1 The Effect of Regular, Skilled Preventive Maintenance on Critical Power System Reliability A White Paper from the Experts in Business-Critical Continuity TM
2 Executive Summary Emerson Network Power has long promoted the need for a comprehensive Preventive Maintenance (PM) program to maximize the reliability and performance of the Uninterruptible Power Supply (UPS) systems on which organizations depend to keep critical systems running. While most organizations intuitively understand the necessity of a good UPS PM program, the value of PM has never been adequately quantified in a manner that could help guide decisions about PM frequency or skill level of the service provider. The industry-wide lack of statistical support for PM can be attributed to an absence of data from which meaningful statistics could be compiled. To confirm the importance of PM and provide insight into the impact of frequency on reliability, Emerson Network Power analyzed data collected by its service organization, which maintains the most extensive database of service related events for Large UPS systems in the data center support services industry. The data covered 185 million operating hours for more than 5,000 three-phase UPS units. The analysis allowed the impact of both electrical failure and service related human error to be factored into the calculations. Emerson enlisted a Ph.D. level mathematician to help develop a mathematical model that takes the unit-related outages that occurred on these systems and accurately projects the impact of PM on UPS reliability. These calculations indicate that the UPS Mean Time Between Failures (MTBF) for units that received two PM service events a year is 23 times higher than a machine with no PM service events per year. At the expected levels of service error attributed to a Liebert trained and certified service engineer, UPS reliability continued to steadily increase up to 19 PM visits per year. The final conclusion of the real-world analysis and mathematical model reaffirmed the long-held industry belief that an increase in the number of PM visits substantially increases system reliability. 1
3 Introduction As organizations become increasingly dependent on data center systems, there is a need for greater reliability in the critical power system. For many organizations, the IT infrastructure has evolved into an interdependent business-critical network that includes data, applications, storage, servers and networking. A power failure at any point along the network can impact the entire operation and have serious consequences for the business. In most cases, the ability to keep critical systems running through power outages, utility spikes and other unforeseeable power issues is dependent on the reliability of the UPS system. Overall, UPS systems are designed to offer the utmost reliability and performance at an affordable price. While only a very small fraction of the Liebert UPS installed base has ever experienced a unit-related output failure, failures do occur. Factors such as application, installation design, real-world operating conditions, and maintenance practices can impact the reliability and performance of UPS systems. Virtually all systems contain life limited components that need to be replaced according to the manufacturer s specifications. The reliability of a system only lasts as long as the shortest component life in the unit. The Liebert design philosophy addresses this issue by reducing the number of parts that need to be replaced, thus decreasing the chance of a failure. One way end users can further minimize unit-related failures is to institute a comprehensive PM program that is implemented by original equipment manufacturer (OEM) trained and certified technicians. When correctly implemented, PM visits ensure maximum reliability of data center equipment by providing systematic inspections, detection and correction of incipient failures, either before they occur or before they develop into major defects that result in costly downtime. Typical PM programs include inspections, tests, measurements, adjustments, parts replacement, and housekeeping practices. While established engineering practices support the need for PM, Emerson Network Power recognized the need for an in-depth analysis that bottom-line driven organizations could use to help shape their PM policies and practices. The analysis conducted by Emerson Network Power is the first in the industry that quantifies the change in system reliability due to the level of PM activity on Liebert equipment. Liebert Services, a division of Emerson Network Power, has one of the largest installed bases of any Large UPS manufacturer and one of the most extensive databases of UPS service events and installations in the industry. Field observed Mean Time Between Failures (MTBF) is a robust measure of reliability that uses the number and types of failures that products actually experience in real applications. Mean Time Between Failures is an industry recognized measure of system behavior and serves as a reliable parameter for the mathematical model in this analysis. When correctly implemented, PM visits ensure maximum reliability of data center equipment by providing systematic inspections, detection and correction of incipient failures, either before they occur or before they develop into major defects that result in costly downtime. 2
