6.2 Flow-Through Planter

Similar documents
Underground Injection Control Storm Water Information

APPENDIX F. RESIDENTIAL WATER QUALITY PLAN: ALLOWABLE BMP OPTIONS

Operation & Maintenance Document Templates

DESCRIPTION OF STORMWATER STRUCTURAL CONTROLS IN MS4 PERMITS

PRIVATE TREATMENT CONTROL BMP OPERATION AND MAINTENANCE VERIFICATION FORM BIORETENTION FACILITIES, VEGETATED SWALES & HIGHER RATE BIOFILTERS

Table 4.9 Storm Drain Inlet Protetion Applicable for

CHAPTER 17: STORM SEWER STANDARDS Introduction Administration Standards 17.1

STANDARD AND SPECIFICATIONS FOR STORM DRAIN INLET PROTECTION

Soakage Trenches. A better way to manage stormwater. Thinking Globally and Acting Locally

C.3 Workshop Track 2: Sizing Calculations and Design Considerations for LID Treatment Measures

Outlet stabilization structure

Guidelines for Control of Water Runoff on Small Lots. Revised 6/09

Index. protection. excavated drop inlet protection (Temporary) Block and gravel inlet Protection (Temporary)

GREEN ROOFS. Location. Design SMALL COMMERCIAL GUIDE CITY OF ATLANTA, GEORGIA DEPARTMENT OF WATERSHED MANAGEMENT

Stormwater/Wetland Pond Construction Inspection Checklist

APPENDIX B DESIGN GUIDELINES FOR APPROVED TREATMENT METHODS

Indiana State Department of Health Construction Guidelines for Gravity and Flood-Dose Trench Onsite Systems

GREEN INFRASTRUCTURE DESIGNS BIOSWALE/HYBRID DITCH

Local Road Assessment and Improvement Drainage Manual

SUSTAINABLE URBAN DRAINAGE SYSTEMS

CHAPTER 8 CIVIL DESIGN

STORM DRAINS CHAPTER 7

Storm Drain Inlet Protection

RIPRAP From Massachusetts Erosion and Sediment Control Guidelines for Urban and Suburban Areas

Storm Drain Inlet Protection

Post-Construction Stormwater Management Checklist* (5,000 SF or Greater)

Property Care White Papers. Site Drainage: Monitor and Maintain

Permeable Pavement Treatment Capacity

Tree Pits Operation & Maintenance Guide

Land Disturbance, Erosion Control and Stormwater Management Checklist. Walworth County Land Conservation Department

Town of Elkton & Cecil Soil Conservation District Checklist for Joint Agency Review Stormwater Management / Erosion and Sediment Control

Emergency Spillways (Sediment basins)

FY11 Sanitary Sewer Main Rehab and Point Repair Bid Tabulation

LS 2540 SEWER LATERALS AND INSPECTION TEES

Sample Punch List. Garth Ruffner Landscape Architect (916) Page 1 of 5

SECTION 7- STORM SEWER

Chapter 3 CULVERTS. Description. Importance to Maintenance & Water Quality. Culvert Profile

Green Infrastructure for Single Family Residences

Low Impact Development Checklist

Minimizes sediment and debris from entering storm drains that lead to waterways and watercourses.

3.4 DRAINAGE PLAN Characteristics of Existing Drainages Master Drainage System. Section 3: Development Plan BUTTERFIELD SPECIFIC PLAN

Permeable Pavement Construction Guide

INDEX STORM DRAINAGE PRE-APPROVED NOTES, DESIGN CRITERIA, & PLANS

Operations and Maintenance Guidelines for Coal Ash Landfills Coal Ash Landfills are NOT the Same as Subtitle D Solid Waste Landfills

Virginia Street Tree Box Filters Demonstration Project

SE-10 STORM DRAIN INLET PROTECTION. Objectives

SUMP PUMP. City of Ann Arbor & C O L L E C T I O N S Y S T E M G L O S S A R Y

A Developer s Guide: Watershed-Wise Development

BMP-7. A sediment filter or an excavated impounding area around a storm drain drop inlet or curb inlet.

CONSTRUCTION MANAGER S WEEKLY PROGRESS REPORT

PART V BEST MANAGEMENT PRACTICES

APPENDIX C INLETS. The application and types of storm drainage inlets are presented in detail in this Appendix.

