Troubleshooting 4-20 ma Current Loops

Similar documents
Contents. Document information

Subminiature Load Cell Model 8417

6/14/02 Chapter 14: Use of Electrical Test Equipment 1/20

RI-215A Operator s Manual. Part Number: RK Revision 0 Released: 10/3/05

Combustible Gas Transmitter RK-05

Service Information CALIBRATION PROCEDURE AND TROUBLESHOOTING FOR LINEAR GOVERNOR CONTROLLERS NOTE

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE

DC Circuits (Combination of resistances)

Basic RTD Measurements. Basics of Resistance Temperature Detectors

ATL Fuel Level Sender Probes

EXPERIMENT 7 OHM S LAW, RESISTORS IN SERIES AND PARALLEL

Installation Guidelines: Resistance Thermometers and Temptran Thermometers for Building Automation Systems

Fig. 1 Analogue Multimeter Fig.2 Digital Multimeter

Modular I/O System Analog and Digital Interface Modules

PART 1 - INTRODUCTION...

Loop Calibration and Maintenance

Electrical Fundamentals Module 3: Parallel Circuits

Essential Electrical Concepts

Series 510 Submersible Level Transmitters

Calibrating DC Shunts: Techniques and Uncertainties

TROUBLESHOOTING GUIDE

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

EMERGENCY EGRESS LIGHTING POWER SUPPLY PART NO COMPONENT MAINTENANCE MANUAL WITH ILLUSTRATED PARTS LIST

GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)

OPERATION MANUAL VALVE CHECKER G

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

Transistor Amplifiers

APPLICATION NOTE. Measuring Current Output Transducers with Campbell Scientific Dataloggers. App. Note Code: 2MI-B Revision: 1

LAB2 Resistors, Simple Resistive Circuits in Series and Parallel Objective:

PRODUCT PROFILE FEATURES

INSTRUCTION MANUAL. SIGNAL AMPLIFIER 4-20 ma

VOLTAGE/CURRENT CALIBRATOR ISO-TECH ILC-421

Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12

EDD-600 FLOW TOTALIZER RATE INDICATOR OPERATION MANUAL. P.O. Box Odessa, Texas USA.

Measuring Electric Phenomena: the Ammeter and Voltmeter

Lab 3 - DC Circuits and Ohm s Law

Precision Miniature Load Cell. Models 8431, 8432 with Overload Protection

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER

Microcontroller to Sensor Interfacing Techniques

T7560A,B,C Digital Wall Module

The Do s and Don ts of Pressure Transducers

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)

T0118 T2118 T3118. Instruction Manual

Objectives: Part 1: Build a simple power supply. CS99S Laboratory 1

FLR 1000 & 1000-BR Series Flow Sensors & Meters For Gases

Manual Ranging MultiMeter

Operating Instructions. UL325 Compliant Non-monitored

Errors Related to Cable Resistance Imbalance in Three Wire RTDs

COOL-01, Cooling Fan Operation and Troubleshooting

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS:

User Manual for CH-PFC76810

MGL Avionics CAN bus interface for Trig Avionics TT21/TT22 transponders

CONTENTS. PAGE Chapter 1 General Information 1. Chapter 2 Setup 4 DP450-VDC 7 DP450-VAC 7 DP450-DCC 7 DP450-F 8 DP450-HACC 9 DP450-HDCC 11 DP450-E 13

Instruction Manual. 2in1 LAN Tester & Multimeter. Model: LA-1011

Resistors in Series and Parallel Circuits

Technical Note Series

WHY DIFFERENTIAL? instruments connected to the circuit under test and results in V COMMON.

