HIGH VOLTAGE INSULATION TESTER KEW 3121A, 3122A, 3123A

Similar documents
User Guide. Model Insulation Tester / Megohmmeter

162 CB CABLE TRACER. Filter Probe & Tone Generator INSTRUCTION MANUAL

MEGGER Insulation & Low Resistance Tester

EPM3. Phase Sequence and Motor Rotation Tester. Users Manual

UT202A Operating Manual. Contents

Manual Ranging MultiMeter

Model UT201/202: OPERATING MANUAL. Table of Contents

User Guide. 4 wire Earth Resistance Tester Model GRT300

Model UT713 OPERATING MANUAL

7 FUNCTION DIGITAL MULTIMETER

Model UT33A: OPERATING MANUAL Table of Contents (1)

AutoRanging Digital MultiMeter

Owner s Manual

CONTIENTS. 1. SPECIFICATIONS (mm) CAUTIONS INSTALLATION INSTRUCTION

User's Guide. True RMS Industrial Multimeter

PowlVac Vacuum Integrity Tester

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual.

400 Amp Rechargeable Jump Start System RAC-HP082

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS:

VOLTAGE/CURRENT CALIBRATOR ISO-TECH ILC-421

EKOS Cart. Instructions for Use

Model UT33B/C/D: OPERATING MANUAL Table of Contents (1)

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

Model 1756 Test Lead Kit

USER S MANUAL. MaxPower UPS. Uninterruptible Power System 28-2MAXPO0018

OPERATING INSTRUCTIONS

Hygro-Thermometer + InfraRed Thermometer Model RH101

USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102

Instructions A Amp AC/DC Current Probe

User s manual FLIR VP50/VP52 Non-contact AC voltage detector

12 Volt 30 Amp Digital Solar Charge Controller

ADM1TE 5/30A DIN rail single phase two wire energy meter

National- Spencer Inc.

323/324/325. Calibration Manual. Clamp Meter

Operating instructions Cordless K impact wrench

User s Manual AURORA 1.2K/2.2K

COMPLETE MANUAL. Version: Optic. September 2015 (English), version 1.0. EnergyOT Optic Developed and Manufactured by Genoa Spark, lda Made in Portugal

Instruction Manual. 2in1 LAN Tester & Multimeter. Model: LA-1011

Ground Resistance Clamp On Tester

Cable Tester Pro ORDERCODE D1909

HVAC Clamp Meter. Users Manual

PART 1 - INTRODUCTION...

RIGOL. Quick Guide. DS1000CA Series Oscilloscope. Aug RIGOL Technologies, Inc.

Owner s Manual & Safety Instructions

User s Manual Before using the inverter, you need to read and save the safety instructions.

Auto Feed Screwdriver

How To Use A Power Supply Unit (Upu)

Seven function digital multimeter

19 LED Tube Controller ORDERCODE 41003

User Guide. Heavy Duty Dissolved Oxygen Meter. Model

FLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION

5800 Temperature Sensor Cable Assembly

LED MOTION ACTIVATED FLOOD LIGHT

Auto-ranging Digital Multimeter INSTRUCTION MANUAL

Instructions: Part I. Charge the Power Bank. Method 1. Charge the Power Bank via Computer USB Terminal.

13 Watt PORTABLE SOLAR POWER KIT

DC POWER SUPPLY ALIMENTATION C.C.

When you switch off your system, or mute the sound, the red indicator light appears immediately, indicating that the subwoofer is not in use.

INSTRUCTION MANUAL PLEASE READ ALL THE INSTRUCTIONS COMPLETELY BEFORE USE AND SAVE THIS MANUAL FOR FUTURE REFERENCE

EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM

How To Use A Cdm250 Digital Multimeter

PTU Series Ultrahigh-Purity Pressure Transducers

Nucleus Freedom BTE Rechargeable Battery (A25) and Nucleus Freedom BTE Recharger

OWNER S MANUAL. Model AE150/AE300/AE AMP MULTI-USE SMART BATTERY CHARGER READ ENTIRE MANUAL BEFORE USING THIS PRODUCT

Manual. Solar Fountain Mobile Phone Charger

Power supply unit Model: PAC-SC50KUA

EzFlex Combustible Gas Leak Detector Model EZ40

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE

BLOOD COLLECTION MIXER

Radio BMR100 INSTRUCTION MANUAL. ENGLISH (Original instructions)

16/32 Channel 1U Rack Mount CCTV Power Supply

i410/i1010 AC/DC Current Clamp

Replacement Instructions. Warning: During this procedure, keep small parts away from children.

