Pulsar EX 700 / 1000 / 1500

Similar documents
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Pulsar M 2200 RT 2U 2200 RT 3U 3000 RT 2U 3000 RT 3U 3000 RT 3U XL EXB RT 3U Installation and user manual FR/AA - Page 1

NEWTECH PRO KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL

Online UPS. PowerWalker VFI 1000R/1U

How To Use A Power Supply Unit (Upu)

User Manual. English. APC Smart-UPS 500 VA 100 VAC 750 VA 100/120/230 VAC. Tower Uninterruptible Power Supply

HP UPS R1500 Generation 3

Powerware 5110 UPS User s manual

Back-UPS Pro 1300/1500 Installation and Operation

User Manual. English. APC Smart-UPS SC. 1000/1500 VA 110/120/230 Vac. 2U Tower/Rack-Mount Uninterruptible Power Supply

User Manual 1K/2K/3K Online UPS

Comet EX 5 RT 3:1 EX 7 RT 3:1 EX 11 RT 3:1

Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS

10000HXL31/15000HXL31/20000HXL31

User s Manual AURORA 1.2K/2.2K

Installation and Operation Back-UPS 1250, 1300, 1500

USER S MANUAL. MaxPower UPS. Uninterruptible Power System 28-2MAXPO0018

USER MANUAL Online UPS 1K/2K/3K

User s Manual. Professional Rack Mount LCD Series PR1000ELCDRT2U/PR1500ELCDRT2U/ PR2200ELCDRT2U K

=============================== WARNING

USER MANUAL Online UPS 1K/2K/3K Rack

EATS16 EATS16N. Installation and user manual ENGLISH. Copyright 2015 EATON All rights reserved.

User s Manual Before using the inverter, you need to read and save the safety instructions.

Back-UPS 650 VA 120 V with AVR (BX650CI-LM)

Line Interactive UPS

12 Volt 30 Amp Digital Solar Charge Controller

750VA/1000VA/1500VA 100/120/230VAC 2U

User Manual. English. APC Smart-UPS VA 120/230 Vac VA 100/120/208/230 Vac. 2U Rack Mount Uninterruptible Power Supply

SNMP Web card. User s Manual. Management Software for Uninterruptible Power Supply Systems

SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial

Line Interactive UPS. PowerWalker VI 500T/HID PowerWalker VI 750T/HID PowerWalker VI 1000T/HID PowerWalker VI 1500T/HID.

SmartPro 230V 1000VA 900W Line-Interactive Sine Wave UPS, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial

HotSwap MBP Maintenance Bypass

Match. GE Digital Energy. Uninterruptible Power Supply VA. Technology for the Digital World. Match UPS. GE Digital Energy.

Safety Precautions WARNINGS

VA

350, 500, 650 and 1000 MODELS

Owner s Manual. Not suitable for mobile applications. Important Safety Instructions 2. Quick Installation 3. Basic Operation 4. Storage & Service 7

Rack Mount LCD KVM Assembly Installer/User Guide

12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual

Infinity C Reference Guide

ViewPower. User s Manual. Management Software for Uninterruptible Power Supply Systems

User Manual. English. APC Smart-UPS 1000/1500 VA 100/120/230 VAC 750/1000XL VA 120/230 VAC. Tower Uninterruptible Power Supply

AC-115 Compact Networked Single Door Controller. Installation and User Manual

HP R12000 and R18000 DirectFlow UPS User Guide

ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS

Installation and Operating instructions for. Control Cabinet Industrial PC C Version: 1.3 Date:

APC Smart-UPS 2400/3000 VA 100/ VAC 3U. Uninterruptible Power Supply

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

Lenovo Miix 2 8. User Guide. Read the safety notices and important tips in the included manuals before using your computer.

Installation Guide Smart-UPS X Tower/Rack-Mount 2U 2000/2200/3000 VA

GSM Alarm System User Manual

PD 100A. Printing data system

Permissible ambient temperature Operation Storage, transport

SPL 2-00/-01 OPERATION INSTRUCTIONS

Portable Air Conditioner

INSTRUCTION MANUAL PLEASE READ ALL THE INSTRUCTIONS COMPLETELY BEFORE USE AND SAVE THIS MANUAL FOR FUTURE REFERENCE

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

PU-USBX. USB over Ethernet Extender OPERATION MANUAL

MCR1900 Media Converter 19-Slot Chassis

USER MANUAL Online UPS 6K/10K RACK

MANUAL. * Supply plugs may differ to suit your wall socket. EN 3. Continue to press the MODE-button to combine charging program with charging options.