4 Two key statistics are incorporated into MTBF, cumulative operating hours and number of unit-related failures, to calculate average reliability across all units in a given population. In general, a higher MTBF number, stated in hours, indicates a more reliable unit. For example, a UPS unit with a MTBF of 2 million hours is more reliable than a unit with a MTBF of 1 million hours. Two key statistics are incorporated into MTBF, cumulative operating hours and number of unit-related failures, to calculate average reliability across all units in a given population. MTBF = cumulative operating hours number of outages + 1 Figure 1. Calculating Mean Time Between Failure (MTBF) The cumulative operating hours metric is calculated according to the number of hours in a given month multiplied by the number of machines that were under contract with Emerson s Services group in that same month. A machine was counted under contract if the contract terms were still active on the last day of that given month. The number of outages used in the analysis is a subset of all failures experienced by systems in the population. This subset only includes unit-related failures, because there are many different causes for failures, ranging from someone pushing the Emergency Power Off button, to batteries reaching the end of discharge. Many of these causes can be attributed to user personnel error, not the reliability of the UPS system. To control for user personnel error, any failures that are not unit-related were removed from the initial analysis of MTBF. Each outage counted in the analysis consisted of a loss of the critical buss and was caused by a failure of some internal UPS mechanism. The mathematical model will include the contribution of errors committed by the service engineer, as described later in this paper. The analysis began by tabulating data covering more than 185 million cumulative operating hours and number of unit-related outages for the 5,000 unit described sample of Liebert three-phase UPS units with a service contract between October 2001 and February Once gathered, the sample was broken into groups according to the number of PM visits written into the contract for a 12-month period. When the MTBF calculations were complete for the sample of three-phase UPS units in the Liebert installed base, the data in each group were checked for validity to ensure efficacy in the sample, and only those numbers that were theoretically and statistically valid were used as a basis for the mathematical model. The observed MTBF for the no PM group was found to be unreliable. First, the no PM group consisted of units under contract for emergency service only, meaning the unit did not have a regularly scheduled maintenance agreement with Liebert Services. However, it is possible that these machines had a maintenance agreement with a third-party vendor or had sporadic maintenance on a time and materials basis from Liebert. In fact, further analysis suggests that some maintenance is occurring to a majority of the no PM group at some point in the life of the machine. Any time a maintenance event occurs it substantially increases the reliability of the unit, which inflates the MTBF for the no PM group in this analysis. Also, it is inaccurate to state that a unit will continue to function properly with no outside intervention after the life span expiration of certain life limited components, such as capacitors and fans. To adjust for these inaccuracies the mathematical model was used to more accurately project the MTBF of a unit with no human intervention. 3
5 The MTBF for the groups containing three or more PM events per year were also deemed unstable and not robust enough upon which to base any statistical inferences. The main reason for this mathematical instability is that none of these units experienced any outages during the test period. The real-world experience of no failures for any machine receiving three or more PM visits is substantial evidence for the need for PM, but for the mathematical model these numbers were too unstable. This instability stems from two major factors, first, if one machine in the sample had a failure the corresponding MTBF would automatically be cut in half, and second, the number of units that receive three or more PM events a year is substantially smaller than the one PM and two PM per year groups. If you put both of these factors together the MTBF for the units that received three or more PM events a year turn out to be a measure of cumulative operating hours for a small group of units, not an MTBF calculation. Out of the more than 185 million operating hours in the analysis, more than 90 percent were in the one or two PM groups. It was found that the MTBF figures for one and two PM visits per year were reliable. The data were then placed in a two-parameter Weibull probability distribution that projected MTBF rates based on PM frequency. The Weibull probability distribution, a widely used mathematical construct, is used as a basis for the mathematical model and allows the impact component aging to be considered in the analysis. The ability to adjust for aging and other variables allows the Weibull distribution to