WIND ALARM. Wind Speed Alarm. Wind Speed. Set Point 2. Set Point 1 NEW BEDFORD, MA USA

Operation Manual Magic Bowling. Warning Please read this manual carefully before using this machine

Battery Charger For Nickel Cadmium and Nickel-Metal Hydride Rechargeable Batteries Model PSN Series

INSTRUCTION MANUAL IPM Phase Power Analyser EN FR IT DE ES

PRO370D 65A Mbus MID DIN rail three phase four wire energy meter. User manual Version 1.03

12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual

12. Inspection and Maintenance

Match. GE Digital Energy. Uninterruptible Power Supply VA. Technology for the Digital World. Match UPS. GE Digital Energy.

Rapide Inline Ceiling Extractor Fan, White Fascia Rapide Inline Ceiling Extractor Fan, Chrome Fascia

Insulation Resistance Testing of Low Voltage Cables in the Field

ACL 395 Resistivity Meter

Ducoterra Radiant Heating Panel Installation Manual

Model HPX10 Series Automatic Battery Charger User s Manual Rev. 1.0 October 17, 2006

Quick start guide smart.power smart.power smart.power

FUJI DIGITAL SOUND DETECTOR FSB-8D INSTRUCTION MANUAL

Contractors Guide Central Inverter System Installation

TIG INVERTER INSTRUCTION MANUAL

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases

NÜVE SANAYİ MALZEMELERİ İMALAT VE TİCARET A.Ş. OT 020 BENCH TOP STEAM STERILIZER USER S MANUAL

FC6 FOOT CONTROLLER OWNER S MANUAL

6/14/02 Chapter 14: Use of Electrical Test Equipment 1/20

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Handheld portable appliance testers

Vario-Series Accessories

How To Read A Pipe From A Sensor

Odyssey of the Mind Technology Fair. Simple Electronics

RS Stock No Instruction Manual RS-1340 Hot Wire Anemometer

Transcription:

INSTRUCTION MANUAL KEW3121A, 3122A KEW3123A HIGH VOLTAGE INSULATION TESTER KEW 3121A, 3122A, 3123A

CONTENTS Page 1 Safety warnings 1 2 Features 2 3 Specifications 3 4 4 Instrument Layout 5 5 Operating Instructions 6 5-1 Mechanical Zero Adjustment 6 5-2 Battery Check 6 5-3 Insulation Resistance Measurement 7 5-4 Continuous Measurement 7 5-5 Use of Guard Terminal 8 6 Battery Replacement 9 7 Accessories and options 9 7-1. Metal part for Line Probe, and replacement 9 7-2. How to use the adaptor for recorder 10 8 How to fix the Meter to the Hard case 11 9 Cleaning Meter Cover 12

1. Safety warnings Please read through these operating instructions before using the instrument to avoid any dangers such as electrical shock and to ensure safe operation of the instrument. Pay particular attention to all WARNING and CAUTION in this instruction manual. WARNING indicates warnings to avoid electrical shock and CAUTION indicates cautions to avoid damage to the instrument. # WARNING This instrument cannot test live conductors. Ensure that the circuit to be tested is powered off before performing a test. Never open the Battery cover or remove the Instrument panel during a measurement. Confirm that the Rotary switch is at the OFF position, and then connect the test leads. Do not attempt to make measurement in the presence of flammable gasses. Otherwise, the use of the instrument may cause sparking, which can lead to an explosion. Never attempt to make any measurement if any abnormal conditions, such as a broken cover or exposed metal parts are present on the Instrument or test leads. Set the Function switch to OFF position after use, and ensure the Test button is released and unlocked. # CAUTION Do not expose the instrument to direct sunlight, high temperatures, humidity or dew. Never leave the instrument in the environment of 60 C or higher temperatures. Do not use the instrument if it or test lead is wet. Remove the batteries if the instrument is to be stored and will not be in use for a long period. Use a damp cloth with neutral detergent or water for cleaning the instrument. Do not use abrasives or solvents. 1

