Review of Code Provisions on Design Seismic Forces for Liquid Storage Tanks
|
|
|
- Alfred Rose
- 9 years ago
- Views:
Transcription
1 Document No. :: IITK-GSDMA-EQ1-V1. Final Report :: A - Earthquake Codes IITK-GSDMA Project on Building Codes Review of Code Provisions on Design Seismic Forces for Liquid Storage Tanks by Dr. O. R. Jaiswal Department of Applied Mechanics Visvesvaraya National Institute of Technology Nagpur Dr. Durgesh C Rai Dr. Sudhir K Jain Department of Civil Engineering Indian Institute of Technology Kanpur Kanpur
2 Review of Code Provisions on Design Seismic Forces for Liquid Storage Tanks Abstract It is well recognized that liquid storage tanks possess low ductility and energy absorbing capacity as compared to the conventional buildings. Accordingly, various design codes provide higher level of design seismic forces for tanks. In this article, provisions of IBC 2, ACI, AWWA, API, Eurocode 8 and NZSEE guidelines are reviewed, to assess the severity of design seismic forces for tanks vis-à-vis those for buildings. It is seen that, depending on the type of tank, design seismic force for tanks can be 3 to 7 times higher than that for buildings. Based on the comparison of provisions in these documents, various similarities, discrepancies and limitations in their provisions are brought out. At the end a brief description of Indian code is given along with a few suggestions to remove the inadequacies in Indian code. 1. INTRODUCTION Seismic safety of liquid storage tanks is of considerable importance. Water storage tanks should remain functional in the post earthquake period to ensure potable water supply to earthquake-affected regions and to cater the need for fire fighting. Industrial liquid containing tanks may contain highly toxic and inflammable liquids and these tanks should not loose their contents during the earthquake. Liquid storage tanks are mainly of two types: ground supported tanks and elevated tanks. Elevated tanks are mainly used for water supply schemes and they could be supported on RCC shaft, RCC or steel frame, or masonry pedestal. Failure of tanks during Chilean earthquake of 196 and Alaska earthquake of 1964 led to beginning of many investigations on seismic analysis of liquid storage tanks. Following two aspects came to forefront: (a) Due consideration should be given to sloshing effects of liquid and flexibility of container wall while evaluating the seismic forces on tanks. (b) It is recognized that tanks are less ductile and have low energy absorbing capacity and redundancy compared to the conventional building systems. Studies focused on the first aspect resulted in the development of mechanical models of tank by Housner (1963) and Veletsos (1974), which represented tank-fluid system in a more realistic fashion. Many investigations IITK-GSDMA-EQ1-V1. 2
3 followed along this line to further refine these mechanical models to include effects of flexibility of soil (Hori (199), Veletsos et. al. (1992)) and base uplifting of unanchored tanks (Malhotra (1997)). Further studies have provided more simplifications to these mechanical models (Malhotra (2)). Most of the design codes use these mechanical models to represent dynamics of tank-fluid system, which are applicable to ground supported as well as elevated tanks. The second aspect which is related to low ductility and redundancy in tanks as compared to the conventional buildings, has been dealt with in a rather empirical manner. Lateral seismic coefficient for tanks is generally taken higher than for the buildings. Wozniak and Mitchell (1978) state the high value of lateral seismic coefficient for tanks in comparison with buildings is appropriate because of the low damping inherent for storage tanks, the lack of nonstructural load bearing elements, and lack of ductility of the tank shell in longitudinal compression. Most of the design codes do follow this approach and assign higher design seismic action for tanks as compared to buildings. How high this design action should be, is perhaps decided on ad-hoc basis or based on past experiences, however, it is influenced by type of tank, supporting subgrade, type of anchorage to tank etc. Basically it depends on how good ductility and energy absorbing capacity a particular type of tank can provide. For elevated tanks, ductility, redundancy and energy absorbing capacity is mainly governed by the supporting structure, which could be in the form of a RCC shaft, RCC frame, Steel frame or even masonry pedestal. This article presents an assessment of design seismic force for tanks visà-vis design seismic force for buildings as mentioned in the following documents: (a) IBC 2 (b) ACI Standards ACI 371 (1998) and ACI 35.3 (21) (c) AWWA D-1 (1996), AWWA D-13 (1997), AWWA D-11 (1995) and AWWA D-115 (1995) (d) API 65 (1998) (e) Eurocode 8 (1998) IITK-GSDMA-EQ1-V1. 3
4 (f) NZSEE guidelines and NZS 423:1992 It may be noted here that IBC 2, ACI, AWWA and API standards are from USA. The quantification of design seismic action in ACI, AWWA and API standards is in a different fashion than IBC 2. However, FEMA 368 (NEHRP 2) has provided modifications to these quantifications to bring them in conformity with provisions of IBC 2. In the present article, provisions of ACI, AWWA and API standards will be discussed along with the modifications of FEMA368. Similarly, in New Zealand, the NZSEE recommendations (Priestly et. al., 1986) on seismic design of tanks, is being presently revised by a study group to bring it in line with New Zealand loading code NZS 423:1992. The outline of the procedure proposed by this study group is given by Whittaker and Jury (2). In the present article, procedure described by Whittaker and Jury is considered along with NZS 423:1992. The assessment of design seismic force for tanks is presented in terms of design response spectra. This assessment is done with respect to corresponding design seismic force for buildings. Such a comparative assessment helps in knowing how severe design seismic action for tank is, as compared to that for a building under similar seismic exposures. First, provisions on design seismic action for tanks described in the above-mentioned documents are discussed, followed by a comparison of design seismic actions from various codes. At the end a brief description of Indian Standard, IS 1893:1984 is given. Inadequacies of IS 1893:1984 in quantifying suitable seismic design forces for tanks are brought out and a few modifications are proposed to remove these limitations. 2. IBC 2 International Building Code (IBC) 2 does provide provisions for certain types of non-building structures which include tanks. For buildings, the seismic base shear is given by V = C s W, where, W is the effective seismic weight. Seismic response coefficient or base shear coefficient, C s should be minimum of the following two values SDS Cs = or R / I SD, where S DS and (R / I)T 1 Cs = S D1 are the design spectral response accelerations at short periods and 1 second IITK-GSDMA-EQ1-V1. 4
5 period, respectively; I is importance factor; R is response modification factor and T is the fundamental time period of building. The minimum value of C s should not be less than.44 S DS I. IBC suggests a value of R = 8. for buildings with ductile frames. For most of the buildings, importance factor, I = 1.. Figure 1 shows the variation of base shear coefficient, C s = (V/W) with time period. The values of S DS and S D1 are taken as 1. and.6 respectively, which correspond to S D = 1.5, F a = 1., S 1 =.6 and F v = 1.5 with site class D. For tanks, due to low ductility and redundancy, low values of R are specified. Table 1 gives details of various types of tanks mentioned in IBC along with their R values. Four values of R are specified, i.e. R = 1.5, 2., 2.5 and 3.. For most of the tanks the value of importance factor I will be I =1.25. However, for tanks containing highly toxic materials, importance factor could be I =1.5. The expression for base shear of tank is same as that for building with suitable values of R and I. For tanks, the minimum value of C s should not be less than.14 S DS I as against.44 S DS I for buildings. For ground-supported tanks (i.e., at-grade tanks), IBC suggests to include the effects of sloshing. Similarly, for elevated tanks (i.e., above-grade tanks), IBC states that when sloshing mode period of the stored liquid is within 7 percent to 15 percent of the fundamental period of the supporting structure, the effects of sloshing shall be included in the design of tank and supporting structure. However, IBC 2 does not provide any particular details on evaluation of sloshing or convective mode forces. Thus, the values of R specified for tanks can be considered only for impulsive modes. The variation of base shear coefficient (BSC) for tanks, with time period is also shown in Figure 1. It is seen from this figure that depending on the type of tank, base shear coefficient is 3 to 7 times higher than that of a ductile building. The ratio of base shear coefficient of tank and building, (BSC tank /BSC bldg ), plotted in Figure 2, directly indicates how severe design base shear for tank is with respect to a ductile building (R = 8.). The effect of response reduction factor of tank is seen up to 2 sec. For time period greater than 3 sec, all types of tank have same base shear coefficient, which is about four times that for a ductile building. IITK-GSDMA-EQ1-V1. 5
6 3. ACI STANDARDS ACI 371 and ACI 35.3 describe provisions for seismic design of liquid storage concrete tanks. ACI 371 deals with pedestal supported elevated RCC tanks only; on the other hand, ACI 35.3 deals with ground supported as well as elevated tanks. Further, ACI 371 describes consideration of impulsive mode only, whereas, ACI 35.3 has provisions for impulsive as well as convective modes. The quantification of design seismic action in these ACI standards is in a manner different from IBC 2. In order to bring these quantifications in conformity with IBC 2, FEMA 368 has suggested modifications to the base shear coefficient expressions of ACI standards. Prior to study of various provisions of ACI standards, it will be appropriate to review the modifications suggested by FEMA 368. Table 2 gives the details of base shear coefficient expressions of ACI 371 and ACI 35.3 along with the modified expressions of FEMA 368. From Table 2 it is seen that as per ACI standards, in velocity-critical range of spectra, the impulsive mode base shear coefficient, C s decreases as a function of 1/T 2/3. However, in FEMA 368, impulsive base shear coefficient, C s decreases as 1/T. For convective mode base shear also similar difference can be noted. To have a better understanding of modifications proposed by FEMA, a comparison of base shear coefficient obtained from ACI 371 expression and one obtained from the modified expression of FEMA368 is shown in Figure 3. The base shear coefficient values shown in Figure 3, correspond to the most sever zone of ACI 371 and equivalent seismic conditions of FEMA 368. It is seen that in short period range ( T <.6 s), base shear coefficient values of FEMA368 are about 12% higher than one obtained from ACI 371. In the long period range, values obtained from both the expressions match well. It may be noted that in the ACI 371, the importance factor does not appear in the expression for base shear coefficient, whereas, FEMA368 modification has introduced an importance factor I =1.25. Similarly, comparison of base shear coefficient of impulsive mode obtained from the expression of ACI 35.3 and the one modified by FEMA 368 IITK-GSDMA-EQ1-V1. 6
7 is shown in Figure 4a. These results are for the most severe zone of ACI 35.3 and FEMA 368. It may be noted that in ACI 35.3 value of response modification factor, R w is in the range of 2. to 4.75, whereas in FEMA 368, R varies in the range of 1.5 to 3.. In Figure 4a, base shear coefficients are shown for the lowest and the highest values of response modification factor. It is seen that for the highest value of response modification factor (i.e. R w = 4.75 and R = 3.), base shear coefficient from both the expressions match well. For the lowest value of response modification factor (i.e. R w = 2. and R = 1.5), results of FEMA 368 are on lower side by 15%. In Figure 4b, base shear coefficient corresponding to convective mode is compared. For T > 2.4 s, ACI 35.3 and FEMA 368 expressions give same values of convective base shear coefficient. 3.1 ACI 371 (1998) This ACI standard provides recommendations for evaluating design seismic forces on concrete pedestal supported elevated tanks. With FEMA modifications, the base shear is given by V = C s.w, where W is the summation of weight of water, container and support structure above the base. The base shear coefficient C s is given by SD s = for T s < T < 4 s (1) (R / I)T C 1 4S D1 C s = for T 4 s (2) 2 (R / I)T SDS Cs and Cs.2S DS (3) (R / I) The quantities, S DS, S D1, R, I and T are same as defined in IBC 2 and T s = S D1 /S DS. FEMA 368 states that except for the above stated modifications, concrete pedestal supported elevated tanks should be designed as per provisions of ACI 371. In this ACI standard, a load factor of 1.1 is given for strength design method, as opposed to unity in IBC 2. A closer look at the base shear formula mentioned above reveals that, this is same as one given in IBC 2 except for the minimum values of C s =.2 S DS (which is.14 S DS I in IBC 2) and a load factor of 1.1 for strength design. FEMA 368 specifies R = 2 IITK-GSDMA-EQ1-V1. 7
8 for pedestal supported elevated tanks. The ratio of base shear coefficient of tank obtained from ACI 371 (i.e. from Eqs. 1 to 3) and base shear coefficient of building (obtained as per IBC 2 with R = 8) i.e. BSC tank / BSC bldg is plotted in Figure 5. The ratio of tank to building base shear coefficient as obtained from IBC 2 is also shown in Figure 5. It is seen that values of base shear coefficient obtained from ACI 371 are higher than the one obtained from IBC 2. The higher value of base shear coefficient as per ACI 371 is due to a load factor of 1.1 and higher value of lower bound limit. ACI 371 does not give details about convective mass component, and recommends its consideration if water weight is less than 8 percent of the total gravity load of tank. 3.2 ACI 35.3 (21) ACI 35.3 gives procedure for seismic design of liquid containing concrete tanks, with detailed description of impulsive and convective components. It mainly deals with ground supported concrete tanks and limited information on pedestal supported elevated tanks is also provided. Considering the modifications suggested by FEMA 368, the base shear coefficient for impulsive mode, is given by (C ) s i SDs (.6 Ti +.4SDS) T = for < T i <T (4) 1.4(R / I) = S DS for T T i < T s (5) 1.4(R / I) = SD1 1.4(R / I)T i for T i T s (6) T =.2S DS /S D1 and T i is time period of impulsive mode. All other parameters are as defined in earlier sections. Similarly the base shear corresponding to convective component is given by V c = (C s ) c W c, where W c is convective mass and base shear coefficient, (C s ) c is given by 6S D1I (C s ) c = 2 T c for all values of T c (7) IITK-GSDMA-EQ1-V1. 8