NeTYS PR VA

GB USER S MANUAL GB 41

How to read this guide

Galleon 6-10K Online UPS. Voltronic Power Technology Corporation

ekil 3 KGK tecrübesi olmayan herhangi bir ki i tarafından çalı tırılabilir.

SNMP Web Management. User s Manual For SNMP Web Card/Box

Keysight N4877A Clock Data Recovery and Demultiplexer 1:2

UPS Monitoring and Management Software

GV- RK1352 Card Reader

Workshop 7 PC Software - Tracker

User Manual. English. APC Smart-UPS RT. 3000/5000/6000 VA VAC Tower/Rack Mount 3U Uninterruptible Power Supply

Operating Manual for the Electronic Built-in Interval Timer. Micro II (Countdown Timer)

Achat 115MA full-range speaker. user manual

Single Day Alarm Clock with. Bluetooth and USB Play-through

3000W Power Inverter

Liebert GXT MT+ CX UPS, 1000VA VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity

DLP-PU/E Instruction Manual

Liebert GXT3 UPS 230V 700VA-3000VA

Wave/PC Interactive System USB Adapter Kit. Installation Guide

User Manual. Smart-UPS. Uninterruptible Power Supply 750/1000/1500 VA. 100/120/230 Vac. Rack Mount 2U

HP ProDisplay P19A LED Backlit Monitor. User Guide

TMS TANK MANAGEMENT SYSTEM

USER MANUAL CHARGING STATIONS FOR ELECTRIC VEHICLES

Smart-UPS APC Smart-UPS 1000VA USB & Serial 230V

Model 70A00-1. GSM Cellular Communications Center

Installation and User Guide

Ambient Temperature In Range Probe X

Battery Power Inverters

Instructions: Part I. Charge the Power Bank. Method 1. Charge the Power Bank via Computer USB Terminal.

Programmable Room Thermostat 7 Day (5-2 Day) Models: / Power Supply: Battery / Mains

SCD Server. SCD Server Pro

instabus KNX / EIB System System E F G H

ST Series POWER SUPPLIES USER INSTRUCTIONS

Job Aid Pre-Installation Information S8500 Media Server

MANUAL PC1000R

Compaq Presario Desktop Products. Upgrading and Servicing Guide

FUSION R400 RAID USB 3.0

Transcription:

Pulsar EX 700 / 000 / 500 Installation and user manual 503604EN/AA - Page

Introduction Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment. The Pulsar EX range has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your UPS. MGE UPS SYSTEMS pays great attention to the environmental impact of its products. Measures that have made Pulsar EX a reference in environmental protection include: the eco-design approach used in product development; recycling of Pulsar EX at the end of its service life. To discover the entire range of MGE UPS SYSTEMS products and the options available for the Pulsar EX range, we invite you to visit our web site at www.mgeups.com or contact your MGE UPS SYSTEMS representative. Page - 503604EN/AA

Safety Safety rules Safety of persons A UPS has its own internal power source (the battery). Consequently, the power outlets may be energised even if the UPS is disconnected from the AC-power source. Product safety Special precautions Dangerous voltage levels are present within the UPS. It should be opened exclusively by qualified service personnel. The UPS must be properly earthed. Measurements are required to ensure that the total leakage current of the UPS and the protected equipment does not exceed 3.5 ma. The battery supplied with the UPS contains small amounts of toxic materials. To avoid accidents, the directives listed below must be observed: Never burn the battery (risk of explosion). Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin). Comply with all applicable regulations for the disposal of the battery. Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high. Precautions must be taken for all handling. UPSs must be connected to a nearby wall outlet that is easily accessible. The UPS can be disconnected from the AC-power source by removing the power cord. Never install the UPS near liquids or in an excessively damp environment. Never let a foreign body penetrate inside the UPS. Never block the ventilation grates of the UPS. Never expose the UPS to direct sunlight or a source of heat. The UPS connection instructions contained in this manual must be followed in the indicated order. Check that the indications on the rating plate correspond to your AC-power system and to the actual electrical consumption of all the equipment to be connected to the UPS. If the UPS must be stored prior to installation, storage must be in a dry place. The admissible storage temperature range is -0 C to +45 C. If the UPS remains de-energised for a long period, we recommend that you energise the UPS for a period of 4 hours, at least once every month. This charges the battery, thus avoiding possible irreversible damage. Prior to handling the battery: remove all watches, rings, bracelets and any other metal objects; use tools with insulated handles. 503604EN/AA - Page 3

