Effects of AC Ripple Current on VRLA Battery Life. A Technical Note from the Experts in Business-Critical Continuity



Similar documents
Charger Output AC Ripple Voltage and the affect on VRLA batteries

Technical Note: Comparing R407C and R410A as Alternatives for R22. A Technical Note from the Experts in Business-Critical Continuity

Constant Voltage Charger Selection for VRLA Batteries

How To Save Energy On A Power Supply

UPS Applications and VRLA Battery Sizing

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity

DISCONTINUED PRODUCT. Infrastructure Management & Monitoring For Business-Critical Continuity. Liebert icom-do. User Manual

Capacity Testing of VRLA Batteries (20 to 200 Ampere-Hours Capacity)

DCIM Readiness on the Rise as Significant Data Center Capacity Remains Unused. A Research Report from the Experts in Business-Critical Continuity TM

DataSafe HX Top Terminated Batteries 6 and 12 Volt HX

How To Run A Data Center Efficiently

Capacitors Age and Capacitors Have an End of Life. A White Paper from the Experts in Business-Critical Continuity TM

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Liebert : The Right Cooling For IT Environments. Precision Cooling For Business-Critical Continuity

Power Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM

IT White Paper IP TELEPHONY AND RELIABILITY: PROTECTING MISSION-CRITICAL PHONE SYSTEMS FROM POWER THREATS

Temperature Compensated Charging of Lead Acid Batteries

Securely Deliver Remote Monitoring and Service to Critical Systems. A White Paper from the Experts in Business-Critical Continuity TM

Reliability of Air Moving Fans, and Their Impact on System Reliability. A White Paper from the Experts in Business-Critical Continuity TM

The Effect of Regular, Skilled Preventive Maintenance on Critical Power System Reliability

Directed Circuits Meet Today s Security Challenges in Enterprise Remote Monitoring. A White Paper from the Experts in Business-Critical Continuity TM

Hospital IT and Facilities Special Report Top concerns in the hospital include budget, power requirements

SmartDesign Intelligent, Integrated Infrastructure For The Data Center. Solutions For Business-Critical Continuity

How To Get The Most Out Of Your Data Center Service From Liebert

Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes

Current and Temperature Ratings

Protecting Our Information, Protecting Our Resources

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers

Height w/o Terminals (in)

Secure Remote Monitoring of the Critical System Infrastructure. An Application Note from the Experts in Business-Critical Continuity

Carefree Sealed Lead Acid (SLA) MSDS

Liebert CW kW Chilled Water Cooled Precision Air Conditioning For Data Centers

Data Center Rack Systems Key to Business-Critical Continuity. A White Paper from the Experts in Business-Critical Continuity TM

Data Center Infrastructure Management Managing the Physical Infrastructure for Greater Efficiency

Application Note #49 RF Amplifier Output Voltage, Current, Power, and Impedance Relationship

10 Year VRLA Battery Periodic Maintenance Instructions

Protecting The Critical IT Infrastructure of the United States

The Technology Behind Liebert Monitoring Services. Services For Business-Critical Continuity TM

Ten Steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring

Liebert Data Center Services. Services For Business-Critical Continuity

Enterprise Remote Monitoring

Ten Steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring

How To Improve Energy Efficiency In Data Center Management

New York City Fire Code & Energy Storage Systems

Precision versus Comfort Cooling Choosing a Cooling System to Support Business-Critical IT Environments

Features: High reliability. Very sharp reverse characteristic. Zener voltage 3.3V to 12V. V z -tolerance ±5%.

Knürr CoolAdd The universal retrofit solution against overheating in server racks. Rack & Enclosure Systems

NP Series VALVE REGULATED LEAD-ACID BATTERIES

LEAD ACID BATTERY working LIFETIME STUDY

The High Performance Floormount Indoor Package Cooling Solution. Precision Cooling for Business-Critical Continuity

2. Add the following definitions to 3.3 General Definitions and renumber 3.3 as required:

875 Dearborn Drive Columbus, Ohio Tel: (614) Fax: (614)

IT White Paper. N + 1 Become Too Many + 1?

