V43/V243 Series Pressure-Actuated Water-Regulating Valves

Similar documents
V46 Pressure-Actuated Water-Regulating Valve

V47 Series Temperature Actuated Modulating Water Valves

PRESSURE REDUCING CONTROL VALVE

P70, P72, and P170 Series Controls for Dual Pressure Applications

Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M (Angle) Schematic. Standard Components

MP8000 Series Pneumatic Valve Actuators

A99B Series Temperature Sensors

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

VG2000 Series Cast Iron Flanged Globe Valves

Fisher 1052 Size 20 Diaphragm Rotary Actuator with F and G Mounting Adaptation

TYPE E Main Valve Sizes 3 /8 through 12

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW

Powers Controls TH 192 S Single Temperature Room Thermostat

Installation, Maintenance, & Repair Series 4000B/LF4000B

STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL Purpose:

BERMAD Waterworks. Pressure Relief/Sustaining Valve. 700 Series. Model 730. Features and Benefits. Major Additional Features

P66 Series Electronic Fan Speed Controls

Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series

Product Manual. CVS Type 67AFR Filter Regulator. Introduction. Installation. Description

OPERATING and MAINTENANCE MANUAL SERIES 2700A CONTROL VALVE CONTENTS. INTRODUCTION...1 Scope...1 Description...1 Valve Identification...

CST29A Adapter Block for Carlyle Compressors

1805 Series Relief Valves

3", 4", 6" & 8" Model H Series Alarm Check Valve Installation and Maintenance Guide

Dual Pressure Controls for Refrigeration, Air-conditioning and Heatpump Applications

Powers Controls TH 192 HC Heating/Cooling Room Thermostat

Fleck Service Manual INSTALLATION AND START-UP PROCEDURE TABLE OF CONTENTS JOB SPECIFICATION SHEET

Installation Instructions S

! WARNING. Before using product, read and understand instructions.

TECHNICAL INSTRUCTIONS REPAIR KITS Hydroguard Series 420 Thermostatic Valve All Models (1 9)

POWERS Controls No. 4 Pneumatic Damper Actuator

TECHNICAL DATA. Dry 122a. November 12, 2013

Float and Thermostatic Traps Series H, C and X

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

Powers Controls Free Energy Band TH 193 HC Heating/Cooling Room Thermostat

Installation Instructions

Overview PARTS LIST. B. Lever mounting base C. Flush handle assembly D. Grey/Blue float stop E. Grey float (Full Flush) F. Flush valve washer

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)

Stainless Steel Single and Dual Circulation Kits

DiscPlus DX195 and DX225 Air Disc Brakes

DeZURIK 3-20" BAW AWWA BUTTERFLY VALVES WITH TRANSFER MOLDED SEAT

2-Port Self-acting Temperature Control Valve Selection for Heating and Cooling Applications

Non-Code Liquid Relief, ASME Section VIII, Air/Gas and Steam, National Board Certified, Safety and Relief Valves

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

758 Heavy-duty Ratchet Guy Wire Cutter

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description

Baumann Flexsleev Sanitary Control Valve

DTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR. Installation and Operation Manual

DESIGN STANDARDS SECTION

APCO SLOW CLOSING AIR/VACUUM VALVES

INSTALLATION, OPERATING, AND MAINTENANCE INSTRUCTIONS PARTS LIST

AIR LINE VALVES AND GAUGES

REGULATORS D& HD Series

Flat Bottom Long Ram Hydraulic Jack

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A

REPAIR AND MAINTENANCE MANUAL

Ve-Lock manufactures Needle Valves from Solid bar stock Materials & all parts details are as below:

G670 Intermittent Pilot Ignition Controls

THERMOSTATIC MIXING VALVE TRIM K-T9493, K-T9494

Pressure Locking & Thermal Binding In Wedge Gate & Parallel Slide Gate Valves

WATER PRESSURE REDUCING VALVES

IF IT FLOWS THE BOWIE PUMP CAN PUMP IT

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)

BERMAD Waterworks. Quick Active Check Valve. 700 Series. Model 740Q. Features and Benefits. Major Additional Features

Type 92S Pilot-Operated Steam Regulator

Types 66R and 66RR Low-Pressure Relief Valves

Introduction. Angle/Flared/Sequence/Changeover Service Valves. Valves D

FLASH TANK ECONOMIZER PRODUCT GUIDE

USE &CARE GUIDE. Remote Faucet Pump System. See Important Safeguards on page 2

OPERATION AND MAINTENANCE MANUAL 5-1/4 B-84-B-5 FIRE HYDRANT

MAINTENANCE MANUAL INDEX DOUBLE CHECK ASSEMBLIES MODELS 850 & 850U 1/2" - 2"

TECHNICAL INSTRUCTIONS #11 REGULATOR 3-Way Water Mix (Type WM)

These features have made Lo Torc valves the choice of high pressure plug value users, worldwide:

DPT-2015 Differential Pressure Transmitter for VAV Box Applications

Your safety and the safety of others are very important.