City of West Linn Public Works Design Standards Table of Contents

CONCRETE SEGMENTAL RETAINING WALL SYSTEM

SECTION STORM DRAINAGE STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

Riprap-lined Swale (RS)

DOÑA ANA COUNTY DESIGN STORM CRITERIA GUIDELINES FOR COMMERCIAL AND RESIDENTIAL SITES. Run-off Analysis Methods

Section 2100-Trenching and Tunneling

Porous Pavement Alternatives Cost Analysis

SECTION PUBLIC STORM UTILITY DRAINAGE PIPING

How to Build a Rain Garden at Your Home

SECTION STORM DRAIN SYSTEM

Storm Drain Inlet Protection

Checklist for plans to Construct, Alter or Repair An Individual Subsurface Sewage Disposal System

CONCRETE SEGMENTAL RETAINING WALL SYSTEM

PROJECT COST ESTIMATE ASSUMPTIONS AND EXCLUSIONS

CHAPTER 11 STORM DRAINAGE

SECTION 5: SANITARY SEWER SYSTEM DESIGN

CASFM Stormwater Quality Field Trip June 23rd, 2011

FY08 SEWER POINT REPAIRS BID TABULATION

Homeowner s Guide to Drainage

SECTION REMOVAL OR ABANDONMENT OF EXISTING UTILITIES AND UNDERGROUND STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

Section 402. STORM SEWERS

Environmental Issues In Your Backyard

1. Water Line Maintenance 2. Sanitary Sewer Maintenance 3. Spill/Leak/Overflow Control, Response, and Containment

Scheduling Maintenance for Infiltration Basins and Trenches

(Source: Center for Neighborhood Technology)

4.3 Cisterns and Rain Barrels

City of Shelbyville Site Inspection Checklist

piles of debris that accumulate after a rain such as leaves, trash, twigs, etc., water stains on fences and buildings, or salts extruded on bricks,

SECTION 5 DRAFTING STANDARDS

3. Contractor shall ensure that all permits are obtained prior to any construction. Contractor shall be responsible for all utility fees.

Extreme Wet Weather in Brookfield. How to Keep Your Basement Dry During Heavy Rains and Floods

SUDAS Revision Submittal Form

Storm Drain Inlet Protection - IP

BMP 6.4.6: Dry Well / Seepage Pit

Storm Drain Inlet Protection for Construction Sites (1060)

Louisiana Administrative Code Title 51 Part XIII. Sewage Disposal

SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701)

SEDIMENT/STORMWATER MANAGEMENT BASIN CONSTRUCTION CHECKLIST

CHAPTER 2 HYDRAULICS OF SEWERS

SUBDRAINS AND FOOTING DRAIN COLLECTORS. A. Construct subdrains, subdrain cleanouts and outlets, and footing drain collectors.

Conveyance means a mechanism for transporting water from one point to another, including pipes, ditches, and channels.

CHAPTER 11 STORM DRAINAGE

Updates on Pervious Pavement Design and Construction. Jason T. Peterein, P.E. June 19, 2012

Permeable Interlocking Concrete Pavement (PICP) A Low Impact Development Tool Training for Schools and Universities

SECTION STORM DRAINAGE TABLE OF CONTENTS

Appendix A: BMP Fact Sheets

URBAN DRAINAGE CRITERIA

FIRST RESPONSE: STORM DAMAGE MITIGATION OF A BMP FAILURE

Transcription:

6.2 Flow-Through Planter Figure 6-8: At-grade flow-through planter. Source: City of Emeryville Best uses Treating roof runoff Next to buildings Dense urban areas Locations where infiltration is not desired Advantages Can be adjacent to structures Multi-use Versatile May be any shape Low maintenance Limitations Requires sufficient head Careful selection of plants Requires level installation Susceptible to clogging Flow-through planters are designed to treat and detain runoff without allowing seepage into the underlying soil. They can be used next to buildings and other locations where soil moisture is a potential concern. Flow-through planters typically receive runoff via downspouts leading from the roofs of adjacent buildings. However, flow-through planters can also be set level with the ground and receive sheet flow. Pollutants are removed as the runoff passes through the soil layer and is collected in an underlying layer of gravel or drain rock. A perforated pipe underdrain must be directed to a storm drain or other discharge point. An overflow inlet conveys flows that exceed the capacity of the planter. TREATMENT DIMENSIONS AND SIZING Flow-through planters may be designed with a 4% sizing factor (percentage of the surface area of planter compared to the surface area of the tributary impervious area). The area of impervious surface multiplied by 0.04 sizing factor will equal the footprint of the flow-through planter. Alternatively, calculations may be performed using either the hydraulic sizing criteria for flow-based treatment measures or the hydraulic sizing criteria for combination flow- and volume-based treatment measures, included in Section 5.1. Install an overflow weir adequate to meet municipal drainage requirements. Flow-through planters can be used adjacent to building and within set back area. Flow-through planters can be used above or below grade. Size overflow trap for building code design storm, set trap below top of planter box walls. Planter wall set against building should be higher to avoid overflow against building. Elevation of the surface area may vary as needed to distribute stormwater flows throughout the surface area. CHAPTER 6 PAGE 75

