EFFICIENCY STUDY OF A CONTRAFLOW MASONRY WOOD BURNING HEATER

Similar documents
Residential HVAC Load Sizing Training October 14, David Kaiser Green Code Plan Reviewer

Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

1/9/2013. Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability

HVAC Calculations and Duct Sizing

2009 IECC Update. Scope. Content. International Energy Conservation Code

BPC Green Builders. Green building for new and existing homes. Health Comfort Energy

New Homes EPS Modeling Frequently Asked Questions. Developed by Energy Trust of Oregon

Climate and Energy Responsive Housing in Continental Climates. The Suitability of Passive Houses for Iran's Dry and Cold Climate. Farshad Nasrollahi

Condensing Boiler Efficiency

Heating Load Calculation

Innovent LASER Packaged Fresh Air Conditioning Units

Water Vapor Permeance of Wood Structural Panels and Wood Wall Construction

Winter heating This winter heating guide includes ways to reduce heating costs and provides advice on choosing the right heater to suit your needs.

Case Studies: Infrared Heating in Industrial Applications

Building Energy Systems. - HVAC: Heating, Distribution -

Residential HVAC System Sizing

Certified Residential Energy Auditor (REA) Study Guide

Software Development for Cooling Load Estimation by CLTD Method

ECHO System for Basements

ELIGIBLE REPAIR PROJECT PARAMETERS

THE NATIONAL BUILDING REGULATIONS PART XA: ENERGY EFFICIENCY. Presentation by Peter Henshall-Howard: HEAD: BUILDING DEVELOPMENT MANAGEMENT.

Underwriters Laboratories Testing Information

HOW AN ENERGY EFFICIENT HOME CAN HELP THE ENVIRONMENT

ELIMINATING AIR CONDITIONERS IN NEW SOUTHERN CALIFORNIA HOUSING

INCORPORATION BY REFERENCE OF INTERNATIONAL. (1) The Department of Labor and Industry adopts and incorporates by

CITY PLAN REVIEW AND INSPECTION. Lisa Fleming Brown, CPM

PLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW

Fuel and Energy Conversion and Equivalence Chart

Dienstleistung. Certification as "Quality Approved Passive House" Criteria for Residential-Use Passive Houses

AIRCONDITIONING Cooling Loads Calculations

Mechanical and Natural Ventilation

IECC Compliance Guide for Homes in Virginia

Energy Efficiency in Buildings

Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, , ]

Case Study Family Room Renovation 3br family home, Melbourne

Housing Fact Sheets. Moisture Condensation at the Windows

DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1

A NEW DESICCANT EVAPORATIVE COOLING CYCLE FOR SOLAR AIR CONDITIONING AND HOT WATER HEATING

CHAPTER 11: PASSIVE SOLAR HOMES

Wood Pellet Stove 101

Selecting Energy Efficient Replacement Windows in Nevada

Chapter 4: Transfer of Thermal Energy

Creating Efficient HVAC Systems

Selecting Energy Efficient New Windows in Georgia

Draft UCL Heating, Cooling and Ventilation Policy

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Ceiling/Airspace

The Engineer s Guide to Efficiency Requirements for Wood Burning Appliances

Temperatures of Bundled Electrical Cables Installed in Bored Holes in Residential Wood Framing

Saving Heating Costs In Warehouses

Selecting Energy Efficient New Windows in Arizona

The Savannah Steel Series Wood Burning Stoves and Inserts

Selecting Energy Efficient New Windows in Florida

Preventing Ice Dams on Roofs

Building Department John Fiedler Construction Official Ext SAMPLE GUIDE FOR 1&2 FAMILY DWELLING BASEMENTS Rev

Whole House Dehumidification for Occupant Comfort and Energy Savings

Home Energy Evaluation Report

Roof insulations must perform the basic function of helping to control fluctuations in building interior temperature

Molds and mildew are fungi that grow

Introduction to Energy Performance of Brick Masonry

Adaptive strategies for office spaces in the UK climate

Energy Code Compliance With SIPs. Frank Baker, PFB Corporation Don Ferrier, Ferrier Custom Homes

EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE

Cost Estimation for Materials and Installation of Hot Water Piping Insulation

Passiv Haus Institut. Certification as "Quality Approved Passive House" Criteria for Residential-Use Passive Houses

FACTORS AFFECTING ENERGY CONSUMPTION OF BUILDINGS

Energy Savings with Window Retrofits

Glossary of Heating, Ventilation and Air Conditioning Terms

Contract for Weatherization Management Address City & State

OREGON BEST COMMERCIALIZATION GRANT PROGRAM FINAL REPORT

In the Fall 2002 issue of HHE News I examined

Solar Homes Catch the Sun. Are you planning a new house? Discover how you can apply solar architecture principles to:

HOW MUCH FUEL DOES A GAS STOVE CONSUME AND HOW MUCH DOES IT COST TO OPERATE?

Twinning «Improvement of the Energy Efficiency in Turkey»

Codes and High Performance Hot Water Systems. Gary Klein Affiliated International Management, LLC

Continuous Insulation Using Polyiso Wall Sheathing

Parametric Analysis of School Classroom Typologies' Energy Performance

Troubleshooting Draft Problems in Chimneys

Passive House in Austin, Texas

SOLAR ENERGY FUNDAMENTALS

VAV Laboratory Room Airflow The Lowdown on Turndown

) and air spaces (R a

Energy Efficiency. Energy Efficient Home Cooling:

HVAC Code Requirements

Solar Heating Basics Page 1. a lot on the shape, colour, and texture of the surrounding

Building Energy Codes 101 October 23, Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance

Building Condition Assessment Report

Differentiating Energy Modeling Software!

Kitchen Ventilation Systems: Part 2 Providing Adequate Makeup Air

Air Conditioning Contractors of America

SENSITIVITY STUDY FOR ARCHITECTURAL DESIGN STRATEGIES OF OFFICE BUILDINGS IN CENTRAL CHILE: EFFECTIVENESS OF NOCTURNAL VENTILATION.

ENERGY EFFICIENT AFFORDABLE HOUSING; Validating HEED s Predictions of Indoor Comfort

Get the FACTS about SEER and Deliver Better Customer Value

ENERGY EFFICIENCY PLAN REVIEW CHECKLIST

2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012

Key energy-efficient features of your new home

BPI Air Conditioning & Heat Pump Professional Training Sample Slides ( ) Agenda

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates

PERFORMANCE OF SIDE-BY-SIDE SOUTH TEXAS HOMES Isolating the Contribution of Spray Polyurethane Foam Insulation

SOLAR HEATED HOME USING AN ATTACHED GREENHOUSE AND A WOODBURNING STOVE

Transcription:

EFFICIENCY STUDY OF A CONTRAFLOW MASONRY WOOD BURNING HEATER Peter M. Hanley hanley@uoregon.edu Devin Saez saezstudio@gmail.com Christopher Nielson christophernielson@gmail.com Hank Warneck hank.warneck@gmail.com University Of Oregon ABSTRACT This study determines the efficiency of a Finnish contraflow masonry wood-burning heater in a residential setting in Pleasant Hill, Oregon. Data concerning the thermal properties of the home were collected between February 15 th and February 23 rd of 2009. This data was used in conjunction with calculations of heat gain and loss to determine an operating efficiency of 79.5 % for the contraflow masonry wood-burning heater. create an internal draft, constantly stoking the fire, producing higher burning temperatures than traditional woodstoves. A higher burning temperature increases combustion efficiency by more thoroughly consuming small particulates and combustible gasses. Secondly, after the combustion process, contraflow masonry stoves increase efficiency by sending the heat-bearing exhaust gas on a circuitous route through channels within the masonry structure surrounding the combustion chamber before exiting out the chimney. 1. INTRODUCTION Contraflow masonry stoves are thermally massive woodburning stoves specifically designed to increase the efficiency of wood combustion for the purposes of residential heating. Contraflow masonry wood stoves were first produced in Finland and other regions of Northern Europe in the 17 th and 18 th centuries as a response to a declining supply of wood resources (Tulikivi, 2008). Contraflow masonry stoves are large wood-burning stoves with several specially designed efficiency increasing thermal characteristics used for residential heating and baking. They were designed in an attempt to provide superior efficiency compared to traditional woodstoves or simple fires. Contraflow masonry stoves increase the heating efficiency of wood combustion through the employment of several key strategies. First, through a controlled air intake, the stoves Figure 1. Section of a contraflow masonry stove, showing the circuitous route taken by the exhaust gasses within the masonry structure. (Modified from Stein, et al. 2005 p. 334)

