DESIGN and IMPLEMENTATION of a SHUNT ACTIVE POWER FILTER with REDUCED DC LINK VOLTAGE

Similar documents
Fundamentals of Power Electronics. Robert W. Erickson University of Colorado, Boulder

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Design a Phase Interleaving PFC Buck Boost Converter to Improve the Power Factor

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

How To Improve Power Quality

Control Strategy for Three Phase Shunt Active Power Filter with Minimum Current Measurements

Single-Stage High Power Factor Flyback for LED Lighting

The design and performance of Static Var Compensators for particle accelerators

New Control Strategy To Improve Power Quality Using A Hybrid Power Filter

LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE

AN ULTRA-CHEAP GRID CONNECTED INVERTER FOR SMALL SCALE GRID CONNECTION

MODELING AND SIMULATION OF A THREE-PHASE INVERTER WITH RECTIFIER-TYPE NONLINEAR LOADS

Principles of Adjustable Frequency Drives

FREQUENCY CONTROLLED AC MOTOR DRIVE

3-Phase Synchronous PWM Controller IC Provides an Integrated Solution for Intel VRM 9.0 Design Guidelines

Closed Loop PWM Control for Induction Motor Drive Using Dual Output Three Phase Inverter

MICRO HYDRO POWER PLANT WITH INDUCTION GENERATOR SUPPLYING SINGLE PHASE LOADS

UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

Considering the effects of UPS operation with leading power factor loads

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

Line Reactors and AC Drives

How To Simulate A Multilevel Inverter

How To Improve Power Quality

An Efficient AC/DC Converter with Power Factor Correction

Design and Simulation of Soft Switched Converter Fed DC Servo Drive

Introduction. Harmonics and IEEE 519 Page 1 of 19

A bidirectional, sinusoidal, high-frequency inverter design

Design and Development of Speed Control of Induction motor drive using Pulse-Width Modulation

Simulation and Analysis of PWM Inverter Fed Induction Motor Drive

Smart Grid and Renewable Energy Grid Integration. Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems

Application Note AN- 1095

UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES

Harmonic components: electrical network polluters. LV and MV networks are becoming increasingly polluted by current and voltage harmonics. Harmonics a

Hybrid Power System with A Two-Input Power Converter

Modeling and Analysis of DC Link Bus Capacitor and Inductor Heating Effect on AC Drives (Part I)

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS

New Pulse Width Modulation Technique for Three Phase Induction Motor Drive Umesha K L, Sri Harsha J, Capt. L. Sanjeev Kumar

Analysis of AC-DC Converter Based on Power Factor and THD

Harmonic Reduction and Load Balancing of Three Phase Four Wire DSTATCOM using Three Leg VSC and a Zig Zag Transformer

Relationship between large subject matter areas

Product Data Bulletin

Transient analysis of integrated solar/diesel hybrid power system using MATLAB Simulink

Analysis of PV cell fed High Voltage Gain Seven and Nine level inverter with Reduced Switches

A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER

Control Development and Modeling for Flexible DC Grids in Modelica

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009

Chapter 4 AC to AC Converters ( AC Controllers and Frequency Converters )

The full wave rectifier consists of two diodes and a resister as shown in Figure

Case Studies in On-Line Measurement of PD in Motors Fed by Voltage Source PWM Drives

Control of a Three Phase Induction Motor using Single Phase Supply

Development of High Frequency Link Direct DC to AC Converters for Solid Oxide Fuel Cells (SOFC)

Reduction of DC Bus Capacitor Ripple Current with PAM/PWM Converter

AC/DC Power Supply Reference Design. Advanced SMPS Applications using the dspic DSC SMPS Family

WIND TURBINE TECHNOLOGY

Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka

POWER QUALITY ISSUES IN A STAND-ALONE MICROGRID BASED ON RENEWABLE ENERGY

Analysis of Space Vector Pulse Width Modulation VSI Induction Motor on various conditions

7-41 POWER FACTOR CORRECTION

Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers

Application Guide. Power Factor Correction (PFC) Basics

Modelling, Simulation and Performance Analysis of A Variable Frequency Drive in Speed Control Of Induction Motor

Modeling Grid Connection for Solar and Wind Energy

Diode Applications. by Kenneth A. Kuhn Sept. 1, This note illustrates some common applications of diodes.

Power Electronics. Prof. K. Gopakumar. Centre for Electronics Design and Technology. Indian Institute of Science, Bangalore.

Inrush Current. Although the concepts stated are universal, this application note was written specifically for Interpoint products.

