these insulation products enhance the building s structural integrity and quality of our indoor environment. About the Author The North American Insulation Manufacturers Association, a trade association for fiberglass, rock wool and slag wool insulation manufacturers, offers general information on product performance characteristics, installation guidelines, energy-savings tips, building code compliance, standards and specifications, sound control recommendations, use of vapor retarders and condensation control, insulation and fire safety, thickness recommendations, energy and its procedures and much more. q 20 November 1993/Construction Dimensions