VM110 SUGGESTED SPECIFICATIONS

Similar documents
RECON WATER HEATER INSTALLATION FORM

DESIGNER S HIGH EFFICIENCY GUIDE SYNC COMMERCIAL BOILERS. Up to 98% Thermal Efficiency.

Up To 99% Thermal Efficiency HIGH EFFICIENCY COMMERCIAL BOILERS WITH MODBUS PROTOCOL, CASCADING SEQUENCER AND FRONT-END LOADING CAPABILITY

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

NAVIEN AMERICA INC FITCH AVENUE

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI).

Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters

Centauri. Condensing Fire Tube Water Boiler 399 to 1000 MBH

PART 11: START-UP PROCEDURES FOR THE INSTALLER

Commercial Gas Water Heaters

LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459

Versatility ::::::::::::::::::::::::::::::::::::::: the best. mod/con Performance. and UP TO.

G234X-55 Conventional Gas Boiler

Commercial Semi-Instantaneous Water Heaters

M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace

Commercial Gas Water Heaters

Commercial Gas Water Heater

Advanced Heating & Hot Water Systems. Ultra High Efficiency Energy Star Listed Condensing Boiler

Originators of the Flexible Water Tube design

Modulex. Gas Fired Boiler Systems PIPING GUIDE GF-115-P. Modular, Condensing, Hot Water Boilers Models: 303, 454, 606, 757, 909, Instruction No.

Commercial Gas Furnace Upflow

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

Commercial Gas Water Heaters

TANKLESS WATER HEATER INSTALLATION DIAGRAMS

ASME Packaged Indirect Fired Water Heater

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-PRESTIGE Date revised: 12/6/10

High Efficiency Copper Finned Tube Boilers 750,000-2,000,000 BTU/HR

Cooling Capacity CFM in. w.c. (125 Pa)

OTF Oil Fired Pool Heater

Series GM. Peerless Boilers. Residential/Commercial Gas Boilers

PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF (10/2011) LF24 Standard

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual

Light Duty Commercial Electric Water Heater

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

INSTALLATION OPERATION AND SERVICE MANUAL

Commercial Boiler Systems and Controls

Installing, Operating & Maintaining MUNCHKIN HIGH EFFICIENCY 399M COMMERCIAL BOILER

Cooling Capacity CFM in. w.c. (125 Pa)

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank

Better Boilers.

Cooling Capacity CFM in. w.c. (125 Pa)

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model GENUS PREMIUM FS CUENOD. R EN - Edition 01-26/10/2009

TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S DESCRIPTION FEATURES

Arapahoe County Residential Water Heater Installation and Inspection Guide

G26 Corp L11 Revised LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS

Morrison Bros. Co. General Product Specifications

RESIDENTIAL HEATING OIL SERVICE CONTRACT ANNUAL COST $276.00

Factory owners must ensure the boiler is:

USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book

OWNER S MANUAL FORCE 10 MARINE COMPANY HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) FAX: (604)

USERS GUIDE. LOGIC Heat 12, 15, 18, 24, 30. For installation guide see reverse of book

SIOUX HYBRID WATER HEATER

DRAFT HOOD OUTLET GS6-30-YORT NG Select - Tall - C3 Technology 28 FIRST HOUR RATING BTU INPUT PER HOUR

Luna 3 Comfort Troubleshooting Guide June 2008

Vitodens 200, B2HA / B2HB - Product Introduction

Installing, Operating & Maintaining MUNCHKIN HIGH EFFICIENCY HEATER with the 925 Controller

F9MXE. Product Specifications

Boiler Preparation, Start-Up and Shutdown

INSTALLATION INSTRUCTIONS GEO-BOOSTER TM

CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS

Seaward Products OWNER S MANUAL WATER HEATERS. Serial Number:

The Concept of Condensing Boilers

Hot Water Boilers and Controls Why Condensing Boilers are Different. Presented Oct. 14, 2008 Long Island Chapter, ASHRAE

For installation guide see reverse of book

DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS

Evaluate, Clean, and Tune Guidance

Service Manual Models:

Your safety and the safety of others are very important.

MAC-120HE-01 Air-Cooled Chiller

G9MXE. Product Specifications

Electric Water Heater

Medical Air Systems: Scroll

ELECTRODE BOILERS VAPOR POWER INTERNATIONAL

THERM Tankless Water Heaters. Applications Manual

Air Conditioner Water Heater Model ACWH18

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

Buderus. Flexible Energy Efficient Solutions. Comfortable. Efficient. Intelligent Heating. GB312 Series Natural Gas Condensing Boiler.