2. Features Battery powered, the instruments test insulation up to 100000M at 2500V for KEW 3121A, 200000M at 5000V for KEW 3122A and 200G at 5000V and 400G at 10000V for KEW 3123A. Suited for heavy duty electrical maintenance and servicing of industrial installations, cables, transformers, generators and switchgear where high voltage insulation tests are required. Dual scales for low an d high ranges which change automatically. Colour coded scales for easy reading plus LED's that illuminate in matching colour. Drip proof construction. The case is sealed with rubber gaskets to protect internal circuit against rain. Hard carrying case furnished as standard accessory. Houses both instrument and test leads in compact form. Made of plastic, it is highly water resistant. Designed for low power consumption. Since the maximum current consumption is 90mA eight pieces of 1.5V SUM-3 or equivalent permit about 6 hours of continuous operation even when the instrument is used on maximum load or twice longer on minimum load. Rated output voltage is maintained down to 100M for KEW 3121A, 200M for KEW 3122A and 0.2G /0.4G for KEW 3123A. This permits accurate measurements of low insulation resistance. Optional adapter MODEL8324 is available for connection to recorder and enables cable insulation monitoring. 2

3. Specifications KEW 3121A KEW 31 DC Test Voltage 2500V 5000 V Measuring Ranges 0 2000M / 1000 100000M automatic change 0 5000 M 2000 20 (automatic ch 5% of reading 100 50000M 10% of reading or 0.5% of scale length ranges other than listed above 5% of re 200 10 10% of re or 0.5% of sc ranges ot listed ab Accuracy Insulation at 23 5 at 23 Resistance 10% of reading 10% of re 100 50000M 20% of reading or 1.0% of scale length ranges other than listed above at 10 40 200 10 20% of re or 1.0% of sc ranges ot listed ab at 10 Output 2500V 5% 5000V 5 Voltage 100 50000M 200 10 Operating Temperature & Humidity 10 Storage Temperature & Humidity 20 Insulation Resistance 1000M max./ 10 Withstand Voltage 5000V AC for one m Dimensions 20 Weight Approx. 1k Power Source 8 pcs of R6 Hard Carrying Case:M-9158 Test Leads Accessories (Line Probe:M-7165A, Earth Cord:M-7224A, Guard Cord:M-7225A) Line cord with alligator clip M-7168A Optional accessories Optional adapter M-8324 Pickel type prod:m-8019 3

3122A KEW 3123A V 5000V 10000V 0 M / 0 5G /2 200G 200000M (automatic change) ic change) of reading 5% of reading 100000M 0.2 100G f reading 10% of reading f scale length or 0.5% of scale length s other than ranges other than d above listed above 5 at 23 5 f reading 10% of reading 100000M 0.2 100G f reading 20% of reading f scale length or 1.0% of scale length s other than ranges other than d above listed above 40 at 10 40 5% 5000V 5% 100000M 0.2~100G 40 at 85% max. relative humidity 60 at 90% max. relative humidity 0 10G /4 400G (automatic change) 5% of reading 0.4 200G 10% of reading or 0.5% of scale length ranges other than listed above at 23 5 10% of reading 0.4 200G 20% of reading or 1.0% of scale length ranges other than listed above at 10 40 10000V 5% 0.4~200G / 1000V between electrical circuit & housing case e minute between electrical circuit & housing case 200 L 140 W 80 D mm 1kg including batteries f R6P (AA) battery or equivalent Hard Carrying Case:M-9158 Batteries, Test Leads (Line Probe:M-7165A, Earth Cord:M-7224A, Guard Cord:M- 7225A) Pickel type prod:m-8019 Line cord with alligator clip M-7168A Optional adapter M-8324 4

4. Instrument Layout 3 2 1 4 4 7 8 5 6 Line Terminal Guard Terminal Earth Terminal LED's for High & Low Range Indication Press to Test Button Function Switch Meter Movement Zero Adjust Battery Compartment Cover Line Probe (Red) Earth Cord (Black) Guard Cord (Green) Fig.1 11 10 9 5

5. Operating Instructions CAUTION: BE CAREFUL ABOUT HIGH VOLTAGE PRESENT ACROSS LINE AND EARTH TERMINALS OF INSTRUMENT WHEN PRESS TO TEST BUTTON IS OPERATED. MAKE SURE TO EARTH CIRCUIT UNDER TEST. ALWAYS CONNECT EARTH TERMINAL OF INSTRUMENT TO EARTH. THE BUZZER WILL KEEP SOUNDING DURING INSULATION RESISTANCE MEASUREMENT. 5-1. Mechanical Zero Adjustment With the function switch set at OFF position, adjust the meter pointer to mark on the scale. Use a screwdriver to turn the zero adjust screw located at the center of the front panel. 5-2. Battery Check With the function switch set at BATT. CHECK position, operate the press to test button. The batteries are good when the pointer stays in BATT. GOOD area or to the right of this area. If not, replace them. Note: Refrain from holding down or locking the press to test button during this test as it will result in current consumption larger than insulation resistance measurement while the batteries are still new. 6