Foreword Using this document Information may be found primarily by consulting: the contents, the index. Pictograms Important instructions that must always be followed. Information, advice, help. Visual indication. Action. Audio indication. In the illustrations on the following pages, the symbols below are used: LED off. LED on. LED flashing. Page 4-503604EN/AA

Contents. Presentation. Pulsar EX range... 7 Tower model... 7 Rack model... 7. Back... 8 Tower model... 8 Rack model... 9.3 Control panel... 0. Installation. Unpacking and checks... Tower model... Rack model.... Installation of the rack version... 3.3 Connection to the RS 3 or USB communications port (optional)... 4.4 Installation of the communications-card option... 5 Tower model... 5 Rack model... 5.5 Connections... 6 Tower model... 6 Rack model... 6 3. Operation 3. Start-up... 7 3. Bargraph indications... 7 3.3 Operation on battery power (following failure of AC input power)... 8 Transfer to battery power... 8 Threshold for the low-battery warning... 8 End of backup time... 8 Sleep mode... 8 503604EN/AA - Page 5

Contents 3.4 Personalisation (optional)... 9 Function... 9 "ON / OFF conditions" tab... 9 "Battery" tab... 9 "Output" tab... 0 "Bypass" tab... 0 3.5 Shutdown... 0 4. Maintenance 4. Troubleshooting... 4. Replacement of the battery module... Tower model... Rack model... 3 5. Environment... 4 6. Appendices 6. Technical characteristics... 5 Simplified diagram... 5 Operating conditions... 5 6. Glossary... 6 6.3 Index... 7 Page 6-503604EN/AA

. Presentation. Pulsar EX range Tower model EX 700 / EX 000 EX 500 Dimensions in mm (H x W x D) 35.5 x 45 x 400 35.5 x 45 x 505 Weight in kg EX 700 EX 000 EX 500 0 5 Rack model EX 700 Rack EX 000 Rack EX 500 Rack Dimensions in mm (H x W x D) 88 (U) x 48.6 x 430 88 (U) x 48.6 x 430 88 (U) x 48.6 x 493 Weight in kg EX 700 Rack EX 000 Rack EX 500 Rack 4 6 0 EX000 Rack 503604EN/AA - Page 7

. Presentation. Back Tower model Pulsar EX 700 / Pulsar EX 000 slot for communications-card option. RS3 USB 3 RS3 communications port. 4 3 USB communications port. 4 four outlets for direct connection of protected equipment. 5 6 5 connector for automatic detection of an additional battery module. 7 8 9 0 6 7 8 input circuit breaker. socket for connection to AC-power source. connector for an additional battery module. Pulsar EX 500 RS3 USB 3 9 0 pushbutton to test phase/neutral inversion of AC-power source. LED indicating phase/neutral inversion of AC-power source. 4 two programmable outlets (outlet and ). 5 8 9 0 6 7 Page 8-503604EN/AA

. Presentation Rack model Pulsar EX 700 Rack / Pulsar EX 000 Rack / Pulsar EX 500 Rack 3 7 4 USB RS3 6 0 9 5 8 slot for communications-card option. 7 socket for connection to AC-power source. RS3 communications port. 8 connector for an additional battery module. 3 4 5 USB communications port. four outlets for direct connection of protected equipment. connector for automatic detection of an additional battery module. 9 0 pushbutton to test phase/neutral inversion of AC-power source. LED indicating phase/neutral inversion of AC-power source. two programmable outlets (outlet and ). 6 input circuit breaker. 503604EN/AA - Page 9

. Presentation.3 Control panel % Alarms % battery remaining % load 00% UPS overload. 00% 00% 80% 3 electronics fault. 80% 80% 50% 4 battery fault. 50% 50% 0% 5 0% 0% % 6 hold down to display percent load: test 7 - lamp test or buzzer OFF. - forced transfer to bypass and back by pressing button 3 times in less than 5 seconds. 8 status of programmable outlet : Supplied with power by-pass 9 0 status of programmable outlet : operation on bypass (no backup power available). Status change in progress. operation in ON-LINE mode (backup power available). operation on battery power. 3 ON / OFF. Page 0-503604EN/AA