98% Efficient Single-Stage AC/DC Converter Topologies

DC/DC BUCK Converter for Renewable Energy Applications Mr.C..Rajeshkumar M.E Power Electronic and Drives,

Design Considerations for an LLC Resonant Converter

Experiment # (4) AM Demodulator

High Power Factor Boost Converter with Bridgeless Rectifier

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

Multilevel DC-AC Converter Interface with Solar Panels

FOUR LEGGED ACTIVE POWER FILTER COMPENSATION FOR A UTILITY DISTRIBUTION SYSTEM

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: [633] [Choudhary, 3(12): December, 2014] ISSN:

THIS paper reports some results of a research, which aims to investigate the

LOW-VOLTAGE three-phase four-wire electrical distribution

UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS

Control of a 3-phase 4-leg active power filter under non-ideal mains voltage condition

Analysis and Control of Three Phase Multi level Inverters with Sinusoidal PWM Feeding Balanced Loads Using MATLAB

Three phase circuits

ANADOLU UNIVERSITY DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING

Power System Harmonics

MODELLING AND SIMULATION OF SVPWM INVERTER FED PERMANENT MAGNET BRUSHLESS DC MOTOR DRIVE

Power supply output voltages are dropping with each

Survey of Harmonics Measurements in Electrical Distribution System of a Technical Institution

EET272 Worksheet Week 9

Power Supplies. 1.0 Power Supply Basics. Module

Power Electronics Technology Trends and Prospects

Diode Applications. As we have already seen the diode can act as a switch Forward biased or reverse biased - On or Off.

Chapter 17 The Ideal Rectifier

Designing Stable Compensation Networks for Single Phase Voltage Mode Buck Regulators

Design A High Performance Buck or Boost Converter With Si9165

Submarine Cable Power Transmission using DC High-Voltage Three-Level Converters

v v v Keywords-- Power Quality, Shunt active filter, Indirect current control, ANN control

Simple PWM Boost Converter with I/O Disconnect Solves Malfunctions Caused when V OUT <V IN

Prototype of an Inverter for Application in Renewable Energy Systems

Transcription:

DESIGN and IMPLEMENTATION of a SHUNT ACTIVE POWER FILTER with REDUCED DC LINK VOLTAGE O. Ucak, I. Kocabas, A. Terciyanli onur.ucak@uzay.tubitak.gov.tr TUBITAK- Space Technologies Research Institute, Power Electronics Group METU Campus, TR 06531, Ankara, TURKEY Keywords: Active power filter, hybrid filter, passive filter, current harmonic ABSTRACT This paper presents a shunt hybrid active power filter application mainly for current harmonic elimination and fixed reactive power compensation. The proposed system consists of a small rated voltage source active power filter and a series of LC passive filter connected to each phase. Besides, no additional switching filter is required for the current ripples. Effectiveness of the system is confirmed by the experimental results obtained from a laboratory prototype. I. INTRODUCTION Voltage and current harmonics has become a serious problem in transmission and distribution systems in recent years. To solve the current harmonic related problems, passive filters connected in several circuit configurations present a low cost solution. However, passive filter implementations to filter out the current harmonics have the following disadvantages: Possibility of resonances with the source impedance Supply impedance dependent system performance Fixed compensation In order to diminish the preceding disadvantages of the passive filters, active power filters (APF) have been worked on and developed in recent years. Elimination of the current harmonics, reactive power compensation and voltage regulation are the main functions of active filters for the improvement of power quality. There exist several active power filter topologies in the literature in accordance with their circuit configurations and connection types [1]. Among these configurations, conventional parallel voltage source active power filter, shown in Fig-1.a, is widely used. The DC link capacitor voltage is required to be higher than the peak value of the utility voltage; otherwise, the generated compensation currents can not be injected to the mains [2]. So, for high power applications, the required high DC link voltage restricts the active power filter implementations due to the increase in the losses, rating and the total cost of the APF. As a result, various hybrid filter topologies have been developed which combine the advantages of both the passive and the active filters [3]. Within these topologies, shunt hybrid filters formed with the use of a three phase voltage source PWM inverter and a series connected LC passive filter are superior to the conventional shunt APFs due to the reduced DC link voltage and the converter rating. The series connected LC filter absorbs the current harmonics arising from the non-linear load; however, the filtering characteristic of just the passive filter itself is not satisfactory. Hence, active filter is used to improve the filtering performance of the overall system. In this paper, a hybrid filter (Fig-1.b) formed by a low-rated APF and a LC passive filter tuned to 350 Hz is presented. The proposed filter ensures a low DC link voltage and a superior filtering performance by the applied feedback and feedforward control methods. In addition, no switching ripple filter is used since the LC filter also operates as a switching ripple filter at high frequencies. The start up procedure used in the laboratory and the experimental results obtained from a 300V laboratory prototype are also presented to show the effectiveness of the overall system. Fig-1 (a) Voltage Source APF (b) Hybrid Power Filter

