Control and Heat Meter Interface

Similar documents
OZW30. Central Unit SYNERGYR

Heating Controller. Building Technologies HVAC Products

RVL470. Heating Controller. Building Technologies HVAC Products. Series B

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

Digital input modules

SEZ220. Signal Converter. Synco 200. With preprogrammed standard applications Freely programmable Menu-driven operation. Use

RRV934. Multi-controller. Synco living

TX OPEN RS232/485 module

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Adjustable room thermostat for heating only or cooling only systems

HCR3.2/.. Chipcard reader HOTEL SOLUTION

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

HERZ-Thermal Actuators

PCS0100en Persy Control Services B.V. Netherlands

Drayton Digistat +2RF/+3RF

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

QFP910. Water detector. Building Technologies. CE1N2732en. Synco living

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT Spur 2. Spur 1. Zone 1. Zone 0

Product and functional description

For UK only RXL39.1 and the applications package SP-03 are sold in the United Kingdom only.

Air damper actuators

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG R0011

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Quick Connect. quick - simple - efficient.

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

VAV compact controller KNX / PL-Link

Alarm over IP. IRIS Touch Home Installation Manual. Version 1.0 ENGLISH. Now certified and compliant with EN50131, EN50136 Security Grade 4 ATS6

PHOENIX CONTACT Features

3/2- and 2/2-way cartridge valve type BVE

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q R0001

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

CompactLogix Power Supplies Specifications

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Three-phase monitoring relay CM-PFE

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

Flush-mounted room thermostats

MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet _en_01. 1 Description

Voltage Regulator SPAU 341 C. Product Guide

Technical Data. General specifications Switching element function Rated operating distance s n 15 mm

Technote. Frese OPTIMA Compact actuators DN10-DN32. Application. Features thermic actuators. Features motoric actuators. Approval.

RM35UA13MW. range V. Main. Product or component type. Relay monitored parameters

MINI MCR-SL-R-UI(-SP)

Smile. The All-In-One Heating Controller

OZS Web server. For LPB/BSB plants

15 Series - Electronic step relay and dimmer. Features SERIE

Power Meter Series 700

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2

OZW V2.0. Web server. Synco TM, Synco TM living

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description

38 Series - Relay interface modules A

HMI display Installation Guide

ACS-30-EU-EMDR-10-MOD

A good connection. International approvals.

VAV compact controller KNX / PL-Link

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ

QFP910. Water detector. Building Technologies. CE1N2732en Synco living

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start * see variants. Applications.

AXIS T81B22 DC 30W Midspan

Mureva Assembly surface mounted wiring devices

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER

ABB i-bus KNX Fan Coil Controller FC/S 1.1

Rack mounted telephone- and leased line modem for industrial applications

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

DEK-REL- 24/1/SEN. Extract from the online catalog. Order No.:

Programmable Room Thermostat 7 Day (5-2 Day) Models: / Power Supply: Battery / Mains

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Installing the Tracer ZN517 Unitary Controller Ordering number: ,

ABB i-bus KNX Switch Actuator, x-fold, 16/20 A, MDRC SA/S x , 2CDG 110 1xx R0011

pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2, /0.65/0.

How To Power A Schen

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Material: Weight: Bearing Life: Shaft Speed: Starting Torque: Mass Moment of Inertia: Shaft Loads:

38 Series - Relay interface modules A

48 SERIES Relay interface modules 10 A

Power Supply and Indicator Unit Type Fig. 1 Type Mounting and Operating Instructions EB 9539 EN

AXIS 291 1U Video Server Rack Installation Guide

Type: DILM32 10(24V50HZ) Article No.:

ABB i-bus EIB / KNX Analogue Input AE/S 4.2

40.3. Control Relays and Timers

Actuator-Sensor-Interface

How To Control A Korean Korean Power Plant

ABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x , 2CDG1101xxR0011

Room Temperature Sensors

Electric Rotary Actuator - On/Off or programmable control actuator

Duct Humidity Transmitter

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Valve series MN-06 acc. to NAMUR, 3/2-way G1/4 750 Nl/min (0.762 Cv)

3/2-way Solenoid Valve, direct-acting, NC or NO

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current.

