PHOENIX CONTACT

Similar documents
DEK-REL- 24/1/SEN. Extract from the online catalog. Order No.:

Spring Cage Feed-Through Terminal Blocks ST

Electronic overload relay EF19 and EF45

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

PHOENIX CONTACT Features

Manual motor starter MS116

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Redundancy Module QUINT-DIODE/40

MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet _en_01. 1 Description

Feed-through terminal block - SSK 110 KER-EX

PC 4/ 5-STF-7,62. Extract from the online catalog. Order No.:

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Type: DILM50(230V50HZ,240V60HZ) Article No.:

Electronic overload relay EF65, EF96 and EF146

Thermal-Magnetic Circuit Breaker M1-..

Type: DILM32 10(24V50HZ) Article No.:

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start * see variants. Applications.

48 SERIES Relay interface modules 10 A

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

PC 4/ 4-ST-7,62. Extract from the online catalog. Order No.:

GMKDS 3/ 3-7,62. Extract from the online catalog. Order No.:

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M

Type: DILM9 10(24VDC) Article No.:

pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2, /0.65/0.

MINI MCR-SL-R-UI(-SP)

PLC-RS /21. PLC INTERFACE With PDT Relay, Universal Version. INTERFACE Data Sheet _en_02. 1 Description

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

49 Series - Relay interface modules A. Features

E-STOP relays, safety gate monitors

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN , VDE 0113 Part 1

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

RM35UA13MW. range V. Main. Product or component type. Relay monitored parameters

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Catalog. Modular DIN rail components Installation contactors

Safety technique. Emergency stop module BO 5988 safemaster

VEO. V4PF480Y/277VSYTK02 Art.Nr.: V4PF480Y/277VSYTK02P Art.Nr.: TECHNICAL DATA

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

AF / AF09Z stack 3-pole Contactors AC / DC Operated - with Screw Terminals

38 Series - Relay interface modules A

Digital input modules

Three-phase monitoring relay CM-PFE

R.C.C.B. s two-pole LEXIC

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

Technicaldata General

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

5SV Residual Current Protective Devices

PHOENIX CONTACT - 01/2007

ABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x , 2CDG1101xxR0011

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

34 Series - Slim electromechanical PCB relays 6 A. Features SERIES 34.51

ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG R0011

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection

TX OPEN RS232/485 module

38 Series - Relay interface modules A

HERZ-Thermal Actuators

Control Devices Catalogue. Control Devices. Preferred and Standard Products

Electric Rotary Actuator - On/Off or programmable control actuator

Pluggable interface relays CR-P Pcb relays

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D

ABB i-bus KNX Switch Actuator, x-fold, 16/20 A, MDRC SA/S x , 2CDG 110 1xx R0011

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/2x15DC/1

Relés e Contatores de Estado Sólido SIRIUS

RM4TG20 three-phase network control relay RM4-T - range V

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A V AC coil

Thermistor motor protection

PNOZsigma - Base units

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

System pro M compact Miniature Circuit Breaker S 200/S 200 M

Bimetallic Overload Relay Specifications

E-STOP relays, safety gate monitors

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

E-STOP relays, safety gate monitors

Contact expander modules

W DATA SHEET: RESIDUAL CURRENT CIRCUIT BREAKER A, SERIES BCF0 AND BCF6

MasterINTERFACE 39 Series - Relay interface modules

Technical catalogue. Modular DIN rail components Installation contactors

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/2

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

1 pole, 16 A Screw terminal connection 35 mm rail (EN 60715) mounting. 2 pole, 8 A Screw terminal connection 35 mm rail (EN 60715) mounting

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Contact expansion modules

CompactLogix Power Supplies Specifications

Multifunctional three-phase monitoring relays CM-MPS CM-MPS.43

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT Spur 2. Spur 1. Zone 1. Zone 0

60 Series - General purpose relays 6-10 A. Features

RY2 miniature industrial relays

The complete range of consumer switchboards and switchgear

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Product and functional description

Transcription:

Thermomagnetic circuit breakers CLIPLINE Data sheet 103943_en_04 PHOENIX CONTACT 2010-08-18 1 Description The UT 6-TMC M circuit breaker is a single-position overload circuit breaker with thermomagnetic tripping. It is a space-saving circuit breaker with trip-free mechanism in the event of overload and short circuits within the maximum interrupting rating. The UT 6-TMC M is mounted on an NS 35 DIN rail. UT 6-TMC M thermomagnetic circuit breakers feature a compact design, large labeling areas, and a double plug-in bridge shaft. The circuit breakers provide a high level of system availability thanks to their reclosure function and clear status display. Eleven nominal current versions can be selected from 0.5 A to 16 A. The large center labeling area enables clear assignment of the relevant circuit breaker. NOTE: The magnetic tripping ranges differ for alternating currents (AC) and direct currents (DC) (see page 3). The magnetic operating currents for direct currents (DC) are approximately 1.6 times higher. NOTE: When mounted in rows with simultaneous load, a mutual thermal effect occurs (see page 4). Calibration is required for an ambient temperature of +23 C. A correction factor must be used to determine the nominal current for a lower or higher ambient temperature (see page 5). Make sure you always use the latest documentation. It can be downloaded at www.phoenixcontact.net/catalog. This data sheet is valid for all products listed on the following page:

2 Ordering data Circuit breakers Description Nominal current Type Order No. Pcs./Pkt. Thermomagnetic circuit breaker, 1-pos. 0.5 A UT 6-TMC M 0,5A 0916603 6 Thermomagnetic circuit breaker, 1-pos. 1 A UT 6-TMC M 1A 0916604 6 Thermomagnetic circuit breaker, 1-pos. 2 A UT 6-TMC M 2A 0916605 6 Thermomagnetic circuit breaker, 1-pos. 4 A UT 6-TMC M 4A 0916606 6 Thermomagnetic circuit breaker, 1-pos. 5 A UT 6-TMC M 5A 0916607 6 Thermomagnetic circuit breaker, 1-pos. 6 A UT 6-TMC M 6A 0916608 6 Thermomagnetic circuit breaker, 1-pos. 8 A UT 6-TMC M 8A 0916609 6 Thermomagnetic circuit breaker, 1-pos. 10 A UT 6-TMC M 10A 0916610 6 Thermomagnetic circuit breaker, 1-pos. 12 A UT 6-TMC M 12A 0916611 6 Thermomagnetic circuit breaker, 1-pos. 15 A UT 6-TMC M 15A 0916612 6 Thermomagnetic circuit breaker, 1-pos. 16 A UT 6-TMC M 16A 0916613 6 Accessories Description Type Order No. Pcs./Pkt. Plug-in bridge, for cross connection in the bridge shaft, red, 2-pos. FBS 2-6 3030336 50 Plug-in bridge, for cross connection in the bridge shaft, red, 3-pos. FBS 3-6 3030242 50 Plug-in bridge, for cross connection in the bridge shaft, red, 4-pos. FBS 4-6 3030255 50 Plug-in bridge, for cross connection in the bridge shaft, red, 5-pos. FBS 5-6 3030349 50 Plug-in bridge, for cross connection in the bridge shaft, red, 10-pos. FBS 10-6 3030271 10 Plug-in bridge, for cross connection in the bridge shaft, red, 20-pos. FBS 20-6 3030365 10 Warning label, for UT series, yellow WS UT 6 3047345 10 Screwdriver SZS 1,0X4,0 1205066 10 UniCard sheet, for labeling UC-TM 12 (See CLIPLINE catalog) Zack marker strip, for labeling ZB 12 (See CLIPLINE catalog) 3 Electrical data Nominal current, nominal voltage, and additional electrical data Rated insulation voltage Rated frequency Nominal voltage Nominal current AC/DC Operating voltage range Operating frequency range Insulation resistance (main circuit) 440 V AC Insulation resistance 50 Hz: 2000 V Pulse: 2800 V Surge voltage category II Pollution degree 2 50/60 Hz (at 240 V AC) 240 V AC, 28 V DC Depending on module: 0.5 A, 1 A, 2 A, 4 A, 5 A, 6 A, 8 A, 10 A, 12 A, 15 A, 16 A 50 V AC... 264 V AC, 5 V DC... 30.8 V DC 48 Hz... 62 Hz > 100 MΩ Switching cycles Service life under load Overload according to IEC 60943 Overload according to UL 1077 6000 cycles at 1 x I n 40 cycles at 6 x I n 50 cycles at 1.5 x I n 6000 cycles at 1 x I n 40 cycles at 6 x I n 50 cycles at 1.5 x I n Short-circuit switching capacity (Inc) 200 A 400 A Conditional short-circuit switching capacity (Inc)[Backup fuse] 2000 A 2000 A AC DC 103943_en_04 PHOENIX CONTACT 2