II. SYSTEM DESIGN i) Voltage Reference Generation Synchronous reference frame method is used to calculate the harmonic components of the mains current [4, 5]. Three phase supply voltage and current vectors are transformed into d (direct) and q (quadrature) frames rotating at the fundamental frequency w1 by applying Clarke & Park transformations. For this reason the fundamental component of the mains current turns out to be a DC signal and the harmonic components which are still AC signals are rotating with respect to the reference frame. Harmonic current components are extracted by a second order high pass filter with 20 Hz cut off frequency. Applying inverse Clarke & Park transformations reproduces the supply harmonic current components in abc frames. Each harmonic component is amplified by a gain of K to obtain a voltage reference for each phase. DC voltage control is maintained by a PI regulator and the current reference ( id1) obtained in the proposed control method is added to the reactive current component I d (Fig-2). Moreover, since the feedback gain K is limited to the certain values due to the stability problems of the system, additional feedforward control loop (Fig-2) is presented [6, 7] for the elimination of 5 th harmonic current component. The reference voltages in the proposed feedforward control are generated by using 250 Hz components of the load currents as indicated in eqn-1. Vd 5 * = Rf * ild 5 + (-w 5 *Lf + 1/ (w 5 *Cf)) * ilq 5 Vq 5 * = (w 5 *Lf - 1/ (w 5 *Cf)) * ild 5 + Rf * ilq 5 w 5 = -5w 1 ii) Modulation Method (Eqn-1) Sinusoidal Pulse Width Modulation (SPWM) is used as the modulation method. The voltage references (V a *, V b *, V c * ) formed by the feedback, feedforward and the DC link voltage control are compared with a 12.5 khz carrier wave to obtain the gate signals of the semiconductors. Fig-2 Voltage Reference Generation in Synchronous Reference Frame

iii) Passive filter configuration and filtering characteristics In the proposed system, conventional APF is connected in series with a passive LC filter. LC passive filter is tuned to a dominant harmonic component [8] and the active filter acts as a damping resistor which also improves the filtering characteristics of the overall system. Since the passive filter tuned at 350 Hz shows lower impedance at 550Hz and 650 Hz than a passive filter tuned at 250 Hz, it has better filtering characteristics when 11 th and 13 th harmonics are taken into account. LC passive filter tuned at 350 Hz amplifies the 5 th harmonic current components at the mains side; however, it is suppressed by the active power filter with the applied feedback and feedforward control explained above. Fig-3 illustrates the single phase equivalent circuit of the system and the harmonic equivalent circuit of the system when the feedback control loop is applied. The load is shown as an ideal current source and the APF is considered as a voltage source. When active filter is not connected (K=0) the following relation takes place between the supply and the load harmonic currents. (Eqn-2) As the APF is connected to the system with the proposed feedback control, the feedback gain K acts as a damping resistor which suppress the resonance between the supply and the passive filter. The mains harmonic current is now as indicated in Eqn-3: inrush current, S2 is remained OFF so that hybrid filter is connected to the supply through the resistors R for a predefined time duration t. After 5 cycles have passed, S2 is turned ON and the hybrid filter is directly connected to the mains. Fig-3 (a) Single phase equivalent circuit (b) Harmonic equivalent circuit Table-I Experimental System Parameters Line voltage Line frequency Supply inductance Rectifier inductance Filter Capacitor Filter Inductor Tuned freq. of series filter APF rating DC link capacitor 300 V-rms 50 Hz 343 uh 1.5 mh 120 uf 1.8 mh 342 Hz 1.47 kva 1.3 mf iv) Experimental System (Eqn-3) A 300 V laboratory prototype has been implemented with the specified system parameters in Table-I. The proposed control algorithm is implemented on a Digital Signal Processor (DSP) of Texas Instruments which is ezdsp28f12. In the experimental set up, additional series resistors (R) and contactors (S1, S2) are used for the start up procedure of the proposed system. The experimental circuit configuration is shown in Fig-4 and a view from the laboratory prototype is given in Fig-5. The start up procedure [7] is as follows: Initially, three upper IGBTs are turned ON and three lower IGBTs are turned OFF. During this time interval, active filter is not operating, and DC side of the active filter is seen as a short circuit by the mains side. When S1 is turned on, the system operates only as a passive LC filter, and to avoid any Fig-4 Experimental System Fig-5 Hybrid Power Filter Prototype

