Comparative Analysis of RCC and Steel-Concrete- Composite (B+G+ 11 Storey) Building

Similar documents
Miss S. S. Nibhorkar 1 1 M. E (Structure) Scholar,

EFFECT OF POSITIONING OF RC SHEAR WALLS OF DIFFERENT SHAPES ON SEISMIC PERFORMANCE OF BUILDING RESTING ON SLOPING GROUND

SEISMIC ANALYSIS AND RETROFITTING OF R.C.C STRUCTURE

Optimum proportions for the design of suspension bridge

SEISMIC DESIGN. Various building codes consider the following categories for the analysis and design for earthquake loading:

DESIGN OF SLABS. 3) Based on support or boundary condition: Simply supported, Cantilever slab,

EVALUATION OF SEISMIC RESPONSE - FACULTY OF LAND RECLAMATION AND ENVIRONMENTAL ENGINEERING -BUCHAREST

4B The stiffness of the floor and roof diaphragms. 3. The relative flexural and shear stiffness of the shear walls and of connections.

ANALYSIS AND DESIGN OF RC TALL BUILDING SUBJECTED TO WIND AND EARTHQUAKE LOADS

Specification for Structures to be Built in Disaster Areas

OPTIMAL DIAGRID ANGLE TO MINIMIZE DRIFT IN HIGH-RISE STEEL BUILDINGS SUBJECTED TO WIND LOADS

SEISMIC RETROFITTING OF STRUCTURES

Seismic performance evaluation of an existing school building in Turkey

Structural Design of Multi-story Residential Building for in Salem, India

CH. 2 LOADS ON BUILDINGS

Analysis and Repair of an Earthquake-Damaged High-rise Building in Santiago, Chile

1.054/1.541 Mechanics and Design of Concrete Structures (3-0-9) Outline 1 Introduction / Design Criteria for Reinforced Concrete Structures

INTRODUCTION TO LIMIT STATES

National Council of Examiners for Engineering and Surveying. Principles and Practice of Engineering Structural Examination

Seismic Risk Prioritization of RC Public Buildings

Hunter College school of Social Work Thesis Proposal

SECTION 5 ANALYSIS OF CONTINUOUS SPANS DEVELOPED BY THE PTI EDC-130 EDUCATION COMMITTEE LEAD AUTHOR: BRYAN ALLRED

1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona

A project report on, Prepared in partial fulfillment of. Study oriented project, Course code: CE G611 Computer Aided Analysis and Design

Prepared For San Francisco Community College District 33 Gough Street San Francisco, California Prepared By

DESIGN OF SLABS. Department of Structures and Materials Engineering Faculty of Civil and Environmental Engineering University Tun Hussein Onn Malaysia

ETABS. Integrated Building Design Software. Concrete Shear Wall Design Manual. Computers and Structures, Inc. Berkeley, California, USA

The International Journal Of Science & Technoledge (ISSN X)

Structural Audit of Buildings

Rehabilitation of Existing Foundation Building to Resist Lateral and Vertical Loads

Draft Table of Contents. Building Code Requirements for Structural Concrete and Commentary ACI

DESIGN OF BLAST RESISTANT BUILDINGS IN AN LNG PROCESSING PLANT

SEISMIC CAPACITY OF EXISTING RC SCHOOL BUILDINGS IN OTA CITY, TOKYO, JAPAN

Methods for Seismic Retrofitting of Structures

Technical Notes 3B - Brick Masonry Section Properties May 1993

MECHANICS OF SOLIDS - BEAMS TUTORIAL 2 SHEAR FORCE AND BENDING MOMENTS IN BEAMS

Aluminium systems profile selection

How To Design A Post Tensioned Deck For A Building

METHODS FOR ACHIEVEMENT UNIFORM STRESSES DISTRIBUTION UNDER THE FOUNDATION

November 20, Heather Sustersic Dear Professor Sustersic,

Field Damage Inspection and Static Load Test Analysis of Jiamusi Highway Prestressed Concrete Bridge in China

MODELLING OF AN INFILL WALL FOR THE ANALYSIS OF A BUILDING FRAME SUBJECTED TO LATERAL FORCE

Design of Steel Structures Prof. S.R.Satish Kumar and Prof. A.R.Santha Kumar. Fig some of the trusses that are used in steel bridges

