OPERATION MANUAL. SI unit EX250-SDN1-X102

Similar documents
No. : EX##-OMF0004 OPERATION MANUAL. SI unit EX12#-SMB1

E/P Regulator (DeviceNet TM type) ITV1000/2000/3000/2090-DE* Series

Adjustment functions for both span and shift have been incorporated

Smart DeviceNet Remote I/O Terminals

EX##-OMN0011-A. SI unit for EtherCAT PRODUCT NAME. EX260 Series MODEL/ Series

EX##-OMN0013. SI unit for DeviceNet TM PRODUCT NAME. EX260 Seires MODEL/ Series

DLP-PU/E Instruction Manual

Cross-beam scanning system to detect slim objects. 100 mm in

USER S MANUAL. CompoBus/D (DeviceNet) Communications Unit MODEL 3G3MV-PDRT1-SINV. (For SYSDRIVE 3G3MV Multi-function Compact Inverters)

CMC-DN01 DeviceNet Slave Communication Card Operation Manual

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

Doc.No. NDP 192U-02. Electric Pump Controller CE-124P. Instruction Manual

Clear Glass Sensor. Ordering Information E3S-CR67/62. Optimum Sensor for Detecting Transparent Glass and Plastic Bottles

T7560A,B,C Digital Wall Module

3 Port Solenoid Valve

Power supply unit Model: PAC-SC50KUA

CQM1-SF200/CS1W-SF200

CAUTION OPC-LM1-IL. Option Card for Encoder of Line Driver Output. Instruction Manual

Termination Resistors:

Install the DeviceNet Module using the following procedure:

Combi switchbox with integrated 3/2 way pilot valve

Modular I/O System Analog and Digital Interface Modules

Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment

Small U-shaped Micro Photoelectric Sensor. Enables space saving and quick installation!

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT Spur 2. Spur 1. Zone 1. Zone 0

EE-SX91. Meeting Customer Needs with Compact Sensors that Mount with M3 Screws

Part number NPN E2EM-X2C1 E2EM-X2C2 PNP E2EM-X2B1 E2EM-X2B2 NPN E2EM-X4C1 E2EM-X4C2 PNP E2EM-X4B1 E2EM-X4B2

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

Mounting Instructions. Torque Transducer. A en

Addendum to the Operating Instructions

ADM1TE 5/30A DIN rail single phase two wire energy meter

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)

Digital input modules

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2

DeviceNet Master Module(EH-RMD)/ Slave Controller(EH-IOCD)/ Discrete I/O slave unit (RDX16D,RDY16TP,RDY16R) APPLICATION MANUAL

Documentation for. KL2602 and KL2622. Two-channel Relay Output Terminals for 230 V AC / 30 V DC. Version: 1.4 Date:

SIMATIC NET. CP AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Series LC6D/LC6C. To power supply PLC. LC6C dedicated teaching box P.971. Options P.973

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC A - M8 connector

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

Installation and safety instructions for AC/DC built-in devices

Data sheet GIOD.1 Input/output module with CAN bus. ERP no.: Data sheet GIOD.1 V_3.0

Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty Safety notes Policy Warranty.

Technical data. General specifications. Signal voltage V DC Signal duration. 1 s Input 2. Signal voltage. 1 s Analog output.

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

PA5. Series. Quick-Connect Cables with Connectors. Simplifies sensor wiring. Wide variety of connectors attached to cables.

CAUTION OPC-LM1-ID. Option Card for Frequency Divider. Fuji Electric FA Components & Systems Co., Ltd. Instruction Manual

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet

No.EX##-OMJ1003. SI Unit Lightbus compatible PRODUCT NAME. EX250-SLB1-DE MODE / Series

USER S MANUAL. MaxPower UPS. Uninterruptible Power System 28-2MAXPO0018

Laser diffuse reflection light scanner with background suppression. Dimensioned drawing

Ordering Information. Cylindrical Proximity Sensor E2E/E2E2

Allen-Bradley/Rockwell

How To Use A Power Supply Unit (Upu)

4 Posiflow Proportional Solenoid Valves

Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit

Contactless Encoder RI360P0-QR24M0-INCRX2-H1181

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

TQ SMD RELAYS TQ SMD LOW-PROFILE SURFACE-MOUNT RELAY FEATURES SPECIFICATIONS

AC 800M. EtherNet/IP DeviceNet Linking Device LD 800DN. Power and productivity for a better world TM SP1134

U-shaped Micro Photoelectric Sensor

Three-phase Asymmetry and Phase-sequence Phase-loss Relay K8AB-PA

EE-SPY801/802. Photomicrosensors for detecting wafer-carrier mounting. Wafer-carrier Mounting Photomicrosensors. Ordering Information.