. Installation. Unpacking and checks Tower model 4 5 6 7 8 9 4 5 6 7 8 two cords for connection of the protected equipment. RS 3 communications cable. USB communications cable. "UPS Driver" diskette for UPS personalisation. "Solution Pac" CD ROM. 9 documentation. 503604EN/AA - Page

. Installation Rack model 4 4 5 6 EX000 Rack 7 8 9 30 4 two cords for connection of the protected equipment. 5 RS 3 communications cable. 6 USB communications cable. 7 "UPS Driver" diskette for UPS personalisation. 8 "Solution Pac" CD ROM. 9 documentation. 30 telescopic rails for mounting in 9" bay with mounting hardware. Page - 503604EN/AA

. Installation. Installation of the rack version Rack mounting diagram with rails. 3 3 3 4 3 EX000 Rack The rails and the necessary mounting hardware are supplied by MGE UPS SYSTEMS. 503604EN/AA - Page 3

. Installation.3 Connection to the RS 3 or USB communications port (optional) 5 - Connect the RS 3 5 or USB 6 communications cable to the serial port or the USB port on the computer. RS3 USB 3 6 - Connect the other end of the communications cable 5 or 6 to the RS 3 or USB 3 communications port on the UPS. The UPS can now communicate with all MGE UPS SYSTEMS supervision, set-up or safety software. 3 The RS 3 and USB communications ports cannot operate simultaneously. Page 4-503604EN/AA

. Installation.4 Installation of the communications-card option Tower model U-Talk USB Slot for the communications-card option. It is not necessary to shut down the UPS to install the communications card: - Remove the slot cover secured by two screws. - Insert the card in the slot. 3 - Secure the card with the two screws. Rack model Slot for the communicationscard option. USB RS3 503604EN/AA - Page 5

press. Installation.5 Connections Check that the indications on the rating plate on the back of the UPS correspond to your AC-power system and to the actual electrical consumption of all the equipment to be connected to the UPS. Tower model 4 - Remove the power cord supplying the equipment to be protected. Check cord characteristics (> 50 V, 0 A, see the technical sheet).? reset 7 - Connect the cord to the AC-power socket 7, then to the AC-power wall outlet. Rack model 4 3 - Connect the protected equipment to the UPS using the two cords 4. It is advised to connect priority loads to the four outlets 4 and any non-priority loads to the two programmable outlets (If the UPS is connected to a computer running MGE communications software, it is possible to program the interruption of power to the two programmable outlets during operation on battery power, thus reserving backup power for the priority loads). 7 4 As soon as the UPS is energised, the battery begins charging. Eight hours are required to charge to the full rated backup time. 4 Page 6-503604EN/AA

3. Start-up 3. Operation The protected equipment connected to the UPS can be energised, whether AC input power is available or not. 3 Press the ON / OFF button 3. The buzzer beeps and all the LEDs go ON. The buzzer beeps twice, then: - If AC input power is available, LED goes ON, indicating operation in ON-LINE mode. - If AC input power is not available and the UPS is configured for automatic restart mode, the buzzer beeps three times and LED goes ON, signalling operation on battery power. All connected equipment is energised. If LEDs or do not go ON or if LEDs to 4 flash, there is a fault (see section 4.). 3. Bargraph indications % 00% 80% 50% 0% % test 3 4 5 6 LEDs to 5 provide three different indications: - Remaining backup time in percent (during normal operation). - Percent load drawn by the protected equipment, when button 6 is pressed. 3 - Operating faults (flashing LED and beeps): Overload. 3 UPS fault. 4 Battery fault. by-pass 8 9 Status LEDs 8 and 9 for programmable outlets and : - LEDs OFF: the outlets are not supplied with power. - LEDs flashing: status change in progress. - LEDs ON: the outlets are supplied with power. Outlets and can be remotely programmed and controlled. They may be used for sequential start-up of the protected applications, shedding of non-priority applications during operation on battery power, and priority management at the end of battery backup time to reserve the longest possible backup time for the most sensitive applications. These outlets are programmed using Solution Pac software. 503604EN/AA - Page 7