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity

Conductance Testing as an Integral Element in Battery Management

A reasonable, new furnace (mid efficiency) has the following electrical requirements:

Digital echo-charge. Owner s Manual. Xantrex Digital echo-charge Battery Charger

Mixing Sodium and Lead Battery Technologies in Telecom Applications

CS4525 Power Calculator

The Basics of Solar Power for Producing Electricity An excellent place to start for those just beginning. The basics of solar power: 1000 W/m²

1.1 ANNUAL PREVENTIVE MAINTENANCE VISIT

Bourns Resistive Products

Height w/o Terminals (in)

Charge Regulator SCR 12 Marine

Liebert GXT MT+ CX UPS, 1000VA VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity

DC GROUND FAULT DETECTION PROVIDED FOR UNINTERRUPTIBLE POWER SUPPLIES

ACHIEVING CHARGE QUALITY FOR LEAD ACID BATTERIES IN INDUSTRIAL MOTIVE APPLICATIONS

THE PROPER CHARGING OF STATIONARY LEAD-ACID BATTERIES. (YOUR BATTERY IS ONLY AS GOOD AS HOW YOU CHARGE IT.)

Stationary Storage Battery Systems

The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity

Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches

Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER

EVERGREEN (C.P.) USA INC. TEL: (650) FAX: (650) SPECIFICATIONS Lithium Battery CR123A- 1700mAh

SELECTION GUIDE FIFTH EDITION

CALCULATED VS. ACTUAL SHORT CIRCUIT CURRENTS FOR VRLA BATTERIES

REPORT ON THE LONG TERM RESULTS OF BATTERY CAPACITY RECOVERY PROCESSES FOR VRLA CELLS

Battery Model: 25 Part Number: Nominal Voltage: 12 volts NSN: Number applied for, product currently available

AAV003-10E Current Sensor

IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity

Understanding Delta Conversion Online "Power Regulation" - Part 2

Technical Information Battery Management of the Sunny Island Gentle charging control for lead-acid batteries based on current state of the battery

Meeting the FCC Backup Power Mandate From Site Audit to Total Site Solutions. DC Power, Outside Plant & Services for Business-Critical Continuity

Power and Cooling Best Practices for IP Communications. A White Paper from the Experts in Business-Critical Continuity

Virginia Tech. Background. Case Summary. Results

Solar Wind Microhydro Water Pumping Inverters Batteries Professional system design and installation

Experiment #4, Ohmic Heat

POWER AND VOLTAGE RATING

CHARGING METHODS. Methods of Charging the Valve Regulated (Sealed) Lead-Acid Battery. 19 Valve Regulated (Sealed) Lead-Acid Batteries

Manual. Solar Fountain Mobile Phone Charger

Abattery voltmeter is the most

Tel.X Ni-Cd battery. The compact maintenance-free solution for telecom networks

Advanced Fuel Cells A Reliable and Green Solution to Reduce Operating Expenses of Telecommunication Networks

LEAD CRYSTAL. User Manual. Valve-regulated lead-crystal batteries Energy storage Cells

1. Scope This specification is applied to ICR Product Specification Table 1 No. Item Rated Performance Remark

Liebert IntelliSlot Web Cards

Schottky Rectifier, 1.0 A

Iron Powder Cores for Switchmode Power Supply Inductors. by: Jim Cox

A Solar Powered Cellular Base Station

K Standard Grade Ni-Cr vs Ni-Al (Chromel vs Alumel)

Transcription:

Effects of AC Ripple Current on VRLA Battery Life A Technical Note from the Experts in Business-Critical Continuity