9 Here, T c is the time period of convective mode. In convective mode, damping is taken as.5%. It is relevant to note that response modification factor, R does not appear in the expression for convective mode base shear coefficient. This implies that value of R is taken as unity i.e. convective base shear corresponds to pure elastic response. Variation of base shear coefficient for impulsive and convective modes with time period is shown in Figure 6. Since ACI 35.3 forces correspond to working stress design, they were multiplied by 1.4 to bring the forces to the level of strength design or ultimate load design. It may be noted that FEMA 368 suggests importance factor, I =1.25 for tanks and there is no lower bound limit on base shear coefficient in eqs. 4 to 6. In Figure 7, ratio of base shear coefficient of impulsive mode and base shear coefficient of a building i.e. BSC tank / BSC bldg is plotted. The base shear coefficient of building is obtained as per IBC 2 with R = 8. It is seen up to T = 2 s, for a tank with R = 1.5, design base shear is 7 times higher than that of a building. However, for longer time period (i.e. T > 2 s), severity of tank shear as compared to that of a building reduces. This is due to the fact that for tanks no lower bound on design seismic force has been defined in ACI 35.3, whereas IBC 2 specifies a lower bound on design seismic force for buildings. For convective mode, ACI 35.3 and FEMA 368, specify.5% damping and for impulsive mode damping is 5%. Convective mode period is usually grater than 2. sec and hence from eq. (6) and (7) it is seen that convective mode spectrum (.5% damping) is 8.4R/T times higher than impulsive mode spectrum (5% damping). 4. AWWA STANDARDS American Water Works Association (AWWA) standards provide guidelines for design and manufacturing of different types of water storage tanks. AWWA D-1 (1996) deals with welded steel tanks, AWWA D-13 (1997) is for factory-coated bolted steel tanks. Similarly, AWWA D-11 (1995) deals with wire- and strand- wound, prestressed concrete water tanks and IITK-GSDMA-EQ1-V1. 9
10 AWWA D-115 (1995) is for prestressed concrete water tanks with circumferential tendons. All these AWWA standards deal with circular tanks only and quantification of seismic loads provided in them is in a fashion different from IBC 2. To bring these quantifications in line with IBC 2, FEMA 368 and its commentary (FEMA 369), has provided modifications to the expressions for base shear coefficients of these AWWA standards. The provisions of these AWWA standards will be discussed along with the modifications of FEMA AWWA D-1 (1996) and D-13 (1997) AWWA D-1 and AWWA D-13 deal respectively with welded steel tanks and factory-coated bolted steel tanks. AWWA D-1 has provisions for ground supported as well as elevated water tanks, whereas AWWA D-13 has provisions for ground-supported tanks only. Provisions of AWWA D-1 and D-13 for seismic design of ground-supported tanks are identical. First the provisions for ground-supported tanks will be discussed Ground supported tanks In Table 3, expressions for base shear coefficients for ground-supported tanks as given in AWWA D-1 and D-13 are given along with the modified expressions of FEMA 368. It is seen that for ground supported steel tanks, both impulsive and convective modes are considered. For impulsive base shear a constant value independent of time period is given. Since ground supported steel tanks will mostly have time period in the constant-acceleration range of spectra, hence it suffices to mention the constant value. It may be noted here that AWWA D-1 specifies the base shear coefficient for working stress design and hence the modified expression given in FEMA 368 contains a factor of 1.4 in the denominator. In AWWA standards, importance factor I is taken as I = Further in AWWA D-1, the response reduction factor, R w varies in the range from 3.5 to 4.5, whereas in FEMA 368, it varies from 2.5 to 3.. To have better understanding of modifications suggested by FEMA 368, it will be appropriate to compare the numerical values of base shear coefficients IITK-GSDMA-EQ1-V1. 1
11 obtained from AWWA D-1 and FEMA 368. In the most severe zone of AWWA D-1, for the lowest and highest value of response reduction factor (i.e. R w = 3.5 and 4.5) the impulsive base shear coefficient turns out to be.36 and.28 respectively. The corresponding values of base shear coefficient as per the modified expression of FEMA 368, are.357 and.298 respectively. The parameters of most sever zone of AWWA D-1 are: Z =.4, S = 1.5 and soil type C. The equivalent parameters of FEMA 368 are: S s = 1.5, S 1 =.6, F s = 1., F v = 1.5, S DS = 1., S D1 =.6, T s =.6, site class D. Regarding the convective mode base shear coefficient it is interesting to observe that in AWWA D-1, convective mode base shear coefficient depends on the response reduction factor. It may be noted that in the provisions of ACI 35.3, the convective base shear is independent of response reduction factor. A comparison of convective base shear coefficient obtained from AWWA D-1 and FEMA 368 for the lowest and highest values of response reduction factor is shown in Figure 8. It is seen that the values obtained from AWWA D-1 expressions are on much higher side. It appears that due to modified expressions of FEMA 368, the convective base shear values have reduced. It is relevant to note here that, as per FEMA 368, the modified expression for convective base shear contains a factor of 1.4 in the denominator to bring the base shear values to working stress level. In this context, one may observe that while suggesting modified expression for convective base shear of ACI 35.3, which is also based on working stress method, FEMA 368 did not use a factor of 1.4 (Table 2). Thus, while modifying the convective base shear expression of AWWA D-1, if a factor of 1.4 is not used in FEMA 368, then the results of AWWA D-1 and FEMA 368 will match well Elevated Tanks For elevated tanks, AWWA D-1 does not consider sloshing effect, and only the impulsive mode is considered. The impulsive base shear is given by V = C s.w, where, W is the summation of weight of water, container and support structure above the base. The expression for base shear coefficient of elevated tank is given in Table 3, along with the modified expression from FEMA 368. It IITK-GSDMA-EQ1-V1. 11
12 is seen that as per AWWA D-1, response reduction factor for elevated tank is in the range of 3. to 4., whereas in FEMA 368 it varies from 2. to 3.. A comparison of the base shear coefficient obtained from AWWA D-1 and FEMA 368 is shown in Figure 9. These results correspond to the most sever zone and are for the lowest and highest values of response reduction factors. In the short period range (i.e., T <.6 s) base shear coefficient corresponding to the highest response factor (i.e., Rw = 4 and R = 3) match well. However, for the lowest value of response reduction factor, the FEMA 368 results are on lower side by 15%. In the long period range (i.e., T >.6 sec), FEMA 368 results are on lower side. The modified expression for base shear given in FEMA 368, is in the same fashion as that of IBC 2. In figure 1, the base shear coefficient of elevated tank obtained from the modified expression of FEMA 368, is compared with the base shear coefficient of a ductile building (with R = 8, I = 1. as per IBC 2). In this figure, the ratio of BSC tank /BSC bldg is plotted for two values of response reduction factor of tanks, i.e., R = 2 and 3.. Since IBC 2 provisions correspond to strength design, the FEMA 368 values of base shear coefficient are multiplied by 1.4 to bring them to strength design level. It is seen that base shear of elevated tanks is about 3 to 5 times higher than that of a building up to T = 1.5 sec. In the long time period range, i.e. T > 1.5 sec, the ratio of tank to building base shear reduces which is due to no lower bound limit on tank base shear in the long period range. 4.2 AWWA D-11 (1995) AWWA D-11 and AWWA D-115 deal with ground supported prestressed concrete tanks, but since their provisions for seismic design are quite different, these two standards will be discussed separately. First, provisions of AWWA D-11 are discussed, and the next section will describe provisions of D-115. Expressions for impulsive and convective base shear coefficients, as per AWWA D-11 are given in Table 4, along with the modified expressions of IITK-GSDMA-EQ1-V1. 12
13 FEMA 368. The base shear coefficients given in AWWA D-11 correspond to working stress method. A comparison of the impulsive base shear coefficient from AWWA D-11 expressions and modified expression of FEMA 368, is shown in Figure 11a. This comparison is shown for the highest and lowest values of response reduction factors. As per AWWA D-11, the values of response reduction factor are in the range of 2. to 4.5, whereas in FEMA 368 these values are in the range of 1.5 to 3.. It is seen that for the highest value of response reduction factor (i.e., R w = 4.5 and R = 3.), base shear coefficient values from AWWA D-11 and FEMA 368 match well in the short period range (i.e., T <.6 sec). However, for the lowest value of response reduction factor (i.e., R w = 2. and R = 1.5), base shear coefficient values from FEMA 368 is 15% less than that of AWWA D-11. In the long period range (i.e., T >.6 sec), base shear coefficient values obtained from FEMA 368 are on lower side for the highest as well as lowest response reduction factor. Regarding the modified convective base shear expressions of FEMA 368, there are certain inconsistencies. As per AWWA D-11, convective base shear coefficient does not depend on response reduction factor (i.e., R c = 1. for all types of tanks). In section of FEMA 368, on page no. 311 it is mentioned that the modified convective base shear coefficient shall be taken as 6S I ( Cs) c =. However, on page no. 312 it is stated that the modified T D1 2 c convective base shear is given by V 6S I D1 c = 2 1.4RTc Wc. Clearly there is inconsistency in the two expressions, second one considers a factor of 1.4R in the denominator and the first one does not. Further, in FEMA 369 (pp 366), which is commentary to FEMA 368, the modified base shear expression is also given as 6S I ( Cs) c =. Since in AWWA D-11 the convective base shear T D1 2 c coefficient does not depend on response reduction factor, in Table 4, the modified base shear coefficient is taken as 6S I ( Cs) c =. A comparison of T D1 2 c IITK-GSDMA-EQ1-V1. 13
14 convective base shear coefficient obtained from AWWA D-11 and FEMA 368 is shown in Figure 11b. It is seen that base shear coefficient values obtained from FEMA 368 about 1.5 times higher than those obtained from AWWA D- 11. Impulsive base shear coefficients given by the modified expressions of FEMA 368 are in line with those given by IBC 2 for buildings. Hence these expressions of FEMA 368 can be used to compare the base shear coefficient of tank with that of a ductile building (R = 8 and I =1 as per IBC 2). Such a comparison is shown in Figure 12, wherein, ratio of BSC tank /BSC bldg is plotted for three different values of response reduction factor of tanks. While plotting these results, the base shear coefficient of tank is multiplied by 1.4 to bring them to strength design level. Again, due to absence of a lower bound limit on base shear coefficient of tanks, the values of BSC tank /BSC bldg decreases in long period range, i.e., for T > 2. sec. 4.3 AWWA D-115 (1995) This AWWA standard deals with circular prestressed concrete tanks with circumferential tendons. Expressions for impulsive and convective base shear coefficients are given in Table 5 along with the modified expressions of FEMA 368. It will be appropriate to note the differences in the base shear coefficient expressions of AWWA D-11 and AWWA D-115. In AWWA D-115, the response reduction factor varies from 1. to 3. whereas in AWWA D-11 it varies from 2. to A comparison of impulsive base shear coefficient obtained from AWWA D-115 and modified expression of FEMA 368 is shown in Figure 13, for extreme values of response reduction factors. It is surprising to observe a large difference in the base shear coefficient values obtained from these two expressions. The values obtained from FEMA 368 expressions are on lower side and there appears to be some inconsistency in the expressions of AWWA D-115 and the modified expression of FEM 368. In this context, it is to be noted that FEMA 368 suggests same modified expression for impulsive base shear IITK-GSDMA-EQ1-V1. 14
15 coefficient of AWWA D-11 as well as AWWA D-115. Thus as per FEMA 368, the values of response reduction factor are identical for AWWA D-11 as well as AWWA D-115. However, as pointed out earlier, response reduction factor values in AWWA D-11 and AWWA D-115 are quite different. Thus, it appears that while suggesting the modified base shear expressions, FEMA 368 has not considered this difference in the range of values of response reduction factors of AWWA D-11 and D-115. Another major inconsistency noted is that in AWWA D-115 convective base shear coefficient depends on response reduction factor, whereas in FEMA 368 the corresponding modified expression does not have any dependence on response reduction factor. Due to this, it is not possible to compare the convective base shear coefficient values obtained from AWWA D-115 and FEMA 368. Again it may be noted that the FEMA 368 expression for convective base shear coefficient is same for AWWA D-11 and D-115, and in AWWA D- 11 also convective base shear does not depend on response reduction factor. It is quite clear that due to the inconsistencies mentioned above, no comparison can be done between the impulsive base shear coefficient of tank obtained from modified expression from FEMA 368 and the base shear coefficient of building. Thus, a review of provisions of AWWA standards and their corresponding modifications in FEMA 368 reveals quite a few inconsistencies and contradictions. These are summarized below: (a) In AWWA D-1 and D-115 convective base shear coefficient depends on response reduction factor whereas, in AWWA D-11 this coefficient does not depend on response reduction factor. (b) Though AWWA D-11 and D-115 deal with prestressed concrete tanks, they use quite different values of response reduction factors. Moreover, in the modified expression of FEMA 368, only one range of value of response reduction factor is suggested for AWWA D-11 and D-115. This led to a large difference in the values of base shear coefficients obtained from AWWA D-115 and FEMA 368. IITK-GSDMA-EQ1-V1. 15