3. Operation 3.3 Operation on battery power (following failure of AC input power) Transfer to battery power The AC-power source is outside tolerances, LED 3 is ON, the buzzer beeps three times. by-pass The equipment connected to the UPS is supplied by the battery. Threshold for the low-battery warning by-pass The low-battery warning threshold can be set by the user, with the "UPS Driver" software (see section 3.4). LED flashes. The buzzer beeps every three seconds. There is very little remaining battery backup time. Close all applications because UPS automatic shutdown is imminent. End of backup time % The buzzer sounds continuously. Press button 7 to turn the buzzer OFF. test 7 The equipment is no longer supplied with power. by-pass Sleep mode The UPS goes to sleep mode at the end of the battery backup time (LEDs to 5 ON) until complete shutdown due to tripping of the battery-protection function against deep discharge. Return of AC input power: If, in spite of the return of AC input power, the UPS does not restart, check that the automatic-restart function (activated by return of AC input power) has not been disabled (see section 3.4). Page 8-503604EN/AA

3.4 Personalisation (optional) Function 3. Operation Personalisation parameters can be set and modified using the "UPS Driver" software installed on a computer that is connected to the UPS (see section.3 Connection to the RS 3 (or USB) communications port). Check that the RS 3 5 or USB 6 cable is properly connected. "UPS Driver" installation: - Insert the "UPS Driver" diskette in the drive of a PC running Windows. - Select the disk drive (A:\). 3 - Double-click "upsdriv.exe". Once "UPS Driver" has been installed, UPS parameters can be modified in a window containing a number of tabs, each presenting a set of parameters. "ON / OFF conditions" tab Personalisable function Automatic start Cold start (battery power) Forced shutdown Sleep mode UPS ON / OFF via software Default setting Enabled Enabled Enabled Disabled Enabled Options Disabled Disabled Disabled Enabled Disabled "Battery" tab Personalisable function Automatic "Battery test" intervals "Low-battery warning" threshold Default setting Every day Options Once a week Once a month No test 0% remaining battery backup time 40% remaining battery backup time 503604EN/AA - Page 9

3. Operation "Output" tab Personalisable function Rated UPS voltage Rated UPS frequency UPS tolerance for AC-power source frequency Overload alarm threshold UPS restart following short-circuit Default setting 30 V F = 50 Hz F ± 5% 0% Disabled Options 00 V - 08 V - 0 V - 40 V 60 Hz F ± % to ± 0%, in % steps 0 to 0%, in 0% steps Enabled (click to add check) "Bypass" tab Personalisable function Transfer to bypass if overload Transfer to bypass following a fault, whatever the conditions on the AC-power source Default setting Enabled Disabled Options Disabled (click to remove check) Enabled (click to add check) 3.5 Shutdown by-pass Press button 3 (return to the OFF position). The connected equipment is no longer supplied with power. 3 Page 0-503604EN/AA

4. Troubleshooting If any of LEDs, 3 or 4 flash, there is a operating anomaly or an alarm. 4. Maintenance If a LED flashes, the bargraph data is no longer displayed. Troubleshooting not requiring MGE UPS SYSTEMS after-sales support Indication LED flashes and the buzzer beeps. LED 4 flashes. Signification UPS overload. Overload is too long or too high. The buzzer sounds continuously. If AC power is present and within tolerances, the UPS goes to bypass mode (supply directly by the AC-power source). LED 0 flashes. If AC power is not present or not within tolerances, the connected applications are no longer supplied. A battery fault was detected during the automatic battery test. Correction Check the power drawn by the equipment and disconnect any nonpriority devices. Connect that the battery connector is fully pushed in. Replace battery module (see the Maintenance section). Troubleshooting requiring MGE UPS SYSTEMS after-sales support Indication LED 3 flashes and the buzzer sounds continuously. Signification UPS electronics have detected a UPS fault. Depending on the UPS personalisation parameters (see section 3.4), there are two possibilities: the equipment connected to the UPS continues to be supplied, but directly from the AC-power source (via the automatic bypass (LED 0 ON); the connected equipment is no longer supplied. The equipment connected to the UPS is no longer protected. Correction Call the after-sales support department. 503604EN/AA - Page

4. Maintenance 4. Replacement of the battery module Tower model Safety rules: Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high. Precautions must be taken for all handling: remove all watches, rings, bracelets and any other metal objects; use tools with insulated handles. Removal of battery module A - Press to open door. B - Slide the door open and remove it. C D E - Procedure to remove the protective cover. F - Disconnect the battery module. G - Remove the battery module. B C F D G A E Reinstallation of the battery module Carry out the above operation in reverse order. To maintain an identical level of performance and safety, use a battery module identical to that previously mounted in the UPS. Press the two parts of the battery connector tightly together to ensure proper connection. Page - 503604EN/AA