Introduction Given the importance of battery life to UPS system users and the fact that battery life is negatively impacted by elevated battery temperature, many IT and data center managers are concerned about the internal heating effects of battery ripple voltage and current present in UPS systems. Data reported by critical power engineering consultants and service personnel indicate that some UPS systems may generate ripple current above the battery manufacturer s recommended levels. Research into ripple current effects shows that while battery ripple current may exceed the battery manufacturer s guidelines, as long as the ripple current is not excessive (more than 3 to 4 times the recommended level) the resulting internal heating effects are minimal, and reduce the statistical expected life by only a few percentage points. Ripple voltage Battery manufacturers recommend that under normal float charge conditions, battery ripple RMS (Root Mean Square) voltage must be limited to <0.5 % of the DC voltage applied to the battery. Ripple Voltage (E) < 0.5% * normal float charge conditions (V float ) This ensures that the instantaneous cell voltage will not fall below the open cell voltage or rise above the maximum float charge voltage. It also eliminates the consequential battery heating that would occur from constantly cycling the battery through discharging and recharging states. Ripple current It is a misconception that as long as the battery ripple voltage specification is adhered to, then the ripple current created by this voltage must also be acceptable. This is not necessarily true since by Ohm s law, the ripple current is a direct function of the ripple voltage applied to the battery, as well as the internal cell resistance of the battery. I = E / R (Ohm s law) ripple current (I) = ripple voltage (E) / cell resistance (R) Because batteries have internal impedance or resistance, ripple current flowing into a battery at normal float charge conditions can cause heating due to simple power dissipation heating (based on I 2 R losses). Battery manufacturers typically recommend that the ripple current into a VRLA (sealed lead-acid battery) jar be limited to a value of the 20 hour discharge rate Amp-Hour Capacity divided by 20 (C/20 @ 20hr rate). As an example, the maximum ripple current for a typical AGM (absorbent glass mat) 12 volt 100 Ah VRLA battery (@ 20hr rate) would be 100/20 or 5 amps (I). 1

Ripple current power dissipation This type of battery may have an internal impedance of 2.5 milliohms (R), so the power dissipation would then be: I 2 R = (5 amps) 2 * 0.0025 ohms = 0.062 watts According to battery manufacturers, this level of ripple current will not cause any appreciable battery heating. As previously stated, the level of ripple current present in a particular battery depends not only on the ripple voltage present, but also on the internal cell resistance of the battery. For example, using the 12 volt 100 Ah battery example above and assuming some nominal battery string wiring and connection impedance of 0.5 milliohms, if the maximum ripple voltage (0.5% of the recommended float voltage of 13.5 volts per jar) is applied to this battery, the resulting ripple current would be: 13.5 volts * 0.5 % / (0.003 ohms [internal + interconnect impedance] ) = 22.5 amps This is well above the 5 amps (C/20) recommended maximum ripple current for this battery. This brings the discussion to the issue the level of ripple current seen in UPS systems. For a typical 540 volt DC bus system, depending on the rectifier and inverter topology employed, the ripple voltage present on the UPS DC bus has been observed to be as much as 2 volts RMS. While this is well below the maximum ripple voltage specified (540 * 0.5% = 2.7 VRMS max.), it can result in battery ripple current in excess of the recommended level. Assuming a 40 jar battery string (13.5 volts float voltage * 40 jars = 540 volts DC bus) with the same battery example being used above, the ripple current would be: (2 volts / 40 jars) / 0.003 ohms = 16.6 amps ( 3 times the recommended 5 amps max) So, the question becomes, what is the result of exceeding this specification? What is the magnitude of the cell heating effect and how does it impact battery life? Predicting the heating effect of ripple current As discussed previously, the amount of heating caused by ripple current is directly related to the magnitude of the current and the internal impedance of the battery (I 2 R losses). At sufficiently high levels of ripple current, Faradaic (electrochemical) heating can also occur, but as long as the ripple current does not cause the cell voltage to exceed the maximum recommended float voltage or fall below the open cell voltage at which discharging occurs (2.14 V), then this effect is insignificant. According to a paper published by C&D Technologies [1], at float conditions, battery heating is almost solely due to ohmic (resistive heating) rather than electrochemical heating. 2

Therefore, using basic thermodynamic principles, an equation for calculating internal battery temperature rise as a function of battery ripple current can be derived. Starting with the basic equation for heat conduction: h (watts) = H (heat transfer coefficient) * A (area) * T Where: h = heat generated by the I 2 R losses in the battery (I = AC ripple current, R = battery internal resistance) H = heat transfer coefficient of the battery A = effective surface area of the battery jar or case in meters 2 T = temperature rise of battery above ambient, T battery - T ambient Taking a specific battery as an example, the manufacturer s battery specification data sheet for the C&D UPS12-490MRLP battery shows the internal resistance to be 0.0023 ohms and the case dimensions to be 323 x 166 x 213 mm. The heat transfer coefficient for this battery is approximately 4.6 W/m2/ C [2]. Rearranging the above equation to get an equation for temperature rise as a function of ripple current: T = I 2 R / (A * H) For the UPS12-490MRLP battery (and converting C to F): T = I 2 * 0.0023 / (0.315 * 4.6) * 1.8 F/ C 0.0028 * I 2 F Summarizing, the temperature rise in degrees F will be 0.0028 times the RMS ripple current squared. Using this equation and the rule of thumb for battery life vs. temperature (50% reduction for 10 C, or 18 F rise) based on the Arrhenius equation [3], a curve can be generated showing temperature rise and predicted battery life as a function of ripple current. 3

Figure 1 shows the curve generated for ripple current values of 1 through 40 amps. 5 % Life 100 % Life 4 95 Degrees F 3 2 90 85 1 T rise 80 0 75 0 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 Amps Fig. 1 Ripple Current vs. Temperature Rise and % Expected Life Remaining C&D UPS12-490MRLP Battery The curve predicts that at 17 Amps (more than 3 times the recommended C/20 ripple current) there is less than 1 F battery heating. This reduces battery life by approximately 3%. Figure 2 demonstrates that the results of lab testing for the UPS12-490MRLP battery verify the calculated values from the chart of figure 1. The internal battery heating for this battery at greater than 17 amps ripple current was 0.44 C, or approximately 0.8 F. Similar results were shown and documented [4, 5, 6] for extensive tests on additional battery samples. Shown below in figures 3 and 4 are example results for other battery models and manufacturers. These batteries have similar ratings, so similar temperature rise values would be expected. UPS12-490MRLP Battery @ 17.7 Amps ripple current 27 26.5 Temperature C 26 25.5 25 24.5 ambient case internal 24 23.5 23 1 19 37 55 73 91 109 127 145 163 181 199 217 235 253 271 289 307 325 343 361 379 397 415 Fig. 2 C&D UPS12-490MRLP Battery 1 minute sample # 4

Battery#3 @ 17 amps ripple (16 Hours) Average internal battery temperature above ambient =.44 C 26 25.5 Temperature C 25 24.5 24 23.5 23 battery side case ambient battery internal 22.5 22 1 47 93 139 185 231 277 323 369 415 461 507 553 599 645 691 737 783 829 875 921 967 Fig. 3 C&D UPS12-400MR Battery 1 minute sample # Enersys Battery @ 17 amps ripple (6 hours) Average internal temperature rise =.35 C 26.5 26 25.5 Temperature C 25 24.5 24 23.5 23 battery side case ambient battery internal 22.5 22 1 15 29 43 57 71 85 99 113 127 141 155 169 183 197 211 225 239 253 267 281 295 309 323 337 351 Fig. 4 EnerSys 12-HX505-FR Battery 1 minute sample # 5

