SECTION MEDIUM VOLTAGE TRANSFORMERS (LIQUID FILLED) 1. Liquid filled pad mounted transformers.

Similar documents
Medium Voltage Electrical Distribution

This section applies to the design and installation of transformers.

Primary and Secondary Electrical Distribution Systems

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Multi-tap Transformers

TRANSFORMER DICTIONARY

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Step Voltage Regulators

CalMod Design-Build Electrification Services

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

16300 MEDIUM VOLTAGE DISTRIBUTION

Practical Transformers: Operation, Maintenance and Testing

Unified requirements for systems with voltages above 1 kv up to 15 kv

Data Center Solutions. Envirotran HDC Transformers Deliver Superior Reliability and Efficiency for Substantial Savings Everyday

Buck - Boost Transformers

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

Instructions for Secondary Unit Substation Transformers KVA, Three Phase

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

SECTION ELECTRICAL ACCEPTANCE TESTS

Low Voltage Transformers Sealed, General Purpose, Dry Type

SECTION SUBSTATION TRANSFORMERS

Heating Cable. Construction

Diesel Engine Driven Generators Page 1 of 6

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE:

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

Project Name: Nortrax Section Project No: SURGE PROTECTION DEVICES Page 1

Short Circuit Current Calculations

City of Riverside Building & Safety Division Phone: (951)

A. Shop Drawing submittals shall include, but not be limited to, the following:

Issued E.C.S. Section WTR00 INFORMATION SECTION Page 1 of 1

Electrical Maintenance Workshop

CURRENT TRANSFORMER MODEL 546 UL1015 #16 AWG LEAD WIRE, STANDARD LENGTH IS 24" 1 X

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

Secondary Unit Substations

FVSU REPAIR & UPGRADE FIBER OPTIC SECTION FIRE ALARM SYSTEM CONNECTIVITY

Electrical Contractors. and the. New Jersey. Rehabilitation Code

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

June July 18, of 7

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

S. C. Electric Cooperative s Specification for a Three-Phase, Padmounted URD Transformer (Revised 12/2014)

HL Series - Commercial Heaters Tankless Water Heating Solutions

Liquid Filled Transformers Load Tap Changing Transformers Three-Phase Voltage Regulators

Doc Ref: baselayer.com 2015 BASELAYER TECHNOLOGY, LLC

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

Magnum Mobile Generator MMG55 Specifications

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

County of Riverside Building and Safety Department

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

Transformer Deluge Systems

HIGH VOLTAGE SHORE CONNECTION

Element D Services Plumbing

MEDIUM VOLTAGE DISTRIBUTION

Electrical Grounding. Appendix C

FAIRBANKS NIJHUIS FIRE PUMPS.

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw

WINDING RESISTANCE TESTING

Distribution Transformers

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services

Motor Protection Voltage Unbalance and Single-Phasing

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design

E-Version SECTION CHLORINATION SYSTEM PART 1 - GENERAL PART 2 - PRODUCT

Screw Plug Immersion Heaters

Power transformers. Special transformers Railway

SECTION LOW VOLTAGE LIGHTING CONTROLS

Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling

How To Plan Out An Array Of Solar Panels

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

SECTION HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

D Youville College July 31, 2008 New Academic Building Cannon Design Project No

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

Hyperlinks are Inactive

Light Duty Commercial Electric Water Heater

Atlanta Chapter IEEE Industry Applications Society

Morrison Bros. Co. General Product Specifications

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

Customer Substation Manual 08/05/02

Distribution Voltage Regulators

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

NET 30 DAYS AFTER RECEIPT OF INVOICE

TABLE OF CONTENT

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

East Central College HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE

Corner-Grounded Delta (Grounded B Phase) Systems

Oil and Coolant Circulating Heating System. Model - OCSM

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

DIVISION 26 - ELECTRICAL SECTION CABLES FOR INSTRUMENTATION

Generator DoCKInG StatIonS

SWIMMING POOL HEAT PUMP

Transcription:

PART I - GENERAL 1.01 SUMMARY SECTION 16320 MEDIUM VOLTAGE TRANSFORMERS (LIQUID FILLED) A. Section Includes: 1. Liquid filled pad mounted transformers. B. Related Sections: 1.02 REFERENCES 1. Section 02200 - Earthwork: Soil Compaction Requirements 2. Section 03300 - Cast-in-Place Concrete: Pads for Transformer Support 3. Section 16110 Raceways 4. Section 09900 Painting A. All characteristics, definitions and terminology shall be in accordance with the latest revision of applicable ANSI and NEMA standards. B. American Society of Testing and Materials (ASTM). C. Institute of Electrical and Electronic Engineers (IEEE). D. Manufacturer must be ISO 9001 certified. 1.03 SUBMITTALS A. Require submittals under the provisions of Section 16010 - Basic Electrical Requirements and Section 01300 - Submittals. B. Submit shop drawings indicating outline dimensions, connection and support points, weight, specified ratings and materials. C. Submit product data indicating standard model design tests and options. D. Submit manufacturer s installation instructions under provisions of Section JULY 2012 UCB STANDARDS 16320-1