Design of Steel Structures Prof. S.R.Satish Kumar and Prof. A.R.Santha Kumar

Chapter 3 Pre-Installation, Foundations and Piers

Spon Press PRESTRESSED CONCRETE DESIGN EUROCODES. University of Glasgow. Department of Civil Engineering. Prabhakara Bhatt LONDON AND NEW YORK

Seismic Isolated Hospital Design Practice in Turkey: Erzurum Medical Campus

FOUNDATION DESIGN. Instructional Materials Complementing FEMA 451, Design Examples

Detailing of Reinforcment in Concrete Structures

Analysis of a Tower Crane Accident

Numerical modelling of shear connection between concrete slab and sheeting deck

Design for Nonstructural Components

International Nursing and Rehab Center Addition 4815 S. Western Blvd. Chicago, IL

Structural Design Criteria & Design Loads on Delhi Metro Rail and Checking of Safety of Radial Joints in Tunnel Lining Segments

SECTION 7 Engineered Buildings Field Investigation

The following sketches show the plans of the two cases of one-way slabs. The spanning direction in each case is shown by the double headed arrow.

REINFORCED CONCRETE. Reinforced Concrete Design. A Fundamental Approach - Fifth Edition. Walls are generally used to provide lateral support for:

[TECHNICAL REPORT I:]

PERFORMANCE BASED SEISMIC EVALUATION AND RETROFITTING OF UNSYMMETRICAL MEDIUM RISE BUILDINGS- A CASE STUDY

Basics of Reinforced Concrete Design

DESIGN SPECIFICATIONS FOR HIGHWAY BRIDGES PART V SEISMIC DESIGN

Expected Performance Rating System

Chapter 3 DESIGN AND CONSTRUCTION FEATURES IMPORTANT TO SEISMIC PERFORMANCE

METHOD OF STATEMENT FOR STATIC LOADING TEST

Retrofitting of Existing RCC Buildings by Method of Jacketing

INTRODUCTION TO BEAMS

ASSESSMENT AND RETROFITTING OF EXISTING RC BUILDINGS IN VIETNAM IN TERMS OF EARTHQUAKE RESISTANCES

CE591 Lecture 8: Shear Walls

SLAB DESIGN. Introduction ACI318 Code provides two design procedures for slab systems:

SPECIFICATIONS, LOADS, AND METHODS OF DESIGN

9.3 Two-way Slabs (Part I)

EFFECTS ON NUMBER OF CABLES FOR MODAL ANALYSIS OF CABLE-STAYED BRIDGES

Wisconsin Building Products Evaluation

Seismic Risk Evaluation of a Building Stock and Retrofit Prioritization

ENGINEERING SCIENCE H1 OUTCOME 1 - TUTORIAL 3 BENDING MOMENTS EDEXCEL HNC/D ENGINEERING SCIENCE LEVEL 4 H1 FORMERLY UNIT 21718P

Structural Analysis. EUROCODE 2 Background and Applications

Concrete Frame Design Manual

16. Beam-and-Slab Design

Foundations 65 5 FOUNDATIONS. by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. Seismic Retrofit Training

Seismic Isolation Retrofitting of Japanese Wooden Buildings

Type of Force 1 Axial (tension / compression) Shear. 3 Bending 4 Torsion 5 Images 6 Symbol (+ -)

EGYPTIAN CODES FOR DESIGN AND CONSTRUCTION OF BUILDINGS

TRUSSES. (b) Space Truss. Bracings. (e) Truss Bridge. (d) Bracings in Single Storey Buildings. (c) Bracings in Multi-storey Building

CSA S16-09 Design of Steel Structures Canada

Review of Code Provisions on Design Seismic Forces for Liquid Storage Tanks

The University of Birmingham (Live System)

Reinforced Concrete Design

Tall buildings. Florea Dinu. Lecture 13: 25/02/2014

THE REPORT ON THE INVESTIGATION OF THE REACTORS AT FUKUSHIMA DAIICHI NUCLEAR POWER STATION (NO. 1)

Best Practice in Best Pra ctice in teel constr uction - onstr industrial B uildings esidential Buildings 01 Introduction 02 Key Design Factors

New approaches in Eurocode 3 efficient global structural design

DEVELOPMENT AND APPLICATIONS OF TUNED/HYBRID MASS DAMPERS USING MULTI-STAGE RUBBER BEARINGS FOR VIBRATION CONTROL OF STRUCTURES

bi directional loading). Prototype ten story

DYNAMIC ANALYSIS ON STEEL FIBRE

ETABS. Integrated Building Design Software. Concrete Frame Design Manual. Computers and Structures, Inc. Berkeley, California, USA

Steel joists and joist girders are

WORLD S TALLEST TIMBER BUILDING, BERGEN

Figure Test set-up

TABLE OF CONTENTS. Roof Decks 172 B, BA, BV Deck N, NA Deck. Form Decks FD,.6 FDV Deck 1.0 FD, 1.0 FDV Deck 1.5 FD Deck 2.0 FD Deck 3.

Transcription:

International Journal of Scientific and Research Publications, Volume, Issue 1, October 21 1 Comparative Analysis of RCC and Steel-Concrete- Composite (B+G+ 11 Storey) Building Mr. Nitish A. Mohite 1, Mr. P.K.Joshi 2, Dr. W. N. Deulkar 3 1, 2 Department of Civil Engineering, PVPIT, Budhgaon, Sangli, MS, India 3 Associate Professor, Department of Civil Engineering, DYPCOET, Kolhapur, MS, India Abstract - Steel-concrete-composite buildings are formed by connecting the steel beams with concrete slab or profiled deck slab with the help of mechanical shear connectors so that slab and beam act as a single unit. In the present work, options of construction of (B+G+11storey) commercial building, situated in Kolhapur, with steel-concrete-composite and RCC are studied and compared with each other. Equivalent linear Static Method of Analysis explained in ETABS version 1 software is used and results are compared for different parameters. Comparative parameter includes roof deflections, base shear, storey drifts, for the building and axial forces and bending moments for column s and beams at different level. It is observed that steel-concretecomposite building is found to be more safe and economical and better option. Key Words: Steel-concrete-composite, RCC, Shear connector, ETAB software, Equivalent linear Static Method I. Introduction In the past, structural engineers had the choice masonry building. Today multi-story buildings in India are constructed with R.C.C framed structure or Steel framed structure. Recentlythe trend of going towards composite structure has started and growing in us. But the failure of many these buildings due to earthquake have forced engineer to look for the alternative method of construction. Use of composite or hybrid material remains the particular interest, due to its significant potential in improving the overall performance through modest changes in manufacturing and constructional technologies. In India, many consulting engineers are reluctant to accept the use of steel-concrete-composite structure because of its unfamiliarity and complexity in analysis and design. But literature shows that if properly configured, steel-concrete-composite system can provide economical structural systems to resist lateral load with high durability, rapid erection and superior seismic performance characteristics. As comparatively new and no updated design codes are available for the same[1], there is a need to study the composite analysis and design of the multistory buildings keeping in view of the rapid development in this field. Hence same can be studied in Indian context. In the present work, comparative study of RCC and Steel-Concrete-Composite (B+G+11Storey) Building is made.comparative study includes roof deflections, base shear, storey drifts, for the building and axial forces and bending moments for column and beam, are compared for two buildings.seismic behavior of building under seismic forces as per IS 1893-22 are observed. II.Composite Construction Composite construction combines properties of concrete and steel. Steel-concrete-composite building has become now a day s quite popular because of its advantages over conventional In composite construction the two different materials are tied together by the use of shear studs at the interface having lesser depth which saves the material cost considerably. Thermal expansion (coefficient of thermal expansion) of both, concrete and steel being is nearly same. Therefore, there is no induction of different thermal stresses in the section under variation of temperature. A steel concrete composite building consists of a composite column,structural steel beam, over which are reinforced concrete slab is cast with shear connectors between beam and slabs as shown in fig.1..the composite action reduces the beam depth. Rolled steel sections themselves are found adequate frequently for buildings and built-up girders are generally unnecessary.the composite beam can also be constructed with profiled sheeting with concrete topping or with cast in place or precast reinforced concrete slab. A steel concrete composite column is conventionally a compression member in which the steel element is a structural steel section. There are three types of composite columns used in practice which are Concrete Encased, Concrete-filled, and Battered Section.