4. Maintenance Rack model Removal of battery module A - Remove the two screws securing the door. B - Slide the door open and remove it. C - Unscrew the bar that holds the battery module in place. D - Remove the bar. E - Disconnect the battery module. F - Remove the battery module. E B A D C F Reinstallation of the battery module Carry out the above operation in reverse order. To maintain an identical level of performance and safety, use a battery module identical to that previously mounted in the UPS. Press the two parts of the battery connector tightly together to ensure proper connection. 503604EN/AA - Page 3

5. Environment This product has been designed to respect the environment: It does not contain CFCs or HCFCs. UPS recycling at the end of service life: MGE UPS SYSTEMS undertakes to recycle, by certified companies and in compliance with all applicable regulations, all UPS products recovered at the end of their service life (contact your MGE branch office). Packing: UPS packing materials must be recycled in compliance with all applicable regulations. Warning: This product contains lead-acid batteries. Lead is a dangerous substance for the environment if it is not properly recycled by specialised companies. Web site: www.mgeups.com Page 4-503604EN/AA

6. Appendices 6. Technical characteristics Simplified diagram Operating conditions Relative humidity: 0 to 90% without condensation. Temperature: 0 to 40 C. 503604EN/AA - Page 5

6. Appendices 6. Glossary Authorised voltage range for transfer to bypass if fault or overload Automatic bypass Automatic start following return of AC input power Backup time Bargraph Battery test Dialog box Double conversion Equipment Forced shutdown Percent load Personalisation Programmable outlets Start on battery power UPS UPS ON / OFF via software Upper and lower voltage thresholds within which the UPS can operate on the automatic bypass in the event of a UPS fault or overload. Automatic switch controlled by the UPS, used to connect the equipment directly to the AC-power source in the event of a UPS failure or an overload. This function automatically starts the UPS when AC input power returns following shutdown at the end of the battery backup time. It can be enabled or disabled. Time that the connected equipment can operate on battery power. Device on the front panel indicating the percent remaining backup time or the percent load. Internal UPS test on battery status. A window in a computer program displayed for selection by the user of various options and parameter settings. The power supplied to the connected equipment is completely regenerated by continuous double conversion, i.e. the AC power from the AC-power source is rectified (AC - DC), then converted back (DC - AC) to AC power. Devices or systems connected to the UPS output. Ten-second interruption in the supply of power to the connected equipment following a system shutdown, even if AC input power returns during the interruption period. Ratio between the power drawn by the connected equipment and the total power that the UPS can supply. A number of UPS functions can be modified using the «UPS Driver» software to better meet the user s needs. Outlets that can be automatically shed during operation on battery power (a shedding time delay may be programmed using Solution-Pac software. This function makes it possible to energise the connected equipment even when AC input power is not available (operation exclusively on battery power). Uninterruptible Power Supply It is possible to enable or disable use of UPS ON / OFF controls by the computersystem protection software. Page 6-503604EN/AA

6.3 Index A AC power Failure... 8 Frequency tolerance... 0 Return... 8 Automatic start... 9 B Bargraph... 0-7 Battery Battery test... 9 End of backup time... 8 Fault... 0-7 Handling precautions... 3 Low-battery warning... 9 Recycling... 3-4 Replacement... -3 Transfer to battery power... 8 Buttons... 8-9-0 Buzzer... 7-8 Bypass Automatic bypass... 0-0- C Communication... 8-9-4-5 Connection Additional battery module... 8-9 Communications card... 4 RS 3 communications port... 4 USB communications port... 4 D Dimensions... 7 E Environnement... -3-4 F Fault (UPS)... 0-7- 6. Appendices M Mode ON LINE mode... 0 O Overload... 0-0- S Safety... 3 Shutdown Buzzer... 0-8 Forced shutdown... 9 UPS ON / OFF via software... 9 UPS shutdown... 0-0 Sleep mode... 8-9 Automatic restart... 9-0 Software UPS Driver...9 Start-up... 7 T Technical characteristics... 5 Temperature Excessive ambient temp.... 5 Transfer (forced)... 0 U UPS Driver... 9 UPS fault... 0-7-0 UPS storage... 3 W Web site... Weight... 7 L LEDs... 8-9-0 Lamp test... 0 503604EN/AA - Page 7

Page 8-503604EN/AA