The analysis method also applies to other VRLA battery Amp-Hour ratings with a similar minimal temperature rise expected at proportional ripple currents for the battery rating. Naturally, higher rated batteries would have higher recommended ripple current values, and since power varies with the square of current, far more potential heat generation would be expected. However, the internal impedance (thus the power dissipation at a given current) varies inversely and the physical dimensions (thus surface area and heat transfer capability) vary proportionally. These two facts tend to counter the significantly different temperature rise that would otherwise be created by higher ripple current. For a given ripple current to battery Amp-Hour rating ratio, the net result yields a slightly higher temperature rise for larger batteries and smaller temperatures rise for smaller batteries. Table 1 shows predicted temperature rises for size of batteries other than those for which detailed analysis was outlined in this report. C&D Battery Model # 20 Hr rating Predicted Temp rise @ 3 times recommended ripple UPS12-100MR 26.0 Ah 0.26 F UPS12-150MR 34.6 Ah 0.41 F UPS12-210MR 53.8 Ah 0.56 F UPS12-300MR 78.6 Ah 0.84 F UPS12-350MR 93.2 Ah 0.78 F UPS12-400MR 103 Ah 0.74 F UPS12-490MR 141 Ah 1.02 F UPS12-540MR 149 Ah 1.18 F Table 1 Predicted Temperature Rise for C&D High Rate Max Series Conclusion Analysis and subsequent battery testing demonstrates that the heating effects of battery ripple current can be predicted. Furthermore, at battery ripple current level of approximately 3 times the recommended, the heating effect is minimal, typically less than 1 F. This results in less than a 3% impact on battery life. It may be noted that a 1 degree change in battery temperature is most certainly within the temperature variation that would occur in battery cabinet ambient temperature; even in a well controlled environment. Informal site surveys have shown that it is not uncommon for battery room temperature to vary as far as 3 degrees above the recommended 77 F. Applicability of Analysis The analysis contained in this report applies to VRLA batteries, which are similar in design and construction and have internal impedance characteristics equivalent to those such as the UPS High Rate Max series manufactured by C&D Technologies or the DataSafe HX series manufactured by EnerSys. These types of batteries employ absorbent glass mat technology, are constructed in thermoplastic cases, and typically have an upper capacity range limit of approximately 600 watts/cell. 6

References 1. S. Gerner, T. Ruhlmann (Dynasty Division, C&D Technologies), Effect of AC Ripple on VRLA Battery Performance. 2. S. Gerner, G Brilmyer, D. Bornemann (Specialty Battery Division, Johnson Controls, Inc.), Thermal Management of Valve Regulated Lead-Acid Batteries. A Comparison of Gelled vs. Absorbed Electrolyte Technologies, Intellec Conference Proceedings, 1990. 3. The Arrhenius equation relates temperature to chemical reaction rates, basically stating that the rate of a chemical reaction process (for example, a lead acid battery) will double for every 10 C rise in temperature. See Battery Life and How to Improve It @ www.mpoweruk.com/life.htm 4. Ripple Current Testing on C&D UPS12-490MR/490MRLP Battery Liebert Corp (10/9/2009) 5. Ripple Current Testing on C&D UPS12-400MR Battery Liebert Corp (12/15/2009) 6. Ripple Current Testing on EnerSys 12HX505-FR Battery Liebert Corp (1/13/2010) Emerson Network Power 1050 Dearborn Drive P.O. Box 29186 Columbus, Ohio 43229 800.877.9222 (U.S. & Canada Only) 614.888.0246 (Outside U.S.) Fax: 614.841.6022 EmersonNetworkPower.com Liebert.com While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Specifications subject to change without notice. 2008 Liebert Corporation. All rights reserved throughout the world. Trademarks or registered trademarks are property of their respective owners. Liebert and the Liebert logo are registered trademarks of the Liebert Corporation. Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. 2009 Emerson Electric Co. TN- 00008 Emerson Network Power. The global leader in enabling Business-Critical Continuity. AC Power Connectivity DC Power Embedded Computing Embedded Power Monitoring Outside Plant Power Switching & Controls Precision Cooling EmersonNetworkPower. com Racks & Integrated Cabinets Services Surge Protection