Through this process heat is transferred to and stored in the thermal-mass of the fireplace structure itself. This heat is then slowly radiated out into the surrounding area over the course of several hours, or even days (Tulikivi, 2008). This study will focus on determining the efficiency of a contraflow masonry stove in a typical, active, single-family home context. The Barkman family of Pleasant Hill Oregon allowed the use of their home and their Tulikivi contraflow masonry stove for the study. The home has a mostly open floor plan on the first floor, making it a good candidate for efficient wood heating as the heat easily spreads from the fireplace through the rest of the space. The stove faces a kitchen island and, according to the homeowner, becomes a social hub around the time of lighting fires. Typically, a single fire is lit every evening in the winter. On the coldest of days a second fire in the morning is required. The fires burn for Figure 3. First floor plan of the Barkman residence showing the location of the contaflow masonry stove and data loggers. To isolate the heat produced by the stove, other internal heat sources (solar gain, occupant and appliance heat) were calculated and subtracted from the net heat loss of the building. The remaining figure represents the net heat loss and therefore the total heat released into the home by the stove. Figure 2. Photograph of Barkman family contraflow masonry heater. Pleasant Hill, Oregon. roughly one hour. 2. HYPOTHESIS The contraflow masonry stove operates at 90% efficiency. 3. METHODOLOGY To accurately calculate the stove s efficiency, the available energy from the fuel consumed by the stove was compared to the net heat loss of the home. For the duration of a 7-day observation period, 5 HOBO H8 Pro Series data loggers were placed in the study area as well as outside to measure internal and external temperature. The average internal and external temperatures were used to calculate an average t for this study. Heat loss though the envelope was calculated using this t, areas derived from architectural drawings of the house, and published R and U values of pertinent envelope assemblies. The energy consumed by the stove was calculated by applying an assumed constant energy content in BTUs per pound of quarter split Douglas fir to the amount of wood used during the observation period. The homeowners weighed and recorded the amount of wood burned each day and at what times the burns occurred on a data sheet. The ratio between the energy consumed by the stove and the net heat loss of the home was then calculated. This difference is presumably due to a combination of inefficient combustion and heat loss up the chimney. The ratio of net heat loss of the home to energy available from the fuel represents the efficiency of the stove. 4. RESULTS Results are broken into four sections: temperature data collected, heat loss, heat gains and measured fuel. 4.1 Temperature Data Collected Temperature recorded by the data loggers shows a distinct day and night swing as well as small peaks in inside temperature after each fire.

Figure 4. Inside VS Outside Temperature over time graph with fire burning events. 4.2 Heat Loss 4.2.1 Indoor/Outdoor Temperature The interior design temperature selected for this analysis was 65.91 0 F. This temperature was chosen because this was the found average indoor temperature. The exterior average temperature was 44.64 0 F, that gives 65.9 44.6 = 21.27 0 F = t. 4.2.2 Opaque Above-Ground Walls TABLE 1 Component R-Value o F ft 2 h / Btu Exterior Moving Air Film.17 (winter) Wood Shingles.87 Vapor Permeable Felt.06 1/2 Plywood Sheathing.62 5 ½ Fiberglass Batt R-21 21 1/2 Gypsum Board.32 Interior Still Air Film.68 Total 23.72 o F ft 2 h / Btu U = 1/R = 0.0422 (Source: Stein, et al. 2005 pp. 1549-1567) Total wall area from design drawings (minus doors and windows) = 2101 ft 2. U A t = 0.0422 x 2101 x 21.27 = 1885 Btu/hr. 4.2.3 Doors Total door area from design drawings = 179.9 ft 2 U Value of Door (wood door with light) = 0.39 BTU/ 0 F ft 2 hr. U A t = 0.39 x 179.9 x 21.27 = 1492 Btu/hr. 4.2.4 Windows Total window area from design drawings = 515 ft 2 U Value of window (double glaze, ½ ) =.51 BTU/ 0 F ft 2 hr. U A t = 0.51 x 400 x 21.27 = 5587 Btu/hr. 4.2.5 Roof Insulated Ceiling area: 1707 ft 2 U Value of roof system with R-30 batt from Stein, et al. =.034 BTU/ 0 F ft 2 hr. U A t = 0.034 x 1707 x 21.27 = 1235 Btu/hr. 4.2.6 Floor