16 (c) In AWWA D-115, convective base shear depends on response reduction factor, however, the base shear given by the corresponding modified expression of FEMA 368 does not depend on response reduction factor. (d) All AWWA codes are based on working stress method. While modifying the convective base shear coefficient of AWWA D-1, the FEMA 368 has considered a factor of 1.4 in the expression; however this factor is not present in the modifications suggested for AWWA D-11 and D-115. In this context it may be noted that ACI 35.3 is also based on working stress method, and while modifying its convective base shear expression, FEMA 368 has not considered a factor of 1.4 in the expression (Table 2). 5. API 65 (1998) American Petroleum Institute (API) has two standards namely, API 65 and API 62 which provide provisions for design and construction of petroleum steel tanks. These API standards deal with ground supported circular steel tanks only. The seismic design provisions in these API standards are identical and hence provisions of only API 65 are described here. API 65 considers impulsive as well as convective component in the seismic analysis. The base shear corresponding to impulsive and convective components is respectively given by V i = C i W i and V c = C c W c. Here, W i and W c are impulsive and convective masses respectively and likewise, C i and C c are base shear coefficients corresponding to these components. In API 65, quantification of base shear coefficients is in a manner different than IBC 2. Hence, FEMA 368 has suggested modifications to base shear coefficients of API 65, to make them consistent with IBC 2. Table 6 provides details of base shear coefficients given in API 65 along with the modified expressions given by FEM 368 For impulsive mode, the base shear coefficient is defined as a constant value which does not depend on the time period. It may be recognized here that ground supported steel tanks will generally have time period in the constant-acceleration range of spectra and hence it suffices to specify the IITK-GSDMA-EQ1-V1. 16
17 magnitude of the spectra in constant-acceleration range. It may be recalled here that AWWA D-1 has also specified a constant value of base shear coefficient for ground supported steel tanks. In API 65 and FEMA 368 the value of importance factor is taken as API 65 prescribes seismic forces at working stress level, and they are to be multiplied by a factor of 1.4, to bring them strength design level. Thus, as per API 65, C i =.84 ZI and as per FEMA 368, at strength design level, C i =.336S DS I, which when compared with IBC 2 expression (i.e. S DS I/R), implies that for ground supported steel tanks, R = For the most severe zone of API 65, Z =.4 and for S3 type site, S = 1.5. For equivalent seismic condition, parameters from FEMA 368 will be S D = 1.5, F a = 1., S 1 =.6 and F v = 1.5, S DS = 1., with site class D. For these parameters, the value of C i, at strength design level, will be.42 from API 65 as well as FEMA 368. This value of base shear coefficient is about 3.4 times higher than the value of base shear coefficient of a building (obtained as per IBC 2 with R = 8). Comparison of convective mode base shear coefficient, at strength design level, obtained from API 65 and FEMA 368 is shown in Figure 14. It is seen that FEMA 368 results are about 2% less than those of API EUROCODE 8 (1998) Five parts of Eurocode 8 (1998) cover provisions for seismic design of various types of civil engineering structures. Part-4 of Eurocode 8 deals with tanks, silos and pipelines. This code describes in detail about dynamic modeling of convective and impulsive components, and also discusses other aspects like base uplifting of unanchored tanks, soil-structure interaction etc. The seismic action is specified in terms of response spectrum. In this code, behavior factor, q, accounts for energy dissipation capacity of the structure, mainly through ductile behavior and other mechanisms. For elastic structures, q = 1. and for structures with good energy dissipation capacity, q = 5.. Eurocode 8 specifies two types of response spectrum, first one is elastic spectrum, S e (T), (for q =1.) and second is spectrum for linear analysis, S d (T), (for IITK-GSDMA-EQ1-V1. 17
18 q > 1.). For tanks on ground, elastic spectrum is to be used, i.e., behavior factor, q = 1.. For buildings with ductile frames, behavior factor q can be as high as q = 5., and spectrum for linear analysis is used. Seismic base shear for building is given by V = γ I S d (T) W, where, γ I is the importance factor and S d (T) is the spectrum acceleration at time period T. Expression for base shear of tank is same as that of building, except that instead of spectrum for linear analysis S d (T), elastic spectrum S e (T) is to be used. The expressions for elastic spectrum and spectrum for linear analysis are given in Table 7. A closer look at these expressions reveals that elastic spectrum depends on damping correction factor η, whereas, spectrum for linear analysis does not depend on η. Further, it can be seen that there is a lower bound limit on values of spectrum for linear analysis in long period range. There is no such lower bound limit on elastic spectrum. It may be noted that Eurocode 8 provides indicative values of behavior factor, q and various parameters defining shape of spectrum. However, there is no indication on maximum value of design ground acceleration, a g, which corresponds to a reference return period of 475 years. It mentions that National Authorities of the member countries should arrive at suitable values of a g for various seismic zones. In the present study, value of a g =.3g (i.e., α =.3) is assumed. Figure 15 shows variation of base shear coefficient with time period for ductile building (q= 5.) and impulsive mode of tank. These results correspond to S =1., β = 2.5, η= 1., K 1 =1., K 2 =2., K d1 =2/3, K d2 =5/3, T B =.15, T C =.6 T D = 3. and α =.3. For buildings, γ I =1. and γ I =1.2 for tanks with high risk to life, and large environmental, economic and social consequences. Sub soil class B is considered which is similar to site class D of IBC 2. In Figure 15, base shear coefficient for convective mode with.5% damping is also shown. It is to be noted that for buildings, i.e., when spectrum for linear analysis is used, there is a lower bound limit on spectrum values, however for elastic spectrum no such limit is specified. Further, it is important to note that shapes of S e (T) and S d (T) are also different beyond T = T B. Elastic spectrum, S e (T) reduces much faster with time period than spectrum for linear analysis, S d (T). Hence, for higher time IITK-GSDMA-EQ1-V1. 18
19 periods (T>.6 s), the difference between base shear of tank and building is reduced considerably. This is clearly seen from Figure 16, wherein ratio BSC tank / BSC bldg is plotted. Eurocode 8 specifies only one value of q (= 1.) for ground-supported tanks. Neither it mentions about different types of groundsupported tanks nor does it give specific values of q for different types of ground-supported tanks. However, it states that if adequately demonstrated, inelastic response (i.e., q > 1) can be considered. For elevated tanks also, Eurocode 8 does not give very specific values of q. It mentions that supporting structure may be designed to respond beyond the yield level, thereby allowing energy dissipation in it. Elevated tanks with simple support and which have little risk to life, negligible environmental and social consequences due to failure, will have the value of q = 2.. For elevated tanks under higher risk category, the selected value of q should be properly substantiated and proper ductility be provided through ductile design of supporting structure. For convective mode, in all types of tanks, the value of behavior factor, q =1. and damping value, ξ =.5% is suggested. For this value of ξ, the damping correction factor η is As a result of this, elastic spectrum corresponding to convective mode (.5% damping) turns out to be times higher than that for impulsive mode (5% damping). 7. NZSEE GUIDELINES AND NZS 423 :1992 In New Zealand, seismic design of liquid storage tanks follow NZSEE s document (Priestley, et. al., 1986). A study group of NZSEE is presently revising this document to bring it in line with the NZS 423:1992, the New Zealand loading code for buildings. Details of the proposed seismic loading are given by Whittaker and Jury (2). This section discusses the proposed seismic loading along with the seismic loading provisions for building in NZS 432:1992. As per NZS 423:1992, seismic base shear for building is given by V = CW, where, lateral force coefficient or base shear coefficient, C is given by IITK-GSDMA-EQ1-V1. 19
20 C = C h (T, μ ) S p R Z L u (7).3 where C h (T, μ) = Basic seismic hazard coefficient which accounts for different soil conditions, ductility factor μ and natural period T of building, S p = Structural performance factor. For buildings S p =.67 R = Risk factor. For ordinary buildings R =1. Z = Zone factor as per seismic map L u = Limit state factor for ultimate limit state. L u = 1. NZS 423:1992 has provided tabulated values of C h (T, μ ) for three different soil conditions, eight different values of μ ( from μ = 1. to 1.) and values of time period T from T =. to 4. sec. For buildings with ductile frames the value of μ could vary from μ = 6 to1. As per Whittaker and Jury (2), seismic base shear for tanks is V=CW, where C = C h (T, 1) S p R Z L u ) C f (μ, ξ ) (8) Eq.(8) differs from Eq.(7) in two ways: First, basic seismic hazard coefficient, C h (T,1) corresponds to μ =1., i.e., purely elastic spectrum is used and secondly, an additional factor, C f (μ,ξ) termed as correction factor is included. This correction factor accounts for ductility and level of damping. For tanks, performance factor S p =1. is recommended as opposed to.67 for buildings. Value of risk factor, R for tanks is arrived at by considering four aspects, namely, risk to number of persons, risk to environment, community significance of the tank and value of adjacent property. Value of R can vary from.5 to 1.6 depending on the risk associated with the tank and a tank with serious risk has R = 1.3. The value of damping depends on material of tank shell and supporting soil. Whittaker and Jury (2) have provided values of ductility factor, μ for different types of tanks, which are shown in Table 8. Similarly, damping level, ξ for different types of concrete and steel tanks are also provided. Further, provisions are made for increasing the damping values of tank depending on flexibility of supporting soil, i.e., to consider radiation IITK-GSDMA-EQ1-V1. 2
21 damping in soil. For different values of ductility factor, μ and damping level, ξ, values of correction factor C f (μ, ξ ) are provided as shown in Table 9. For three different values of C f, namely, C f =.72,.54 and.38, variation of base shear coefficient with time period is plotted in Figure 17. These results are for the most severe zone (Z =1.2) and site subsoil category (C), i.e., flexible and deep soil condition, which is similar to site class D of IBC 2. Also plotted in this figure is the variation of base shear coefficient for a building with μ = 6.. It would be appropriate to note that variation of C h (T,6) and C h (T,1) with time period is of different nature. This gets reflected in the variation of base shear coefficient of tanks and building with time period. For T >.6s, reduction in C h (T,1) with time period is slower than corresponding reduction in C h (T,6). This implies that elastic spectrum (C h (T,1)) is more flatter than inelastic spectrum (C h (T,6)). Moreover values of C h (T, 1) and C h (T,6) at various time period do not have a constant ratio. From the ratio of BSC tank / BSC bldg shown in Figure 18, it is seen that the ratio of base shear coefficients increases at around T=.6s, then remains almost constant up to T=3.s and for T>3.s it starts decreasing. The increase is due to the fact that values of C h (T, 6) (i.e. for building) and C h (T, 1 ) (i.e., for tank) are not in same proportion for values of T from.6-3.s. The decrease in ratio of base shear for higher value of T (i.e., T > 3.s) is due to the fact that there is a lower bound on value of C (i.e., C can t be less than.3) for buildings, but for tanks (i.e., elastic case of μ =1.) there is no such lower bound limit. For elevated tanks, Whittaker and Jury (2) do not provide specific information on ductility factor, μ. However, it mentions that for elevated tanks, ductility factor as appropriate for support structure should be considered. This may imply that if supporting structure is quite ductile then value of μ can be as high as for buildings (i.e., μ = 6 to 1). At the same time it should be noted that in Table 9, values of response modification factor, C f is given only for maximum value of μ = 4., i.e., for values of μ greater than 4., response modification factor is not available. IITK-GSDMA-EQ1-V1. 21
