Water Mist System Test Methods: Comparison of FM, UL and IMO Procedures

Similar documents
Safety of Life at Sea, 1974 (SOLAS)

TECHNICAL NOTES. Literature Review on Hybrid Fire Suppression Systems. Peter Raia Michael J. Gollner University of Maryland

GUIDELINES FOR THE DRAINAGE OF FIRE-FIGHTING WATER FROM CLOSED VEHICLE AND RO-RO SPACES AND SPECIAL CATEGORY SPACES OF PASSENGER AND CARGO SHIPS

Watermist fire suppression systems for commercial low hazard occupancies

High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications

IMO. 8 June 1998 *** I:\CIRC\MSC\848.WPD INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR

ANNEX 3. RESOLUTION MSC.339(91) (adopted on 30 November 2012) ADOPTION OF AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE)

Challenges for Use of Fixed Fire Suppression Systems in Road Tunnel Fire Protection

Safer.Smarter.Tyco. Watermist fire protection Technology you can trust

New Water Mist Solutions according to Annex B of CEN TS Guidelines for developing fire test procedures for Water Mist Systems

Inert Gas Extinguishing System Two Minute Discharge Study. Gene Hill, P.E. Brad Stilwell

M-20.2 SOLAS II-2. The latest IMO Briefing (IMO 29,2000) offered the following description of the 73rd Meeting of the Maritime Safety Committee:

Ethanol Vehicle and Infrastructure Codes and Standards Citations

PANAMA MARITIME AUTHORITY MERCHANT MARINE CIRCULAR MMC-281

Denver Fire Department Idle Pallet Storage Guidelines Per NFPA 13_Chpt 12

EXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS

- Save lives and reduce material damage

OVERSEAS MARINE CERTIFICATION SERVICES (OMCS)

SPRINKLER RULES & STANDARDS IN EUROPE CEA 4001 & EN 12845

Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009

International Code for Fire Safety Systems (FSS Code) Resolution MSC.98(73)

MOTOR FUEL DISPENSING SAFETY

Working Towards Protection Guidance for Warehouse Storage Li-ion Batteries

ANALYSIS OF FIRE HAZARD AND SAFETY REQUIREMENTS OF A SEA VESSEL ENGINE ROOMS

Approval Standard for Hybrid (Water and Inert Gas) Fire Extinguishing Systems

Commercial Kitchen Fire Safety

INTERNATIONAL REGULATIONS FOR HIGH-SPEED CRAFT AN OVERVIEW *

Preliminary study of the Øko-Ø-færge project

REPUBLIC OF ALL SHIPOWNERS, OPERATORS, MASTERS AND OFFICERS OF MERCHANT SHIPS, AND RECOGNIZED ORGANIZATIONS

MSC/Circ June 2001 GUIDELINES ON ALTERNATIVE DESIGN AND ARRANGEMENTS FOR FIRE SAFETY

Resolution A.1053(27) Adopted on 30 November 2011 (Agenda item 9)

MOBILE OFFSHORE DRILLING UNITS 2012

EACH CLASS of fire A, B, C, or D has a different source. Some

Inspection and Testing of Water-Based Systems

RESIDENTIAL SPRINKLER INSTALLATION GUIDE

Performance Criteria of Systems to Reduce Fire Damage by Prevention or Suppression

FLAMMABILITY REQUIREMENTS FOR AIRCRAFT SEAT CUSHIONS

FUELING AND FUEL STORAGE

Extended Coverage Sprinklers

THE REPUBLIC OF LIBERIA LIBERIA MARITIME AUTHORITY

In accordance with NFPA 30, these containers are not to store Class I flammable liquids.

LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.

Technical Information

Part 0 - Classification and Surveys Classification and Surveys I

Effectiveness of sprinklers in residential premises: Section 4: Benchmark tests. Project report number Dr Corinne Williams and R Harrison

ANNEX 1. RESOLUTION MSC.380(94) (adopted on 21 November 2014)

PANAMA MARITIME AUTHORITY

UNIFIED INTERPRETATION OF PARAGRAPH OF THE LSA CODE UNIFIED INTERPRETATION OF SOLAS REGULATION II-1/26.3

- Save lives and reduce material damage

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description

FIRE SAFETY SHIPS RULES FOR CLASSIFICATION OF NEWBUILDINGS DET NORSKE VERITAS MACHINERY AND SYSTEMS MAIN CLASS PART 4 CHAPTER 10 JANUARY 2001

UL 300 Standard. RS 1021 (9/13) 2013 Nationwide Mutual Insurance Company Page 1 of 6 All Rights Reserved

LIST OF CERTIFICATES AND DOCUMENTS REQUIRED TO BE CARRIED ON BOARD SHIPS, 2013

HSE information sheet. Fire and explosion hazards in offshore gas turbines. Offshore Information Sheet No. 10/2008

Fire suppression in buildings using water mist, fog or similar systems

12 November 2008 *** I:\CIRC\MEPC\01\642.DOC INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR

Fire-Rated Glass and Glazing START

Fire Pump Plan Review March 2010

FIRE-FIGHTING SYSTEMS

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011

Decree of the Ministry of the Environment on fire safety of ventilation systems

Fire Extinguishers. A Health and Safety Guideline for Your Workplace. Fire Extinguishing Methods. Introduction. Types of Extinguishers

GUIDELINE 5. CLASSES OF FIRE, TYPES OF PORTABLE FIRE EXTINGUISHERS, INSPECTION & MAINTENANCE OF FIRE EXTINGUISHERS IN UNIVERSITY BUILDINGS

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

IMO REQUIREMENTS FROM JULY 2015 TO JULY 2018 INCLUSIVE

All You Ever Wanted to Know About Fire Extinguishers...

Türk Loydu Newsletter

To: All Shipowners, Ship Managers, Ship Masters and Classification Societies

Casey C. Grant, P.E., FSFPE Research Director Fire Protection Research Foundation

Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection. OSHA Office of Training and Education 1

FedEx s Fire Suppression System

PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS

IMO Ships Systems & Equipment (SSE 1)

Approval Standard for Plastic Suspended Ceiling Panels

MAIB SAFETY BULLETIN 1/2006. Fire on board the Bermuda registered cruise ship. Star Princess

BP WIND ENERGY POLICIES AND PROCEDURES

A Code Review for Emergency Generators and Indoor Use of Portable Generators

STEEL VESSELS UNDER 90 METERS (295 FEET) IN LENGTH 2012

COMPARISON TESTING IN A SIMULATED DATA PROCESSING/ TELECOMMUNICATIONS FACILITY: FM-200 AND AUTOMATIC SPRINKLER SYSTEMS

Know the Code: Using Spray Foam Insulation In Attics and Crawl Spaces

FIRE CODE INTERPRETATION

ANNEX 17 DRAFT AMENDMENTS TO SOLAS REGULATIONS II-2/4 AND II-2/16. Part B Prevention of fire and explosion

Fire Extinguishers Water Extinguishers

MINISTRY OF TRANSPORTATION OF THE REPUBLIC OF LITHUANIA MARINE SHIP ACCIDENT AND INCIDENT INVESTIGATION MANAGER

FOR CERTIFICATION AS PRESCRIBED BY THE STATE FIRE PREVENTION COMMISSION ON NOVEMBER 11, 2009 IN ACCORDANCE WITH THE STATE FIRE PREVENTION REGULATIONS

Fire testing for BCA compliance

ELECTRIC/DIESEL FIRE PUMP CHECK LIST

FIRE PROTECTION SYSTEMS

SOLAS CONSOLIDATED EDITION Supplement December 2015

1.0 Purpose Definitions Hot Work Operations. 5

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP

HealthandSafetyOntario.ca. Introduction. Storage Containers. Storing Flammable Liquids

city of edmonds development information

FIRE,FIREFIGHTING & FIREFIGHTING EQUIPMENT

18 June 2001 GUIDELINES ON FIRE TEST PROCEDURES FOR ACCEPTANCE OF FIRE-RETARDANT MATERIALS FOR THE CONSTRUCTION OF LIFEBOATS

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings

Recommendations for the Safety of Cargo Vessels of less than Convention Size

presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Monday, 17 June, 13

and Extinguisher Training

Tema. Easily installed automatic extinguishing system

Transcription:

Suppression and Detection Research and Applications (SUPDET 2016) San Antonio, TX, March 1-4, 2016 Water Mist System Test Methods: Comparison of FM, UL and IMO Procedures Jason P. Huczek Principal Engineer Southwest Research Institute Fire Technology Department

OUTLINE Introduction Water Mist Standard Background FM 5560 UL 2167 IMO Resolutions NFPA 750 Comparison of Light/Ordinary Hazard Requirements Comparison of Machinery Space Requirements Questions San Antonio Sights

INTRODUCTION Hazard/Occupancy FM 5560 UL 2167 IMO Resolution NFPA 750* Light/Ordinary Hazard Appendix G Sections 41-43, 45-46 MSC.265, Sections 5-7 Chapter 10, Annex C Cabin/Corridor Section G.4.1-G.4.2 Sections 41-42, 45 Section 5 Chapter 10, Annex C Public/Open Spaces Section G.4.3-G.4.5 Sections 43, 46 Section 6 Chapter 10, Annex C Storage/Ord. Spaces N/A Sections 43, 46 Section 7 Chapter 10, Annex C Machinery Spaces Appendix A, C and E Section 40 1165/1237/1269 Chapter 16, Annex C Turbine Spaces Appendix B, D and F Section 40 1165/1237/1269 Chapter 16, Annex C Local Applications Appendix I N/A 913/1387 Chapter 16, Annex C Residential Applications N/A Section 44 N/A Chapter 10, Annex C Roll-on / Roll-off Spaces on a Ship N/A N/A 1272 N/A Balcony Spaces on a Ship N/A N/A 1268 N/A * Annex C of NFPA 750 provides a good overview of different fire test protocols, but it is not completely up to date.

INTRODUCTION Photos of Selected Tests in Progress

TEST STANDARD BACKGROUND FM 5560 FM 5560, Approval Standard for Water Mist Systems Sections 1-3: Introduction, General Information and General Requirements. Section 4: Performance Requirements (system component testing) Section 5: Operations Requirements (QA testing) Appendices: Fire Test Methods A-F: Machinery and Turbine Spaces G: Hazard Category 1 (HC-1) [previously called Light Hazard] H: Wet Bench I: Local Application

TEST STANDARD BACKGROUND FM 5560 (cont.) Appendices: Fire Test Methods (cont.) J: Industrial Oil Cookers K: Computer Room Raised Floors L: Continuous Wood Board Presses M: Chemical Fume Hoods (not included in Annex C of 2015 edition of NFPA 750) New Fire Test Methods (2016 Edition) N: Data Processing Equipment Rooms/Halls Above Raised Floor O: Data Processing Equipment Rooms/Halls Below Raised Floor P: Scaling Methodology for Machinery/Turbine Spaces Froude Modeling - Scaling relationships given to adjust nozzles and test setup as appropriate

TEST STANDARD BACKGROUND UL 2167 UL 2167, Water Mist Nozzles for Fire Protection Service Sections 1-7: Introduction, General Information and Construction Requirements. Section 8-39: Performance Requirements (system component testing) Section 40-47: Fire Testing Section 40: Shipboard Machinery Spaces Section 41: Shipboard Passenger Cabin Section 42: Shipboard Passenger Cabin Greater than 12 m 2 Section 43: Shipboard Public Spaces

TEST STANDARD BACKGROUND UL 2167 (cont.) Section 40-47: Fire Testing Section 44: Residential Areas Section 45: Light Hazard Areas Section 46: Ordinary Hazard Group 1 Areas Section 47: Ordinary Hazard Group 2 Areas Section 48: Manufacturing and Production Tests Section 49-50: Instructions and Marking

TEST STANDARD BACKGROUND IMO Resolutions Individual resolutions for each type of test method Machinery/Pump Room Space Protection IMO 1165 (2005), Revised Guidelines for the Approval of Equivalent Water-Based Fire Extinguishing Systems for Machinery Spaces and Cargo Pump Rooms This basically replaced the previous version published in MSC/Circ. 668 and 728, which is still referenced in NFPA 750 Appendix A of the Annex contains definitions, requirements for system component testing and guidance on nozzle markings Appendix B of the Annex contains the fire test procedures, which are very similar to FM 5560 (Appendix E) and UL 2167 (Section 40) IMO 1237 (2007), Revised Drawings for IMO 1165 fire test procedures IMO 1269 (2008), Additional editorial and technical changes to 1165