better represent reality than data estimates that are not substantiated. For example, Liebert Services has no information about a piece of equipment that has never had a service event, but the Weibull probability distribution can take the reliable data for the one PM and two PM groups and project more a realistic MTBF figure for the no PM group. For the mathematical model, a two-parameter Weibull probability distribution is used to model the time between unit-related outages versus the number of annual PM visits. The major inputs for this model include the real-world MTBF metrics for one and two PM visits per year along with the measure of service related error labeled PM safety. PM safety can be thought of as the probability of coming through a PM visit without incurring any human error. The PM Safety factor used, , is derived from real-world Emerson Network Power quality assurance data. PM Safety = 1 - Number of CE caused outages Number of PM visits Figure 2. Calculating the preventive maintenance safety factor PM safety can be thought of as the probability of coming through a PM visit without incurring any human error. The PM Safety factor used, , is derived from real-world Emerson Network Power quality assurance data. 4
6 When projected out farther than 6 PM visits, the MTBF begins to level off around 19 PM visits per year and then slowly declines at higher levels of maintenance. This decline after a large number of PM visits can be attributed to the fact that every service event introduces the possibility of service-related human error. Times Better Increase in MTBF When Compared to No Preventive Maintenance 0x 0 10x 2.3x 23x 37x x Number of Annual Preventive Maintence Visits Figure 3. An increase in the number of annual preventive maintenance visits increases the MTBF. 1.6x 1.4x 1.3x 67x 1.2x 82x The outcome of the model can be seen in Figure 3, which depicts the expected MTBF figures projected up to six PM events per year. The mathematical model incorporated real-world Emerson Network Power data to arrive at Figure 3. The MTBF estimate for the no PM group is substantially lower than the observed MTBF for units with emergency service only contracts with Liebert Services, but is in line with the lifespan of components that must be replaced. There is a substantial increase in MTBF from zero to six PM visits per year. When projected out farther than 6 PM visits, the MTBF begins to level off around 19 PM visits per year and then slowly declines at higher levels of maintenance. This decline after a large number of PM visits can be attributed to the fact that every service event introduces the possibility of service-related human error. The PM safety factor for Emerson Network Power trained and certified Customer Engineers (CE) is extremely high, it has been calculated to be one CE caused failure for every 5,000 PM events. The high level of quality service from Liebert engineers stems from the fact that all Liebert CEs are continuously trained to be current with new procedures, equipment, designs and changes that have been made. Also, each Liebert CE uses the OEM specified testing equipment, which accurately collects Liebert equipment data within the specified limits of the calibration procedures. Therefore, it can be concluded that the risk of human error is minimal when Liebert trained personnel access the system. It is reasonable to assume that an engineer who has not been properly trained and certified on Liebert equipment will have a higher error rate than a Liebert trained CE. Also, without the manufacturer s specified testing equipment it is reasonable to assume that data collection and settings may be inaccurate, or not within the specified limits of the calibration procedures. In an effort to take these training and quality standards into account, different PM Safety factors are compared in Figure 4. A Liebert trained and certified CE with a PM Safety Factor of will have gains in unit reliability up to 19 PM service events a year, after which there are diminishing returns. 5
7 Number of PMs at Which MTBF Peaks According to PM Safety Factor The research supports Emerson s recommendation of at least two PM visits per year, but also makes the case for more PM visits for data centers where downtime is unacceptable. PM Safety Factor and Error Rate or 2% or 1/ or 1% or 1/ or 0.5% or 1/ or 0.002% or 1/ Number of Annual Preventive Maintence Visits Figure 4. A Liebert trained and certified CE with a PM Safety Factor of could provide gains in unit reliability up to 19 PM service events a year, after which there are diminishing returns. The reliability of the UPS unit theoretically increases up to 19 PM events per year but realistically Emerson would not recommend this high level of maintenance activity. Instead, two or more maintenance events per year will substantially increase unit reliability. For a non-liebert trained CE with a higher error rate, of one CE caused failure for every 100 PM events, the unit reliability will only increases to one PM visit a year before realizing diminishing returns. This shows that an increase in PM events will increase reliability only if the engineer completing the work has a very low error rate. Figure 4 illustrates the solid relationship between proper training and MTBF. Conclusion This analysis is a preliminary look at the connection between preventive maintenance and UPS system reliability for Liebert equipment. This analysis does not lend itself to all-encompassing conclusions; instead the interpretation is straightforward and specific: the number of preventive maintenance visits and the service engineer s level of training have a substantial impact on system reliability. The research supports Emerson s recommendation of at least two PM visits per year, but also makes the case for more PM visits for data centers where downtime is unacceptable. Further work will be completed using this analysis as a basis to provide data center managers with tools such as the total cost of ownership and return on investment calculations. Depending on the cost of downtime for a particular application, a high return on investment can be realized in many cases by increasing PM frequency. 6
8 Emerson Network Power 1050 Dearborn Drive P.O. Box Columbus, Ohio (U.S. & Canada Only) (Outside U.S.) Fax: EmersonNetworkPower.com Liebert.com While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Specifications subject to change without notice Liebert Corporation. All rights reserved throughout the world. Trademarks or registered trademarks are property of their respective owners. Liebert and the Liebert logo are registered trademarks of the Liebert Corporation. Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co Emerson Electric Co. WP SL (11/07) Emerson Network Power. The global leader in enabling Business-Critical Continuity. AC Power Embedded Computing Outside Plant Connectivity Embedded Power Power Switching & Controls DC Power Monitoring Precision Cooling EmersonNetworkPower.com Racks & Integrated Cabinets Services Surge Protection
DCIM Readiness on the Rise as Significant Data Center Capacity Remains Unused. A Research Report from the Experts in Business-Critical Continuity TM
DCIM Readiness on the Rise as Significant Data Center Capacity Remains Unused A Research Report from the Experts in Business-Critical Continuity TM Introduction Data center management is in a stage of
Directed Circuits Meet Today s Security Challenges in Enterprise Remote Monitoring. A White Paper from the Experts in Business-Critical Continuity TM
Directed Circuits Meet Today s Security Challenges in Enterprise Remote Monitoring A White Paper from the Experts in Business-Critical Continuity TM Executive Summary With continued efforts to reduce overhead,
How To Improve Energy Efficiency In Data Center Management
A White Paper from the Experts in Business-Critical Continuity TM Data Center Users Group Special Report Energy efficiency and capacity concerns increase Fall 2012 Survey Results Executive Summary The
Protecting Our Information, Protecting Our Resources
Solutions For Business-Critical Continuity Protecting Our Information, Protecting Our Resources Energy Efficient Power And Cooling For IT And Telecommunications Network Infrastructures The Challenge You
Power Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM
Power Management Strategies for High-Density IT Facilities and Systems A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Increases in data center density and diversity
Protecting The Critical IT Infrastructure of the United States
Solutions for Business-Critical Continuity Protecting The Critical IT Infrastructure of the United States Emerson Network Power Products And Support Services We Help Make Sure Systems Are Available IT
Enterprise Remote Monitoring
Enterprise Remote Monitoring Alarm Management, Predictive Maintenance, Advanced Network Security Services For Business-Critical Continuity Can You Really Afford Not To Know? Loss of productivity and the
Technical Note: Comparing R407C and R410A as Alternatives for R22. A Technical Note from the Experts in Business-Critical Continuity
Technical Note: Comparing R407C and R410A as Alternatives for R22 A Technical Note from the Experts in Business-Critical Continuity Purpose The purpose of this document is to provide a brief overview of
Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
Data Center Rack Systems Key to Business-Critical Continuity. A White Paper from the Experts in Business-Critical Continuity TM
Data Center Rack Systems Key to Business-Critical Continuity A White Paper from the Experts in Business-Critical Continuity TM Executive Summary At one time, data center rack enclosures and related equipment
How To Run A Data Center Efficiently
A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly
LIFECYCLE COSTING FOR DATA CENTERS: DETERMINING THE TRUE COSTS OF DATA CENTER COOLING
LIFECYCLE COSTING FOR DATA CENTERS: DETERMINING THE TRUE COSTS OF DATA CENTER COOLING Summary Experts estimate that the average design life of a data center is 10-15 years. During that time, equipment
IT White Paper. N + 1 Become Too Many + 1?
IT White Paper Balancing Scalability and Reliability in the Critical Power system: When Does N + 1 Become Too Many + 1? Summary Uninterruptible Power Supply (UPS) protection can be delivered through a
How To Save Energy On A Power Supply
Technical Note: Using EC Plug Fans to Improve Energy Efficiency of Chilled Water Cooling Systems in Large Data Centers A Technical Note from the Experts in Business-Critical Continuity Introduction A U.S.