22 Whittaker and Jury (2) have specified.5% damping for convective mode. Thus, in Table 9, values of C f (μ,ξ) corresponding to ξ =.5, can be used for convective mode. These values of C f (μ,ξ) change with ductility factor, μ, implying that convective mode base shear will vary with ductility of tank. It may be noted that in AWWA D-1 also convective base shear depends on ductility of tank i.e. on response reduction factor. However, in ACI 35.3 and Eurocode 8, convective mode shear does not depend on ductility of tank and it corresponds to pure elastic case, i.e., R = 1, and q =1., respectively. 8. COMPARISON OF DESIGN FORCES FROM VARIOUS CODES In the previous sections provisions related to base shear coefficients for tanks as given in various codes, standards and guidelines are described. It will be interesting to compare base shear coefficients obtained from these documents. Before comparing the results for tanks, a comparison of base shear coefficient for a ductile building is shown in Figure 19. In this figure, base shear coefficients of building (BSC bldg ), obtained from IBC 2, Eurocode 8 and NZS 423:1992 are shown. These results correspond to the most severe zone of each code. It is seen that in the short period range (i.e., T=.1-.6s), results from Eurocode 8 and NZS 423 match well. In this short period range, IBC 2 results are on lower side by about 15%. Further, all the three codes have different shape of spectra in constant-velocity range (i.e., T>.6s). Moreover, magnitude of the lower bound limit on spectra is also seen to be different in these codes. To obtain similar comparison for tanks, first of all, for a particular type of tank, all the relevant parameters (such as R, q, C f ) from different codes will have to be identified. It is seen that most of the codes consider ground supported unanchored concrete water tank as a low ductility tank or a tank with low energy absorbing capacity. For such a tank the relevant parameters will be as shown in Table 1. In Figure 2, comparison of base shear coefficient for this tank (BSC tank ) obtained from different codes is shown. It may be noted here that FEMA 368 has modified the base shear expressions of ACI 35.3 and AWWA D-11 and brought them in line with IBC 2. In view of these IITK-GSDMA-EQ1-V1. 22
23 modifications, parameters from ACI 35.3, AWWA D-11 and IBC 2 are same. From Figure 2 it is seen that in the short period range (T<.6s), Eurocode 8 results are 1% higher and NZSEE results are 35% higher than the one obtained from IBC2. Further, it can also be seen that except for IBC 2, no other code has lower bound limit on base shear coefficient in long period range. Comparison of ratio of base shear coefficient of tank and building (BSC tank /BSC bldg ) is shown in Figure 21. Here, base shear coefficient of tank from a particular code is divided by corresponding base shear coefficient of a ductile building. It is seen that from T=.1-.6s, this ratio is constant for all the codes. This constant value is 6 for Eurocode 8 and for IBC and NZSEE it is 6.7 and 7.3 respectively. The decrease in the value of this ratio for T>.6s for the case of Eurocode 8, is due to difference in shapes of spectrum used for tank and building. Another factor contributing to this decrease, particularly in higher period range, is absence of lower bound limit on spectral values for tanks. The decrease in the value of this ratio in long period range, for NZSEE, ACI 35.3 and AWWA D-11 is also attributed to similar reasons. For the case of IBC 2, due to lower bound limit on spectral values for tanks, the ratio of tank to building shear does not fall below the value of 4, even in long period range. Results similar to one presented in Figure 21, can be obtained for a high ductility tank, i.e., a tank with high energy absorbing capacity. For such a tank, various parameters of different codes are given in Table 11. These parameters can as well be applicable to some of the elevated tanks. For Eurocode 8, value of q = 2 is considered, which is suggested for a low risk category elevated tank with simple type of supporting structure. Results on ratio of base shear coefficient of tank to building, (BSC tank / BSC bldg ), are shown in Figure 22. It is seen that maximum value of this ratio is about 3 to 4 in all the codes, as against a value of 6 to 7 for low ductility tanks. This implies that design base shear for a low ductility tank is double that of a high ductility tank. Variation in the ratio of base shear of tank and building, in the higher time period range is seen in Figure 22 also, which is due to reasons discussed earlier. IITK-GSDMA-EQ1-V1. 23
24 On similar lines, comparison of convective base shear coefficients obtained from various codes is shown in Figure 23. Before looking into this results it will be appropriate to recognize that as per AWWA D-1, AWWA D- 115 and NZSEE (i.e., Whittaker and Jury (2)), the convective base shear coefficient depends on response reduction factor or ductility factor. However, as per ACI 35.3, AWWA D-11, API 65 and Eurocode 8 the convective base shear coefficient does not depend on response reduction factor. The comparison shown in Figure 23 considers only those documents in which convective base shear coefficient does not depend on response reduction factor. Hence in Figure 23, results of ACI 35.3, AWWA D-11, API 65 and Eurocode 8 are shown. It can be seen that convective base shear coefficient obtained from Eurocode 8 and API 65 match well. However, ACI 35.3 gives very high values of convective base shear coefficient. For time period greater than 3.s, the results of ACI 35.3 are about 2.5 times higher than that of API PROVISIONS OF INDIAN CODE Indian Standard IS: provides guidelines for earthquake resistant design of several types of structures including liquid storage tanks. This standard is under revision and in the revised form it has been divided into five parts. First part, IS 1893 (Part 1):22, which deals with general guidelines and provisions for buildings has already been published. Second part, yet to be published, will deal with the provisions for liquid storage tanks. In this section, provisions of IS: for buildings and tanks are reviewed briefly followed by an outline of the changes made in IS 1893 (Part 1):22. In IS: , base shear for building is given by V = C s W, where, C s is the base shear coefficient given by C s = K C βi α o (9) Here, K = Performance factor depending on the structural framing system and brittleness or ductility of construction; C = Coefficient defining flexibility of structure depending on natural period T; β = Coefficient depending upon the soil-foundation system; I = Importance factor; α o = Basic seismic coefficient IITK-GSDMA-EQ1-V1. 24
25 depending on zone. For buildings with moment resisting frames, K = 1.. Importance factor, for buildings is usually I = 1.. IS: , does not have any provision for ground supported tanks. It has provisions for elevated tanks, for which it does not consider convective mode. Base shear for elevated tank is given by V = C s W, where, base shear coefficient, C s is given by C s = βi F o (S a /g) (1) Here, S a /g = average acceleration coefficient corresponding to the time period of the tank, obtained from acceleration spectra given in the code; F o = seismic zone factor; W = weight of container along with its content and one third weight of supporting structure. For elevated tanks, Importance factor I = 1.5. It may be noted that in the expression for base shear coefficient of tank, the performance factor K does not appear, i.e. K = 1 is considered, which is same as that for a building with ductile frame. This implies that in IS: , there is no provision to account for lower ductility and energy absorbing capacity of elevated tanks. Thus, as per IS: , base shear coefficient for tank will be only 1.5 times higher than that for a building, which is due to higher value of importance factor. This is in contrast to other codes, reviewed in earlier sections, wherein tank base shear coefficient is seen to be 3 to 7 times higher than buildings. This lacunae needs to be corrected in the next revision of the code. As mentioned earlier, IS 1893 is under revision and first part, of the revised code, IS 1893 (Part 1): 22, has already been published. In this revised code, base shear for building is given by V = C s W, and base shear coefficient C s is given by ZI Cs = (Sa / g) (12) 2R where Z = zone factor, I = importance factor, R = response reduction factor and S a /g = average response acceleration coefficient, obtained from acceleration spectra given in the code. For buildings with ductile frames value of R is 5. In Figure 24, a comparison of base shear coefficients for building obtained from IITK-GSDMA-EQ1-V1. 25
26 IS: and IS 1893 (Part I):22 is shown, along with the base shear coefficient from IBC 2. Since IS: , does not specify specific value of load factors for strength design, the results in Figure 24 are presented for working stress level. It is seen that base shear coefficient from IS: is lower than one from IS 1893 (Part I):22. Further, unlike IBC 2, there is no lower bound in IS 1893 (Part I):22 and IS: Subsequent parts of IS 1893:22, will be using acceleration spectra given in Part I, and will be based on same design philosophy. Thus, for liquid storage tanks, base shear coefficient will be given by Eq.(12), in which suitable values of R will have to be used for different types of tanks. From the review presented in earlier sections, it is seen that low and high ductility tanks have design base shear 3 to 7 times higher than ductile buildings. In Figure 25, base shear coefficients for low and high ductility tanks, from IBC 2 (i.e., tanks with R=1.5 and R=3.) are shown. To achieve this level of base shear coefficients the value of R in IS 1893 (Part 1):22 should be 1.1 and 2.25 as can be seen from Figure 25. Also shown in this figure is the base shear coefficient for tank obtained from IS: , which is on much lower side. Based on the comparison shown in Figure 25, proposed values of R which can be used in IS 1893 (Part 2):22 for different types of tanks, are given in Table DISCUSSION Due to low ductility and energy absorbing capacity, liquid storage tanks are generally designed for higher seismic forces as compared to conventional buildings. In this article, provisions of various codes on design seismic forces for tanks are reviewed. It is found that there is considerable variation in the types of tanks described in various codes. For example, ground supported tanks described in IBC 2, ACI 35.3, AWWA D-11 and NZSEE guidelines are having different types of base conditions. Eurocode 8 does not provide any details about base supports of ground-supported tanks. Provisions on elevated tanks are described in IBC 2, ACI 371, ACI 3.3, AWWA D-1, Eurocode 8 and IITK-GSDMA-EQ1-V1. 26
27 NZSEE guidelines. Less information is available on energy absorbing capacity of different types of supporting towers of elevated tanks. Less frequent use of elevated tanks in these countries may be one reason for low emphasis on elevated tanks in these codes. All the codes, consider impulsive and convective modes of vibration in the seismic analysis of ground-supported tanks. The level of design seismic force for a particular tank obviously depends on its ductility and energy absorbing capacity. It is observed that for a tank with low ductility, impulsive base shear coefficient (ratio of lateral force to weight) is 6 to 7 times higher than the base shear coefficient of a ductile building; and for a high ductility tank this value is 3 to 4 in all the codes (Figures 21 and 22). However, this is so only for tanks with short time period (i.e., T<.6s). Beyond this short period range, there is considerable difference in the values of BSC tank /BSC bldg. For example, at T=1.5s, for a tank with low ductility, the value of BSC tank /BSC bldg, as per NZSEE guideline is 8.2 and as per IBC 2 and Eurocode 8 this value is 6.7 and 4.4, respectively. Thus, Eurocode 8 results are on lower side by almost 5%. In fact, beyond T=.6s, as per Eurocode 8, the value of BSC tank /BSC bldg, decreases continuously, which is due to two reasons. First, in Eurocode 8, elastic spectrum (used for tank) has much faster reduction with time period than spectrum for linear analysis (used for buildings) in the constant-velocity range. Secondly, unlike for buildings, there is no lower bound limit on spectrum used for tanks. In NZSEE guidelines [i.e., NZS 423:1992 and Whittaker and Jury (2)] the elastic spectrum (used for tanks) reduction with time period is slower than inelastic spectrum (used for buildings). Due to this reason, the NZSEE results in Figure 21, show a slight increase in the value of BSC tank /BSC bldg at T=.6s. In IBC 2, spectra used for tank and building, have same shape in constantvelocity range. Further, IBC 2 specifies, lower bound limits on spectral values for buildings as well as tanks. Hence, as per IBC 2, values of BSC tank /BSC bldg, do not fall below four even in the long period range. In case of ACI 35.3 and AWWA D-11 also, there is no lower bound specified on IITK-GSDMA-EQ1-V1. 27
28 spectral values for tanks. This, as explained earlier, leads to loss of severity of tanks shear in long period range as compared to that of buildings (Figures 21 and 22). The reason for providing a lower value of response reduction factor for tanks is their low ductility and low energy absorbing capacity as compared to buildings. However, it is seen that in many codes, due to non-availability of lower bound limit on spectral values of tanks, the ratio of tank to building base shear reduces in long period range. ACI 371, which deals with shaft supported elevated tanks, is a good example on provision of lower bound limit on spectral values. Due to availability of suitable lower bound limit in ACI 371, the value of BSC tank /BSC bldg does not reduce even in long period range (Figure 5). Thus, there is a need to provide suitable lower bound limit on spectral values of tanks in other codes. Absence of such a lower bound limit can lead to nonconservative estimate of base shear for tanks with longer time period, particularly the elevated tanks on flexible supports. For the case of ground supported steel tanks, API 65 and AWWA D-1 specify a constant value of base shear coefficient, which does not depend on time period. For steel tanks, it is quite likely that impulsive time period will be in the constant-acceleration range of spectra, and hence it suffices to specify this constant value of base shear coefficient. However, in IBC 2, the base shear coefficient for ground supported steel tanks is not defined as a constant value. Further, as per AWWA D-1 and IBC 2, response reduction factor for ground supported steel tanks changes with type of base support provided. However, in API 65, tanks with different types of base supports are not described. As per API 65, the base shear coefficient for ground supported steel tank is about 3.4 times higher than that of a ductile building; and in AWWA D- 1 and IBC 2, depending on type of base support, the base shear coefficient of ground supported steel tank is 3 to 3.7 times higher. While considering the convective base shear, all the codes suggest a damping value of.5%. However, in the evaluation of convective base shear coefficient, considerable differences are seen in the provisions of various codes. IITK-GSDMA-EQ1-V1. 28