TEST STANDARD BACKGROUND IMO Resolutions (cont.) Cabin, Corridor, Public Spaces and Storage Space Protection IMO MSC.265 (2008), Amendments to the Revised Guidelines for the Approval of Sprinkler Systems Equivalent to that Referred to in SOLAS Regulation II-2/12 (Resolution A.800(19)) Appendix 2 of the Annex basically replaced Appendix 2 of MSC/Circ. 800, which is still referenced in NFPA 750 The primary difference is that the Luxury Cabin tests are no longer included in MSC.265 Section 5 includes requirements for Cabin and Corridor tests Section 6 includes requirements for the Public Spaces tests Section 7 includes requirements for the Storage tests FM 5560 (Appendix G) does not include storage tests, but does include a Large Compartment test, which is basically the old Luxury Cabin Test described in MSC/Circ. A.800 (Appendix 2)

TEST STANDARD BACKGROUND IMO Resolutions (cont.) Local Application Protection IMO MSC/Circ. 913 (1999), Guidelines for the Approval of Fixed Water- Based Local Application Fire-Fighting Systems for use in Category A Machinery Spaces The Appendix describes the fire test procedures, which include two different size spray fires, tested at different locations under a nozzle grid at minimum and maximum heights above the spray fire. IMO MSC/Circ. 1387 (2010), Revised Guidelines for the Approval of Fixed Water-Based Local Application Fire-Fighting Systems for use in Category A Machinery Spaces Fire test procedures are basically unchanged, but more clear guidance given as to how the results are used in a real installation after approval is obtained. FM 5560 (App. I) requires many more tests, such as square and channel pool fires, combination spray/pool fires and obstructed fires.

TEST STANDARD BACKGROUND IMO Resolutions (cont.) Other Applications IMO MSC/Circ. 1268 (2008), Guidelines for the Approval of Fixed Pressure Water-Spraying and Water-Based Fire-Extinguishing Systems for Cabin Balconies The Appendix describes the fire test procedures, which include similar fuel loads as used in cabin and corridor test from MSC.265 with and without a crosswind through the test volume. IMO MSC/Circ. 1272 (2008), Revised Guidelines for the Approval of Fixed Water-Based Fire-Fighting Systems for RO-RO Spaces and Special Category Spaces Equivalent to that Referred to in Resolution A.123(V). This circular supersedes IMO/Circ. 914. The Appendix describes fire scenarios in roll-on and roll-off deck operations (freight truck trailer and passenger vehicle fires simulated with pallets).

TEST STANDARD BACKGROUND NFPA 750 NFPA 750, Standard on Water Mist Fire Protection Systems This standard focuses on guidance for the design, installation and maintenance of these systems, as opposed to the approval fire testing required. This is akin to most NFPA standards in the area of active fire protection, which rely on FM and UL standards for the fire test approval and listing Chapter 9: discusses design objectives and generic fire test protocols and makes reference to annex language. Chapter 10: discusses different occupancies and their associated requirements Chapter 16: discusses marine systems and the IMO requirements. Annex C: summarizes the various fire test protocols (FM, UL, IMO)

Comparison of Light/Ordinary Hazard Requirements (1 of 3) FM considers the same small cabin (3x4x2.4-m high) as IMO and UL and also considers a Large Compartment, similar to the old Luxury Cabin in IMO and the Large Compartment in UL (Section 42). FM does not consider storage spaces (Ordinary Hazard 1 or 2 in UL, Storage Spaces in IMO). FM considers Open Space tests at a 5-m height, but does not consider them at a 2.5-m height, as in IMO. FM requires 5 tests (light hazard only), IMO requires 19 tests and UL could require more than 30 tests, as applicable. Hazard/Occupancy FM 5560 UL 2167 IMO Resolution Light/Ordinary Hazard Appendix G Sections 41-43, 45-46 MSC.265, Sections 5-7 Cabin/Corridor Section G.4.1-G.4.2 Sections 41-42, 45 Section 5 Public/Open Spaces Section G.4.3-G.4.5 Sections 43, 46 Section 6 Storage/Ord. Spaces N/A Sections 43, 46 Section 7