5-3. Insulation Resistance Measurement With the function switch set at OFF position, always connect the circuit under test to earth. Attach the test lead to the earth terminal of the instrument and connect to the earthed side of the circuit under test. With the function switch set at 2500V and 5000V for KEW 3121A and 3122A or 5000V or 10000V for KEW 3123A, connect the black earth code to the earth terminal (EARTH) and place the line probe in contact with the circuit under test and press the Test button. When the green LED illuminates, read insulation resistance on the outer scale (for high range). Use the inner scale where the red LED illuminates. For insulation testing at 5000V and 10000V, read the black and red scales respectively (for KEW 3123A). After a test, release the press to test button and wait for several seconds without disconnecting the line probe from the circuit tested. This is intended to discharge the charge stored in the circuit tested. 5-4. Continuous Measurement Make sure that the circuit under test is earthed and that the test lead attached to the earth terminal of the instrument is connected to the earthed side of the circuit under test. Push the press to test button and turn clockwise to lock for continuous measurement. When making this measurement, good care must be taken against the high voltage continuously present across the line and earth terminals of the instrument. Note: Make certain that the circuit under test does not include components which will be damaged by the high voltage applied. 7

5-5. Use of Guard Terminal When measuring the insulation resistance of a cable, Ieakage current flowing on the surface of cable jacket and the current flowing inside the insulator are mixed and may cause error in insulation resistance value. In order to prevent such error, wind a conductive wire around the point where leakage current flows. Then connect it to the Guard terminal as shown in below Fig.2. This is to move out the surface leakage resistance of the cable insulation to measure only the volume resistance of insulator. Make sure to use the Guard cord supplied with this instrument to connect the instrument to Guard terminal. Connect the terminals with reference to the following figure of an equivalent circuit. * Wind a protective wire, any conductive bare wires are ok, around the point where leakage currents flow. Then connect it to the Guard terminal as follows. Fig.2 * It is possible to move out the surface leakage resistance of the insulation and measure only the volume resistance by using the Guard terminal. This is helpful when performing tests in humid air. 8

6. Batttery Replacement Remove the battery compartment cover by loosening the screw located on the back of the housing case. Replace the whole battery pack. Alkaline batteries are recommended where the instrument is used at a temperature below the freezing point. The ordinary manganese batteries will deteriorate below the freezing point. 7. Accessories and options 7-1. Metal part for Line Probe, and replacement 1 Tip metal parts MODEL8252: Standard Prod (straight type, with molded parts) MODEL8254: Straight Type Prod MODEL8019: Pickel Type Prod (accessory) To be used to hook the instrument. Note:Option KEW3121A, KEW3122A 2 How to replace it Turn the Line probe counterclockwise to remove the attached tip metal. Put the tip metal you want to use to the hexagon socket and turn it to clockwise together with the tip of probe and tight up screws. 9

7-2. How to use the adaptor for recorder MODEL8324 is the adaptor for recorder for output current measurement. Connect it as shown in the below Fig.3. Output is DC10mV when current of 1 A is flowing To shield or Earth To recorder Fig.3 10

8. How to fix the Meter to the Hard case Please follow the instructions below to fix MODEL9159 main unit to MODEL9158 Hard case with Dual lock fastener. 1. Place a hard board beneath the Hard case. The board should be located under the fastener attached to the Hard case. 2. Put the unit in place, and then press down the sides of the unit so that the mushroom-shaped stems on the fastener are engaged each other with audible snap sound. 11

9. Cleaning Meter Cover This earth tester is managed by our company's quality standard and is delivered in the best condition after passed the inspection. But in the dry time of winter static electricity sometimes builds up on the meter cover due to the characteristic of plastic. When the pointer deflects by touching the surface of this tester or zero adjustment can not be made, do not try to make measurement. When static electricity builds up on the meter cover and affects the meter reading, use a cloth dampened with off-the-shelf anti-statics agent or detergent to wipe the meter cover surface. 12

DISTRIBUTOR Kyoritsu reserves the rights to change specifications or designs described in this manual without notice and without obligations. 7-11 92-1919C