29 Firstly, as per ACI 35.3, API 65, AWWA D-11 and Eurocode 8, convective base shear coefficient does not depend on response reduction factor. However, as per AWWA D-1, AWWA D-115 and NZSEE guidelines (i.e. Whittaker and Jury (2)), convective base shear coefficient depends on response reduction factor. From the comparison presented in Figure 23, it is seen that base shear coefficient evaluated as per ACI 35.3 is about two and half times greater than the one obtained from AWWA D-11 and Eurocode 8. For the elevated tanks, AWWA D-1 does not recommend consideration of convective mode of vibration. However, Eurocode 8 and NZSEE guidelines recommend consideration of convective mode. At the same time, IBC 2 and ACI 371 suggest that convective mode need not be considered if certain conditions on weight of water and time period of convective mode are met with. As far as AWWA Standards are considered, there appears to be quite a few inconsistencies in them and also in the modifications suggested for them in FEM 368. These have been described in detail in section 4. There is a need to properly address these inconsistencies. In the context of Indian codes it is noted that design seismic forces for buildings, as per revised Indian code (i.e., IS 1893 (Part 1):22), compare well with those specified in IBC 2 (Figure 24). However, Indian code does not have a lower bound limit on spectral values for buildings, which otherwise is present in all the other codes. As far as liquid storage tanks are concerned, Indian scenario is bit different. In India, elevated tanks are quite commonly used in public water distribution systems and a large number of them are in use. These tanks have various types of support structures, like, RC braced frame, steel frame, RC shaft, and even masonry pedestal. Ground supported tanks are used mainly by petroleum and other industrial installations. For different types of elevated and base supports for ground-supported tanks, values of response modification factor, R, to be used in Indian code are proposed (Table 12). However, it is felt that for elevated tanks with different types of supporting structures, a detailed investigation is needed to ascertain IITK-GSDMA-EQ1-V1. 29
30 their energy absorbing capacity and ductility characteristics. Similarly, suitable values of lower bound limits on spectral values for buildings as well as other types of structures, including tanks, needs to be arrived at. 11. CONCLUSIONS Following conclusions are drawn from the comparative assessment of provisions of different codes on seismic design of liquid storage tanks: 1) There is no uniformity in types of tanks described in various documents. Most of the codes put emphasis on ground-supported tanks and very limited information is available on elevated tanks. 2) All the documents suggest consideration of convective and impulsive components in seismic analysis of tanks. 3) For a particular type of tank with short period (less than.6s), ratio of base shear of tank and building is almost same in all the codes. This ratio is 6 to 7 for low ductility tanks and 3 to 4 for high ductility tanks. However, for tanks with time period greater than.6s, there is a large variation in the values of this ratio obtained from different codes. For example, at time period of 1.5 sec, value of this ratio from Eurocode 8 is almost 5% less than the one obtained from NZSEE guidelines. This is attributed to the use of spectra of different shapes for buildings and tanks. 4) Unlike for buildings, most of the documents do not provide lower bound limit on spectral values for tanks. This results in decrease in the ratio of base shear of tank and building, in long period range. This effectively results in reduction in severity of tank base shear as compared to building base shear. 5) Suitable provisions for lower bound limit on spectral values for tanks are necessary. Only ACI 371, which deals with elevated tanks, and IBC 2 have provisions for lower bound limit on spectral values of tanks. 6) Convective mode base shear values obtained from API 65 and Eurocode 8 match well, however one obtained as per ACI 35.3 is 2.5 times higher than that of ACI IITK-GSDMA-EQ1-V1. 3
31 7) There are quite a few inconsistencies among different AWWA standards. These need to be resolved. Further modifications suggested by NEHRP recommendations (FEMA 368) to provisions of AWWA codes are also having certain inconsistencies. 8) Indian code needs to include provisions on lower bound limit on spectral values of buildings and tanks. Further, provisions for inclusion of convective mode of vibration in the seismic analysis of tanks also need to be included. Based on the review of various international codes presented in this paper, it is recommended that IS 1893 should have values of response reduction factor in the range of 1.1 to 2.25 for different types of tanks. Acknowledgements This work has been supported through a project entitled Review of Building Codes and Preparation of Commentary and Handbooks awarded to IIT Kanpur by the Gujarat State Disaster Management Authority (GSDMA), Gandhinagar through World Bank finances. The views and opinions expressed therein are those of the authors and not necessarily those of the GSDMA or the World Bank. References ACI 35.3, 21, Seismic design of liquid containing concrete structures, An American Concrete Institute Standard ACI 35, (21), Code requirements for environmental engineering concrete structures, An American Concrete Institute Standard ACI 371, 1998, Guide for the analysis, design and construction of concrete pedestal water towers, An American Concrete Institute Standard API 65, 1998, Welded storage tanks for oil storage, American Petroleum Institute Standard, Washington, DC AWWA D-1, 1996, Welded steel tanks for water storage, American Water Works Association, Colorado AWWA D-13, 1997, Factory-coated bolted steel tanks for water storage, American Water Works Association, Colorado AWWA D-11, 1995, Wire- and strand-wound circular, prestressed concrete water tanks, American Water Works Association, Colorado AWWA D-115, 1995, Circular prestressed concrete water tanks with circumferential tendons, American Water Works Association, Colorado IITK-GSDMA-EQ1-V1. 31
32 Eurocode 8, 1998, Design provisions for earthquake resistance of structures, Part 1- General rules and Part 4 Silos, tanks and pipelines, European committee for Standardization, Brussels FEMA 368, 2, NEHRP recommended provisions for seismic regulations for new buildings and other structures Part I: Provisions, Building seismic safety council, National Institute of Building Sciences FEMA 369, 2, NEHRP recommended provisions for seismic regulations for new buildings and other structures Part II: Commentary, Building seismic safety council, National Institute of Building Sciences. Hori,N., 199, Effect of soil on dynamic response of liquid-tank systems, Journal of Pressure Vessel Technology, ASME, 112, Housner,G.W., 1963, The dynamic behavior of water tanks, Bulletin of the Seismological Society of America, 53 (2), IBC 2, International Building Code International Code Council, 2, Falls Church, Virginia. IS 1893 (Part 1):22, Criteria for earthquake resistant design of structures, Bureau of Indian Standards, New Delhi. Malhotra,P.K., 1997, Seismic response of soil-supported unanchored liquidstorage tanks, Journal of Structural Engineering, ASCE, 123 (4), Malhotra,P.K., 2, Simple procedure for seismic analysis of liquid-storage tanks, Structural Engineering International, 3, NZS 423:1992, Code of practice for general structural design and design loading for buildings, New Zeeland. Priestley,M.J.N., et. al., 1986, Seismic design of storage tanks, Recommendations of a study group of the New Zealand National Society for Earthquake Engineering Veletsos,A.S., 1974, Seismic effects in flexible liquid storage tanks, Proceedings of Fifth World Conference on Earthquake Engineering, Rome Italy, 1, Veletsos,A.S., Tang,Y., and Tang,H.T., 1992, Dynamic response of flexibly supported liquid-storage tanks, Journal of Structural Engineering, ASCE, 118 (1), Whittaker,D. and Jury,D., 2, Seismic design loads for storage tanks, Paper No. 2376, 12 th World Conference on Earthquake Engineering, New Zealand Wozniak,R.S. and Mitchell,W.W., 1978, Basis of seismic design provisions for welded steel oil storage tanks, American Petroleum Institute 43 rd midyear meeting, session on Advances in Storage Tank Design, Toronto, Canada. IITK-GSDMA-EQ1-V1. 32
33 Table 1: Various types of tanks and their R values as mentioned in IBC 2 Type of tank Ground supported tanks Flat bottomed welded or bolted steel tanks Anchored Flat bottomed welded or bolted steel tanks Unanchored Reinforced or prestressed concrete tanks with anchored flexible base Reinforced or prestressed concrete tanks with reinforced nonsliding base Tanks with unanchored and unconstrained flexible base Elevated tanks On braced legs On unbraced legs On irregular braced legs single pedestal or skirt supported Tanks supported on structural towers similar to buildings R IITK-GSDMA-EQ1-V1. 33
34 Table 2: Expressions for base shear coefficients from ACI and FEMA 368 ACI 371 FEMA C S V C s = C s = D 1 2 / 3 for Ts < T < 4 s RT (R / I)T 2.5Ca 4S D1 = for T 4 s R 2 (R / I)T.5 C a S Values of coefficients, C V and C a depend DS (R / I) on seismic zones; R is response modification factor with maximum.2 S DS value of 2. R = 2. for pedestal supported elevated tanks ACI 35.3 FEMA 368 Impulsive mode Impulsive mode 2.75ZI SDs (C s ) i = for T i.31 s (.6 Ti +.4S DS ) R W T (C s ) i = for < T i <T 1.25ZIS 2.75ZI 1.4(R / I) = < for T 2/3 i >.31 s RWTi R W S = DS for T T i < T s 1.4(R / I) SD1 = for T i T s 1.4(R / I)Ti Convective mode Convective mode 1.875ZIS 6S D1I (C s ) c = for T 2/3 c < 2.4 sec (C s ) c = for all values of T 2 c. Tc Tc < 2.75 ZI Values of R are in the range of 1.5 to 3. 6ZIS for different types of tanks = for T 2 c 2.4 sec Tc Z is zone factor; S is soil profile coefficient; I is importance factor and R W is response modification factor. Values of R W are in the range of 4.75 to 2. for different types of tanks. IITK-GSDMA-EQ1-V1. 34
35 Table 3: Expressions for base shear coefficients from AWWA D-1, D-13 and FEMA 368 AWWA D 1 and D13 (Ground supported tanks) Impulsive mode 2.52ZI ( Cs ) i = R w Convective mode 3ZIS ( Cs ) c = for T c 4.5 s R T w c 13.5ZIS = for T c > 4.5 s R 2 w T c Z is zone factor; I is importance factor; S is soil factor; T c is time period of convective mode; R w is response reduction factor with values in the range of 3.5 to 4.5 AWWA D 1 (Elevated tanks) 1.25ZIS ( Cs) i = 2 / 3 R T w.75zi R w 2.75ZI R w R w is in the range of 2. to 3. FEMA 368 Impulsive mode SDSI (Cs ) i = 1.4R Convective mode Cs ) c 1.5S D1I 1.4RTc 6SD1I 2 1.4RTc ( = for T s < T c 4 s = for T c > 4 s I is importance facor; R is response reduction factor with values in the range of 2.5 to 3. for steel tanks. FEMA 368 SDSI ( Cs ) i = for T < T s 1.4R S 1 I = D for Ts < T c 4 s 1.4RT 4SD1I = for T 2 c > 4 s 1.4RT R is in the range of 2. to 3. IITK-GSDMA-EQ1-V1. 35
36 Table 4: Expressions for base shear coefficients from AWWA D-11 and FEMA368 AWWA D11 FEMA 368 Impulsive mode Impulsive mode 1.25ZIS S ( Cs) i = Ds 2 / 3.6 Ti +.4S RiTi T (C s ) i = 2.75ZI 1.4(R / I) <T R i ( DS ) for < T i = S DS 1.4(R / I) for T T i Convective mode 4ZIS ( Cs) c = 2 RcTc R i is response reduction factors for impulsive mode with values in the range of 2 to 2.75 and R c is response reduction factor for convective mode; R c = 1. for all types of tanks < T s SD1 = for T i T s 1.4(R / I)Ti Convective mode 6SD1I ( Cs) c = 2 Tc Values of R are in the range of 1.5 to 3. for different types of concrete tanks IITK-GSDMA-EQ1-V1. 36
37 Table 5: Expressions for base shear coefficients from AWWA D-115 and FEMA368 AWWA D FEMA 368 Impulsive mode Impulsive mode 1.25ZIS S ( Cs) i = Ds 2 / 3 (.6 Ti +.4SDS) R wti T (C s ) i = for < T i <T 2.75ZI 1.4(R / I) R i S = DS for T T i < T s 1.4(R / I) SD1 = for T i T s 1.4(R / I)Ti Convective mode Convective mode ZIS 6SD1I ( Cs) c = ( Cs) c = 2 R wtc Tc R w is response reduction Values of R are in the range of 1.5 to 3. for factor with values in the different types of concrete tanks range of Table 6: Expressions for base shear coefficients from API 65 and FEMA 368 API 65 FEMA 368 Impulsive mode Impulsive mode C i =.6 Z I C i =.24 S DS I Convective mode Convective mode.75zsi.6s DSI C c = for T c 4.5 s C c = for T s < T c 4. s T c Tc 3.375ZSI 2.396S = for T 2 c > 4.5 s DSI = for T T 2 c > 4. s c Tc Z is zone factor; I is importance factor; S is site coefficient IITK-GSDMA-EQ1-V1. 37
38 Table 7: Elastic spectrum S e (T) and Spectrum for linear analysis S d (T) of Eurocode 8 T T β S e (T) = α S 1 + ( ηβ 1) S d (T) = α S 1 + ( 1) TB TB q T < T B T < T B = α Sηβ β = α S T B T < T C q K1 TC T B T < T C = α Sηβ T Kd1 β TC = α S T C T < T D q T K1 K2 TC TD (.2 α) T = α Sηβ C T < T D T D T Kd1 Kd2 β TC TD = α S T D T q T D T (.2 α) T D T where α=a g /g; a g =design ground acceleration ; β =Spectral acceleration amplification factor for 5% viscous damping; S = Soil parameter; η=damping correction factor. η = 1. for 5% damping. For any other damping ξ, the value of η = {7/(2+ξ)}.5 ; K 1, K 2, K d1, K d2 = Exponents which influence the shape of spectrum. Values of these exponents depend on soil condition. Their values for different soil conditions are given in Tables 4.1 and 4.2 of Eurocode 8 Part 4; T B, T C = Limits of the constant spectral acceleration branch; T D = Value defining beginning of the constant displacement range of the spectrum IITK-GSDMA-EQ1-V1. 38
39 Table 8: Different types of tanks with their ductility factor, μ (Whittaker and Jury (2)) Type of Tank Steel Tanks on Grade Elastically supported Unanchored tank designed for uplift (elephant foot shell buckling may occur under seismic overload) Unanchored tank designed for uplift and elastic (diamond shaped) shell buckling mode Anchored with non-ductile holding down bolts Anchored with ductile tension yielding holding down bolts Ductile skirt pedestal On concrete base pad designed for rocking Concrete Tanks on Grade Reinforced Concrete Prestressed Concrete Tanks of other materials on Grade Timber Non-ductile materials (eg. Fiberglass) Ductile materials and failure mechanisms Elevated Tanks μ As appropriate for support structure 3 Notes 1. Check that elastic buckling does not occur before elephant foot 2. Capacity design check required to protect against other forms of failure 3. Capacity design approach shall be used to protect elevated tanks against failure while yielding occurs in the chosen support system Table 9: Correction factor, C f (Whittaker and Jury (2)) Ductility Damping level, ξ (%) factor, μ IITK-GSDMA-EQ1-V1. 39