Data Center Infrastructure Management Managing the Physical Infrastructure for Greater Efficiency
Data Center Infrastructure Management Managing the Physical Infrastructure for Greater Efficiency Infrastructure Management & Monitoring for Business-Critical Continuity TM DATA CENTER INFRASTRUCTURE MANAGEMENT
Liebert : The Right Cooling For IT Environments. Precision Cooling For Business-Critical Continuity
Liebert : The Right Cooling For IT Environments Precision Cooling For Business-Critical Continuity New Challenges To IT System Uptime Many IT professionals are finding that dedicated precision cooling
Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity
Proper Application of 415V Systems in North American Data Centers A White Paper from the Experts in Business-Critical Continuity Introduction Increasing pressure to reduce operating expenses and be more
SmartDesign Intelligent, Integrated Infrastructure For The Data Center. Solutions For Business-Critical Continuity
SmartDesign Intelligent, Integrated Infrastructure For The Data Center Solutions For Business-Critical Continuity Prepare Your Data Center For What s Next Efficiency. Availability. Capacity. Control. One
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,
Effects of AC Ripple Current on VRLA Battery Life. A Technical Note from the Experts in Business-Critical Continuity
Effects of AC Ripple Current on VRLA Battery Life A Technical Note from the Experts in Business-Critical Continuity Introduction Given the importance of battery life to UPS system users and the fact that
Changing the way companies run their data centers
Infrastructure Management & Monitoring for Business-Critical Continuity TM Changing the way companies run their data centers The Aperture Suite OPTIMIZE PERFORMANCE OF YOUR DATA CENTER WITHOUT COMPROMISING
Capacitors Age and Capacitors Have an End of Life. A White Paper from the Experts in Business-Critical Continuity TM
Capacitors Age and Capacitors Have an End of Life A White Paper from the Experts in Business-Critical Continuity TM Executive Summary This white paper discusses large DC aluminum electrolytic and AC polymeric
The Trellis Dynamic Infrastructure Optimization Platform
Infrastructure Management & Monitoring for Business-Critical Continuity TM The Trellis Dynamic Infrastructure Optimization Platform Delivering Confidence through Connection TM Is Your Data Center Operating
Reliability of Air Moving Fans, and Their Impact on System Reliability. A White Paper from the Experts in Business-Critical Continuity TM
Reliability of Air Moving Fans, and Their Impact on System Reliability A White Paper from the Experts in Business-Critical Continuity TM Summary Air-moving fans are used to remove waste heat on all UPS
Liebert CW 26-181kW Chilled Water Cooled Precision Air Conditioning For Data Centers
Liebert CW 26-181kW Chilled Water Cooled Precision Air Conditioning For Data Centers Precision Cooling For Business-Critical Continuity A Chilled Water Precision System That Handles The Most Demanding
Secure Remote Monitoring of the Critical System Infrastructure. An Application Note from the Experts in Business-Critical Continuity
Secure Remote Monitoring of the Critical System Infrastructure An Application Note from the Experts in Business-Critical Continuity TABLE OF CONTENTS Introduction................................................2
Data Center Users Group Special Report Inside the Data Center 2008 and Beyond. A White Paper from the Experts in Business-Critical Continuity TM
Data Center Users Group Special Report Inside the Data Center 2008 and Beyond A White Paper from the Experts in Business-Critical Continuity TM Executive Summary If there were any question about the pace
Advantages and Efficient Use of Programmable Sockets. By Miguel Rascon AC Power Senior Product Manager
Advantages and Efficient Use of Sockets By Miguel Rascon AC Power Senior Product Manager Abstract Emerson Network Power s most recent products feature programmable s embedded in the UPS to provide the
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection AC Power for Business-Critical Continuity Liebert GXT MT+ CX UPS, 1000VA -3000VA Intelligent, Reliable UPS Protection Liebert
DISCONTINUED PRODUCT. Infrastructure Management & Monitoring For Business-Critical Continuity. Liebert icom-do. User Manual
Infrastructure Management & Monitoring For Business-Critical Continuity Liebert icom-do User Manual TABLE OF CONTENTS 1.0 INTRODUCTION............................... 1 2.0 INSTALLATION...............................
Data Center Infrastructure Management Managing the Physical Infrastructure for Greater Efficiency
Data Center Infrastructure Management Managing the Physical Infrastructure for Greater Efficiency Infrastructure Management & Monitoring for Business-Critical Continuity TM DATA CENTER INFRASTRUCTURE MANAGEMENT
RagingWire Enterprise Solutions
Background Enterprise Solutions was founded in May 2000 to be an enterprise-class Managed Services Provider (emsp) that could provide and support colocated data center services for Fortune 1000 customers.