SAN MATEO COUNTYWIDE WATER POLLUTION PREVENTION PROGRAM Minimum 2 and up to12 inches of water surface storage between the planting surface and crest of overflow weir. VEGETATION Plantings should be selected for viability in a well-drained soil. See planting guidance in Appendix A. Use integrated pest management (IPM) principles in the landscape design to help avoid or minimize any use of synthetic pesticides and quick-release fertilizer. Check with the local jurisdiction for any local policies regarding the use of pesticides and fertilizers. Irrigation shall be provided, as needed, to maintain plant life. Trees and vegetation do not block inflow, create traffic or safety issues, or obstruct utilities. INLETS TO TREATMENT MEASURE Flow may enter the treatment measure (see example drawings in Section 5.13): As overland flow from landscaping (no special requirements) As overland flow from pavement (cutoff wall required) Through a curb opening (minimum 18 inches) Through a curb drain With drop structure through a stepped manhole (refer to Figure 5-3 in Chapter 5) Through a bubble-up manhole or storm drain emitter Through roof leader or other conveyance from building roof Where flows enter the biotreatment measure, allow a change in elevation of 4 to 6 inches between the paved surface and biotreatment soil elevation, so that vegetation or mulch build-up does not obstruct flow. Splash blocks, cobbles or rocks shall be installed to dissipate flow energy where runoff enters the treatment measure. For long linear planters, space inlets to planter at 10-foot intervals or install flow spreader. SOIL CONSIDERATIONS SPECIFIC TO FLOW THROUGH PLANTERS Waterproofing shall be installed as required to protect adjacent building foundations. If site conditions permit infiltration to underlying soils, waterproofing is not required. An underdrain system is generally required for flow through planters. Depending on the infiltration rate of in situ soils, the local jurisdiction may allow installation without an underdrain on a case-by-case basis. Underdrain trench shall include a 12-inch thick layer of Caltrans Standard Section 68-1.025 permeable material Class 2, or similar municipality-approved material. A minimum 4-inch diameter perforated pipe shall be placed within the backfill layer. To help prevent clogging, two rows of perforation may be used. Planting soil shall have minimum percolation rate of 5 inches per hour and a maximum long-term percolation rate of 10 inches per hour. Soil specifications are provided in Appendix K. Check with municipality for additional requirements. The biotreatment soil shall be at least 18 inches thick. Provide 3-inch layer of mulch in areas between plantings. SOIL CONSIDERATIONS FOR ALL BIOTREATMENT SYSTEMS Beginning December 1, 2011, soils in the area of inundation within the facility shall meet biotreatment soil specifications approved by the Regional Water Board (Appendix K), which supersedes other soil specifications. The minimum percolation rate for the PAGE 76 CHAPTER 6

biotreatment soil is 5 inches per hour. The long-term desired maximum infiltration rate is 10 inches per hour, although initial infiltration rate may exceed this to allow for tendency of infiltration rate to reduce over time. Filter fabric shall not be used in or around underdrain trench. The underdrain shall include a perforated pipe with cleanouts and connection to a storm drain or discharge point. Clean-out shall consist of a vertical, rigid, non-perforated PVC pipe, with a minimum diameter of 4 inches and a watertight cap fit flush with the ground. There shall be adequate fall from the underdrain to the storm drain or discharge point. CONSTRUCTION REQUIREMENTS FOR ALL BIOTREATMENT SYSTEMS When excavating, avoid spreading fines of the soils on bottom and side slopes. Remove any smeared soiled surfaces and provide a natural soil interface into which water may percolate. Minimize compaction of existing soils. Protect from construction traffic. Protect the area from construction site runoff. Runoff from unstabilized areas shall be diverted away from biotreatment facility. MAINTENANCE CONSIDERATIONS FOR ALL TREATMENT MEASURES A Maintenance Agreement shall be provided. Maintenance Agreement shall state the parties responsibility for maintenance and upkeep. Prepare a maintenance plan and submit with Maintenance Agreement. Maintenance plan templates are in Appendix G. Figure 6-9: Plan view of long, linear planter, with inlets to the planter distributed along its length at 10 intervals. CHAPTER 6 PAGE 77

SAN MATEO COUNTYWIDE WATER POLLUTION PREVENTION PROGRAM Figure 6-10: Plan view of planter designed to disperse flows adequately with only one inlet to planter 4 8 12 of CLASS II PERMEABLE ROCK PER CALTRANS SPECIFICATIONS OR SIMILAR MUNICIPALITY-APPROVED MATERIAL Figure 6-11: Cross section A-A of flow-through planter, shows side view of underdrain (Not to Scale) PAGE 78 CHAPTER 6

OPTIONAL PLANTING MOUND PARAMETERS: 4 8 OR SIMILAR MUNICIPALITY-APPROVED MATERIAL Figure 6-12: Cross section B-B of flow-through planter, shows cross section of underdrain Figure 6-13: Above-grade planters. Source: City of Portland Figure 6-14: Close-up of Flow Through Planter. (Source: City of Portland) CHAPTER 6 PAGE 79