40 Table 1: Parameters for a low ductility tank Code Parameters IBC 2 and ACI 35.3 R = 1.5, I =1.25 Eurocode 8 q = 1., γ I = 1.2 NZSEE guidelines Sp = 1., μ = 1.25, ξ = 5%, C f =.72 Table 11: Parameters for a high ductility tank Code Parameters IBC 2 and ACI 35.3 R = 3., I =1.25 Eurocode 8 q = 2., γ I = 1.2 NZSEE guidelines Sp = 1., μ = 3., ξ = 5%, C f =.38 Table 12: Proposed values of Response reduction factor, R for IS 1893:22 Tank Ground supported tanks Unanchored steel tank Anchored steel tank Concrete tank with unconstrained flexible base Concrete tank with non-sliding base Elevated tanks Supported on RCC shaft Supported on RCC frame staging Supported on steel frame staging Supported on masonry shaft Proposed value of R IITK-GSDMA-EQ1-V1. 4
41 Base shear coefficient (BSC) R = 8. R = 1.5 R = 2. R = 2.5 R = 3. For building For tanks Time Period (S) Figure 1: Variation of base shear coefficient with natural period; IBC 2 (S D =1.5, S 1 =.6, F a =1., F v = 1.5, Class D site) R = 1.5 R =2. R = 2.5 R = 3. For tanks BSC tank / BSC bldg (S S = 1.5, S 1 =.6, F a = 1., F v = 1.5, site class D) (I = 1 and R = 8 for building; I = 1.25 for tanks) Time Period (S) Figure 2: Ratio of tank and building base shear coefficient (IBC 2) IITK-GSDMA-EQ1-V1. 41
42 Base shear coefficient (BSC) As per modified equation of FEMA368 (S S = 1.5, S 1 =.6, F a = 1., F v = 1.5, I =1.25, R = 2, site class D) As per equation of ACI 371 (Ca =.44, Cv =.64, R =2., soil type D) Time period (S) Figure 3: Comparison of base shear coefficient from ACI 371 and FEMA 368 Base shear coefficient(bsc) (a) Impulsive mode ACI 35.3; Rw = 2. FEMA 368; R=1.5 ACI 35.3; Rw = 4.75 FEMA 368; R = Time period (S) 1.2 (b) Convective mode ACI 35.3 Base shear coefficient (BSC).8.4 FEMA 1 2 Time period (S) 3 4 Figure 4: Comparison of base shear coefficient from ACI 35.3 and FEMA 368 (For ACI 35.3: Z =.4, S = 1.5, I = 1.25, soil type C; For FEMA 368: S S = 1.5, S 1 =.6, F a =1., F v = 1.5, I = 1.25, site class D) IITK-GSDMA-EQ1-V1. 42
43 6 BSC tank / BSC bldg 4 2 ACI 371 IBC 2 (S S = 1.5, S 1 =.6, F a = 1., F v = 1.5, site class D) (I = 1 and R = 8 for building; I = 1.25, R = 2 for tanks) Time Period (S) Figure 5: Ratio of tank and building base shear coefficient (ACI 371) 1.5 R = 1.5 R = 2. R = 2.5 R = 3. Base shear coefficient (BSC) 1..5 No lower bound x Convective mode Time Period (S) Figure 6: Variation of base shear coefficient with time period (ACI 35.3) (S D =1.5, S 1 =.6, F a =1., F v = 1.5, site class D) IITK-GSDMA-EQ1-V1. 43
44 7 6 5 R = 1.5 R = 2. R = 2.5 R = 3. BSCtank / BSCbldg (S S = 1.5, S 1 =.6, F a = 1., F v = 1.5, site class D) (I = 1 and R = 8 for building; I = 1.25 for tanks) Time Period (S) Figure 7: Ratio of base shear coefficient of tank (impulsive mode) and building (ACI 35.3) Base shear Coefficient AWWA D-1; R = 3.5 AWWA D-1; R = 4.5 FEMA 368; R = 2.5 FEMA 368; R = Time (S) Figure 8: Comparison of convective base shear coefficient for ground-supported tank from AWWA D-1 and FEMA 368 (For AWWA D-1 Z =.4, S = 1.5, I = 1.25, soil type C; For FEMA 368: S S = 1.5, S 1 =.6, F a =1., F v = 1.5, I = 1.25, site class D) IITK-GSDMA-EQ1-V1. 44
45 Base shear Coefficient AWWA D-1; Rw = 3 AWWA D-1; Rw = 4 FEMA 368; R = 2 FEMA 368; R = Time (S) Figure 9: Comparison of impulsive base shear coefficient for elevated tank from AWWA D-1 and FEMA 368 (For AWWA D-1 Z =.4, S = 1.5, I = 1.25, soil type C; For FEMA 368: S S = 1.5, S 1 =.6, F a =1., F v = 1.5, I = 1.25, site class D) 5 4 R = 2 R = 3 For tanks BSC tank /BSC bldg (S S = 1.5, S 1 =.6, F a = 1., F v = 1.5, site class D) (I = 1 and R = 8 for building; I = 1.25 for tanks) Time (S) Figure 1: Ratio of elevated tank and building base shear coefficient (AWWA D-1) IITK-GSDMA-EQ1-V1. 45
46 Base shear Coefficient AWWA D-11; Rw = 2. AWWA D-11; Rw = 4.5 FEMA 368; R = 1.5 FEMA 368; R = Time (S) 3 4 (a) Impulsive base shear 1.5 AWWA D-11 FEMA 368 Base shear Coefficient Time (S) (b) Convective base shear Figure 11: Comparison of base shear coefficient from AWWA D-11 and FEMA 368 (For AWWA D-11 Z =.4, S = 1.5, I = 1.25, soil type C; For FEMA 368: S S = 1.5, S 1 =.6, F a =1., F v = 1.5, I = 1.25, site class D) IITK-GSDMA-EQ1-V1. 46
47 7 6 5 R = 1.5 R = 2. R = 3. For tanks BSC tank /BSC bldg (S S = 1.5, S 1 =.6, F a = 1., F v = 1.5 site class D) (I = 1. and R = 8 for building; I = 1.25 for tanks) 1 Time (S) Figure 12: Ratio of tank and building base shear coefficient (AWWA D-11) Base shear Coefficient AWWA D-115; Rw = 1. AWWA D-115; Rw = 3. FEMA 368; R = 1.5 FEMA 368; R = 3. 1 Time (S) Figure 13: Comparison of impulsive base shear coefficient from AWWA D-115 and FEMA368 (For AWWA D-115: Z =.4, S = 1.5, I = 1.25, soil type C; For FEMA 368: S S = 1.5, S 1 =.6, F a =1., F v = 1.5, I = 1.25, site class D) IITK-GSDMA-EQ1-V1. 47
48 1.8 Base shear coefficient.6.4 API 65 (Z =.4, S = 1.5, I = 1.25, site type S3).2 FEMA 368 (S s = 1.5, S 1 =.6, F a = 1, F v = 1.5, site class D) Time period (S) Figure 14: Convective base shear coefficient from API 65 and FEMA 368 Base shear coefficient (BSC) Building ( q = 5) Tank (q = 1) x Convective mode No Lower bound Lower bound Time Period (S) Figure 15: Variation of base shear coefficient with time period as per Eurocode 8 (S =1., β = 2.5, η= 1., K 1 =1., K 2 =2., K d1 =2/3, K d2 =5/3, T B =.1, T C =.4 T D = 3., γ I =1. for building and γ I =1.3 for tank) IITK-GSDMA-EQ1-V1. 48
49 Tank (q = 1) 6 5 BSCtank / BSCbldg Time Period (S) Figure 16: Ratio of base shear coefficient of tank impulsive mode and building (Eurocode 8) Base shear coefficient (BSC) Building Tank Cf =.72 Tank; Cf =.54 Tank; Cf =.38 No Lower bound Lower bound Time Period (S) Figure 17: Variation of base shear coefficient with time period (NZSEE Guidelines) ( S p =.67, R = 1. for building, S p = 1. R =1.3 for tank, Z =1.2, L u =1.) IITK-GSDMA-EQ1-V1. 49
50 9 Tank Cf =.72 Tank; Cf =.54 Tank; Cf =.38 BSCtank / BSCbldg Time Period (S) Figure 18: Ratio of base shear coefficient of tank and building (NZSEE Guidelines) Base shear coefficient (BSCbldg) Eurocode 8 ( α =.3,S = 1, β = 2.5, γ = 1, K d1 = 2/3, K d2 = 5/3, T A =.15, T B =.6, q = 5, sub soil class B) IBC 2 ( S S = 1.5, S 1 =.6, F a = 1., F v = 1.5, R = 8, I = 1, site class D) NZSEE ( Z = 1.2, Sp =.67, R = 1, Lu = 1, Site category C) Time (S) Figure 19: Comparison of base shear coefficient for ductile building obtained from various codes. Most severe zone in each code is considered IITK-GSDMA-EQ1-V1. 5
51 1.2 Eurocode 8 (α =.3, S = 1, β = 2.5, η = 1, γ = 1.2, K 1 = 1, K 2 = 2, T A =.15, T B =.6, q = 1, sub soil class B) Base shear coefficient (BSCtank).8.4 IBC 2 ( S S = 1.5, S 1 =.6, F a = 1., F v = 1.5, R = 1.5, I = 1.25, site class D) NZSEE ( Z = 1.2, S p = 1., R = 1.3, C f =.72, L u = 1, site category C) ACI 35.3 and AWWA D Time (S) Figure 2: Comparison of base shear coefficient for ground supported unanchored concrete water tank obtained from various codes. Most severe zone in each code is considered. 1 NZSEE ( Z = 1.2, S p = 1., R = 1.3, C f =.72, L u = 1, site category C) IBC 2 ( S S = 1.5, S 1 =.6, F a = 1., F v = 1.5, R = 1.5, I = 1.25, site class D) 8 BSCtank / BSCbldg Eurocode 8 (α =.3,S = 1, β = 2.5, η = 1, γ = 1.2, K 1 = 1, K 2 = 2,T A =.15, T B =.6, q = 1, sub soil class B) ACI 35.3 and AWWA D Time (S) Figure 21: Comparison of ratio of base shear coefficients of tank and building from various codes (Low ductility tank). IITK-GSDMA-EQ1-V1. 51
52 6 NZSEE ( Z = 1.2, S p = 1., R = 1.3, C f =.38, L u = 1, site category C) IBC 2 ( S S = 1.5, S 1 =.6, F a = 1., F v = 1.5, R = 1.5, I = 1.25, site class D) BSCtank / BSCbldg 4 2 Eurocode 8 (α =.3,S = 1, β = 2.5, η = 1, γ = 1.2, K 1 = 1, K 2 = 2, T A =.15, T B =.6, q = 2, Sub soil class B) ACI 35.3 and AWWA D Time (S) Figure 22: Comparison of ratio of base shear coefficient of tank and building from various codes (High ductility tank). 2 ACI 35.3 and AWWA D-11 ( S S = 1.5, S 1 =.6, F a = 1., F v = 1.5, I = 1.25, site class D) Base shear coefficient Eurocode 8 (S = 1, β = 2.5, η = 1.673, γ = 1.2, K 1 = 1, K 2 = 2, T A =.15, T B =.6, q = 1, sub soil class B) API 65 (S S = 1.5, S 1 =.6, F a = 1., F v = 1.5, I = 1.25, site class D) Time (S) Figure 23: Comparison of base shear coefficient for convective mode IITK-GSDMA-EQ1-V1. 52
53 .1 IBC 2 ( S S = 1.5, S 1 =.6, F a = 1., F v = 1.5, R = 8, I = 1, site class D) Base shear coefficient IS IS 1893 (Part I):22 (Z =.36, R = 5, I = 1, soft soil) (K=1, β = 1, α =.8, soft soil) Time Period (S) Figure 24: Comparison of base shear coefficient for building from IBC 2, IS 1893:1984, IS 1893(Part 1):22. IBC values are divided by 1.4 to bring them to working stress level..8 IBC 2 ( Lowest value of R = 1.5) Base shear coefficient IS1893: 22 (R = 1.1) IBC 2 ( Highest value of R = 3) IS1893: 22 (R = 2.25) IS1893: Time period (S) Figure 25: Base shear coefficients for tanks from IBC 2, IS 1893:1984 and IS 1893(Part 1):22. IBC values are divided by 1.4 to bring them to working stress level. IITK-GSDMA-EQ1-V1. 53
for SEISMIC DESIGN OF LIQUID STORAGE TANKS
IITK-GSDMA GUIDELINES for SEISMIC DESIGN OF LIQUID STORAGE TANKS Provisions with Commentary and Explanatory Examples Indian Institute of Technology Kanpur Gujarat State Disaster Management Authority October
Seismic Analysis and Design of Steel Liquid Storage Tanks
Vol. 1, 005 CSA Academic Perspective 0 Seismic Analysis and Design of Steel Liquid Storage Tanks Lisa Yunxia Wang California State Polytechnic University Pomona ABSTRACT Practicing engineers face many
Effect of Container Height on Base Shear of Elevated Water Tank
Effect of Container Height on Base Shear of Elevated Water Tank Rupachandra J. Aware 1, Dr. Vageesha S. Mathada 2 Shri Vitthal Education & Research Institute College of Engineering, Pandharpur, Maharashtra,
Design Example 1 Design Spectral Response Acceleration Parameters 11.4
Design Example 1 Design Spectral Response Acceleration Parameters 11.4 OVERVIEW For a given building site, the risk-targeted maximum considered earthquake spectral response accelerations S S, at short
SEISMIC APPROACH DESIGN COMPARISON BETWEEN
IABSE ANNUAL MEETING, LONDON, 19 TH SEPTEMBER 2011 SEISMIC APPROACH DESIGN COMPARISON BETWEEN IBC AND ITALIAN DM2008 Ing. Luca Zanaica Senior Structural Engineer Ing. Francesco Caobianco Senior Structural
Chapter 14 Commentary NONBUILDING STRUCTURE DESIGN REQUIREMENTS
Chapter 14 Commentary NONBUILDING STRUCTURE DESIGN REQUIREMENTS 14.1 GENERAL 14.1.1 Scope. Requirements concerning nonbuilding structures were originally added to the 1994 Provisions by the 1991-94 Provisions
Reinforced Concrete Design
FALL 2013 C C Reinforced Concrete Design CIVL 4135 ii 1 Chapter 1. Introduction 1.1. Reading Assignment Chapter 1 Sections 1.1 through 1.8 of text. 1.2. Introduction In the design and analysis of reinforced
G. Michele Calvi IUSS Pavia
CONVEGNO SISMA ED ELEMENTI NON STRUTTURALI Approcci, Stati Limite e Verifiche Prestazionali Bologna 24 ottobre 2014 PROGETTO DI ELEMENTI NON STRUTTURALI SOGGETTI AD AZIONI SISMICHE G. Michele Calvi IUSS
Miss S. S. Nibhorkar 1 1 M. E (Structure) Scholar,
Volume, Special Issue, ICSTSD Behaviour of Steel Bracing as a Global Retrofitting Technique Miss S. S. Nibhorkar M. E (Structure) Scholar, Civil Engineering Department, G. H. Raisoni College of Engineering
SEISMIC DESIGN. Various building codes consider the following categories for the analysis and design for earthquake loading:
SEISMIC DESIGN Various building codes consider the following categories for the analysis and design for earthquake loading: 1. Seismic Performance Category (SPC), varies from A to E, depending on how the
DESIGN SPECIFICATIONS FOR HIGHWAY BRIDGES PART V SEISMIC DESIGN
DESIGN SPECIFICATIONS FOR HIGHWAY BRIDGES PART V SEISMIC DESIGN MARCH 2002 CONTENTS Chapter 1 General... 1 1.1 Scope... 1 1.2 Definition of Terms... 1 Chapter 2 Basic Principles for Seismic Design... 4
Cover. When to Specify Intermediate Precast Concrete Shear Walls. 10.10 Rev 4. White Paper WP004
Cover Introduction In regard to precast concrete systems, the addition of two new categories of Seismic Force Resisting Systems (SFRS) in IBC 2006 has created some confusion about whether to specify intermediate
TECHNICAL NOTE. Design of Diagonal Strap Bracing Lateral Force Resisting Systems for the 2006 IBC. On Cold-Formed Steel Construction INTRODUCTION
TECHNICAL NOTE On Cold-Formed Steel Construction 1201 15th Street, NW, Suite 320 W ashington, DC 20005 (202) 785-2022 $5.00 Design of Diagonal Strap Bracing Lateral Force Resisting Systems for the 2006
Untopped Precast Concrete Diaphragms in High-Seismic Applications. Ned M. Cleland, Ph.D., P.E. President Blue Ridge Design, Inc. Winchester, Virginia
Untopped Precast Concrete Diaphragms in High-Seismic Applications Ned M. Cleland, Ph.D., P.E. President Blue Ridge Design, Inc. Winchester, Virginia S. K. Ghosh, Ph.D. President S. K. Ghosh Associates,
SEISMIC DESIGN OF MULTI-STORY BUILDINGS WITH METALLIC STRUCTURAL FUSES. R. Vargas 1 and M. Bruneau 2 ABSTRACT
Proceedings of the 8 th U.S. National Conference on Earthquake Engineering April 18-22, 26, San Francisco, California, USA Paper No. 28 SEISMIC DESIGN OF MULTI-STORY BUILDINGS WITH METALLIC STRUCTURAL
Seismic performance evaluation of an existing school building in Turkey
CHALLENGE JOURNAL OF STRUCTURAL MECHANICS 1 (4) (2015) 161 167 Seismic performance evaluation of an existing school building in Turkey Hüseyin Bilgin * Department of Civil Engineering, Epoka University,
NATURAL PHENOMENA HAZARDS DESIGN AND EVALUATION CRITERIA FOR DEPARTMENT OF ENERGY FACILITIES
TS NOT MEASUREMENT SENSITIVE DOE-STD-1020-2002 January 2002 DOE STANDARD Superseding DOE-STD-1020-94 April 1994 NATURAL PHENOMENA HAZARDS DESIGN AND EVALUATION CRITERIA FOR DEPARTMENT OF ENERGY FACILITIES
Specification for Structures to be Built in Disaster Areas
Ministry of Public Works and Settlement Government of Republic of Turkey Specification for Structures to be Built in Disaster Areas PART III - EARTHQUAKE DISASTER PREVENTION (Chapter 5 through Chapter
Methods for Seismic Retrofitting of Structures
Methods for Seismic Retrofitting of Structures Retrofitting of existing structures with insufficient seismic resistance accounts for a major portion of the total cost of hazard mitigation. Thus, it is
Contractor s Statement of Responsibility for Seismic-Force-Resisting Systems This form is to be filled out by the contractor.