OIL FURNACES CLASSIC PREMIUM CLASS UPFLOW OIL FURNACES. ROBD- SERIES Heating Capacities 56,000 to 151,200 BTU/HR [16.41 to 44.

FLASH TANK ECONOMIZER PRODUCT GUIDE

TB-A A. O. SMITH - FVIR INTELLI-VENT TROUBLESHOOTING CHART # LED STATUS PROBLEM SOLUTION

High efficiency, cast-iron gas boiler

Technical Data Manual

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model. CELTIC RSc b CUENOD. R EN - Edition 02-21/04/2005

Rheem Spare Parts Manual. Commercial gas model A Exterior 265L

ELECTRIC CENTRAL HEATING FLOW BOILER

Commercial Electric Water Heater

Fossil fuel heating equipment

Fire Pump Plan Review March 2010

Installation & Operation Manual Models: SIT030 - SIT119

REGULATORS 175/153 Series

Electric Flow Boiler

Product and Safety Information... 2,3 Service and Maintenance Munchkin Operation Primary Water

What you can expect from your Solar Hot Water System

STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL Purpose:

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

RVR Hybrid System Installer Instructions RVR Hybrid System Controller Installation Instructions

"EC" Series Electric Humidifier

Stainless Steel Single and Dual Circulation Kits

Transcription:

Project Name: Location: Engineer: Contractor: I. GENERAL Date: A. Supply and install modulating and condensing boiler(s) as specified herein. Each boiler shall be factory assembled and tested. Each boiler shall be shipped self-contained and ready for operation except for connection at the installation site of heating piping, fuel, electrical, combustion air, exhaust venting, condensate drainage and relief valve discharge piping. B. The boiler shall be capable of operating on natural gas or LP gas. The boiler shall be capable of normal operation and full rated input with natural gas supply pressure between 4 inches w.c. [1.0kPa] and 10.5 inches W.C. [2.6kPa], or LP gas supply pressure between 8 inches w.c. [2.0kPa] and 13 inches W.C. [3.2kPa]. The boiler shall be factory set for natural gas, and shall include a factory-supplied kit for conversion to LP gas operation. C. The boiler shall have an AFUE rating of %, with a minimum input of BTU/hour [ kw] and a maximum input of BTU/hour [ kw]. Rep: D. The boiler shall be certified to the ANSI Z21.13 / CSA 4.9 Gas-fired Boiler Standard. E. The boiler shall be certified for installation with zero clearance to combustibles, and shall be certified for closet and alcove installation when vented in accordance with the manufacturer s instructions. F. The boiler stainless steel heat exchanger shall be designed and constructed in compliance with the ASME Boiler and Pressure Vessel Code Section IV. A permanent nameplate bearing the H stamp and National Board registration number shall be attached to the heat exchanger in a readily viewable location. G. The boiler heat exchanger shall have a limited lifetime warranty, and other parts shall have warranty covering defects in materials and workmanship five (5) years from the date of manufacture or one (1) year from date of installation (whichever period is longer). (effective 2014-03-06) II. PRODUCT A. Acceptable manufacturers 1. The boiler shall be Vmax, VM manufactured by (NTI). B. Boiler Construction 1. Heat Engine (a) The heat engine shall be a vertical firetube down-fired design. The combustion chamber, firetubes, tubesheets and shell shall be constructed of Type 439 (ASME SA240, UNS S43932) stainless steel. The heat engine assembly shall be of all-welded construction. The heat engine for models VM110 shall be rated for 30PSI [206.8kPa] maximum operating pressure. The composite shell shall collect condensate and provide an outlet for drainage. Transparent flexible tubing shall be factory installed to drain condensate to an exterior connection at the base of the boiler cabinet. An anti-siphon condensate trap shall be factory-supplied for field installation. reserves the right to change these specifications without notice 1