In Fig-6 experimental waveforms obtained during the start up procedure are shown. It is inferred that only passive filter is operating and possible inrush current is minimized. When DC link capacitor voltage reference is set to 60V and APF starts to operate with the feedback control, the waveforms shown in Fig-7 & Fig-8 are obtained. The mains current becomes nearly a pure sinusoidal, DC link voltage is kept stable at 60V and filter current is ripple free. When feedforward control is included in the system, the waveforms shown in Fig-9 & Fig-10 are obtained. Addition of feedforward control results in 0.9 A reduction on the 5 th harmonic current component and nearly 1.0% reduction on THD (Table-II). The nonlinear thyristor rectifier load used in the experimental set up introduces considerable amount of higher order harmonics (Fig-11, Fig-12), so unavoidable notches appear on the mains current in both of the applied control methods. Fig-8 Only Feedback Control, C1 DC link voltage (50V/div), C2 Mains voltage (100V/div), C3 Mains current (10A/div), C4 Filter current (10A/div) Fig-6 During Start Up, C1 DC link voltage (50V/div), C2 Mains voltage (100V/div), C3 Mains current (10A/div), C4 Filter current (10A/div) Fig-9 Feedback & Feed forward Control, C1 DC link voltage (50V/div), C2 Mains voltage (100V/div), C3 Mains current (10A/div), C4 Load current (10A/div) Fig-7 Only Feedback Control, C1 DC link voltage (50V/div), C2 Mains voltage (100V/div), C3 Mains current (10A/div), C4 Load current (10A/div) Fig-10 Feedback & Feed forward Control, C1 DC link voltage (50V/div), C2 Mains voltage (100V/div), C3 Mains current (10A/div), C4 Filter current (10A/div)

Table-II Mains Current Under Different Conditions Cases THD% Mains Current (A RMS ) I 1 I 5 I 7 I 11 I 13 Load 30.6 21.3 6 1.8 2.1 0.7 PF 42 20.5 7.8 1.0 1.6 0.6 FB 9.5 20.5 1.0 0.1 0.6 0.6 FF 8.6 20.7 0.1 0.1 0.6 0.6 (PF: passive filter, FB: active filter with feedback control, FF: active filter with feedforward control) voltage is much less when compared with a standard voltage source type active power filter. As a result, rating of the active filter is greatly reduced with the proposed system. If the harmonics of the load indicated in Table-II is to be filtered by a conventional voltage source type active power filter, the rating of the APF is nearly 9 kva. However, in the proposed system it is reduced to 1.47 kva. Although no additional switching filter is used, high frequency current ripples are also minimized with the applied system. Moreover, experimental results have shown the effectiveness of the feedback and feedforward control methods which are also easy to implement. As a result, the advantages listed above shows that especially for large power applications, hybrid power filters are seem to be an appropriate solution. IV. ACKNOWLEDGEMENT All the studies presented in this paper are performed under the scope of Support Programme for Research Projects of Public Institutions of TUBITAK (Program Code: 1007) with the project entitled Guc Kalitesi Milli Projesi (Project Code: 105G129). Fig-11 Mains Current Frequency Spectrum (only Feedback Control, I fund = 20A RMS ) Fig-12 Mains Current Frequency Spectrum (Feedback & Feedforward, I fund = 20A RMS ) III. CONCLUSION This paper has analyzed a shunt hybrid active power filter consisting of a small rated voltage source active power filter and a series 7 th tuned LC passive filter. The series LC filter used in the proposed system results in an increase on the current flowing through the active power filter. However, the required DC link REFERENCES [1] H. Akagi, Active Harmonic Filters Proceedings of the IEEE,Vol. 93, pp 2128-2141, 2005 [2] Đ.Kocabaş, O.Uçak, A.Terciyanlı, DSP Based Voltage Source Paralel Active Power Filter Implementation, Eleco, pp 171-175, 2006 (Originally in Turkish) [3] L.Chen, A.V.Jouanne A Comparison and Assessment of Hybrid Filter Topologies and Control Algorithms IEEE Power Electronics Specialists Conference, Vol. 2, pp 565-570, 2001 [4] A. Altintas, O. Bingol, The Evaluation and Comparison of Mathematical Models Utilized in Active Power Filters Süleyman Demirel Üniversitesi Fen Bilimleri Enstitüsü Dergisi pp 145-150, 2004 (Originally in Turkish) [5] S.Bhattacharya, T.M. Frank, D.M. Divan, and B. Banerjee Active Filter System Implementation IEEE Industry Applications Magazine, Vol. 4, pp 47-63, 1998 [6] H.Akagi, S. Srianthumrong, Y.Tamai Comparisons in Circuit Configuration and Filtering Performance between Hybrid and Pure Shunt Active Filters Industry Application Conference, Vol.2, pp 1195-1202, 2003 [7] W. Tangtheerajaroonwong, T.Hatada, K.Wada, H.Akagi, Design of a Transformerless Shunt Hybrid Filter Integrated into a Three-Phase Diode Rectifier Power Electronics Specialists Conference, pp 1-7, 2006 [8] S. Srianthumrong, H.Akagi A Medium Voltage Transformerless AC/DC Power Conversion System Consisting of a Diode Rectifier and a Shunt Hybrid Filter IEEE Trans On. Vol. 39, pp 874-882, 2003