SPECIAL INSPECTION PROCEDURE IBC CHAPTER 17 2012 EDITION When Required All projects that require a SC licensed Architect or Engineer per SC Architectural and Engineering registration law. Overview The
SEISMIC DESIGN PROVISIONS FOR PRECAST CONCRETE STRUCTURES. S.K. Ghosh, Ph. D. President S.K. Ghosh Associates Inc. Northbrook, IL BACKGROUND
SEISMIC DESIGN PROVISIONS FOR PRECAST CONCRETE STRUCTURES S.K. Ghosh, Ph. D. President S.K. Ghosh Associates Inc. Northbrook, IL BACKGROUND Until recently, precast concrete structures could be built in
Detailing of Reinforcment in Concrete Structures
Chapter 8 Detailing of Reinforcment in Concrete Structures 8.1 Scope Provisions of Sec. 8.1 and 8.2 of Chapter 8 shall apply for detailing of reinforcement in reinforced concrete members, in general. For
EVALUATION OF SEISMIC RESPONSE - FACULTY OF LAND RECLAMATION AND ENVIRONMENTAL ENGINEERING -BUCHAREST
EVALUATION OF SEISMIC RESPONSE - FACULTY OF LAND RECLAMATION AND ENVIRONMENTAL ENGINEERING -BUCHAREST Abstract Camelia SLAVE University of Agronomic Sciences and Veterinary Medicine of Bucharest, 59 Marasti
Protecting data centers from seismic activity Understanding enclosure standards is critical to protecting equipment
Protecting data centers from seismic activity Understanding enclosure standards is critical to protecting equipment Author: Joel Young, engineer at Crenlo Abstract In the event of an earthquake, the type
SEISMIC CAPACITY OF EXISTING RC SCHOOL BUILDINGS IN OTA CITY, TOKYO, JAPAN
SEISMIC CAPACITY OF EXISTING RC SCHOOL BUILDINGS IN OTA CITY, TOKYO, JAPAN Toshio OHBA, Shigeru TAKADA, Yoshiaki NAKANO, Hideo KIMURA 4, Yoshimasa OWADA 5 And Tsuneo OKADA 6 SUMMARY The 995 Hyogoken-nambu
Seismic Risk Prioritization of RC Public Buildings
Seismic Risk Prioritization of RC Public Buildings In Turkey H. Sucuoğlu & A. Yakut Middle East Technical University, Ankara, Turkey J. Kubin & A. Özmen Prota Inc, Ankara, Turkey SUMMARY Over the past
FOUNDATION DESIGN. Instructional Materials Complementing FEMA 451, Design Examples
FOUNDATION DESIGN Proportioning elements for: Transfer of seismic forces Strength and stiffness Shallow and deep foundations Elastic and plastic analysis Foundation Design 14-1 Load Path and Transfer to
Prepared For San Francisco Community College District 33 Gough Street San Francisco, California 94103. Prepared By
Project Structural Conditions Survey and Seismic Vulnerability Assessment For SFCC Civic Center Campus 750 Eddy Street San Francisco, California 94109 Prepared For San Francisco Community College District
EGYPTIAN CODES FOR DESIGN AND CONSTRUCTION OF BUILDINGS
in the Euro-Mediterranean Area EGYPTIAN CODES FOR DESIGN AND CONSTRUCTION OF BUILDINGS By Prof. Amr Ezzat Salama Chairman of Housing, Building National Center Cairo, Egypt Former Minister of High Education
Introduction. Eurocodes. Specification. Cost
Introduction Eurocodes Specification Cost Structural Eurocodes BS EN 1990 (EC0): BS EN 1991 (EC1): Basis of structural design Actions on Structures BS EN 1992 (EC2): BS EN 1993 (EC3): BS EN 1994 (EC4):
Draft Table of Contents. Building Code Requirements for Structural Concrete and Commentary ACI 318-14
Draft Table of Contents Building Code Requirements for Structural Concrete and Commentary ACI 318-14 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE (ACI 318 14) Chapter 1 General 1.1 Scope of ACI 318
SEISMIC RETROFIT DESIGN CRITERIA
SEISMIC RETROFIT DESIGN CRITERIA British Columbia Ministry of Transportation June 30, 2005 Prepared by: Recommended by: Approved by: Don Kennedy, P.Eng., Associated Engineering (BC) Sharlie Huffman, P.
SLAB DESIGN. Introduction ACI318 Code provides two design procedures for slab systems:
Reading Assignment SLAB DESIGN Chapter 9 of Text and, Chapter 13 of ACI318-02 Introduction ACI318 Code provides two design procedures for slab systems: 13.6.1 Direct Design Method (DDM) For slab systems
SEISMIC RETROFITTING OF STRUCTURES
SEISMIC RETROFITTING OF STRUCTURES RANJITH DISSANAYAKE DEPT. OF CIVIL ENGINEERING, FACULTY OF ENGINEERING, UNIVERSITY OF PERADENIYA, SRI LANKA ABSTRACT Many existing reinforced concrete structures in present
THE RELIABILITY OF CAPACITY-DESIGNED COMPONENTS IN SEISMIC RESISTANT SYSTEMS
THE RELIABILITY OF CAPACITY-DESIGNED COMPONENTS IN SEISMIC RESISTANT SYSTEMS A DISSERTATION SUBMITTED TO THE DEPARTMENT OF CIVIL AND ENVIRIONMENTAL ENGINEERING AND THE COMMITTEE ON GRADUATE STUDIES OF
AN IMPROVED SEISMIC DESIGN APPROACH FOR TWO-COLUMN REINFORCED CONCRETE BENTS OVER FLEXIBLE FOUNDATIONS WITH PREDEFINED DAMAGE LEVELS
AN IMPROVED SEISMIC DESIGN APPROACH FOR TWO-COLUMN REINFORCED CONCRETE BENTS OVER FLEXIBLE FOUNDATIONS WITH PREDEFINED DAMAGE LEVELS ABSTRACT: T. Yılmaz 1 ve A. Caner 2 1 Araştırma Görevlisi, İnşaat Müh.
Design for Nonstructural Components
14 Design for Nonstructural Components Robert Bachman, S.E., John Gillengerten, S.E. and Susan Dowty, S.E. Contents 14.1 DEVELOPMENT AND BACKGROUND OF THE REQUIREMENTS FOR NONSTRUCTURAL COMPONENTS... 3
Structural Dynamics of Linear Elastic Single-Degree-of-Freedom (SDOF) Systems
Structural Dynamics of Linear Elastic Single-Degree-of-Freedom (SDOF) Systems SDOF Dynamics 3-1 This set of slides covers the fundamental concepts of structural dynamics of linear elastic single-degree-of-freedom
Development of Seismic-induced Fire Risk Assessment Method for a Building
Development of Seismic-induced Fire Risk Assessment Method for a Building AI SEKIZAWA National Research Institute of Fire and Disaster 3-14-1, Nakahara, Mitaka, Tokyo 181-8633, Japan [email protected]
Design of reinforced concrete columns. Type of columns. Failure of reinforced concrete columns. Short column. Long column
Design of reinforced concrete columns Type of columns Failure of reinforced concrete columns Short column Column fails in concrete crushed and bursting. Outward pressure break horizontal ties and bend
CONTRIBUTION TO THE IAEA SOIL-STRUCTURE INTERACTION KARISMA BENCHMARK
CONTRIBUTION TO THE IAEA SOIL-STRUCTURE INTERACTION KARISMA BENCHMARK Presented by F. Wang (CEA, France), CLUB CAST3M 2013 28/11/2013 5 DÉCEMBRE 2013 CEA 10 AVRIL 2012 PAGE 1 CONTRIBUTION TO THE IAEA SSI
Chapter 3 DESIGN AND CONSTRUCTION FEATURES IMPORTANT TO SEISMIC PERFORMANCE
Chapter 3 DESIGN AND CONSTRUCTION FEATURES IMPORTANT TO SEISMIC PERFORMANCE To satisfy the performance goals of the NEHRP Recommended Seismic Provisions, a number of characteristics are important to the
Page 1 of 18 28.4.2008 Sven Alexander Last revised 1.3.2010. SB-Produksjon STATICAL CALCULATIONS FOR BCC 250
Page 1 of 18 CONTENT PART 1 BASIC ASSUMPTIONS PAGE 1.1 General 1. Standards 1.3 Loads 1. Qualities PART ANCHORAGE OF THE UNITS.1 Beam unit equilibrium 3. Beam unit anchorage in front..1 Check of capacity..
Advanced Retrofitting Methods and Techniques for RC Building: State of an Art
Advanced Retrofitting Methods and Techniques for RC Building: State of an Art Miss. Swati Sanjay Nibhorkar * M. E (Structure) Scholar, Civil Engineering Department, G. H. Raisoni College of Engg and Management,
Seismic design of beam-column joints in RC moment resisting frames Review of codes
Structural Engineering and Mechanics, Vol. 23, No. 5 (2006) 579-597 579 Technical Report Seismic design of beam-column joints in RC moment resisting frames Review of codes S. R. Uma Department of Civil
SEISMIC RETROFITTING OF REINFORCED CONCRETE BUILDINGS USING TRADITIONAL AND INNOVATIVE TECHNIQUES
ISET Journal of Earthquake Technology, Paper No. 454, Vol. 42, No. 2-3, June-September 25, pp. 21-46 SEISMIC RETROFITTING OF REINFORCED CONCRETE BUILDINGS USING TRADITIONAL AND INNOVATIVE TECHNIQUES Giuseppe
Performance-based Evaluation of the Seismic Response of Bridges with Foundations Designed to Uplift
Performance-based Evaluation of the Seismic Response of Bridges with Foundations Designed to Uplift Marios Panagiotou Assistant Professor, University of California, Berkeley Acknowledgments Pacific Earthquake
Structural Design Criteria & Design Loads on Delhi Metro Rail and Checking of Safety of Radial Joints in Tunnel Lining Segments
International Journal of Scientific and Research Publications, Volume 5, Issue 7, July 2015 1 Structural Design Criteria & Design Loads on Delhi Metro Rail and Checking of Safety of Radial Joints in Tunnel
Rehabilitation of a 1985 Steel Moment- Frame Building
Rehabilitation of a 1985 Steel Moment- Frame Building Gregg Haskell, a) M.EERI A 1985 steel moment frame is seismically upgraded using passive energy dissipation, without adding stiffness to the system.