International Journal of Scientific and Research Publications, Volume, Issue 1, October 21 2 Fig1-Typical composite construction, column-footing (left) and beam-slab (right) III. Linear static Analysis for Lateral load IS 1893 gives procedure to satisfy the objectives[3]. This can be achieved by elastic structural response and limiting the storey drifts to minimize damage. The inelastic deformation demands are smaller than their deformation capacities on account of gravity loads and deterioration of stiffness and strength due to loading. Displacement is the key parameter for performance during earthquake rather than force or strength. Deformation can be classified in to three categories as roof displacement, Story drifts & other internal deformations and inelastic deformations for structural components and elements. These movements occur due to rigid body displacement and shear deformations. High base shear and moment can be avoided due to high shear capacity requirement, development of ductility in elements and structure under gravity and lateral loads and hence stresses, and controlling lateral displacement, story drifts, forces and moments in the structure To study the above issues, composite and RCC model has been studied and compared for the parameters mentioned. This will give the idea about the behavior of the building. The static analysis of building model is performed using IS 1893 and software ETAB version 1. Models are analyzed for lateral load (earthquake) in two lateral X and Y direction. While performing the analysis, slab is considered as rigid diaphragm. RCC model was designed as per code IS 46: 2 [4] and composite system was designed as per code AISC 36-1 [8]. IV. Project details of Architectural plan: Architectural plan educational building with area 41.28 x 17.21m 2 is shown in fig.2, constructed at Kolhapur, Maharashtra. Other considered during analysis are as follows. Other details of educational complex and site conditions are mentioned in table 1. Live load : 4 kn / m 2 Super Dead Load : 3 kn/ m 2 Slab thickness : 1mm Lift shaft : 3 mm thick shear wall Earthquake Zone : III Soil type : Hard soil Importance factor : 1 Time period : User Defined Reduction factor : 3 Damping Ratio : % Wind Speed : 39 m/s Fig 2- Typical floor Plan Table 1-Project details Particular Details Remarks Depth of foundation 3m below GL Basement provided Number of stories 11 Story height - 3m Thickness of walls 23mm External walls Tie at bottom level 3m interval At 3 levels Parking storey 2 stories Basement and 1st floor Parapet height 1.m Type of foundation Raft Columns-fixed Lift Centre shaft Machine roomat top RCC water tank Over staircase columns At terrace level Fig. 3 and 4 shows the typical structural plan and 3D elevation of the model respectively to be analysed.

International Journal of Scientific and Research Publications, Volume, Issue 1, October 21 3 Fig3 - Typical plan for all floors of buildings in ETAB. Fig. 4 Typical 3D Model showing the selected elenments. With above data, the models were constructed, analysed and designed as per 46 and AISC code. The sizes of the different members in different model has been finalized as per strength as well as displacement requirements. The summary of final sizes for different elements are as follows. Table 2 shows of beam and column sizes used during design and analysis. Table 3 shows properties of materials used. Table 2- Beam and column Sizes Particular RCC Composite Levels Main beams.3m x.6m ISMB3 Basement Secondary Beams.23m x.6m ISMB4 to 1 st Floor Main beams.38m x.6m ISMB 6 Secondary Beams.3m x.6m ISMB4 2 nd to 1 th Floor Basement.38m x 1.2m.23m x 1 m withismb4embedded Columns upto 1 st Floor.23m x 1 m.23m x 1 m withismb3embedded 1 st to 1 th Floor Table 3- Properties of material Name of E, MPa ν α G, Unit Weight, Fc, Fc, MPa materials MPa kn/m³ MPa M3 27386.13.2 9.9E-6 1141.89 2 3 - STEEL 1.17E- 199947.98.3 7693.7 76.819 344.74 448.16 V. Results of analysis in two different models Following are the results of analysis. Comparison of parameters mentioned is tabulated in following tables. Response of Storey displacement and Drift for earthquake in X and Y direction is shown in fig and 6 respectively. Results are presented for load combination 1.(DL + LL + EQX/WL). Mass source is from load, which is, lumped at story levels. Contribution of dead load was 1% and from live load was % as live load is more than 3 kn/m 2. In modal analysis, CQC method of combination was used and SRSS method was followed for directional combination. 12 modes were considered in modal analysis. Response spectrum method was used to apply earthquake load as per IS 1893 [] and wind load as per IS 87[6]. Table 4-Roof displacement Load Parameter Type of Model combination RCC COMPOSITE UX, mm 213.6 12.1 DL+LL+EQX UY, mm -13.7-13.9