Backup fuse Nominal current UT 6-TMC M Maximum backup fuse NOTE: If in the application the maximum short-circuit switching capacity (I cn ) could be exceeded in the event of an error, a backup fuse must be used in combination with the circuit breaker. The following maximum backup fuse values are recommended according to characteristic gg (VDE 0636, IEC 269) Tripping characteristics Type of actuation Tripping method Tripping type Specified non-tripping current (no tripping within an hour) Specified tripping current (tripping within an hour) Instantaneous non-tripping current Instantaneous tripping current 0.5 A 16 A 1 A 16 A 2 A 16 A 4 A 16 A 5 A 20 A 6 A 20 A 8 A 25 A 10 A 25 A 12 A 25 A 15 A 25 A 16 A 25 A Manual ON/OFF (S type) Thermomagnetic (TM) Trip-free mechanism 1.05 x I n 1.32 x I n 6 x I n (AC) 12 x I n (AC) NOTE: The magnetic tripping ranges differ for alternating currents (AC) and direct currents (DC). Please observe the tripping characteristics shown in Figure 1. The magnetic operating currents for direct currents (DC) are approximately 1.6 times higher. 3.1 Tripping characteristics AC tripping characteristics DC tripping characteristics Switching time [s] 10000 1000 100 10 < 7.0A > 7.0A Switching time [s] 10000 1000 100 10 < 7.0A > 7.0A 1 1 0.1 0.1 0.01 0.01 0.001 1 2 3 4 6 8 10 20 40 60 100 Multiples of I N 0.001 1 2 3 4 6 8 10 20 40 60 100 Multiples of I N Figure 1 AC and DC tripping characteristics 103943_en_04 PHOENIX CONTACT 3

3.2 Effect on thermal tripping of mounting in rows NOTE: When mounted in rows with simultaneous load, a mutual thermal effect occurs. The mutual thermal effect is tantamount to an increase in the ambient temperature (see page 5). This depends on the following: The nominal current The ambient temperature The number of devices The distance between devices The nominal device current can be either overdimensioned or limited. When the UT 6-TMC M is mounted in rows, the correction factor is usually in the range of 1.25 or at 80% (reciprocal) in relation to the limiting nominal current. These values apply in the event of continuous load and at an ambient temperature of +23 C. Since the thermal effect varies for each planned installation when mounting in rows, the correction factors must be defined individually and tested. Calculation example for overdimensioning 5 circuit breakers with I n = 10 A are to be mounted in rows. The ambient temperature is +23 C. Nominal current when not mounted I n = 10 A in rows Typical correction factor d f = 1.25 Theoretical nominal current when mounting in rows I n row = 10 A X 1.25 = 12.5 A 3.3 Internal resistance of the UT 6-TMC M Nominal current Resistance 0.5 A 4.37 Ω 1.0 A 0.95 Ω 2.0 A 0.33 Ω 4.0 A 88.0 mω 5.0 A 55.8 mω 6.0 A 41.7 mω 8.0 A 22.2 mω 10.0 A 12.3 mω 12.0 A 10.9 mω 15.0 A 8.3 mω 16.0 A 7.7 mω Measurement between the LINE and LOAD connections. Tolerance: ±10% 4 Mechanical data Fixing Mounting method On a DIN rail according to DIN EN 60715, NS 35N/7,5 or NS 35/15 The tripping characteristics are not dependent on the mounting position. Plug-in bridge, for cross connection in the bridge shaft FBS x-6 plug-in bridge (see "Accessories" on page 2) Connection polarity Independent polarity (for DC) for the LINE and LOAD connections Suitability "Factory wiring" Weight 51 g Housing material PA 66 Fuse type Medium blow fuse Inflammability class according to UL 94 Maximum number of cycles V0 6000 at 1 x I n Connection terminal block Screw connection M4 Connection capacity Solid Stranded With ferrule 1 conductor 0.2 mm²... 10 mm² 0.2 mm²... 10 mm² 0.25 mm²... 6 mm² 2 conductors (two conductors with same cross-section, ferrule without 0.2 mm²... 2.5 mm² 0.25 mm²... 1.5 mm² plastic sleeve) 2 stranded conductors with a TWIN ferrule 0.5 mm²... 4 mm² Stripping length 12 mm Tightening torque (EN 60934) 1.5 Nm... 1.8 Nm 103943_en_04 PHOENIX CONTACT 4

5 Environmental influences 5.1 Temperature range, influence on the ambient temperature NOTE: Calibration is required for an ambient temperature of +23 C. Temperature range Reference temperature The following typical correction factors must be observed to calculate the nominal current: Correction factors -30 C +60 C +23 C I n [A] -30-20 -10 0 10 23 30 40 50 60 0.5 0.77 0.81 0.84 0.87 0.90 1.00 1.03 1.08 1.15 1.21 1 0.77 0.81 0.84 0.87 0.90 1.00 1.03 1.06 1.13 1.19 2 0.77 0.81 0.84 0.87 0.90 1.00 1.03 1.08 1.15 1.21 4 0.77 0.81 0.84 0.87 0.90 1.00 1.03 1.08 1.15 1.21 5 0.77 0.81 0.84 0.87 0.90 1.00 1.03 1.08 1.15 1.25 6 0.70 0.73 0.78 0.84 0.90 1.00 1.03 1.08 1.15 1.21 8 0.70 0.73 0.78 0.84 0.90 1.00 1.03 1.06 1.13 1.21 10 0.78 0.81 0.84 0.87 0.90 1.00 1.05 1.15 1.21 1.30 12 0.77 0.80 0.85 0.90 0.95 1.00 1.03 1.08 1.15 1.21 15 0.73 0.73 0.78 0.84 0.90 1.00 1.03 1.08 1.11 1.21 16 0.70 0.73 0.78 0.84 0.90 1.00 1.03 1.08 1.15 1.21 C 5.3 Resistance to vibrations and shocks Shock resistance according to EN 60068-2-27, Test Ea [3 shocks in each direction (= 18 shocks)] Peak G Pulse length Pulse form 50g 11 ms Half-sine Vibration resistance according to EN 60068-2-6, Test Fc - frequency range: 5 Hz... 500 Hz < 60 Hz (constant amplitude) 0.15 mm 2g 5.4 Approvals Certification body VDE 6 Dimensions > 60 Hz (constant acceleration) Standard License number Approved as IEC 60934 400028127 Circuit Breaker for Equipment UL UL 1077 E140459 Supplementary UL CSA 22.2 No.235 CSA CSA 22.2 No.235 E140459 Supplementary 250505 Supplementary ø 0.75 0.78 0.82 0.86 0.90 1.00 1.03 1.08 1.15 1.22 Example calculation: A circuit breaker with I n = 4 A is to be used at an ambient temperature of +60 C. Nominal current at +23 C I n (+23 C) = 4 A Ambient temperature T amb = +60 C Correction factor df = 1.21 Theoretical nominal current at +60 C I n (+60 C) = 4 A x 1.21 = 4.84 A At +60 C, a nominal current of 5 A should be selected. 5.2 IP protection class IP protection class Actuation area IP40 Connection area IP20 Figure 2 Dimensions (in mm) 103943_en_04 PHOENIX CONTACT GmbH & Co. KG 32823 Blomberg Germany Phone: +49-52 35-30 0 5 PHOENIX CONTACT P.O.Box 4100 Harrisburg PA 17111-0100 USA Phone: +717-944-1300 www.phoenixcontact.com