Telefon (+45) Telefax (+45) Installation and operating manual

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

12 Volt 30 Amp Digital Solar Charge Controller

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

VOLTAGE REGULATOR AND PARALLEL OPERATION

MOUNTING AND OPERATING INSTRUCTIONS

Dynamax Inc Copyright

How To Use A Cdm250 Digital Multimeter

PHYSICS 111 LABORATORY Experiment #3 Current, Voltage and Resistance in Series and Parallel Circuits

Multi-Protocol decoder with Load regulation

PASSIVE INFRARED INTRUSION DETECTOR PASSIVE INFRAROOD DETECTOR DETECTEUR D INTRUSION PASSIF INFRAROUGE

Liquid Leakage Sensor Amplifier

LocoNet, the Digitrax Difference

Section 3. Sensor to ADC Design Example

Troubleshooting Guide, Freedom and Fleet Power Inverter/Chargers

Tips for connecting 24-volt power

Circuit Analyses. Laboration 1 how to measure Current and Voltage and Resistance

Current Loop Application Note 1495

HOW TO USE MULTIMETER. COMPILE BY: Dzulautotech

The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions:

Panel Meters and Controllers Modular Panel Meter Type EDM 35

Constructing a precision SWR meter and antenna analyzer. Mike Brink HNF, Design Technologist.

3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE

Using Thermocouple Sensors Connecting Grounded and Floating Thermocouples

INSTALLATION & SERVICE MANUAL. Display Panel

Bipolar Transistor Amplifiers

Building the AMP Amplifier

Tristan s Guide to: Solving Series Circuits. Version: 1.0 Written in Written By: Tristan Miller Tristan@CatherineNorth.com

Radiant Temperature Sensor TY7321

Series /16 DIN Multi-Mode Bar Graph Display Timer TIMERS PRODUCT HIGHLIGHTS

Streaming Potential System (SPT1000, SPD1000)

Quick Start Guide , Rev DA March Rosemount 8714D (Calibration Standard) Magnetic Flowtube Simulator

FMA 3100/3100ST/3300/3300ST Series Thermal Mass Flow Sensors and Meters

User's Manual. Research Isometric Transducer 0 to 5 grams and 0 to 50 grams

WIND ALARM. Wind Speed Alarm. Wind Speed. Set Point 2. Set Point 1 NEW BEDFORD, MA USA

Experiment #5, Series and Parallel Circuits, Kirchhoff s Laws

LM134-LM234-LM334. Three terminal adjustable current sources. Features. Description

PTU Series Transducer Digital Display Indicator User s Manual

RTD and thermocouple circuits, with millivolt calculations

Series and Parallel Circuits

Water Leak Detection System

Load Cell Troubleshooting

Transcription:

General: The MINCO Temptran TM converts an RTD's (resistance temperature detector's) signal into a dc current whose value is proportional to the RTD's temperature. The current matches the temperature range marked on the Temptran: 4 ma at the lowest temperature of the range, 20 ma at the top of the range. The power supply leads carry the current signal. Installation: Locate the Temptran near the RTD in an area where the ambient temperature stays within the range 32 to 122 F. Mount the Temptran with a screw into the mounting hole from the bottom. Connect the Temptran as shown below, observing the +/- polarity of the current loop. Maximum DC supply voltage = 35 VDC. The RTD connections have no polarity. For the RTD, good connections are a must; a few ohms of resistance in the connection can cause an error of several degrees. The Temptran has been factory-calibrated for its marked temperature range. Do not change the zero or span adjustments. Figure 1 Typical hookup of a single current loop MINCO Products, Inc. 7300 Commerce Lane, Minneapolis, MN 55432-3177 U.S.A. Phone: (763)571-3121 FAX: (763)571-0927 WWW@MINCO.com 2001 Page 1