International Journal of Scientific and Research Publications, Volume, Issue 1, October 21 4 DL+LL+WLX UZ, mm -14.1-11.6 UX, mm 22 16.2 UY, mm -31.8-18.4 UZ, mm -13.6-11. Table - shows Base shear, base moment, torsional moment due to earthquake and wind loads for the load combination dead load plus live load plus, earthquake or wind load. It is seen that the base shear is more in case of RCC than Composite structure. Vertical reaction is same in all the cases irrespective of earthquake/wind load applied in x and y direction. The torsional moment is observed to be same in both model. Bending moment about the transverse axis of load applied is more than the moment about self-direction. These moment is little bit more in case of earthquake load combinations. Table -Base shear, base moment, torsion due to earthquake and wind load Load Combination Parameter Type of model RCC Composite DLLLEQX Base Shear ( in kn ) -6,37.68 -,87 Base Moment ( in kn-m) 11,,462 1,11,27 Torsion ( in kn-m),71.1,977.71 DLLLWX Base Shear ( in kn ) -94.72-94.72 Base Moment ( in kn-m) 12,7,62 11,76,414 Torsion ( in kn-m) 8,86.779 8,86.779 Fig.a and b shows the variation of drift along the storey height. It is seen that story drift is less in case of earthquake load and more in case of wind load. Story drift in case of composite structure is less than RCC structure to both loads ( earthquake and wind ). IN EQX IN WX STOREY LEVEL 1 1..1 DRIFT RCC EQX COMPOSITE EQX STOREY LEVEL 1 1..1.1 DRIFT RCC WX COMPOSITE WX Fig a) - Response of story drift in X direction due to earthquake Fig b) - Response of story drift due to wind load along x direction respectively Fig 6a and b shows variation of story shear along story height. Story shear is more in case of earthquake load than wind load. Story shear is less in case of composite structure. STORY SHEAR IN EQX STORY SHEAR COMPOSITE -1 - EQX FORCE IN kn Fig 6 a) - Response of story shear in X direction due to earthquake 1 1 STOREY LEVEL STORY SHEAR RCC EQX STORY SHEAR IN WX -1 - FORCE IN kn Fig 6 b) - Response of story sheardue to wind load along x direction respectively 1 1 STORY LEVEL STORY SHEAR RCC WX STORY SHEAR COMPOSITE WX

International Journal of Scientific and Research Publications, Volume, Issue 1, October 21 Table 6 : Max. values of different action of AF,SF, BM and TM for main beams at different story for RCC and Composite Action AF SF BM TM Level Max value for RCC Max value for Composite Remark End 1 End 2 End 1 End 2 Top Axial force in beam is Middle absent. basement 8.3 8.3 3.97 4.14 Top -161.14 227.76-16.21 211.1 Shear force decreases Middle -49.72 34.46-18.77 34.3 from top to bottom. basement 47.7 87.21 12.64 141.42 Top -16-344.37-197.96-38.8 BM is higher in middle Middle 266.89-736.4 281.1-917.99 level beams. In top level basement 234.6-26.7 446.23-37.42 beam, BM is less. Top 3.1-36.66.8 -.99 TM is negligible for Middle 31.88-38.3.68 -.99 Bottom beams and max. basement -.16 -.16 -.213 -.74 for top level beam All action are less for Composite structure Table 7 : Max. values of different action of AF,SF, BM and TM for secondary beam at different story for RCC and Composite Action Level Max value for RCC Max value for Composite Remark End 1 End 2 End 1 End 2 Top Axial force in beam is AF Middle absent. basement -23.1-23.1-1.71-1.71 Top -14.8 169.32-133.1 181.33 Shear force decreases SF Middle -161.12 199.73-149.49 194.8 from top to bottom. basement -22.18 42.94-19.39 3.14 Top -211.19-244.7-13.68-2.87 BM is higher in middle BM Middle -239.34-39 -192.37-28.8 level beams. In top level basement 1.89-39.98.49-31.1 beam, BM is less. Top -7.6 2.89 -.4.31 TM is negligible for TM Middle -23.1 8.27 -.17.969 Bottom beams and max. basement -.23 -.23 -.49 -.49 for top level beam All action are less for Composite structure Table 8: Max. values of different action of AF,SF, BM and TM for column at different story for RCC and Composite Action Level Max value for RCC Max value for Composite Remark End 1 End 2 End 1 End 2 Top -634.32-634.32-26.26-26.26 Axial force increase AF Middle -4119.3-4119.3-378.9-378.9 For RCC structure basement -848.7-848.7-778.61-778.61 From top to bottom Top -32.6-32.6 14.43 14.43 Shear force increase SF Middle 316.3 316.3 336.22 336.22 For RCC structure basement 682.26 682.26 11.13 11.13 From top to bottom Top -41. -332.2 91.76-23.46 BM increase BM Middle 226.77-32.47 44.68-31.82 For RCC structure basement 32.9 2641.86 13.96 972.61 From top to bottom Top -1.89-1.89-2.63-2.63 Negligible TM TM Middle.61.61-2.24-2.24 basement -.2 -.2 -.78 -.78 All action are less for Composite structure