PARAMETRIC STUDY OF THE STRUCTURES (INFLUENCE OF THE SHELLS)
ABSTRACT: PARAMETRIC STUDY OF THE STRUCTURES (INFLUENCE OF THE SHELLS) S. Mourad 1 and R. Mitiche-Kettab 2 1 Doctor, Civil Eng. Department, National Scholl of Polytechnic Algiers, Algeria 2 Professor,
Reinforced concrete moment-resisting frames are structural systems that work to
i Abstract Reinforced concrete moment-resisting frames are structural systems that work to resist earthquake ground motions through ductile behavior. Their performance is essential to prevent building
Loads and Load Combinations for NBCC. Outline
Loads and Load Combinations for NBCC Prepared by Dr Michael Bartlett, P.Eng University of Western Ontario Presented with minor modifications by Dr Robert Sexsmith, P.Eng. University of British Columbia
Recent Earthquakes: Implications for U.S. Water Utilities [Project #4408]
Recent Earthquakes: Implications for U.S. Water Utilities [Project #4408] ORDER NUMBER: 4408 DATE AVAILABLE: July 2012 PRINCIPAL INVESTIGATORS: John Eidinger and Craig A. Davis PROJECT PURPOSE: The purpose
1.054/1.541 Mechanics and Design of Concrete Structures (3-0-9) Outline 1 Introduction / Design Criteria for Reinforced Concrete Structures
Prof. Oral Buyukozturk Massachusetts Institute of Technology Outline 1 1.054/1.541 Mechanics and Design of Concrete Structures (3-0-9) Outline 1 Introduction / Design Criteria for Reinforced Concrete Structures
PROHITECH WP3 (Leader A. IBEN BRAHIM) A short Note on the Seismic Hazard in Israel
PROHITECH WP3 (Leader A. IBEN BRAHIM) A short Note on the Seismic Hazard in Israel Avigdor Rutenberg and Robert Levy Technion - Israel Institute of Technology, Haifa 32000, Israel Avi Shapira International
1.2 Advantages and Types of Prestressing
1.2 Advantages and Types of Prestressing This section covers the following topics. Definitions Advantages of Prestressing Limitations of Prestressing Types of Prestressing 1.2.1 Definitions The terms commonly
Tension Development and Lap Splice Lengths of Reinforcing Bars under ACI 318-02
ENGINEERING DATA REPORT NUMBER 51 Tension Development and Lap Splice Lengths of Reinforcing Bars under ACI 318-02 A SERVICE OF THE CONCRETE REINFORCING STEEL INSTITUTE Introduction Section 1.2.1 in the
Design Parameters for Steel Special Moment Frame Connections
SEAOC 2011 CONVENTION PROCEEDINGS Design Parameters for Steel Special Moment Frame Connections Scott M. Adan, Ph.D., S.E., SECB, Chair SEAONC Structural Steel Subcommittee Principal Adan Engineering Oakland,
9.3 Two-way Slabs (Part I)
9.3 Two-way Slabs (Part I) This section covers the following topics. Introduction Analysis and Design Features in Modeling and Analysis Distribution of Moments to Strips 9.3.1 Introduction The slabs are
Seismic Isolated Hospital Design Practice in Turkey: Erzurum Medical Campus
Seismic Isolated Hospital Design Practice in Turkey: Erzurum Medical Campus J. Kubin, D. Kubin, A. Özmen, O.B. Şadan, E. Eroğlu Prota Engineering Design and Consultancy Services Inc. H. Sucuoğlu, S. Akkar
Seismic Risk Evaluation of a Building Stock and Retrofit Prioritization
Seismic Risk Evaluation of a Building Stock and Retrofit Prioritization Seismic risk assessment of large building stocks can be conducted at various s depending on the objectives, size of the building
ABSTRACT. SUAREZ, VINICIO A. Implementation of Direct Displacement-Based Design for Highway Bridges. (Under the direction of Dr. Mervyn Kowalsky).
ABSTRACT SUAREZ, VINICIO A. Implementation of Direct Displacement-Based Design for Highway Bridges. (Under the direction of Dr. Mervyn Kowalsky). In the last decade, seismic design shifted towards Displacement-Based
SPECIFICATIONS, LOADS, AND METHODS OF DESIGN
CHAPTER Structural Steel Design LRFD Method Third Edition SPECIFICATIONS, LOADS, AND METHODS OF DESIGN A. J. Clark School of Engineering Department of Civil and Environmental Engineering Part II Structural
Control of Seismic Drift Demand for Reinforced Concrete Buildings with Weak First Stories
Earthquake Yoshimura: Engineering Control and of Engineering Seismic Drift Seismology Demand for Reinforced Concrete Buildings with Weak First Stories 7 Volume 4, Number, September 3, pp. 7 3 Control of
NIST GCR 10-917-9 Applicability of Nonlinear Multiple-Degree-of-Freedom Modeling for Design
NIST GCR 0-97-9 Applicability of Nonlinear Multiple-Degree-of-Freedom Modeling for Design NEHRP Consultants Joint Venture A Partnership of the Applied Technology Council and the Consortium of Universities
1. Fluids Mechanics and Fluid Properties. 1.1 Objectives of this section. 1.2 Fluids
1. Fluids Mechanics and Fluid Properties What is fluid mechanics? As its name suggests it is the branch of applied mechanics concerned with the statics and dynamics of fluids - both liquids and gases.
Deflection Calculation of RC Beams: Finite Element Software Versus Design Code Methods
Deflection Calculation of RC Beams: Finite Element Software Versus Design Code Methods G. Kaklauskas, Vilnius Gediminas Technical University, 1223 Vilnius, Lithuania ([email protected]) V.
4B-2. 2. The stiffness of the floor and roof diaphragms. 3. The relative flexural and shear stiffness of the shear walls and of connections.
Shear Walls Buildings that use shear walls as the lateral force-resisting system can be designed to provide a safe, serviceable, and economical solution for wind and earthquake resistance. Shear walls
Elasticity. I. What is Elasticity?
Elasticity I. What is Elasticity? The purpose of this section is to develop some general rules about elasticity, which may them be applied to the four different specific types of elasticity discussed in
Earthquakes and Data Centers
7x24 Exchange Fall Symposium September 11, 2013 Hilton Bellevue Andrew W. Taylor, Ph.D., S.E., FACI Earthquake Hazards 2 September 11, 2013 1 Cascadia Earthquake Sources Figure Credit: Craig Weaver, Pacific
16. Beam-and-Slab Design
ENDP311 Structural Concrete Design 16. Beam-and-Slab Design Beam-and-Slab System How does the slab work? L- beams and T- beams Holding beam and slab together University of Western Australia School of Civil
CRYOGENIC ABOVE GROUND STORAGE TANKS: FULL CONTAINMENT AND MEMBRANE COMPARISON OF TECHNOLOGIES
CRYOGENIC ABOVE GROUND STORAGE TANKS: FULL CONTAINMENT AND MEMBRANE COMPARISON OF TECHNOLOGIES Jérôme Thierçault Caroline Egels Technical Division BOUYGUES Travaux Publics 1 Avenue Eugène Freyssinet 78061
PERFORMANCE BASED SEISMIC EVALUATION AND RETROFITTING OF UNSYMMETRICAL MEDIUM RISE BUILDINGS- A CASE STUDY
Paper No. 682 PERFORMANCE BASED SEISMIC EVALUATION AND RETROFITTING OF UNSYMMETRICAL MEDIUM RISE BUILDINGS- A CASE STUDY Jimmy Chandra, Pennung Warnitchai, Deepak Rayamajhi, Naveed Anwar and Shuaib Ahmad
REVISION OF GUIDELINE FOR POST- EARTHQUAKE DAMAGE EVALUATION OF RC BUILDINGS IN JAPAN
10NCEE Tenth U.S. National Conference on Earthquake Engineering Frontiers of Earthquake Engineering July 21-25, 2014 Anchorage, Alaska REVISION OF GUIDELINE FOR POST- EARTHQUAKE DAMAGE EVALUATION OF RC
CSA S16-09 Design of Steel Structures Canada
CSA S16-09 Design of Steel Structures Canada Ed Whalen, P.Eng CISC President CSA S16-09 1 CSA Standard S16-09 Standard, Design of Steel Structures. Sets out minimum requirements used by engineers in the
SEISMIC ANALYSIS AND RETROFITTING OF R.C.C STRUCTURE
International Journal of Advanced Research in Biology Engineering Science and Technology (IJARBEST) Vol., Issue, April 1 SEISMIC ANALYSIS AND RETROFITTING OF R.C.C STRUCTURE M.R.NAVANEETHA KRISHNAN 1,
Tentative Interim Amendment NFPA 59A. Standard for the Production, Storage, and Handling of Liquefied Natural Gas (LNG) 2016 Edition
Tentative Interim Amendment NFPA 59A Standard for the Production, Storage, and Handling of Liquefied Natural Gas (LNG) 2016 Edition Reference: Various TIA 16-1 (SC 15-12-4 / TIA Log #1187R) Note: Text
Water hammering in fire fighting installation
Water hammering in fire fighting installation Forward One of major problems raised in the fire fighting network installed at Pioneer company for pharmaceutical industry /Sulaymania was the high water hammering
Requirements for the Use of PRESSS Moment-Resisting Frame Systems
Requirements for the Use of PRESSS Moment-Resisting Frame Systems Neil M. Hawkins, Ph.D. Professor Emeritus Department of Civil Engineering University of Illinois at Urbana-Champaign Urbana, Illinois S.
RC Detailing to Eurocode 2
RC Detailing to Eurocode 2 Jenny Burridge MA CEng MICE MIStructE Head of Structural Engineering Structural Eurocodes BS EN 1990 (EC0): BS EN 1991 (EC1): Basis of structural design Actions on Structures
DESIGN OF PRESTRESSED BARRIER CABLE SYSTEMS
8601 North Black Canyon Highway Suite 103 Phoenix, AZ 8501 For Professionals Engaged in Post-Tensioning Design Issue 14 December 004 DESIGN OF PRESTRESSED BARRIER CABLE SYSTEMS by James D. Rogers 1 1.0
HUS-H Screw Anchor. Technical data. Seismic design data. HUS-H Carbon steel screw anchor. HUS-H diameter 8, 10, 14. Seismic design data
Technical data HUS-H Carbon steel screw anchor HUS-H diameter 8, 10, 14 10 / 011 Version 011-10 1 HUS-H screw anchor seismic design data Anchor version Carbon steel screw Benefits - Quick and easy setting
Optimum proportions for the design of suspension bridge
Journal of Civil Engineering (IEB), 34 (1) (26) 1-14 Optimum proportions for the design of suspension bridge Tanvir Manzur and Alamgir Habib Department of Civil Engineering Bangladesh University of Engineering
ES250: Electrical Science. HW7: Energy Storage Elements
ES250: Electrical Science HW7: Energy Storage Elements Introduction This chapter introduces two more circuit elements, the capacitor and the inductor whose elements laws involve integration or differentiation;
SEISMIC DESIGN OF HIGHWAY BRIDGES
Journal of Japan Association for Earthquake Engineering, Vol.4, No.3 (Special Issue), 2004 SEISMIC DESIGN OF HIGHWAY BRIDGES Kazuhiko KAWASHIMA 1 and Shigeki UNJOH 2 1 Member of JAEE, Professor, Department
ICC-ES Evaluation Report
ICC-ES Evaluation Report ESR-2369 Reissued May 1, 2010 This report is subject to re-examination in one year. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council
Fluid Mechanics: Static s Kinematics Dynamics Fluid
Fluid Mechanics: Fluid mechanics may be defined as that branch of engineering science that deals with the behavior of fluid under the condition of rest and motion Fluid mechanics may be divided into three
DISASTER RESISTANCE EARTHQUAKES AND STRUCTURES
DISASTER RESISTANCE EARTHQUAKES AND STRUCTURES EARTHQUAKES Origin of earthquakes The earth was a single land about two hundred million years ago. This land split progressively over a long period of time
SOFTWARE FOR GENERATION OF SPECTRUM COMPATIBLE TIME HISTORY
3 th World Conference on Earthquake Engineering Vancouver, B.C., Canada August -6, 24 Paper No. 296 SOFTWARE FOR GENERATION OF SPECTRUM COMPATIBLE TIME HISTORY ASHOK KUMAR SUMMARY One of the important
Critical Facility Round Table
Critical Facility Round Table October 16, 2003 San Francisco Seismic Risk for Data Centers David Bonneville Senior Principal Degenkolb Engineers San Francisco, California Presentation Outline Seismic Risk
Strengthening of Brick Masonry Walls against Earthquake Loading
International Journal of Advanced Structures and Geotechnical Engineering ISSN 2319-5347, Vol. 01, No. 01, July 2012 Strengthening of Brick Masonry Walls against Earthquake ing KHAN SHAHZADA, MUHAMMAD
EARTHQUAKE INDUCED AMPLIFIED LOADS IN STEEL INVERTED V- TYPE CONCENTRICALLY BRACED FRAMES
EARTHQUAKE INDUCED AMPLIFIED LOADS IN STEEL INVERTED V- TYPE CONCENTRICALLY BRACED FRAMES Bora Akşar 1, Selçuk Doğru 2, Jay Shen 3, Ferit Cakir 4, Bulent Akbas 5 1 Res.Asst,, Gebze Technical University,
Seismic Assessment and Retrofitting of Structures: Eurocode8 Part3 and the Greek Code on Seismic Structural Interventions
Working Group 7: Earthquake Resistant Structures Geneva, 25 September 2015 Seismic Assessment and Retrofitting of Structures: Eurocode8 Part3 and the Greek Code on Seismic Structural Interventions Prof.
National Council of Examiners for Engineering and Surveying. Principles and Practice of Engineering Structural Examination
Structural Effective Beginning with the April 2011 The structural engineering exam is a breadth and exam examination offered in two components on successive days. The 8-hour Vertical Forces (Gravity/Other)
Spon Press PRESTRESSED CONCRETE DESIGN EUROCODES. University of Glasgow. Department of Civil Engineering. Prabhakara Bhatt LONDON AND NEW YORK
PRESTRESSED CONCRETE DESIGN TO EUROCODES Prabhakara Bhatt Department of Civil Engineering University of Glasgow Spon Press an imprint of Taytor & Francfe LONDON AND NEW YORK CONTENTS Preface xix Basic
SIESMIC SLOSHING IN CYLINDRICAL TANKS WITH FLEXIBLE BAFFLES
SIESMIC SLOSHING IN CYLINDRICAL TANKS WITH FLEXIBLE BAFFLES Kayahan AKGUL 1, Yasin M. FAHJAN 2, Zuhal OZDEMIR 3 and Mhamed SOULI 4 ABSTRACT Sloshing has been one of the major concerns for engineers in
III. Compression Members. Design of Steel Structures. Introduction. Compression Members (cont.)
ENCE 455 Design of Steel Structures III. Compression Members C. C. Fu, Ph.D., P.E. Civil and Environmental Engineering Department University it of Maryland Compression Members Following subjects are covered:
