1.0 GENERAL TECHNICAL SPECIFICATION FOR DRY TYPE 11/.433 KV, 750 KVA TRANSFORMER :

Similar documents
SECTION DRY-TYPE TRANSFORMERS

This section applies to the design and installation of transformers.

Presentation of the France Transfo factories

TECHNICAL SPECIFICATION FOR 200, 315 & 630 KVA, 11/0.433 KV DRY-TYPE (VPI) DISTRIBUTION TRANSFORMERS (INDOOR AND OUTDOOR)

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS

SECTION SUBSTATION TRANSFORMERS

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003

DRY TYPE TRANSFORMER

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

Low Voltage Transformers Sealed, General Purpose, Dry Type

SPECIFICATIONS OF STATCOM TRANSFORMER (FOR 2.5 MVAR STATCOM)

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

UGVCL/SP/591/11KV HT AB CABLE

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

FAQs-Main switchboard design criteria

TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.)

Unified requirements for systems with voltages above 1 kv up to 15 kv

understanding medium frequency induction melting furnace and its components


Technical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva

11KV/433 V- MOBILE SKID MOUNTED SUBSTATION

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Tasarım ve Baskı: AJANSBRAND A

Primary and Secondary Electrical Distribution Systems

Fault location on power cables. Fault location on power cables

Aerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW

SECTION HEAT PUMPS

Multi-tap Transformers

THE VALUE OF POWER FACTOR TESTING

INTERNATIONAL STANDARD

GUIDE FOR TESTING POWER TRANSFORMERS

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

SPECIFICATIONS FOR 220KV CAPACITOR VOLTAGE TRANSFORMER. The equipment is required for 220KV system. The system data is given as under:

Diesel Engine Driven Generators Page 1 of 6

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

Transformer Bushings for GIS

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Secondary Unit Substations

CATHODIC PROTECTION TRANSFORMER RECTIFIER (CPTR)

Commercial Gas Furnace Upflow

CAPACITOR BANK TESTING SWP

Modular Systems wind portfolio overview Power Collection and Grid Connection products

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)

Distribution Dry Type Transformers

SURGE PROTECTIVE DEVICES

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

Transformer Design & Design Parameters

TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR

ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) J. Instruction Leaflet

CLAMPS CONNECTORS & EQUIPOTENTIAL RING

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

2013 RESIBLOC transformers Product presentation. ABB Group October 2, 2013 Slide 1

CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd

Receiving, Installing, Operating and Maintaining Dry Type, VPI Sealed, Cast Coil and UNICLAD Transformers

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

MODEL 2202IQ (1991-MSRP $549.00)

An Overview of Lapp Insulator High Voltage Bushing Design

TC Grounding and Bonding for Telecommunications Systems

2 X 2000 KVA, 415V DG SYSTEM FOR PROPOSED DATA CENTRE NCMRWF, NOIDA, UP.

R=Required by Lab S=May be subcontracted IEC SYSTEM FOR CONFORMITY TESTING AND CERTIFICATION OF ELECTRICAL EQUIPMENT COMMITTEE OF TESTING LABORATORIES

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

Instructions for Secondary Unit Substation Transformers KVA, Three Phase

HV Submarine Cable Systems Design, Testing and Installation

Power transformers. Special transformers Railway

Voltage Rated operating voltage [kv] Rated power frequency withstand voltage [kv] Rated lightning impulse withstand voltage [kv]

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS

Lightning Arresters P KVA P KVA. Description & Installation

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold C

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation

the quality par excellence Meghna Industries Manufacturer of : All types of fiberglass Cables

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Distribution Transformers. The most comprehensive range of solutions for distribution transformer applications

600 Volt Class Transformers

CABLE ACCESSORIES kv

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR

21.1 Functions, Basic Configuration, and Interfaces

ECOCIAT. Domestic hot water heat recovery unit

RADIANT PLASMA 4700 Plasma Spark Generator

Explosion proof enclosures

Practical Transformers: Operation, Maintenance and Testing

SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor

TRANSFORMER DICTIONARY

Solid-Cast Versus Resin-Encapsulated Transformers

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA

Series 8146/5-V37 and Series 8150/5-V37

TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer

Transcription:

1.0 GENERAL TECHNICAL SPECIFICATION FOR DRY TYPE 11/.433 KV, 750 KVA TRANSFORMER : 2.1 Supply of Transformer: The specifications given below relates to the design, manufacture, testing and supplying of Step Down Vacuum process Impregnated Dry Type Indoor Transformer. 2.2 Standards: A. The design, manufacture and performance of equipment shall comply with all currently applicable statutes, regulations and safety codes in the locality where the equipment will be installed. Nothing in this specifications shall be construed to relieve the Vendor of this responsibility. B. Unless otherwise specified equipment shall conform to the following latest applicable Indian Standards. (a) IS:11171 - Transformer (b) IS:3639 - Fittings and Accessories for Power Transformer (c) IS: 2099 - High Voltage Porcelain Bushings. 2.3 System of Supply: 11 kv, 3 phase, 50 cycles solidly earthed system. 2.4 Rating: Suitable for continuous rating. 2.5 Ratio: 11000 / 433 Volts. 2.6 kva Rating: 750 kva 2.7 Connections: Delta on H.V. Side and star on L.V. side with neutral terminal brought out for solid earthing in addition to the neutral terminal in the L.V. cable box. 2.8 Vector Groups: Corresponding to the Vector Symbols Dyn-11, Impedance shall not exceed 6.25%. 2.9 Type: Indoor. 2.10 Constructional Features: A. Similar parts, particularly removable ones, interchangeable. B. Exposed parts shall not leave pockets where water can collect. C. Internal design of transformer shall ensure that air is not trapped in any location.