International Journal of Scientific and Research Publications, Volume, Issue 1, October 21 6 VI. CONCLUSION: The reduction in the self-weight of the Steel-Concrete Composite structure is reduced by is 9.48 % as compared to R.C.C. frame Structure. Shear forces in main beams in composite structure are increased by average 39.43% as compared to R.C.C. framed structure while in secondary beams in composite structure are reduced by average 14.39 % as compared to RCC framed structure. Bending moments in main beams in composite structure are increased 2.7% as compared to R.C.C. framed structure while in secondary beams in composite structure are reduced by average 28.93 % as compared to RCC framed structure. Axial forces in column in Composite framed structure have been reduced by average reduced by average 9.8 % as compared to RCC framed structure. Overall response of composite structure is better than RCC structure i.e. composite structure produces less displacement, resist more structure forces/ action. Earthquake response is more than wind load. In both the options the values of story displacements are within the permissible limits as per code limits. Still roof displacement and drift with earthquake in X and Y direction are less in Composite framed structure as to R.C.C. framed structure. This may be due to more ductility in case of Composite structure as compared to the R.C.C. which is best suited under the effect of lateral forces. From the observations and concluding remark, it can be said that Steel-Concrete-Composite option is better than RCC for high rise building. VII. REFERENCES: 1. [1] Institute for steel development & Growth, "B+G+4 Storied Residential Building with Steel-Concrete Composite Option India, Dec 27. 2. [2] M. Nageh, How To Model and Design High Rise Building Using ETABs Program Cairo 27. 3. [3] M. Willford, A. Whittaker and R. Klemencic, Recommendations for Seismic Design of High-Rise Buildings Council of Tall building and urban habitat Feb 28. 4. [4] IS: 46, Code of practice for plain and reinforced concrete code of practice, Bureau of Indian Standards, New Delhi, 2.. [] IS: 1893, Criteria for earthquake resistant design of structures general provisions for buildings, Part 1, Bureau of Indian Standards, New Delhi, 22. 6. [6] IS: 87, code of practice for design load (other than earthquake) for buildings and structures Bureau of Indian Standards, New Delhi, 22. 7. [7] IS: 8, Code of practice for general construction in steel, Bureau of Indian Standards, New Delhi, 27. 8. [8] AISC 36-1, Specification of structural steel building, An American national standard, American Institute Of Steel Construction, Inc., 2. 9. [9] IS: 11384, Code of practice for composite construction in structural steel and concrete, Bureau of Indian Standards, New Delhi, 198. Authors First Author Mr. Nitish A. Mohite, M.E. Civil Structural Engg. Student, Department of Civil Engineering, PVPIT, Budhgaon, Sangli, MS, India, nitish.mohite381@google.com Second Author- Mr. P.K.Joshi, Associate Professor, Department of Civil Engineering, PVPIT, Budhgaon, Sangli, MS, India pkjpvpit@gmail.com Third Author- Dr. W. N. Deulkar, Associate Professor, Department of Civil Engineering, DYPCOET, Kolhapur, MS, India wasudeon@gmail.com