Terminology: RTD (Resistance Temperature Detector): The temperature sensor. Current Loop: The pair of wires, which simultaneously carry power to the transmitter and the temperature signal, as a current, from the transmitter. Troubleshooting Guide - Malfunction or incorrect operation may be caused by: 1. Reversed polarity: Check the wiring. If the temperature of the thermocouple increases while the current magnitude decreases, the problem could be caused by reversed polarity of the: a. thermocouple wiring b. power supply leads c. monitor instrument. 2. Loose or broken wires: Check each terminal connection for tightness. Move each wire back and forth, and note any changes in operation. 3. Too high a load resistance in the output current loop or too low a current rating on the power supply: a. Measure the total resistance of each device (excluding the transmitter and power supply) in the 20-mA loop, including the resistance of the lead wires. b. Calculate maximum allowable loop resistance using the formula: Loop Resistance (maximum) = V supply - 7V 0.020A For example, a 24V power supply would give a maximum loop resistance of 17V/0.20A = 850 ohms. c. Make sure the power supply is rated for at lease 28 ma times the number of TX93 transmitters being powered. For example, if the supply is powering five transmitters, the supply should be rated for at least 140 ma. TROUBLESHOOTING: Look up the troubleshooting procedure according to the symptoms you have. Symptoms: See "POTENTIAL CAUSES" TEMPERATURE DOES NOT CHANGE 1 to 10, 11 to 13 TEMPERATURE STAYS BELOW BOTTOM OF RANGE (below 4 ma) TEMPERATURE STAYS ABOVE TOP OF RANGE (above 20 ma) TEMPERATURE CHANGES UNPREDICTABLY/UNEXPECTEDLY TEMPERATURE CHANGES WHEN OTHER ELECTRICAL LOADS ARE SWITCHED ON OR OFF TEMPERATURE IS SEVERAL DEGREES TOO HIGH OR LOW TEMPERATURE IS JUST A DEGREE HIGH OR LOW 2 to 11, 14, 16 to 20, 23 1, 2, 7 to 10, 12 to 14, 22, 24 to 26 6, 7, 14, 17, 19 to 22, 27 to 29 7, 14, 15, 27 to 29 6 to 10, 14, 21 to 23, 25, 30 8 to 10, 13, 23, 25, 30 to 32 TEMPERATURE KEEPS INCREASING OR 7, 13, 24, 30 DECREASING DAY-BY-DAY Page 2

1. RTD open-circuited or Temptran short-circuited. CHECK THAT THE RTD IS OPERATING CORRECTLY A. Turn power to Temptran off because the current may rise above 20 ma 2. RTD resistance too high or low. while the RTD is disconnected. 3. RTD short-circuited B. Disconnect the RTD and ohm it. Its resistance should approximately agree with the room temperature values listed in Table 1, below. Caution - it may read high if your hands accidentally warm it up. If you're not sure which kind of RTD you have, read it from the code on the transmitter, e.g. for a TT151PD1A use the "PD or PE" column in Table 1. Ambient temperature Sensing Element type (resistance in ohms) PD or ( F) PA PB PE PF NA FB FC 60 106.2 106.2 106.1 1060.7 131.2 975.4 1950.7 70 108.4 108.4 108.2 1082.2 135.4 1000.0 2000.0 80 110.6 110.5 110.4 1103.8 139.5 1025.0 2050.0 Table I RESISTANCE OF SEVERAL TYPES OF MINCO RTD s AT ROOM TEMPERATURE 4. Temptran or current loop open-circuited. A. Ohm the current loop wiring. B. Verify the Temptran connections to the loop. 5. Current loop and RTD connections swapped. Check wiring at Temptran. 6. Below minimum operating voltage at Temptran's current loop terminals due to excess resistance in the current loop. Voltage across Temptran's current loop terminals must be at least 8.5 VDC - measure it. Note: The voltage may range as high as the power supply's voltage and the voltage across the Temptan will change when the current signal changes. Some Temptran models, in the round cases, require 12 volts minimum. Check total resistance of the loop: A. Turn off power supply, temporarily place a short across its terminals. B. Disconnect the two current loop wires from the Temptran and ohm the loop. Resistance should be less than that given by this formula: R LOOP MAX = (V SUPPLY - 8.5)/.02 amps for example, if you're using a 24 VDC supply, (24-8.5)/.02 = 775 ohms max. 7. RTD or current loop misconnected to other control wiring, current loops, or voltages. With meter, check for unwanted currents, voltages, and connections. 8. Temptran type does not match RTD type. Read the RTD element code off the Temptran label and check that the color-coded wires of the RTD are in agreement (see Table 2 below), e.g. a Temptran labeled Page 3

TT111PB1C should have a sensor whose leadwires are colored red, white, and white (or just red and white for a 2- lead sensor *). RTD RTD Leadwire Color RTD Element lead number Description Code 1 2 3 * FB Red Red ** 1000 Ω nickel-iron FC White White ** 2000 Ω nickel-iron PB Red White White 100 Ω platinum, TCR =.00391 PD Yellow White White 100 Ω platinum, TCR =.00385 PE Yellow White White 100 Ω platinum, TCR =.00385 PF Yellow Red Red 1000 Ω platinum, TCR =.00385 Note: This table applies only to Minco's standard Energy Management RTD's with model numbers between S400 and S499. *Some RTD's do not have a third lead and some Temptrans require only 2 leads. If you have a 3-lead sensor and the Temptran only has terminals for two, connect the common-color wires together. For example, connect the two white wires of a PD sensor together in the same terminal of the Temptran and connect the yellow lead to the second Temptran terminal. ** FB & FC element codes are not available with a third leadwire. Table II IDENTIFYING RTD TYPES Page 4

9. Wrong Temptran range installed. Check against your records/plans that the temperature range matches the one listed on Temptran's label and that it matches what the computer is programmed for. 10. Energy Management System scaled for another temperature range or is not reading correctly. If everything matches and the RTD's resistance ohms okay (see 3B), you can test that the computer is reading correctly: 1. Connect as shown in Fig. 2. 2. The variable resistor should have a resistance which covers the sensor's range of resistance (printed on the Temptran label), e.g., for a 100 ohm PD platinum RTD, use a decade box or a 250 ohm pot to simulate the 97 to 119 ohm resistance of the sensor from 20 to 120 F. 3. Set the decade box or RTD simulator or variable resistor/potentiometer to whatever it takes so that the Temptran puts out 4 ma, as measured by your current meter. Check that the computer's reading is correct. 4. Set the variable resistor so Temptran puts out 20 ma. Check computer's reading. Figure 2 Check computer's reading 11.Current loop polarity reversed. Using voltmeter, check the polarity of the voltage at the Temptran's current loop terminals. Temptran terminal 1, or the red lead on a model with wire leads, should be positive. 12. Current loop wires shorted together at some point. Check for short. Page 5

13.You're asking for Duct #1's temperature but the computer is answering with Duct #4's temperature, for example. Open the current loop at the Temptran for Duct #1 or else short the sensor's terminals (see #34 below). The computer should correctly sense that the temperature is below the bottom of the range. 14.Ground loop currents are adding or Ohm from each current loop to earth ground or other suspect wiring subtracting from current loop because to check for accidental shorting along the wire run. None of the circuit is earth-grounded at some point. Temptran's connection points should be grounded. However, some control systems may intentionally connect the positive or negative side of the current loop to earth ground as shown in Fig. 1. 15.RTD element or its leads are not insulated Disconnect the RTD from the Temptran, and while installed, ohm from mounting hardware. from the RTD leads to its mounting hardware - the resistance should be greater than 2 megohms. 16.Power supply voltage too low or high. Measure the voltage at the power supply's terminals to see that it is within your system's tolerances. 17.Power supply not connected to current loop. Check for loose wires. 18.DC power supply not plugged in/turned on. Check for correct voltage at the power supply output terminals. 19.Power supply overloaded - too many current Measure the voltage at the power supply's terminals to see that it is loops on one supply. within your system's tolerances. Low output voltage is a sign of overloading the supply. Alternatively, compare measured output voltage and current with the supply's specs. 20.Wrong AC source for power supply, e.g. Check for proper 115 or 230 VAC wiring and switch settings. trying to run off 115 VAC with input switch set to 230 VAC. 21.Poor RTD connections or broken/intermittent To discover broken lead wires, monitor the temperature or wires at terminations. current as you flex the lead wires. 22.Corrosion has increased resistance at the Clean connections & wire. RTD terminations. 23.Shunting by a high resistance path across Remove dirt & debris, clean. 2 megohms is the threshold where RTD connections is causing lowered shunting may become a problem. Don't try to ohm the reading. Temptran's terminals - they are a low impedance. 24.Operating temperatures beyond ratings of Maximum temperature of standard Energy Management RTD's RTD. is 275 F (135 C). Note: Max ambient for the Temptran is 122 F (50 C) for TT110 & TT111. 25.Calibration pot settings disturbed. RECALIBRATE Temptran: Use a decade resistance box, a fixed point RTD simulator, or some other variable resistor, which you can set very accurately to ± 0.02%. (If your resistor is not precisely 100 ohms or your decade box will not provide the exact resistances required, calculate the offsets they cause and calibrate to include them. Page 6