Liebert IntelliSlot Web Cards
Monitoring For Business-Critical Continuity Liebert IntelliSlot Web Cards Firmware Upgrade Manual Liebert IntelliSlot Web Card, Liebert IntelliSlot Web Card-LB, Liebert IntelliSlot Web Card-LBDS, Liebert
Applying Data Center Infrastructure Management in Collocation Data Centers
Applying Data Center Infrastructure Management in Collocation Data Centers Infrastructure Management & Monitoring for Business-Critical Continuity TM Applying Data Center Infrastructure Management (DCIM)
IT White Paper IP TELEPHONY AND RELIABILITY: PROTECTING MISSION-CRITICAL PHONE SYSTEMS FROM POWER THREATS
IT White Paper IP TELEPHONY AND RELIABILITY: PROTECTING MISSION-CRITICAL PHONE SYSTEMS FROM POWER THREATS Executive Summary IT managers who are used to implementing power protection for IT network or data
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Downtime Is Not An Option The industrial uninterruptible power supply (UPS) is the foundation of your
Liebert. Liebert Universal Monitor Monitoring, Control And Remote Communications For Critical Applications
Site Monitoring and Services for Business-Critical Continuity Liebert Universal Monitor Monitoring, Control And Remote Communications For Critical Applications Liebert MONITORING AND ALARM CAPABILITIES
Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity
Liebert Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Precision Cooling For Business-Critical Continuity The Intelligent Data Center Cooling Solution: Liebert Trust the industry
The Avocent Data Center Planner Real-World Insight for Smarter Data Center Management
Infrastructure Management & Monitoring for Business-Critical Continuity TM The Avocent Data Center Planner Real-World Insight for Smarter Data Center Management EXECUTION AVAILABILITY EFFICIENCY What s
Microsoft Technology Center: Philadelphia
A Customer Success from the Experts in Business-Critical Continuity TM. Background Microsoft Technology Center: Philadelphia Microsoft Technology Centers are collaborative, state-of-the-art facilities
Virginia Tech. Background. Case Summary. Results
Background Virginia Tech When Virginia Tech initiated plans to build a supercomputer by clustering hundreds of desktop computers, it had ambitious goals for the performance of the new system and a very
Power Distribution Considerations for Data Center Racks
Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical
Ten Steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring
Ten Steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring A White Paper from the Experts in Business-Critical Continuity Summary The first decade of the 21st century
Revolutionizing Data Center Infrastructure Management
Infrastructure Management & Monitoring for Business-Critical Continuity TM Revolutionizing Data Center Infrastructure Management The Trellis Platform A Real-Time Solution to Continuous Performance Improvement
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers A market position paper from the experts in Business-Critical Continuity TM Executive Summary Electrocutions are the fourth
The Four Trends Driving the Future of Data Center Infrastructure Design and Management
A White Paper from the Experts in Business-Critical Continuity TM The Four Trends Driving the Future of Data Center Infrastructure Design and Management Introduction Throughout the first decade of the
Unified Infrastructure Monitoring, Access and Control
A White Paper from the Experts in Business-Critical Continuity Unified Infrastructure Monitoring, Access and Control Streamline Infrastructure Management with a Single, Multi-Purpose Appliance the Avocent
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
Move beyond the expected.
Infrastructure Management & Monitoring for Business-Critical Continuity TM Move beyond the expected. The Avocent Data Center Planner Taking data center operations to the next level Execution Availability
Knürr CoolAdd The universal retrofit solution against overheating in server racks. Rack & Enclosure Systems
Knürr CoolAdd The universal retrofit solution against overheating in server racks Rack & Enclosure Systems Knürr CoolAdd When cold air is no longer enough! Data centers are subject to constant changes:
Considerations for a Highly Available Intelligent Rack Power Distribution Unit. A White Paper on Availability
Considerations for a Highly Available Intelligent Rack Power Distribution Unit A White Paper on Availability Introduction Data centers are currently undergoing a period of great change. Data center managers
POWER. Your Partners in Availability POWER
Your Partners in Availability The Service Arm for All Liebert Products We have the industry-leading technical expertise, top onsite response times and the most sophisticated parts logistics in the industry.