(b) The heat engine shall be able to accept up to 35% mixture of inhibited propylene glycol HVAC antifreeze, without damage to the heat engine or other components. (c) The heat engine shall be accessible for inspection and cleaning via a removable burner access cover. The cover shall include a flame observation port. (d) The heat engine shall be provided with an automatic air vent (field installed). (e) A factory-supplied field-installed anti-siphon trap shall be connected to the combustion chamber for collection and removal of condensate. The trap shall be easily disassembled for cleaning 2. Gas Train and Combustion System (a) The combustion system shall be fully modulating with a 6.5:1 turndown ratio. (b) The combustion system shall contain: 1) Adjustable air/gas ratio valve with integral regulator 2) Mixing venturi 3) Variable speed blower utilizing pulse width modulation 4) Stainless steel cylindrical premix burner 5) Dual-electrode spark igniter 6) Independent flame sensing electrode. 3. Venting and Combustion Air (a) The boiler shall be designed for venting with 2 inch or 3 inch diameter Schedule 40 PVC, Schedule 40 CPVC, AL29-4C stainless steel or Polypropylene pipe. Maximum exhaust vent length with 3 inch pipe shall be 150 equivalent ft. [45.7m]. Maximum combustion air inlet length with 3 inch pipe shall be 150 equivalent ft. [45.7m]. Maximum exhaust vent length with 2 inch pipe shall be 100 equivalent ft. [30.5m]. Maximum combustion air inlet length with 2 inch pipe with shall be 100 equivalent ft. [30.5m]. (b) The combustion chamber exhaust outlet shall include an access port to permit insertion of a combustion analyzer probe. The access port shall be provided with a threaded cap. 4. Cabinet (a) The unit internal structure shall be constructed of 16ga galvanized steel. (b) The cabinet jacket shall be constructed of removable panels fabricated from 20ga steel finished with a durable factory-applied coating on both sides. Removal of jacket panels shall not compromise sealing of the combustion chamber. 5. Electrical (a) The boiler shall operate from a 120VAC/1 phase/60hz power supply designed to supply a maximum current draw of 12A. (b) Two (2) barrier strips shall be provided. One shall be for connection of: 1) Argus Link 2) System temperature sensor 3) Outdoor temperature sensor 4) DHW indirect tank sensor or aquastat 5) Thermostat connection reserves the right to change these specifications without notice 2

(c) The second barrier strip shall be for connection of: 1) External safety limit 2) DHW pump 3) CH Pump 4) Boiler Pump 5) Line-voltage connections (i) The total load of the Boiler pump in combination with either the Central Heat pump or Domestic Hot Water pump shall not exceed 2.6 Amps @ 120VAC. 6. Controls (a) The integrated microprocessor-based controller shall incorporate all operational and safety control functions, including: 1) Burner spark ignition 2) Flame detection and supervision 3) Burner firing rate modulation 4) High temperature limit (UL353 rated) (b) The controller shall incorporate a proportional-integral-derivative (PID) algorithm for two (2) separate temperature controls: one (1) for space heating with independent setpoint; one (1) for domestic hot water with independent setpoint. (c) The controller shall provide: 1) Operation of up to three (3) pumps: Boiler, Central Heating and Indirect Domestic Hot Water 2) Domestic hot water prioritization with a field-adjustable priority time 3) Outdoor reset to automatically set system water temperature based on outdoor air temperature. An outdoor sensor shall be factory-supplied 4) Manual firing rate control, settable to minimum, ignition or maximum firing rate 5) Warm weather shutdown to disable heating, with field adjustable setpoint 6) Pump exercise for 10 seconds at 24 hour intervals 7) Freeze protection to operate the boiler and central heat pumps when inlet or outlet water temperature falls below 50 F [10 C], and fire the burner at minimum modulation when either inlet or outlet temperature falls below 41 F [5 C] 8) Field setting of the following: Central heat setpoint (cold weather) from 80 F [26.7 C] to 190 F [87.8 C] Central heat setpoint differential 3⁰F [1.7⁰C] to 36⁰F [20⁰C] Central heat mode Central heat setpoint (warm weather) from 60 F [15.6 C] to 140 F [60 C] Outdoor reset temperature boost Domestic hot water (DHW) setpoint from 104 F [40 C] to 190 F [87.8 C] DHW mode (tank sensor or thermostat) Minimum firing rate Maximum firing rate for CH Service reminder reset Adjustable post purge for DHW, CH and Boiler circulator outputs reserves the right to change these specifications without notice 3