MBA-MM-1040/10/13/1665 MULTI MEDIA FILTERS

ball valves Flomite 71 Series 2-way Integral Panel Mount Ball Valves

Application Feature Valve Nominal Liquid Capacity R-22 (in tons)*

American- Darling 5¼" B-84-B-5.

Tri-Homo Style Operation and Maintenance Instructions

Flow controller with integrated control valve (PN 16, 25, 40*) AFQM, AFQM 6 - return and flow mounting

Compressor Service & Maintenance Manual

FUEL SYSTEMS OUR PARTS PUT YOU IN THE PASSING LANE. Protect your fuel system. velvac.com

POWERS CONTROL RC 195 Single Input Receiver-Controller

FJ2. 2 Ton Trolley Floor Jack Assembly & Operating Instructions

HENRY TECHNOLOGIES - OIL LEVEL REGULATORS (CONVENTIONAL)

Type 119 Control Valve

Hose Clamps & Fittings

BOWIE PUMPS OPERATION - MAINTENANCE

167D Series Switching Valves

Flygt Ball Check Valves

BULLETIN OCTOBER DeZURIK ROTARY DIAPHRAGM ACTUATORS

Mini Tank water heater Electric undersink Water heaters GL GL 4 - GL 6+

Fisher 249 Caged Displacer Sensors

Baumann Little Scotty Bronze Control Valve

Front axle components, overview

Toroidal Conductivity Sensor

REGULATORS 175/153 Series

ABV20 Air Actuated Boiler Blowdown Valve Installation and Maintenance Instructions

Transcription:

V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin Code No. LIT-125683 Part No. 24-7664-699, Rev. C Issued April 7, 215 The V43/V243 Pressure-Actuated Water-Regulating Valves are designed to regulate water flow through the condenser of large refrigerated cooling systems. These pilot-operated valves open on an increase in refrigerant head pressure and provide modulating operation. The V43/V243 water-regulating valves are available for commercial and maritime applications. V43 valves are available for non-corrosive low- and medium-pressure refrigerants such as R-134A, R-44A, R-52, and R-57. Specially designed V43 valves are also available for ammonia service (R-717). V243 valves are available for non-corrosive high-pressure refrigerants such as R41A. Commercial V43/V243 valves are constructed with a cast iron body, brass internal parts, and bronze seat material. To resist the corrosive action of sea water, the V43/V243 maritime and navy models are constructed with a red brass body, bronze and monel interior parts, and monel seat material. Refer to the QuickLIT website for the most up-to-date version of this document. Figure 1: V43 Pressure-Actuated Valve Table 1: Features and Benefits Features Built-in Pilot Valve Easy Adjustment Drain Plug Mesh Monel Screen Benefits Allows more precise throttling. Allows service and adjustment without breaking line connections. Allows water to be drained during shutdown to reduce the possibility of freeze-up. Protects pilot valve from items such as dirt and scale and is easily removed for cleaning and servicing without breaking any line connections. V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin 1

Application IMPORTANT: All V43/V243 water-regulating valves are designed for use only as operating devices. Where valve failure can result in personal injury and loss of property, it is the responsibility of the installer to add and maintain devices (pressure relief or safety shutoff) or systems (alarm or supervisory) that protect against or warn of device failure. Note: The V43 and V243 Series Head Pressure Regulating Valves are available for cooling applications only (direct acting). Operation The V43/243 valves are refrigerant actuated units, requiring only system refrigerant head pressure to operate (no electrical power is required). Only the inlet and outlet water lines and refrigerant head pressure connections need to be made for the valve to function. A built-in pilot valve, driven by refrigerant head pressure, operates the main valve using water and spring pressures as the opening and closing forces. The main valve seat disc assembly is suspended on a heavy duty rubber diaphragm, eliminating any close-fitting or sliding parts. This reduces friction within the valve, allowing more reliable control. Also, the chance of the valve stem sticking in dirty water conditions is reduced. Determining the Required Valve Size Every system is unique and requires specific engineering data to properly size and design. Typically, a valve is replaced with another valve of the same size. IMPORTANT: An undersized valve does not deliver the required amount of water flow under full load conditions, and an oversized valve tends to hammer under low load conditions. To select the correct valve size, determine the following variables: Maximum Water Flow Required Available Water Pressure Drop (Differential) across the Valve Use these variables to locate a point on one of the flow capacity charts (Figure 5 through Figure 12) that slightly exceeds the maximum water flow required. The flow capacity chart containing this point represents the proper valve size. Maximum Water Flow Required Use the information provided by the manufacturer of the condensing unit to determine the maximum water flow required. If this information is not available, calculate the maximum water flow required by using the following formula: Maximum Water Tons of Refrigeration x 3 = Flow Required (GPM) Outlet Temperature - Inlet Temperature Example: If a 1-ton capacity system has an inlet water temperature of 85 F and an outlet water temperature of 95 F, the maximum water flow required is: Maximum Water Flow Required Maximum Water Flow Required 1 x 3 95-85 Available Water Pressure Drop (Differential) across the Valve The available water pressure drop (differential) across the valve is the supply pressure to the valve minus all downstream pressures. This pressure drop is the force available to push water through the valve. Water supply pressure is the water pressure supplied to the inlet side of the valve from a cooling tower, a city water main, or other source. P Loss 2 P 2 Opening Point - the Refrigerant Head Pressure Rise Above the Opening Point The forces that operate the valve are refrigerant head pressure, water pressure, and spring pressure. These forces oppose each other. = Cooling Tower = 3 GPM Pump Figure 2: Pressure Drop across the Valve Pressure Drop Across the Valve P = P - COND 1 P 2 Condenser P P 1 V43/V243 P Loss 1 P P Loss 1 Loss 2 P IN = + +... LOSS P DROP = P - ( P + P ) IN COND LOSS All Downstream Pressure Drops (Across = Supply Pressure - Condensor Piping, Pipe Fittings, and Valves) FIG:2wy_prss_drp 2 V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin

When the head pressure rises, and the refrigerant pressure overcomes the spring force (pilot valve), the valve begins to open (the disk lifts off of the seat). This point is called the opening point. The opening point is adjusted by increasing or decreasing the spring force by using the adjustment stem. If the head pressure continues to rise, the refrigerant pressure further opens the valve until the valve is fully open. The range from the point where the valve lifts off the seat (the opening point) to the point where the valve is fully open is called the throttling range. The throttling range is fixed and cannot be adjusted. The throttling range is approximately 4 psig for the low-pressure V43 Series Valves, approximately 5 psi for the medium-pressure V43 Series Valves, and approximately 6 psi for the high pressure V243 Series Valves. Head Pressure Rise Above the Opening Point When the head pressure rises, the force of the refrigerant head pressure overcomes the spring force (plus any hysteresis) and pushes the disc off the seat, allowing water to start flowing through the valve. Anything above that point is head pressure rise above the opening point. Typically, the opening point is approximately 7 psi above the closing point. Refrigerant Head Pressure Rise Above Opening Point = Refrigerant Head Pressure greater than Opening Point Refrigerant Head Pressure at Opening Point Proper Valve Size A properly sized valve meets the requirements of the maximum water flow required yet functions at an acceptable level when minimum flow is required (does not water hammer, cut, or wire draw the seats and seating discs). See Figure 3 and Figure 4 to select the correct valve size for your application. Use the following steps to help determine the appropriate valve size for your application: 1. Locate the point where the valve is fully open on the Valve Opening Point (y-axis). 2. Draw a horizontal line from this point to where the line intersects with the Water Pressure Available WPA curve. This is Point A. - 3. Draw a vertical line from point A to where it intersects with Maximum Water Flow Available line (x-axis). This is Point B. Point B is the maximum amount of water that the valve can flow, when fully open, under the stated conditions. See Figure 3. 4. Locate the Maximum Water Flow Required for your application (x-axis). This is Point C. 5. Draw a vertical line from Point C to where the line intersects with the WPA curve. This Point D. 6. Draw a horizontal line from Point D to the left where it intersects with the Refrigerant Head Pressure Rise Above Opening Point. This is where the selected value meets the maximum flow requirement of the application. CAPACITY CHART REPRESENTING THE PROPER VALVE SIZE Point D Point C WPA Curve Maximum Water Flow Required Value Determined in Step 1 Point A Point B Figure 3: Capacity Chart Difference ensures that the valve meets the maximum flow rate required. Use the flow charts to select the valve that is most appropriate for your application. Example In this example, the required flow for an R-44A system is 3 GPM. The cooling tower pump discharge pressure is 3 psig, and the condenser manufacturer's table gives a pressure drop through the condenser at 8 psid. The pressure drop through the installed piping, fittings, and valves is approximately 12 psi. Maximum Water Flow Required = 3 GPM Water Pressure Available= 3 - (12 + 8) Water Pressure Available= 1 psid You need to select the proper valve size. The proper size valve is indicated by the flow chart that slightly exceeds the maximum required flow when the valve is wide open. FIG:capacity chart V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin 3

As indicated in Figure 4, the correct valve for this application is a 3-inch medium-pressure (16/26 psi), non-corrosive, commercially constructed V43 Series Valve. The maximum water flow that a 3-inch valve can deliver (3 GPM) under the stated condition is slightly greater than the maximum water flow required (3 GPM). Point Where Valve is Wide Open and Intersects with the WPA Curve Maximum Flow the Valve Provides Under the Given Conditions (Valve Wide Open with a 1 psid) Maximum Water Flow Required for the Application Head Pressure Rise Above Opening Point Where Maximum Flow Required for the Application Occurs = 5 psig = Appr. 33 GPM = 3 GPM = 36 psig Point A Point B Point C Point D Note: The maximum flow required for the application is to the left of the dotted vertical line between Point A and Point B (3 GPM when the valve is approximately 72% open). CAPACITY CHART FOR 3 in. VALVE Low Pressure 5 4 3 2 1 4 3 2 1 Medium Pressure 1 2 3 5 Point A Point D Point C Point B 1 2 3 4 5 6 7 8 9 FIG:Valve Size Figure 4: Correct Valve Size for Application Select the valve type from Table 5 through Table 7. 4 V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin

V43 Capacity Flow Charts CAPACITY CHART FOR 2 in. VALVE Low Pressure 5 4 3 2 1 4 3 2 1 Medium Pressure 1 2 3 5 5 1 15 2 25 3 35 4 45 Figure 5: 2 in. V43 Capacity Flow Chart CAPACITY CHART FOR 2-1/2 in. VALVE Low Pressure 5 4 3 2 1 4 3 2 1 Medium Pressure 1 2 3 5 5 1 15 2 25 3 35 4 45 Figure 6: 2-1/2 in. V43 Capacity Flow Chart CAPACITY CHART FOR 3 in. VALVE Low Pressure 5 4 3 2 1 4 3 2 1 Medium Pressure 1 2 3 5 1 2 3 4 5 6 7 8 9 Figure 7: 3 in. V43 Capacity Flow Chart CAPACITY CHART FOR 4 in. VALVE Low Pressure 5 4 3 2 1 4 3 2 1 Medium Pressure 5 1 2 3 5 15 3 45 6 75 9 15 12 135 Figure 8: 4 in. V43 Capacity Flow Chart V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin 5

V243 Capacity Flow Charts CAPACITY CHART FOR 2 in. VALVE 6 4 2 2 5 1 14.5 2 253 4 5 6 5 1 15 2 25 3 35 4 45 Figure 9: 2 in. V243 Capacity Flow Chart CAPACITY CHART FOR 3 in. VALVE 6 4 2 2 5 1 14.5 2 25 3 4 5 6 1 2 3 4 5 6 7 8 9 Figure 11: 3 in. V243 Capacity Flow Chart CAPACITY CHART FOR 4 in. VALVE CAPACITY CHART FOR 2-1/2 in. VALVE 6 4 2 2 5 114.5 2 253 4 5 6 1 2 3 4 5 6 7 8 9 2 5 1 14.5 2 25 3 4 5 6 6 4 2 1 2 3 4 5 6 7 8 9 1 11 12 13 Figure 12: 4 in. V243 Capacity Flow Chart Figure 1: 2-1/2 in. V243 Capacity Flow Chart 6 V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin

Installation and Initial Adjustment 1. Flush the lines to remove any foreign matter before connecting the lines to the valve. See Servicing. 2. Screw each companion flange and gasket onto the inlet and outlet water lines as indicated in Figure 13. The inside of the companion flange is threaded. See Table 1 for flange and gasket kit information. 3. Mount the V43/V243 valves so that the water flow follows in the direction indicated by the arrow on the V43/V243 casting. Mount the V43/V243 valves onto a horizontal water line, with the bellows up. 4. Secure the inlet and outlet water lines (with companion flange and gasket) to the inlet and outlet flange connections on the V43/V243 valves with hex bolts and nuts. 9. If necessary, adjust the operating head pressure as instructed in the Valve Adjustment section. To Refrigerant Line Bellows 1/4 in. Copper (or UltraCap) Tube Adjusting Screw Outlet Flange Connection Inlet Flange Connection Drain Plug FIG:Adjustments Gasket Companion Flange Water Line Hex Bolt Figure 13: V43/V243 Gasket and Flange Connections (V43AV Shown) 5. Connect a 1/4-inch copper (or UltraCap) tube from the bellows of the V43/V243 valves to the refrigerant line as indicated in Figure 14. (In reciprocating compressor applications, make the refrigerant connection as far from the compressor discharge as possible.) If possible, make the connection on the outlet side of the condenser. 6. Manually flush the valve to remove debris. See Servicing. 7. Put the system into operation under normal operating conditions. 8. Determine the correct refrigerant operating head pressure for the system. Observe the refrigerant pressure indicated at the high side pressure service gauge. Nut Inlet Flange Connection FIG:Gasket Connections Figure 14: V43/V243 Connections and Adjustments (V43AV Shown) Checkout Procedure Note: Before operating equipment, always manually flush the valve. See Servicing. Before leaving the installation site, observe at least three complete operating cycles (bellows open and close) to verify that all components are functioning properly. Valve Adjustment Make adjustments gradually. Adjust by 1/2 revolution and wait for the system to stabilize after each adjustment change. The throttling range (differential) is not adjustable. To increase the opening point of the valve, turn the adjusting screw (Figure 15, inset) inward, away from main valve body (clockwise) as viewed from the bottom up. To decrease the opening point, turn the adjusting screw outward, toward the main valve body (counterclockwise). V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin 7