CUSTOMER EXPERIENCE CENTER
v CUSTOMER EXPERIENCE CENTER ABOUT THE CUSTOMER EXPERIENCE CENTER MAKE YOUR DATA CENTER AS DYNAMIC AS YOUR BUSINESS Emerson Network Power continuously strives to provide the best solutions by working collaboratively
The High Performance Floormount Indoor Package Cooling Solution. Precision Cooling for Business-Critical Continuity
Liebert HPF The High Performance Floormount Indoor Package Cooling Solution Precision Cooling for Business-Critical Continuity We re Emerson Network Power, backed by Emerson, a global company that brings
The Trellis Dynamic Infrastructure Optimization Platform for Data Center Infrastructure Management (DCIM)
The Trellis Dynamic Infrastructure Optimization Platform for Data Center Infrastructure Management (DCIM) TM IS YOUR DATA CENTER OPERATING AT PEAK PERFORMANCE? MITIGATE RISK. OPTIMIZE EFFICIENCY. SUPPORT
Liebert SiteScan Web. Quick-Start Guide. Monitoring For Business-Critical Continuity
Liebert SiteScan Web Quick-Start Guide Monitoring For Business-Critical Continuity Getting Started This guide provides information necessary for installing the Liebert SiteScan Web software. System Requirements
How To Make A Data Center More Efficient
IT Solutions for Business-Critical Continuity Emerson Network Power Data Center Infrastructure Many Needs. One Source. Emerson Network Power, a division of Emerson Electric Co., is a global company that
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER SUMMARY A proper balance of temperature and humidity control is essential for efficient data center operation, and integral
DataCenter.BZ. Background. Case Summary. & dark fiber solutions
A Customer Success from the Experts in Business-Critical Continuity TM. DataCenter.BZ & dark fiber solutions Background Headquartered in Columbus, Ohio, DataCenter.BZ provides enterprisegrade data center
Meeting the FCC Backup Power Mandate From Site Audit to Total Site Solutions. DC Power, Outside Plant & Services for Business-Critical Continuity
Meeting the FCC Backup Power Mandate From Site Audit to Total Site Solutions DC Power, Outside Plant & Services for Business-Critical Continuity Integrated Backup Power Solutions to increase your network
The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity
The Quest for Energy Efficiency A White Paper from the experts in Business-Critical Continuity Abstract One of the most widely discussed issues throughout the world today is the rapidly increasing price
RCM Success Starts with CMMS
RCM Success Starts with CMMS Ruth Olszewski, President CMMS data group, inc. 5701 N. Sheridan Road, Suite 17Q Chicago, Illinois 60660 Phone: (773) 275-8846 Fax: (801) 991-6567 [email protected]
The Trellis Dynamic Infrastructure Optimization Platform for Data Center Infrastructure Management (DCIM)
The Trellis Dynamic Infrastructure Optimization Platform for Data Center Infrastructure Management (DCIM) TM Emerson Network Power s R&D investment, sales channels and partnerships within the DCIM ecosystem
Secure, Remote Access for IT Infrastructure Management
Infrastructure Management & Monitoring for Business-Critical Continuity TM Secure, Remote Access for IT Infrastructure Management ACS Advanced Console Server Secure, Remote Access for IT Infrastructure
Avoiding AC Capacitor Failures in Large UPS Systems
Avoiding AC Capacitor Failures in Large UPS Systems White Paper #60 Revision 0 Executive Summary Most AC power capacitor failures experienced in large UPS systems are avoidable. Capacitor failures can
Reference Guide: SmartDesign Approach: Common Data Center Challenges:
Smart Solutions Reference Guide Solutions For Business-Critical Continuity 1100kW Tier 3 With High Density Design Intelligent, Integrated Infrastructure for the Data Center Reference Guide: 1100kW Tier
Liebert APM from 30-150 kw. The Compact Row-Based UPS With FlexPower Technology TM
Liebert APM from 30-150 kw The Compact Row-Based UPS With FlexPower Technology TM Emerson Network Power, a division of Emerson, is a global company that combines technology with design to supply innovative
Miracel 19 rack platform for data center, telecommunication and network technology. Rack & Integrated Enclosure Systems