1. Connect as shown in Fig. 3. 2. Set calibration resistor to value for 4 ma (printed on the side of the Temptran). Adjust the ZERO pot of the Temptran to get 0.4000 ±.0016 volts. 3. Set the calibration resistor to value for 20 ma (printed on the side of the Temptran). Adjust the SPAN pot of the Temptran to get 2.0000 ±.0016 volts. 4. Since the pots interact slightly, repeat steps 2 and 3 until both currents are calibrated. In troubleshooting and calibrating, be aware that getting good accuracy is difficult. The accuracy tolerances of some voltmeters, current meters, and temperature meters may be as poor as ±0.5% of reading range, while you would like to calibrate with instruments whose accuracy is five to ten times better than the ±0.1% accuracy of the Temptran. Figure 3 Calibration 26.Power supply connected in parallel with loop readout Check for this miswiring and correct. resistor. 27.Leadwires are in area of high AC noise. Because of the good AC noise rejection of modern instruments, electrical noise is not normally a problem. Switch your current meter to the AC scale to check for noise above the background AC level; read the background with meter leads shorted together. Next, clip the leads across the R1 sense resistor shown in Figure 1. Test if AC pickup is through the RTD leads by shorting the RTD terminals together right at the Temptran to see if the AC decreases. You will have to judge how much AC is too much for your computer. The 4-20 ma current loop is highly immune to noise pickup, however, any noise picked up in long RTD input leads will show up Page 7

in the current signal. When extending the leads of the RTD, use twisted pair. If you want to use shield braid around the twisted extension leads to the RTD, connect the shield braid to the negative current loop terminal of the Temptran (terminal 2, or brown wire) at the Temptran end; do not connect the shield at the end by the RTD. 28.Noise picked up on current loop. Use twisted pair instead of straight wires. 29.AC power applied to the current loop terminals of Set meter to AC volts scale and connect to Temptran current loop Temptran. or terminals. If you find excess AC, check power supply and check Power supply is providing AC riding atop the DC. for accidental connection to other wiring. 30.Ambient temperatures are too high or low for Move the Temptran to a more moderate environment and extend Temptran. the lead wires to the RTD using twisted pair. 31.Temptran calibrated for a specific sensor has been connected to the wrong sensor. TT110 & TT111 Temptrans' ambient limits are 32 to 122 F (0 to 50 C). The Temptran will function outside these limits, but the factory spec. s are not guaranteed. Prolonged operation at temperatures above 122 F is likely to cause more calibration drift than operation at temperatures below 32 F. Temptrans of certain model numbers are calibrated to one individual RTD. If there is a number tag on the RTD which matches the number printed on the Temptran's label, then you have a matched set. If Temptrans or RTD s were swapped around, an error of a few degrees is likely. 32.Temptran or sensor has drifted just a degree or two. Adjust ZERO pot of Temptran or recalibrate per #25 above. Notes: 33. As the temperature increases, causing an increase in the current signal to 20 ma, the voltage across the Temptran's current loop terminals always drops. 34. By temporarily shorting the RTD's terminals with a wire or paper clip, the current loop may be forced to a 2 to 3 ma value to test the computer's readout. The Temptran will not be harmed and calibration will not be changed. 35. You can check the current in a loop without causing a discontinuity or a change in current to be seen by the computer: To insert a current meter into a loop, connect its leads to the wire or terminals on each side of the point where you're going to break the loop - then go ahead and open the loop there. The Temptran will handle the meter's added resistance with no change in current. Copyright 2001, G:\MOD\TT\730.DOC Page 8