HEAT INTERFACE UNITS (Modular)

Type: DILM50(230V50HZ,240V60HZ) Article No.:

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

Plug and Socket Devices SolConeX 16 A Series 8570

Series 8146/5-V37 and Series 8150/5-V37

Transcription:

2 827 SYNERGYR Control and Heat Meter Interface WRI80 Electronic control and heat meter interface. Controls the room temperature by driving a motorized valve, reads heat energy consumption from the connected M- bus heat meter, acquires pulses from third-party devices, stores data and communicates with other SYNERGYR devices via the building bus. Use The WRI80 control and heat meter interface is a component of the SYNERGYR Control & Metering System. For use and overview of the SYNERGYR system, refer to Data Sheets 2802 and 2803 (System Overview). CE1N2827en 13.08.2010 Building Technologies

Functions Control of the reference room temperature with the QAW room unit by driving a motorized zone and / or room valve Central night setback Boost heating and quick setback Minimum and maximum limitation of the flow rate Release of the zone valve for DHW heating Control of an apartment pump Frost protection for the apartment Periodic pump and valve kick Reading the consumption data and measured values from the connected M-bus heat meter Acquisition of pulses delivered by a third-party heat meter Storage of meter readings on the set days and at the end of the month Hours run meter Transmission of all relevant data to the central unit Indication of operating state with LED Type summary Type of device Control and heat meter interface Conduit box for WRI80 Address plug set for address numbers 1 16 Address plug set for address numbers 1 32 Address plug set for address numbers 33 64 Address plug set for address numbers 65 96 Type reference WRI80 ALW84 PTG1.16 PTG1.32 PTG1.64 PTG1.96 For suitable mounting kits for heat meters and valves, refer to the system overviews. Ordering When ordering, please give type reference WRI80. Address plug sets and additional system components, such as valve, actuator, heat meter, room unit and conduit box must be ordered as separate items. Delivery The scope of delivery comprises the WRI80 with ready mounted connecting cable and Mounting Instructions. Equipment combinations For each apartment, 1 WRI80, 1 heat meter, 1 actuator (zone valve), 2 AEW2.1 pulse adapters, 2 AEK84 control modules (apartment pump, room valve actuator) and 1 QAW10 or QAW20 room unit can be connected. Suitable types of heat meters Suitable types of valves and actuators The following lines of Siemeca M-bus heat meters can be used: WFM21 WFQ21 For other types of heat meters, please contact us. VVP47 valves with SSP81 actuator VVP45 valves with SSB81 actuator 2/10

Product documentation Type of document Title Number System overview System overview Planning Manual Operating Manual Mounting Instructions SYNERGYR control and billing system For new plant SYNERGYR control and billing system For service and replacement SYNERGYR control and billing system Planning Manual SYNERGYR control and billing system Operating Manual SYNERGYR control and billing system Mounting Instructions N2802 N2803 J2841 U2841 M2827 Technical design Room temperature control The WRI80 controls the room temperature via a zone valve with a 3-position actuator and, if required, a room valve with 2-position actuator. DIP switch 1 is used to select the required application. Comfort application individual room control During occupancy times, room temperature control is accomplished via the room valve, and the zone valve remains open. During nonoccupancy times, central night setback is ensured via the zone valve. ON 1 2 3 2827G02 Position for Comfort application: Switch 1 = ON Eco application reference room control Room temperature control of the reference room always takes place via the zone valve. ON Position for Eco application: Switch 1 = OFF (as supplied) 1 2 3 2827G01 Standard application heat metering The Standard application makes possible heat metering without room temperature control. ON Position for Standard application: Switch 1 = OFF (as supplied) 1 2 3 2827G01 Flow rate limitations Maximum limitation of the flow rate Minimum and maximum limitation of the flow rate is ensured via the zone valve. The limitations can be individually switched on and off. Maximum limitation of the flow rate limits the volumetric flow to the apartment to the adjusted maximum value. This ensures that sufficient amounts of heat will be delivered to the other apartments. Maximum limitation of the flow rate can be activated with DIP switch 2. It has priority over normal room temperature control. ON 1 2 3 2827G03 Position without maximum limitation of the flow rate: Switch 2 = OFF (as supplied) ON 1 2 3 2827G04 Position with maximum limitation of the flow rate: Switch 2 = ON 3/10

Minimum limitation of the flow rate DHW charging Apartment pump Frost protection for the apartment Valve kick Pump kick Acquisition of heat consumption Set day values Monthly values Handling pulses from third-party devices Handling faults Indication of operating state Minimum limitation of the flow rate ensures that a minimum flow rate will be maintained although the normal room temperature is reached. This ensures that during occupancy times with the Eco application, floors and radiators (bathrooms, reference room and other rooms without thermostatic radiator valves) will attain a certain temperature level. Heat generation and circulating pumps must be in operation. If minimum limitation of the flow rate is set to 0 l/h, it is continuously off. If activated, minimum limitation of the flow rate leads to higher heat consumption. The WRI80 receives the request for DHW via a digital input and fully opens the zone valve during the time the request is present. A short-circuit on the room unit bus has the same effect. Maximum limitation of the flow rate remains active during the entire charging cycle. The WRI80 controls an apartment pump, if present, via an external AEK84 control module. The apartment pump s overrun time is adjustable. The WRI80 features a frost protection function for the apartment. If the temperature (flow and return temperature of the heat meter, or the room temperature) falls below 3 C, both the zone and the room valve will be released until all temperatures have exceeded 5 C again. If present, the apartment pump will be activated. If not in operation for a week, both the zone and the room valve will be operated at 10:00 the next morning, to prevent valve seizing. If present, an apartment pump will operate during the time the valve kick is active (including overrun time). This prevents pump seizing. All 3 applications (Eco, Comfort and Standard) offer acquisition of heat consumption. Heat consumption acquired by the connected heat meter is transmitted via the M-bus to the WRI80 where it is made available for readout. Set day information is adopted by the heat meter provided the date of the set day a- grees with that of the WRI80. Otherwise, the set day information is generated by the WRI80 on the set day at 0:00. The last and last but one set day will be stored. If available, monthly information will be adopted by the heat meter. Otherwise, monthly information is generated by the WRI80 at the end of the month. The last 12 monthly values will be stored. Any type of meter (e.g. gas, water, electricity) can be connected to the WRI80 using one of the following pulse contacts: Reed contact Reed contact with Namur circuitry The connection is made via the ALW84 conduit box. The pules are converted to consumption values and stored like heat consumption values (current value, set day values, and monthly values). If additional meters are used, an AEW2.1 pulse adapter is required. It offers the same storage facilities as the WRI80. The WRI80 records faults (own faults and faults of the heat meter, room unit and pulse interface). The most severe fault is transmitted to the central unit. The LED on the front of the WRI80 indicates the operating state: LED steady on: Fault LED flashes: Normal operation LED off: No operating voltage 4/10

Mechanical design Basic design The WRI80 consists of base, printed circuit board with electronics and cover. The base is suited for both wall mounting with screws or DIN rail mounting. To make the electrical wiring, the rear and the underside of the unit have knockout holes for cable entry glands PG11 or rubber grommets. In addition to the electronics, the printed circuit board with the covering plate carries the connection terminals, the DIP switch, the connecting cable and the connection facility for the service unit. It also accommodates the address plug which is used to mechanically assign the WRI80 a number (address) during commissioning. The ready fitted connecting cable (1.5 m) is used for connecting the WRI80 to the ALW84 conduit box. It carries the lines for the power supply, the building data bus, the room unit bus, an input for a third-party meter and the control output for the room valve. The other wiring (M-bus, zone valve actuator, input for DHW request, and control output for the apartment pump) is made via the connection terminals of the WRI80. Terminal strip: 8 connection terminals for 2 wires each (1.5 mm 2 ) The connection terminals are screw terminals. Cover Address plug DIP switch LED Connection facility for service unit Connection terminals Connecting cable The connection diagram is printed on the inner side of the cover. Accessories ALW84 conduit box The ALW84 conduit box consists of base, terminal block and cover. The mechanical design corresponds to that of the WRI80. The base has 3 holes for wall mounting. The rear carries the snap-on facility for DIN rail mounting. Wiring: There are 3 knockout holes at the bottom for PG11 cable entry glands or rubber grommets The rear has 5 knockout holes for a standard conduit box Terminal block: 5 connection terminals for 4 wires each (1.5 mm 2 ) 3 connection terminals for 2 wires each (1.5 mm 2 ) The connection terminals of the ALW84 are spring cage terminals. 5/10

ALW84 conduit box Engineering notes General Control outputs Circulating pump and valves The local regulations for heat metering and electrical installations must be complied with. AC 24 V operating voltage is delivered by an isolating transformer which powers the entire SYNERGYR plant and which is to be installed near the central unit. The isolating transformer must be sized for the power consumption of all devices powered via the building bus. The transformer must not be earthed on the secondary side. If several buildings are involved, it is recommended to use a separate power supply (AC 24 V) for each building. To control external components via control outputs R1 and Q1, separate AEK84 control modules are required. If all valves are fully closed while the circulating pump runs, and in case there is no pressure control, the whole piping system on the flow side is subjected to the full pump pressure at zero flow rate. For this reason, to prevent damage to the circulating pump and the zone valve, an overflow valve should be installed at the remotest point of the hydraulic system. For differential pressure control, it is recommended to use a speed-controlled pump. Mounting notes Mounting Electrical installation Owing to its compact design, the WRI80 can be installed in the apartment s cabinet or in the cable riser. When choosing the mounting location, the environmental conditions must be taken into consideration. The WRI80 is suited for mounting on a flat surface, such as a wall, or in the control cabinet, or DIN rail Above the WRI80, a free space of at least 50 mm must be observed, enabling the address plug to be fitted. The WRI80 is supplied complete with Mounting Instructions. To simplify wiring between the WRI80 and the conduit box, the 8-core connecting cable is color-coded (refer to Connection diagram ). Commissioning notes The WRI80 must be parameterized and the address plug fitted by authorized staff (after mounting). This ensures a uniform metering start of the system. After commissioning, 6/10

Technical data General unit data Operating voltage SELV / PELV AC 24 V +20 % / 33 % Rated voltage Nominal frequency Total power consumption Power consumption WRI80 basic unit Power consumption per control module Power consumption zone valve actuator AC 24 V 50 / 60 Hz 3.7 VA 1.9 VA 0.5 VA 0.8 VA Perm. ambient temperature Transport and storage 25 +70 C Operation 0 50 C Perm. ambient humidity class F to IEC 721 Weight Length of connecting cable 0.32 kg to conduit box 1.5 m (fixed) Wiring Terminals for power supply and extra low-voltage per terminal (solid wire or stranded wire, twisted or with ferrule) 1 core: 0.5 mm 2 2.5 mm 2 2 cores: 0.5 mm 2 1.5 mm 2 3 cores: not permitted Safety data Degree of protection IP54 to EN 60529 Safety class III to EN 60730 Standards Product standard EN 60730-1 Electromagnetic compatibility Immunity (residential) EN 60730-1 Emissions (residential) EN 60730-1 conformity to EMC directive 2004/108/EC Building data bus Type 2-wire connection, non-interchangeable Baud rate 4800 Perm. cable length according to Planning Manual SYNERGYR J2841D Room unit bus Type 2-wire connection, non-interchangeable Baud rate 4800 Perm. cable lengths copper cable 0.5 mm 2 75 m copper cable 0.75 mm 2 115 m copper cable 1.0 mm 2 125 m M-bus Type 2-wire connection, interchangeable, master for 1 heat meter Standard compatible with M-bus heat meter to EN 1434-3 or pren 13757-2 /-3 Baud rate 2400 Perm. cable length copper cable 0.6 mm dia.,max.100 m 7/10

Pulse input (P1) for third-partytype meters Max. input frequency Min. pulse duration Perm. cable length for potential-free contact, with or without Namur circuitry to DIN 19234 15 Hz 33 ms copper cable 0.6 mm dia. max.10 m Input for DHW request (H2) Type for potential-free contact Transfer resistance max. 100 Ω. Control outputs (R1, Q1) Voltage DC 0 / 12 V Current max. 25 ma Output for zone valve Voltage AC 0 / 24 V actuator (Y1, Y2) Power consumption max. 5 VA Perm. cable length copper cable 0.6 mm dia. max.10 m. 8/10

Connection diagram G1 U1 B1 P1 K1 G1 G2 MB DB D1 D2 MD R1 G2 G1 N1 G1 G2 MB DB D1 MD P1 R1 X1 AC 24 V DB MB G1 G2 MB DB D1 MD P1 R1 C G1 G2 MB DB D1 MD P1 R1 I1 Y1 G2 Y2 CM+ CM- H2 MD Q1 Y1 G Y2 MD R1 G2 Y1 W1 S1 K2 2827A01 Devices B1 K1 K2 N1 P1 U1 X1 I1 W1 Y1 S1 C QAW room unit AEK84 control module for room valve AEK84 control module for apartment pump OZW30 central unit Third-party meter with potential-free pulse contact AEW2.1 pulse adapter ALW84 conduit box WRI80 control and heat meter interface Heat meter Zone valve actuator Potential-free switching contact Connecting cable Connecting cable (fixed) R1 red Control output 1 G1 white AC 24 V power supply G2 brown AC 24 V power supply MD green Ground P1 yellow Input for third-party meter D1 grey Room unit data DB pink Building bus data MB blue Building bus ground Connection terminals Y1 Control voltage for zone valve actuator OPEN G2 Reference potential AC 24 V for zone valve actuator Y2 Control voltage for zone valve actuator CLOSE CM+ M-bus data CM M-bus ground H2 Input for DHW request MD Ground Q1 Control output for apartment pump (via AEK84) 9/10

Dimensions 2 61 75 112 27 37 37 PG11 16 1500 Minimum space for fitting the address plug: = 50 mm 10/10 2004-2010 Siemens Switzerland Ltd Subject to alteration