Cascade emergency setpoint from 104⁰F [40⁰C] to 190⁰F [87.8⁰C] Cascade rotation interval from 0 to 30 days Combustion fan post purge time 5 to 60 seconds Temperature units, F or C. (d) The control system shall include a backlit LED display with keypad to permit monitoring of unit operation and field adjustment of control parameters. The display shall be capable of showing: 1) Heat demand source 2) Burner state 3) Heat exchanger entering water pressure 4) Heat exchanger exiting water temperature 5) Current target temperature 6) CH setpoint 7) DHW temperature (or tank thermostat condition) 8) DHW setpoint 9) Actual blower RPM 10) Flame signal strength 11) Outdoor Temperature 12) Heat exchanger entering water temperature 13) Exhaust gas temperature 14) Boiler, CH and DHW pumps status 15) System sensor temperature 16) Accumulated flame failures 17) Accumulated successful ignition attempts 18) Accumulated failed ignition attempts 19) Blocking and lockout error code numbers (e) The controller shall be capable of Lead-Lag staging and rotation of up to sixteen (16) VM-series boilers with no additional control hardware required, apart from the necessary field-supplied cabling to connect the units via terminals provided on the field wiring barrier strip. Field configuration of Lead-Lag operation shall be accomplished through the built-in display. (f) A factory-optional module shall be available for communication capability using the Modbus RTU protocol over an EIA-485 interface. Communication with external third-party building management networks utilizing BACnet MS/TP, BACnet/IP, Johnson Metasys N2, or LonWorks protocol shall be accomplished with factory-optional NTI communication gateway(s). The gateway shall map factory-selected internal controller data registers to (select one): BACnet objects, Johnson Metasys N2 data points or LonWorks SNVTs. The gateway shall: 1) communicate with the boiler controller(s) at 38,400 bits/second 2) be equipped with DIP switches for field selection of node address and protocol 3) auto-discover Modbus addresses of up to eight (8) connected VM-series boilers. C. Trim kit 1. The following shall be factory supplied with each boiler, for field installation: (a) Qty. 1 - Tee, Brass, 1 x ½ x 1 (b) Qty. 1 - Bushing, Brass, 1 x ¾ NPT reserves the right to change these specifications without notice 4

(c) Qty. 1 Condensate trap (d) Qty. 2 - Round Mesh Vent Screen, 2 (e) Qty. 2 Round Mesh Vent Screen, 3 (f) Qty. 1 - Bottom Wall Mounting Bracket Set (g) Qty. 1 - CPVC Pipe 3, System 636, 5 Long (h) Qty. 1 - Pressure Relief Valve, ASME, ¾ NPT, 30 PSI (Boiler) (i) Qty. 1 - Auto Air Vent, ½ NPT (j) Qty. 1 - Elbow, Brass, Street 90, ¾ (k) Qty. 1 - Pressure Gauge, Back Mount, 60 PSI (l) Qty. 1 - Hose Clamp, 9/16 to 1-1/16 (m) Qty. 1 - Natural Gas to LP Conversion Kit D. Manuals III. Installation 1. Each boiler shall include the following manuals: (a) Installation and Operating (I&O) manual (b) LP conversion manual (c) User manual A. Boiler shall be installed and vented in accordance with manufacturers instructions. B. Venting 1. The boiler shall be vented as shown on the plans and specified below: (a) Venting method (select one): 1) Sidewall Direct Vent with exterior termination of separate exhaust and combustion air pipes 2) Sidewall Direct Vent with termination by manufacturer specified sidewall termination kit of separate exhaust and combustion air pipes 3) Sidewall Direct Vent with termination by manufacturer specified concentric vent termination kit of separate exhaust and combustion air pipes 4) Vertical Direct Vent with exterior roof-top termination of separate exhaust and combustion air pipes 5) Vertical Direct Vent with termination by manufacturer specified concentric vent termination kit of separate exhaust and combustion air pipes (b) Exhaust venting 1) Foam Core pipe is not an approved exhaust vent material and shall not be used. 2) Exhaust vent material shall be (select one): (i) 2 inch/3 inch Schedule 40 PVC pipe, Schedule 40 CPVC pipe, AL29-4C stainless steel pipe, or Polypropylene pipe (Note to specifier - In Canada: all vent pipe materials must meet ULC S636; PVC venting is limited to applications where exiting water temperature from heat exchanger is less than 140 F [60 C]) 3) A reducer shall be field-supplied if 2 inch pipe is used. 4) Exhaust vent length shall not exceed 100 equivalent ft. [30.5m] of 2 inch pipe including fittings. Exhaust vent length with 3 inch pipe shall not exceed 150 equivalent ft. [45.7m] of pipe including fittings. reserves the right to change these specifications without notice 5

(c) Combustion air inlet 1) Combustion air inlet material shall be (select one): (i) 2 inch/3 inch Schedule 40 PVC pipe, Schedule 40 CPVC pipe, or (to be inserted by specifier using material acceptable to the local AHJ). 2) A reducer shall be field-supplied if 2 inch pipe is used. 3) Combustion air inlet length shall not exceed 100 equivalent ft. [30.5m] of 2 inch pipe including fittings. Combustion air inlet length with 3 inch pipe shall not exceed 150 equivalent ft. [45.7m] of pipe including fittings. reserves the right to change these specifications without notice 6