Total floor area from design drawings = 1707 ft 2 U Value of floor system from Stein, et. al. =.074 BTU/ 0 F ft 2 hr. U A t = 0.074 x 1707 x 21.27 = 2687 Btu/hr. East: 163Btu / ft 2 / day 76 ft 2 1day West: 163Btu / ft 2 / day 207 ft 2 1day 24hr Total: 4.3.2 Internal Heat Sources = 516 Btu/hr = 890 Btu/hr = 5308 Btu/hr 4.2.7 Infiltration This construction falls into the medium category (Stein et al. 2005 p.1602) Since we are working with a winter outdoor design temperature of 44.6 0 F, the table gives us a design infiltration rate (ACH) of.73 cfm. Volume of interior space from design drawings = 20243 ft 3. 230 Btu/hr per occupant for 4 occupants was used to determine total heat gain from occupants as 920 Btu/hr (Stein, et al, 2005 p 1611). Heat gain from equipment was estimated as 1400 Btu/hr (Stein, et al, 2005 p 1611). Total Heat Gain = 7628 Btu/hr V = (ACH )(volume, ft 3 ) 60 min/ hr =.73x27670 60 =246.29 cfm. 4.4 Measured Fuel Heat loss is calculated as q = cfm x 1.1 x t = 336.7 x 1.1 x 21.27 = 5762 Btu/hr. 4.2.8 Latent Heat Loss The relative humidity in the house is not intentionally controlled (which allows latent heat loss to be ignored. ) 4.2.9 Total Heat Loss The sum of above mentioned heat losses is17400 Btu/hr. The occupants heat 76.8% of their home with this system (the rest of the rooms are closed off) which gives: 17400 Btu/hr X.768 = 14608 Btu/hr Total Calculated Heat Loss = 14608 Btu/hr 4.3 Heat Gains 4.3.1 Solar Heat Gain The Solar heat gain was calculated using the Window Heat Gain Calculator (Gronbeck, 2005). Clearness factor for Eugene was determined to be 42% (Kusterer, 2009). The outside surface was variable, so the default reflectance of 0.2 was used. The SHGC for double glazed clear wood windows is 0.58. Window areas were determined from design drawings. Solar Heat Gain By Window Orientation: = 3748 Btu/hr South: 398Btu / ft 2 / day 226 ft 2 1day North: 37Btu / ft 2 / day 82 ft 2 1day = 126 Btu/hr The study was conducted over 7 days starting at 3:30 pm on February 15, 2009 until 5:30 pm on February 23, 2009. Over that period of time, 239 pounds of douglas fir were loaded into the masonry heater and burned to heat the house. TABLE 2 Date Time of Burn Amount of Fuel 2.15.09 3:25 pm 5:53pm 54 lbs 2.16.09 8:40 pm 27 lbs 9:35pm 2.17.09 6:17 pm 8:40 35lbs pm 2.18.09 NO BURN NO BURN 2.19.09 7:50 am 10:30 am 56 lbs 2.20.09 NO BURN NO BURN 2.21.09 4:20 pm 7:00 pm 2.22.09 11:30 am 1:15pm 43 lbs 24 lbs Douglas fir has 18.1 MBtu/cord and weighs 2900 lbs/cord (Sweep s Library, 2009). 18.1MBtu / cord 2900lbs/ cord = 6241 Btu/lb. 6241 Btu/hr X 239 = 1,492,000 Btu