01300. 1.04 OPERATION AND MAINTENANCE DATA A. Submit operation and maintenance data under provisions of Sections 01700, 01730, 16010 Division I. B. Include procedures for cleaning unit and replacing components. C. Submit product data indicating standard model design tests and options. D. Submit manufacturer s installation instructions under provisions of Section 01300. 1.05 QUALITY ASSURANCE A. Manufacturer: Company specializing in distribution transformers with three (3) years documented experience. 1.06 DELIVERY, STORAGE, AND HANDLING A. Store and protect products under provisions of Sections 01600 and 16010. B. Protect transformers as instructed by the manufacturer. PART 2 - PRODUCTS 2.01 MANUFACTURERS Medium Voltage Transformers: A. ABB B. Cooper/Power Systems C. Square D 2.02 EQUIPMENT A. Pad Mounted Oil-Filled Transformers: 1. Liquid-filled Transformer, FM labeled, UL listed: a. Three phase, pad mounted, self-cooled transformer unit. JULY 2012 UCB STANDARDS 16320-2

b. Indicate kva capacity, secondary voltage. Transformers larger than 1000 kva shall not be used without special written authorization from the Director of Utility Services. c. Primary voltage 13.8 KV Three Phase Delta with wye secondary. Specify with 2-2 ½% above and 2-2 ½% below normal primary taps, with externally-operated no load tap changer. Secondary voltage as required. d. Impedance: Per ANSI Standards. Consult with the Director of Utility Services if the new transformer can be paralleled with an existing transformer. e. Cooling and Temperature Rise: 65 o C, self cooled. f. Accessories: All accessories shall be housed in a side accessories cabinet having the full height of the transformer with a lockable Penta-head cabinet door. All gauges and pressure indication shall have remote alarm contact. i. NSI tank ground pad ii. iii. iv. 1 filling plug mounted in the cover 1 drain plug 1 sampling valve v. Tap changer handle vi. vii. viii. ix. Liquid level gauge ¼ NPT with vacuum/pressure gauge Pressure relief valve Liquid temperature gauge g. Dielectric fluid shall be non-toxic, non-bioaccumulating and be readily and completely biodegradable per EPA OPPTS 835.3100. The fluid shall have a minimum open cup fire point (ASTM D92) of 350 C and be FM approved, UL Classified less-flammable JULY 2012 UCB STANDARDS 16320-3

Envirotemp FR3, all in accordance with current NEC Section 450-23. h. Primary Terminations: i. Specify six (6) ANSI/IEEE 386 600 dead break bushings as specified by the Director of Utility Services for loop fed application. Parking stands shall be provided. Specify three (3) internal oil immersed, two-position load-break switches to allow alternate circuit service and isolation of transformer. The three (3) switches shall be wired as shown in the diagram at the end of this section. i. Primary Overcurrent Protection: Two fuse system consisting of Bayonet-type, oil immersed expulsion fuse in series with current limiting backup fuse. Current limiting backup fuse to be mounted inside the transformer under oil. The current limiting fuse should be located as near as practical to the incoming primary bushing, on the source side of the expulsion fuse. The two fuses shall be coordinated so that the expulsion fuse clears low energy faults on the secondary system and the current limiting fuse clears only high energy includes overload protection, can be provided as an alternate with approval from the Manager of Utilities Distribution. All transformer fusing shall be coordinated with upstream phase overcurrent devices. j. Copper windings or aluminum windings, as specified by Manger of Utilities Distribution. k. NEMA TP1 Design l. Cabinet to be sized to accommodate 600 AMP bushings. m. Provide three spare Bayonet fuses. n. Transformer ID tag marking: Contractor is responsible to install transformer identification tag and cable ID on the new installed transformer. Install 2 x2 new non reflective weather resistant transformer identification tags. Cables ID tags on the transformer inside wall above each loop feed switch: Cable ID XX From XXX to XXX JULY 2012 UCB STANDARDS 16320-4

B. Transformer start-up: The on site test shall be completed after it is set on it s permanent pad and grounded. The transformer will not be started until all tests are complete and turned over to Owner and engineer (2 sets) for review and approval. PART 3 - EXECUTION 3.01 INSTALLATION A. Require installation in accordance with manufacturer s instructions. B. Require safety labels per NEMA, and provide code listed and label option for the non-toxic dielectric fluid. C. Transformer clearances shall comply with Xcel Energy requirements. D. Transformers shall be looped into the primary electric distribution system E. All secondary conductors shall be terminated utilizing compression type 2 hole lugs. F. Transformer grounding per specification E16390 transformer installation. G. New transformer installation shall have fault indicator as per specification E16366. 3.02 FIELD QUALITY CONTROL A. Factory and field testing shall be performed under provisions of Section 01400. All field tests shall be witnessed by the University. All test reports shall be turned over to the University. Perform the following tests: 1. Sample insulating liquid in accordance with ASTM 3612 D3613 and perform dissolved gas analysis (DGA) in accordance with ANSI/IEEE C57.104 and ASTM 3612. The oil shall be tested for: a. ASTM D-1533B Moisture in oil b. ASTM D-971 Inter Facial Tension c. ASTM D-974 Acid Number d. ASTM D-1500 Color Number JULY 2012 UCB STANDARDS 16320-5

e. ASTM D-1524 Visual Exam f. ASTM D-1816 Dielectec Breakdown g. ASTM D-924 Power Factor 25C 2. Turns ratio test on all taps. 3. Power factor test or dissipation factor test. 4. Excitation. 5. Require oil testing 48 hours after energization. Contractor shall submit reports to University for keeping. B. Factory test transformer to ANSI/IEEE C57.12.91 and provide University the test results prior to setting the transformer. 3.03 ADJUSTING Field test transformer to ANSI/IEEE C57.12.91. All field tests to be witnessed by Owner. All test reports shall be turned over to Owner. Adjust primary taps to tap 4 (13,455 volts) on 13,800 volt nominal transformers. END OF SECTION 16320 JULY 2012 UCB STANDARDS 16320-6