Comparison of Light/Ordinary Hazard Requirements (2 of 3) The fuel loads are very similar between FM, UL and IMO methods, however, a different foam is used in the Large Compartment (FM) test and Luxury Cabin test (UL). All standards define the fuel load materials in terms of material flammability performance in various bench-scale fire test methods. FM uses the Fire Propagation Apparatus for some of these materials, while UL and IMO use the Cone Calorimeter.

Comparison of Light/Ordinary Hazard Requirements (3 of 3) For the storage tests, standard Group A plastic commodity is specified in IMO and UL for Ordinary 2, and Class II commodity is used for UL for Ordinary 1. For light hazard in UL, wood cribs are used, in addition to the shipboard requirements given in IMO. Nozzles are automatically activated in all testing (FM, UL and IMO). The fire test acceptance criteria is a function of maximum developed temperatures within the test setup (gas temperature, surface temperature) as well as the amount of damage observed to the standard test fuels. FM uses instantaneous temperature, while IMO and UL use a 30-s running average to evaluate the peak gas and surface temperatures during testing.

Comparison of Machinery Space Hazard Requirements (1 of 3) FM has separate appendices to 5560 that describe test procedures and requirements for different ranges of volumes for machinery and turbine spaces. Appendix A/B: volumes not exceeding 80 m 3 (2825 ft 3 ) Appendix C/D: volumes not exceeding 260 m 3 (9175 ft 3 ) Appendix E/F: volumes exceeding 260 m 3 (9175 ft 3 ) Primary difference between machinery space tests and turbine space tests is the required spray cooling test in addition to the optional turbine insulation tests (saturated mat and spray fires). Appendix A-D uses a horizontal steel plate with angled baffle plates to simulate the engine/turbine, while E/F use a larger engine mockup, which is the same as specified in UL and IMO. Hazard/Occupancy FM 5560 UL 2167 IMO Resolution Machinery Spaces Appendix A, C and E Section 40 1165/1237/1269 Turbine Spaces Appendix B, D and F Section 40 1165/1237/1269

Comparison of Machinery Space Hazard Requirements (2 of 3)

Comparison of Machinery Space Hazard Requirements (3 of 3) The IMO and UL procedures also include bilge fire tests and IMO also includes thermal management tests. The bilge fire tests consist of three different pool fires (small pool with heptane and motor oil and larger pool fire with diesel fuel). The thermal management tests are large shielded pool fires that are sized as a function of the test enclosure. The system is discharged while the fire is burning and the 1-min peak running average temperature must be maintained below 100 ⁰C. For IMO, all fires must be extinguished within 15 minutes. For UL and FM, there is no maximum extinguishment time, but the system must be designed to twice the capacity of the longest extinguishment time.

SUMMARY Hazard/Occupancy FM 5560 UL 2167 IMO Resolution NFPA 750* Light/Ordinary Hazard Appendix G Sections 41-43, 45-46 MSC.265, Sections 5-7 Chapter 10, Annex C Cabin/Corridor Section G.4.1-G.4.2 Sections 41-42, 45 Section 5 Chapter 10, Annex C Public/Open Spaces Section G.4.3-G.4.5 Sections 43, 46 Section 6 Chapter 10, Annex C Storage/Ord. Spaces N/A Sections 43, 46 Section 7 Chapter 10, Annex C Machinery Spaces Appendix A, C and E Section 40 1165/1237/1269 Chapter 16, Annex C Turbine Spaces Appendix B, D and F Section 40 1165/1237/1269 Chapter 16, Annex C Local Applications Appendix I N/A 913/1387 Chapter 16, Annex C Residential Applications N/A Section 44 N/A Chapter 10, Annex C Roll-on / Roll-off Spaces on a Ship N/A N/A 1272 N/A Balcony Spaces on a Ship N/A N/A 1268 N/A * Annex C of NFPA 750 provides a good overview of different fire test protocols, but it is not completely up to date.

QUESTIONS? http://www.fire.swri.org