239 lbs of wood therefore gives 1,492,000 Btu total for the 7 days, two hours. 1492000Btu 170hrs = 8776 Btu/hr. 4.5 Total Heat Losses and Gains Net heat loss is calculated by subtracting the total internal heat gains due to solar, occupant and equipment sources from the heat loss of the building: 14608 Btu/hr 7628 Btu/hr = 6980 Btu/hr Potential Heat from Masonry Heater = 8776 Btu/hr Stove efficiency = (6980 Btu/hr) / (8776 Btu/hr) x 100 = 79.5% efficiency 5. ANALYSIS The masonry heater in conjunction with other sources of heat gain supplied sufficient heat to overcome the home s heat loss. It kept the home at an average temperature of 65.9 0 F despite relatively cold temperatures outside. Heat loss through the thermal envelope accounted for 14608 Btu/hr. The single largest source of heat loss was predictably through the windows, which accounted for 38% of the total heat loss. Heat gains from sources other than the masonry heater produced 7628 Btu/hr. By subtracting the heat gains (7628 Btu/hr) from the total heat loss through the envelope (14608 Btu/hr), the net heat loss of the building is determined (6980 Btu/hr). This value represents the heat produced by the masonry heater. Comparing this number to the potential available energy from the wood (8776 Btu/hr) provides the efficiency of the stove. The stove was found to be 79.5% efficient. 6. CONCLUSIONS The initial hypothesis that the masonry heater would operate at 90% efficiency proved incorrect. The heater in fact operated at 79.5% efficiency. This is most likely due to the process of burning wood, which can only operate at a limited efficiency level. Further study of the stove s efficiency would benefit from testing in a closed environment. The variables of internal heat gain from occupants and appliances and the passive solar heat gain were estimated in this study but could be eliminated entirely in a closed laboratory experiment. perhaps in the kitchen where it provides a natural focus for talk and dreams and thought ( Pattern Language, #181). The data obtained from the data loggers suggests that heating a home with fire provides a feeling of thermal comfort at lower temperatures, as the temperatures in the space fell below American Society of Heating Refrigeration and Air-conditioning Engineers (A.S.H.R.A.E) standard 55-2004 (Stein et. al. 2005 p.88) on a few different occasions. Conversations with the homeowner revealed that the stove was not lit on two of the seven days because they considered the space warm. The data loggers indicate that on these days the outdoor temperature was higher than the other days, but interior temperatures went well below the temperatures experienced on the days when the stove was used. This suggests that heating with such a stove allows occupants to customize how often and to what temperature they heat their space on a more intimate level than a traditional system and, since the owners are in such close contact with the method of heating, they realize its significance and importance and are able to live with and appreciate the variations in temperature. 7. ACKNOWLEDGEMENTS The authors of this study would like to thank the Barkman family for allowing us to study their home. Also, thanks to Rob Thallon for setting up the initial meeting the family. 8. REFERENCES Gronbeck, Christopher. "Window Heat Gain." Sustainable by Design. 2005. 11 Mar 2009 <http://www.susdesign.com/windowheatgain/index.php>. Kusterer, John M. "NASA Surface meteorology and Solar Energy:." Atmospheric Science Data Center. March 2009. 11 Mar 2009 <NASA Surface meteorology and Solar Energy:>. Stein et. al. Mechanical and Electrical Equipment for Buildings, 10th Edition. New York, NY: Wiley, 2005. "Sweep's Library: Firewood Comparison Charts." Chimney Sweep Online. 2009. 11 Mar 2009 <http://chimneysweeponline.com/howood.htm>. Tulikivi Product Brochure: 2007-2008. Juuka, Finland: Tulikivi, 2008. In A Pattern Language, Christopher Alexander highlights the importance of fire in human existence: There is no substitute for fire build the fire in a common space