Servicing The V43/V243 valves can be disassembled, cleaned, and reassembled without breaking the line connections. Accessing Internal Parts 1. Shut off water flow to the V43/V243 valves. 2. Remove the hex bolts (Figure 15) from the top of the bellows flange. 3. Remove the bellows flange. Note: For internal parts replacement instructions, refer to the respective replacement parts instruction sheet. Manual Flushing Before starting equipment, manually flush the valve to remove any foreign material from the valve. 1. Turn the adjusting screw (Figure 15, inset) clockwise, raising the adjusting screw away from the valve body as much as possible (count the number of turns for reference). 2. Insert a standard slotted screwdriver tip between the adjusting screw and the push pin. 3. Pry the push pin down with the screwdriver to open the valve as indicated. 4. Hold the push pin down to hold the valve open. Flush the valve for several minutes, removing all foreign matter from the V43/V243 valves. 5. After flushing the V43/V243 valves, remove the screwdriver and set the adjusting screw to the desired operating pressure. See Valve Adjustment. Cleaning the Monel Screen The pilot valve is protected from debris by a fine mesh monel screen. To clean the screen, shut off the water supply, relieve the water pressure, unscrew the hex bolt (Figure 15), remove the monel screen, brush, and rinse clean. Draining the V43/V243 Valves During Shutdown To reduce the possibility of freeze-up, drain the V43/V243 valves during shutdown. To drain, unscrew the drain plug at the base of the V43/V243 valves. See Figure 15. Note: In order to drain, the V43/V243 valves must be mounted in a horizontal water line with the bellows up and the drain plug down. Bolt Push Pin Monel Screen Manual Flushing Procedures Adjusting Screw Hex Bolt Bellows Flange Insert screwdriver tip between adjusting screw and push pin. Pry push pin down to open valve. Drain Plug Figure 15: Monel Screen, Drain Plug, and Manual Flushing Procedures FIG:Drain Plug 8 V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin

Dimensions V43/V243 Valves Dimensions 6- and 8- Flange Hole Configurations G E D E F A G B C D H G E D FIG:Dimensions Figure 16: V43/V243 Flange Connection Valves Dimensions Table 2: Dimensions Symbol 2 Inch 2-1/2 Inch 3 Inch 4 Inch A 1 9-1/2 in. (241 mm) 1-3/4 in. (273 mm) 11-3/4 in. (298 mm) 14 in. (356 mm) B 7-1/2 in. (191 mm) 8 in. (23 mm) 9 in. (229 mm) 1-3/4 in. (273 mm) C 4-3/4 in. (121 mm) 5-1/2 in. (14 mm) 6 in. (152 mm) 7-1/2 in. (191 mm) D 6 in. (152 mm) 7 in. (178 mm) 7-1/2 in. (191 mm) 9 in. (229 mm) E 2-1/8 in. (54 mm) 2-5/8 in. (67 mm) 3-1/8 in. (8 mm) 4-1/8 in. (15 mm) F 2 15-1/4 in. (387 mm) 15-9/16 in. (395 mm) 16-9/16 in. (421 mm) 18-7/32 in. (462 mm) F 3 15-29/32 in. (44 mm) 16-7/32 in. (412 mm) 17-7/32 in. (437 mm) 18-7/8 in. (479 mm) G 3/4 in. (19.5 mm) Dia. (4) 3/4 in. (19.5 mm) Dia. (4) 3/4 in. (19.5 mm) Dia. (4) 3/4 in. (19.5 mm) Dia. (8) H 3-5/8 in. (92 mm) 3-15/16 in. (1 mm) 4-1/4 in. (18 mm) 5-1/16 in. (128 mm) 1. Flange face to flange face. 2. These are the measurements for the V43 valves. 3. These are the measurements for the V243 valves. V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin 9

Selection When ordering V43/V243 valves, specify the complete product code number including an optional companion flange and gasket kit. A companion flange and gasket kit is required to mount the water lines to commercial type V43/V243 water-regulating valves. Table 3: Valve Construction and Pressure Type Designator Construction and Pressure Type A Commercial Service with Iron Body, Open on Pressure Increase, V43 B Maritime Service with Brass Body, Open on Pressure Increase, V43 C Navy Service with Brass Body, Open on Pressure Increase, V43 G Commercial Service with Iron Body, Open on Pressure Increase, V243 H Maritime Service with Brass Body, Open on Pressure Increase, V243 Table 4: Flange Size Designator Flange Size S 2 in. T 2-1/2 in. V 3 in. W 4 in. Table 5: V43 Series Pressure Actuated Water Valves (except NAVSEA valves, see Table 6) Code Number Pipe Size (in.) Inlet and Outlet Opening Point Adjustment Range psig (kpa) Commercial Type Non-Corrosive (R) Ship Wt. lb (kg) V43AS-1C 2 4 Hole ASME Flanged 7 to 15 (483 to 1,34) 59 (26.76) V43AS-2C 16 to 26 (1,13 to 1,793) V43AT-1C 2-1/2 7 to 15 (483 to 1,34) 65 (29.48) V43AT-2C 14 to 26 (1,13 to 1,793) V43AV-1C 3 7 to 15 (483 to 1,34) 9 (4.82) V43AV-2C 16 to 26 (1,13 to 1,793) 9 (4.82) V43AW-2C 4 8 Hole ASME Flanged 142 (64.41) Commercial Type - Ammonia (R) V43AV-5C 3 16 to 26 (1,13 to 1,793) 9 (4.82) Maritime Type Non-Corrosive (R) V43BS-6C 2 4 Hole ASME Flanged 7 to 15 (483 to 1,34) 59 (26.76) V43BS-7C 16 to 26 (1,13 to 1,793) V43BT-6C 2-1/2 7 to 15 (483 to 1,34) 65 (29.48) V43BT-7C 14 to 26 (1,13 to 1,793) V43BV-1C 3 7 to 15 (483 to 1,34) 9 (4.82) V43BV-7C 14 to 26 (1,13 to 1,793) 1 V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin

Table 6: V43 Series Pressure Actuated Water Valves, Navy NAVSEA Certified Code Number Pipe Size (in.) Inlet and Outlet Pressure Connector Opening Point Adjustment Range psig (kpa) Ship Wt. lb (kg) Navy NAVSEA Certified Non-Corrosive (R) V43BS-3C 2 4 Hole ASME Flange 1/4 in. Male Flared Conn. 7 to 15 (483 to 1,34) 59 V43CS-1C 6 Hole Navy Flange (26.76) V43CS-2C Female Sweat Conn. V43BT-3C 2-1/2 4 Hole ASME Flange 1/4 in. Male Flared Conn. 65 V43CT-2C 6 Hole Navy Flange (29.48) V43BV-4C 3 4 Hole ASME Flange Female Sweat Conn. 9 V43CV-1C 8 Hole Navy Flange 1/4 in. Male Flared Conn. (4.82) V43CV-2C Female Sweat Conn. V43BW-7C 4 8 Hole ASME Flange 1/4 in. Male Flared Conn. 142 V43BW-2C 14 to 26 (1,13 to 1,793) (64.41) Table 7: V243 Series Pressure Actuated Water Valves Code Number Pipe Size (in.) Inlet and Outlet Opening Point Adjustment Range psig (kpa) Ship Wt. lb (kg) Commercial Type High Pressure V243GS-1C 2 4 Hole ASME Flange 2 to 4 (1,379 to 2,758) 59 (26.76) V243GT-1C 2-1/2 65 (29.48) V243GV-1C 3 9 (4.82) V243GW-1C 4 8 Hole ASME Flange 142 (64.41) Maritime Type High Pressure V243HS-1C 2 4 Hole ASME Flange 2 to 4 (1,379 to 2,758) 59 (26.76) V243HT-1C 2-1/2 65 (29.48) V243HV-1C 3 9 (4.82) V243HW-1C 4 8 Hole ASME Flange 142 (64.41) V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin 11