Miracel 19 rack platform for data center, telecommunication and network technology Rack & Integrated Enclosure Systems The Miracel innovation rack multi-talented, distinguished, integrative The Miracel
Effective Model Risk Management for Financial Institutions: The Six Critical Components
January 2013 Effective Model Risk Management for Financial Institutions: The Six Critical Components A White Paper by Brookton N. Behm, John A. Epperson, and Arjun Kalra Audit Tax Advisory Risk Performance
Power and Cooling Best Practices for IP Communications. A White Paper from the Experts in Business-Critical Continuity
Power and Cooling Best Practices for IP Communications A White Paper from the Experts in Business-Critical Continuity Executive Summary IP telephony and Power over Ethernet (PoE) are driving the requirement
Statement Of Work. Data Center Thermography Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary
Statement Of Work Professional Services Data Center Thermography Assessment Data Center Thermography Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits
DISTRIBUTED REDUNDANCY:
DISTRIBUTED REDUNDANCY: MAXIMUM AVAILABILITY AT MINIMAL COST A White Paper by: Liebert Corporation As the need for greater system availability intensifies across virtually every industry from global banking
Liebert NXL Power-Tie Controls
AC Power For Business-Critical Continuity Liebert NXL Power-Tie Controls Operation and Maintenance Manual CONTACTING EMERSON NETWORK POWER FOR SUPPORT Contact Emerson Network Power Liebert Services for
Energy Efficient Cooling Solutions for Data Centers
A White Paper from the Experts in Business-Critical Continuity TM Energy Efficient Cooling Solutions for Data Centers Introducing an Emerson Network Power tool for evaluating cooling system total cost
Knürr DCL Modular Rack Cooling from 6 kw to 60 kw
Knürr DCL Modular Rack Cooling from 6 kw to 60 kw Emerson Network Power Business-Critical Continuity so your success continues! Core competencies AC Power Connectivity DC Power Embedded Computing Embedded
Liebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit
Liebert EFC from 100 to 350 kw The Highly Efficient Indirect Evaporative Freecooling Unit Liebert EFC, the Highly Efficient Indirect Evaporative Freecooling Solution Emerson Network Power delivers innovative
Modular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity
Modular architecture for high power UPS systems A White Paper from the experts in Business-Critical Continuity Abstract Today, more than ever before, energy efficiency and cost-savings are among the top
Applying Proper Cable Management In IT Racks A Guide For Planning, Deployment And Growth
Applying Proper Cable Management In IT Racks A Guide For Planning, Deployment And Growth Integrated Cabinet Solutions For Business-Critical Continuity Why Proper Cable Management Is So Important Your rack
DCF Optimized Rack System
Integrated Cabinet Solutions For Business-Critical Continuity DCF Optimized Rack System User Manual IMPORTANT SAFETY GUIDELINES SAVE THESE INSTRUCTIONS This manual contains important instructions that
Green HPC - Dynamic Power Management in HPC
Gr eenhpc Dynami cpower Management i nhpc AT ECHNOL OGYWHI T EP APER Green HPC Dynamic Power Management in HPC 2 Green HPC - Dynamic Power Management in HPC Introduction... 3 Green Strategies... 4 Implementation...
Future-Proof the Banking and Finance Data Center
Future-Proof the Banking and Finance Data Center Reinier Dungca Rey Perea Marketing Manager, Southeast Asia and North Asia Manager, Local Technical Support Emerson Network Power Emerson Network Power Philippines
IT@Intel. Measuring the Return on IT Security Investments. White Paper Intel Information Technology Computer Manufacturing Information Security
White Paper Intel Information Technology Computer Manufacturing Information Security Measuring the Return on IT Security Investments Intel IT developed a model for measuring return on security investment
NetSure DC Power Solutions with esure High-Efficiency Technology. DC Power for Business-Critical Continuity TM
NetSure DC Power Solutions with esure High-Efficiency Technology DC Power for Business-Critical Continuity TM NetSure solutions with esure high-efficiency technology Our Efficiency Without Compromise promise