2.11 Core: A. The magnetic circuit shall be of Core Type construction. The core shall be built out of high grade, non-aging, low loss, high permeability, cold rolled grain oriented silicon steel laminations. B. The finally assembled core shall be free from distortion. It shall be rigidly clamped to ensure adequate mechanical strength and to prevent vibrations during operation. C. The core shall be provided with lugs suitable for lifting the complete core and coil assembly. D. The core and coil assembly shall be so fixed in the enclosure that shifting will not occur during transport or short circuits. E. The core must be treated with high temperature resistant paint to prevent corrosion at edges of the core plates. 2.12 Internal Earthing: All internal metal parts of transformers shall be earthed. 2.13 Winding: A. Winding shall be subjected to shrinking and seasoning process, that, no further shrinkage occurs during service. Adjustable devices shall be provided for taking up possible shrinkage in service. B. Materials used in the insulation and assembly of the windings shall have high tensile and dielectric strength. These shall not soften or otherwise get affected under the operating conditions. C. In case of Dyn-11 transformers, neutral shall be brought out in open for solid earthing on the secondary side. D. The windings shall be copper wound. 2.14 Transformer Losses : The Maximum allowable losses shall be within IS Tolerance. 2.15 Enclosure: Steel enclosure with screens of metal at top and bottom for indoor type transformer and ventilation required from the top. 2.16 Impregnation: A. Coils to be impregnated with epoxy resin by vacuum pressure impregnation process to ensure void free impregnation. B. The process shall consist of but not limited to preheating, vacuum drying, under vacuum entry of resin, vacuum submersion, pressurization, draining, transfer to oven and curing. C. Class of Insulation: Type H.

2.17 Tappings: Off load tap changing arrangement on H.V. side. The tappings to be provided for variation of H.V. voltage from +5% to -5% in steps of 2.5%, with arrangement interlocking with HT breakers with door opening including 2 sets of keys. 2.18 Temperature Rise: Continuously rated for full load; temperature rise not to exceed 115 0 C over ambient. 2.19 Cooling: Natural air cooling. 2.20 Fittings: The following accessories and fittings shall be provided with the transformers: A. Inspection covers: Hinged type inspection cover on side of the transformer shall be provided. B. Lifting lugs: The arrangement of lifting the active part of the transformer along with the cover of the tank by means of lifting lugs without disturbing the connections. Also complete transformer lifting lugs shall be provided. Lifting arrangement for core and coils shall also be provided. C. Jacking pads: Jacking pads shall be provided on the transformer. D. Earthing terminal: Two nos. earthing terminals shall be provided of copper of non-corrosive material on transformer enclosure and one earthing terminal of neutral on the cable boxes. E. Diagram and rating plate: One diagram and rating plate indicating the details of transformer, connecting diagram vector group, tap changing diagram etc. shall be provided. F. Rollers: 4 Nos. bi-directional type roller shall be provided to the transformers on cross channels to facilitate the movement of transformers in both the directions. G. Temperature Indicator: Winding temperature indicator with contacts for operating trip circuits as well as for alarm shall be provided. Also suitable thermistors or RTD sensors shall be provided in all three windings. 2.21 Cable End Boxes: A. On H.V. Side Cable end box suitable for 11 kv, 3C x 150 sq.mm. XLPE cable. The size of box should be sufficient for termination using cable jointing kit.

B. On L.V. Side On L.V. Side cable end box shall be provided suitable to accept 6 Nos. 3.5 x 300 sq mm XLPE, armoured, Al conductor cables. The cable terminal box shall be provided with suitable cable glands of proper size and number of lugs shall be provided on the terminal for all cables. 2.22 Thermo Junction Box: A thermo junction box shall be provided on the transformer to have Alarm contacts for temperature Indicator. The above box shall be suitably mounted on transformer and shall have a glass window for viewing purpose. 2.23 Painting: The interior of transformer enclosure and internal structural steel work shall be painted with heat resistant insulating varnish after thorough cleaning of all scales and dust. 2.24 Testing: The transformer shall be subjected to the following tests at the factory before dispatching the same and test certificates, in quadruplicate, shall be furnished: A. Measurement of winding resistance. B. Ratio polarity and phase relationship. C. Measurement of Impedance of Voltage (Principle Tapping), short circuit impedance and load loss. D. Load losses. E. No load loss and no load current. F. Insulation resistance. G. Induced over voltage withstand. H. Separate source voltage withstand. I. Temperature rise by no load plus short circuit method. 2.25 Type test: The following Type test reports shall be submitted A. lightning impulse test B. Measurement of acoustic noise level C. Partial Discharge Measurement D. Short Circuit Test The routine and other tests to be performed as per IS:11171-1985 and IS:2026-1977.

2.26 Instruction Manual: The contractor shall submit three copies of manual of complete instructions for the installation, operation, maintenance and repairs, circuit diagram and foundation details shall be provided with the transformers. 2.27 Drawings: Four sets of drawings of the transformers being supplied shall be furnished within two weeks of placement of order for approval to the P.M.C./ Architects.