Repair and Replacement Information If a V43/V243 Pressure-Actuated Water-Regulating Valve fails to operate within its specifications, replacement sensing elements, internal parts, and diaphragms are available for valve repair. See Servicing for servicing instructions. To obtain replacement parts kits instructions and details, contact your nearest Johnson Controls distributor at http://cgproducts.johnsoncontrols.com/ dist_locate/locatedist.asp. For replacement parts kits product code numbers, see Table 8 and Table 9. Table 8: Repair Parts (Part 1 of 2) 1 Model Diaphragm Kit Seat Disc and Diaphragm Kit Seat Repair Kit Screen Repair Kit Push Rod Kit 2 Sensing Element Kit Disc Body Kit V43AS-1C DPM18A-6R DSC16A-6R STT19A-62R SCN1A-6R ROD18A-6R SEP88A-6R DBK11A-6R V43AS-2C DPM18A-6R DSC16A-6R STT19A-62R SCN1A-6R ROD18A-6R SEP88A-61R DBK11A-6R V43AS-5C DPM18A-6R DSC16A-6R STT19A-62R SCN1A-6R ROD18A-6R SEP87A-6R DBK11A-6R V43AT-1C DPM18A-61R DSC16A-61R STT19A-63R SCN1A-6R ROD18A-61R SEP88A-6R DBK11A-61R V43AT-2C DPM18A-61R DSC16A-61R STT19A-63R SCN1A-6R ROD18A-61R SEP88A-61R DBK11A-61R V43AT-5C DPM18A-61R DSC16A-61R STT19A-63R SCN1A-6R ROD18A-61R SEP87A-6R DBK11A-61R V43AV-1C DPM18A-62R DSC16A-62R STT19A-66R SCN1A-6R ROD18A-61R SEP88A-6R DBK11A-62R V43AV-2C DPM18A-62R DSC16A-62R STT19A-66R SCN1A-6R ROD18A-61R SEP88A-61R DBK11A-62R V43AV-5C DPM18A-62R DSC16A-62R STT19A-66R SCN1A-6R ROD18A-61R SEP87A-6R DBK11A-62R V43AW-1C DPM18A-63R DSC16A-63R STT19A-68R SCN1A-6R ROD18A-62R SEP88A-6R DBK11A-63R V43AW-2C DPM18A-63R DSC16A-63R STT19A-68R SCN1A-6R ROD18A-62R SEP88A-61R DBK11A-63R V43AW-5C DPM18A-63R DSC16A-63R STT19A-68R SCN1A-6R ROD18A-62R SEP87A-6R DBK11A-63R V43BS-1C 1 DPM18A-6R DSC16A-6R STT19A-62R SCN1A-61R ROD18A-62R SEP88A-6R DBK11A-6R 1 V43BS-2C DPM18A-6R DSC16A-6R STT19A-62R SCN1A-61R ROD18A-62R SEP88A-61R DBK11A-6R V43BS-3C DPM18A-6R DSC16A-6R STT19A-6R SCN1A-61R ROD18A-62R SEP88A-6R DBK1A-6R V43BS-6C DPM18A-6R DSC16A-6R STT19A-6R SCN1A-61R ROD18A-62R SEP88A-6R DBK1A-6R V43BS-7C DPM18A-6R DSC16A-6R STT19A-6R SCN1A-61R ROD18A-62R SEP88A-61R DBK1A-6R V43BT-1C 1 DPM18A-61R DSC16A-61R STT19A-63R SCN1A-61R ROD18A-63R SEP88A-6R DBK11A-61R 1 V43BT-2C DPM18A-61R DSC16A-61R STT19A-63R SCN1A-61R ROD18A-63R SEP88A-61R DBK11A-61R V43BT-3C DPM18A-61R DSC16A-61R STT19A-65R SCN1A-61R ROD18A-63R SEP88A-6R DBK1A-62R V43BT-6C DPM18A-61R DSC16A-61R STT19A-65R SCN1A-61R ROD18A-63R SEP88A-6R DBK1A-62R V43BT-7C DPM18A-61R DSC16A-61R STT19A-65R SCN1A-61R ROD18A-63R SEP88A-61R DBK1A-62R V43BV-1C 1 DPM18A-62R DSC16A-62R STT19A-66R SCN1A-61R ROD18A-63R SEP88A-6R DBK11A-62R 1 V43BV-2C DPM18A-62R DSC16A-62R STT19A-66R SCN1A-61R ROD18A-63R SEP88A-61R DBK11A-62R V43BV-4C DPM18A-62R DSC16A-62R STT19A-67R SCN1A-61R ROD18A-63R SEP88A-6R DBK1A-61R V43BV-5C1 DPM18A-62R DSC16A-62R STT19A-66R SCN1A-61R ROD18A-63R SEP88A-6R DBK11A-62R 1 V43BV-6C DPM18A-62R DSC16A-62R STT19A-66R SCN1A-61R ROD18A-63R SEP88A-61R DBK11A-62R V43BV-7C DPM18A-62R DSC16A-62R STT19A-67R SCN1A-61R ROD18A-63R SEP88A-61R DBK1A-61R V43BV-8C DPM18A-62R DSC16A-62R STT19A-67R SCN1A-61R ROD18A-63R SEP88A-6R DBK1A-61R V43BV-9C DPM18A-62R DSC16A-62R STT19A-67R SCN1A-61R ROD18A-63R SEP88A-61R DBK1A-61R V43BV-1C DPM18A-62R DSC16A-62R STT19A-67R SCN1A-61R ROD18A-63R SEP88A-6R DBK1A-61R V43BW-1C DPM18A-63R DSC16A-63R STT19A-69R SCN1A-61R ROD18A-62R SEP88A-6R DBK1A-63R V43BW-2C DPM18A-63R DSC16A-63R STT19A-69R SCN1A-61R ROD18A-62R SEP88A-61R DBK1A-63R V43BW-5C DPM18A-63R DSC16A-63R STT19A-69R SCN1A-61R ROD18A-62R SEP88A-6R DBK1A-63R V43BW-6C DPM18A-63R DSC16A-63R STT19A-69R SCN1A-61R ROD18A-62R SEP88A-61R DBK1A-63R V43BW-7C DPM18A-63R DSC16A-63R STT19A-69R SCN1A-61R ROD18A-62R SEP88A-6R DBK1A-63R V43CS-1C DPM18A-6R DSC16A-6R STT19A-6R SCN1A-61R ROD18A-62R SEP88A-6R DBK1A-6R V43CS-2C DPM18A-6R DSC16A-6R STT19A-6R SCN1A-61R ROD18A-62R SEP88A-6R DBK1A-6R 12 V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin

Table 8: Repair Parts (Part 2 of 2) 1 Model Diaphragm Kit Seat Disc and Diaphragm Kit Seat Repair Kit V43CS-3C DPM18A-6R DSC16A-6R STT19A-6R SCN1A-61R ROD18A-64R SEP88A-6R DBK1A-6R V43CT-1C DPM18A-61R DSC16A-61R STT19A-65R SCN1A-61R ROD18A-63R SEP88A-6R DBK1A-62R V43CT-2C DPM18A-61R DSC16A-61R STT19A-65R SCN1A-61R ROD18A-63R SEP86A-6R DBK1A-62R V43CV-1C DPM18A-62R DSC16A-62R STT19A-67R SCN1A-61R ROD18A-63R SEP86A-6R DBK1A-61R V43CV-2C DPM18A-62R DSC16A-62R STT19A-67R SCN1A-61R ROD18A-63R SEP88A-6R DBK1A-61R V243GS-1C DPM18A-6R DSC16A-6R STT19A-62R SCN1A-6R ROD18A-6R SEP9A-6R DBK11A-6R V243GT-1C DPM18A-61R DSC16A-61R STT19A-63R SCN1A-6R ROD18A-61R SEP9A-6R DBK11A-61R V243GV-1C DPM18A-62R DSC16A-62R STT19A-66R SCN1A-6R ROD18A-61R SEP9A-6R DBK11A-62R V243GW-1C DPM18A-63R DSC16A-63R STT19A-68R SCN1A-6R ROD18A-6R SEP9A-6R DBK11A-63R V243HS-1C DPM18A-6R DSC16A-6R STT19A-6R SCN1A-61R ROD18A-62R SEP9A-6R DBK1A-6R V243HT-1C DPM18A-61R DSC16A-61R STT19A-65R SCN1A-61R ROD18A-63R SEP9A-6R DBK1A-61R V243HV-1C DPM18A-62R DSC16A-62R STT19A-67R SCN1A-61R ROD18A-63R SEP9A-6R DBK1A-62R V243HW-1C DPM18A-63R DSC16A-63R STT19A-69R SCN1A-61R ROD18A-62R SEP9A-6R DPK1A-63R 1. Repair parts are supplied in kits only and include all parts required to recondition that portion of the valve. To order, specify code number only. 2. Replacement push rod kit requires a seat repair kit and/or a diaphragm kit when replaced. The following valves, manufactured after date code 872, contain monel interior trim. Order replacement kits as listed in Table 8 or V43xx and V243xx Series Repair Parts Kits Technical Bulletin (LIT-12169). Table 9: Parts Kits Valve Model V43BS-1C V43BS-2C V43BT-1C V43BT-2C V43BV-1C V43BV-2C V43BV-5C V43BV-6C Order Parts Kits for: V43BS-6C V43BS-7C V43BT-6C V43BT-7C V43BV-1C V43BV-7C V43BV-1C V43BV-9C Screen Repair Kit Push Rod Kit 2 Sensing Element Kit Disc Body Kit V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin 13

Accessories Table 1: Companion Flanges and Gaskets Kit Code Number Water Valve Size (in.) Shipping Wt. lb (kg) KIT14A-613 1 2 2 11.8 (5.4) KIT14A-614 1 2 2-1/2 16.5 (7.5) FLG15A-6 1 3 3 2 (9.1) FLG15A-61 1 3 4 34 (15.4) 1. Commercial valves only. 2. See Figure 17 for a diagram of the parts included in the flange and gasket kit for the 2-inch and 2-1/2-inch valves. 3. See Figure 18 for a diagram of the parts included in the flange and gasket kit for the 3-inch and 4-inch valves. A companion flange and gasket kit is required to mount the water lines to commercial type V43/V243 water-regulating valves. Cast Iron Flange (2) Machine Bolt (8) Ring Gasket (2) Cast Iron Flange (2) Gasket (2) Hex Nut (8) Machine Bolt (8) Hex Nut (8) FIG:FLG15A Figure 17: KIT14A flange Figure 18: FLG15A 14 V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin

Technical Specifications V43/V243 Pressure-Actuated Water-Regulating Valves Maximum Water Supply Pressure 15 psig (1,34 kpa) V43 Maximum Head Pressure 3 psig (2,68 kpa) V243 Maximum Head Pressure 63 psig (4,344 kpa) Head Pressure Range (Opening Points) V43 Low Pressure R-134A 7 to 15 psig (482 to 1,34 kpa) Medium Pressure R-22, R-52, R44A 16 to 26 psig (1,13 to 1,793 kpa) Ammonia 16 to 26 psig (1,13 to 1,793 kpa) V243 High Pressure R41A 2 to 4 psig (1,379 to 2,758 kpa) Factory Settings 1 V43 Low Pressure 9 psig (621 kpa) Medium 18 psig (1,241 kpa) Pressure Ammonia 18 psig (1,241 kpa) V243 High Pressure 2 psig (1,379 kpa) Maximum Water Supply Temperature 16 F (71 C) Valve Body Material Commercial Cast Iron Maritime Red Brass Internal Parts Material Commercial Brass Maritime Bronze, Monel Seat Material Pilot Monel Main Valve Commercial Bronze, Maritime Monel Seat Disc Material Buna N Packing Bellows Assembly Brass Stem, Stainless Steel Spring, Synthetic Rubber Boot Pressure Connection Refrigerant Side Non-corrosive 1/4 in. SAE Male Flare Ammonia 1/4 in. FNPT 1. Factory setpoint for the valve is adjustable. The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, contact Johnson Controls/PENN Refrigeration Technical Support at 1-8-275-5676. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Building Efficiency 57 E. Michigan Street, Milwaukee, WI 5322 Johnson Controls and PENN are registered trademarks of Johnson Controls, Inc. in the United States of America and/or other countries. All other trademarks used herein are the property of their respective owners. Copyright 215 by Johnson Controls, Inc. All rights reserved. V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin 15 Published in U.S.A. www.johnsoncontrols.com