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

OPERATING MANUAL. Table of contents. 2 Phase Stepping Motor Driver 2M542. Rev. A. Introduction page 2. Specifications page 2 Timing chart page 3

MasterINTERFACE 39 Series - Relay interface modules

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2, /0.65/0.

Liquid Leakage Sensor Amplifier

Advantium 2 Plus Alarm

Practical steps for a successful. PROFIBUS Project. Presented by Dr. Xiu Ji Manchester Metropolitan University

How To Read A Pipe From A Sensor

Automotive Sensor Simulator. Automotive sensor simulator. Operating manual. AutoSim

Safety Manual BT50(T) Safety relay / Expansion relay

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

G670 Intermittent Pilot Ignition Controls

TYPE 65UV CEX Integrated Flame Scanner with Internal Flame Relay and Analog Output

48 SERIES Relay interface modules 10 A

NC-12 Modbus Application

DVPPF02-H2. PROFIBUS DP Slave Communication Module Application Manual

38 Series - Relay interface modules A

Operating Instructions

12 Volt 30 Amp Digital Solar Charge Controller

T0118 T2118 T3118. Instruction Manual

DeviceNet Communication Manual

PRELIMINARY MANUAL STAGE COLOR 48. Preliminary User Guide. Official version will follow soon on: TABLE OF CONTENTS

VAQ. Built-in V-series Miniature Basic Switch for Compatibility with Business and Consumer Equipment. Pushbutton Switch (Cylindrical 10.5-dia.

Telefon (+45) Telefax (+45) Installation and operating manual

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

Backup Scanner Module

EZmoto V2. Product description Rev. 6 10/01/2014. EZmoto V2 Product description Rev.6 10/01/2014

Signaling Lights. LH Series Surface Mount Indicators. Part Numbers. Jumbo Dome (one color) Jumbo Dome (two color)

4 non-safe digital I/O channels 2 IO-Link Master V1.1 slots. Figure 1. Figure 2. Type code. TBPN-L1-FDIO1-2IOL Ident no

=============================== WARNING

Kvaser Mini PCI Express User s Guide

LM10. Micro Laser Displacement Sensor. The LM10 makes laser sensors super easy to use! New circuitry lowers costs

Transcription:

No. EX## - OME0012 OPERATION MANUAL SI unit EX250-SDN1-X102 SMC Corporation

Contents 1.Precautions ------------------------------------------ P2 2.Specifications 2-1.General specification ------------------------------------------ P5 2-2.Electrical and network ------------------------------------------ P5 2-3.Applicable solenoid valve series ------------------------------------------ P6 3.Wiring and setting 3-1.Connection type -------------------------------------------- P7 3-2.Wiring of power supply -------------------------------------------- P9 3-3.Installation and maintenance ------------------------------------------ P11 3-4.Address setting ------------------------------------------ P13 4.LED indicator and Physical dimensions 4-1.LED indication ------------------------------------------ P15 4-2.Physical dimensions ------------------------------------------ P16 5.Trouble Shooting ------------------------------------------ P17

1. Precaution Following safety requirements aim at the prevention of hazardous condition and the damage of instruments. Here, the hazard is classified in Dangerous, Warning and Caution on the level of hazard. Please refer to regulation of safety on ISO and JIS to ensure safety. Warning : Operator error may cause the death or serious injury. Caution : Operator error may cause the injury or equipment damage. Warning 1.The product is designed to use in ordinary full automation equipment. Don t use this product in equipment or instrument where human life may be directly injured or malfunction of failure may cause devastating loss. 2.Don t disassemble the product to repair and modification. Caution Read this operation manual carefully to ensure the safety and proper operation. Design,Selection 1. See the specification Keep all requirements in the specification (Voltage, operating ambient temperature, impact) to avoid damage, malfunction and fire. 2. Specified maintenance space is necessary Design must consider the space necessary for maintenance. Installation,Adjustment,Wiring 1. Don t drop nor hit the unit Don t apply impact more than 100m/s 2. Internal parts of SI unit may be damaged and malfunction. 2. Wire properly SI unit may damage by improper wiring. 3. Don t wire power supply line and high power line together Wire SI unit wiring (piping) and power line/high power line separately to avoid interference of noise and surge from high power line to the signal line. 4. Ensure the insulation of wiring Insulation failure (mixture with other circuit, insulation between terminals etc.) may cause excessive voltage or current to SI unit which leads to damage the SI unit. - 2 -

5. Keep the tightening torque The screw should be tighten with the specified torque, otherwise IP67 protection can not be guaranteed. 6. Don t apply repeated bend and tensile force Wiring applying repeated bending stress and tensile force lead to cause disconnection. Operating Condition 1. Never use in explosive environment SI unit is not explosion proof. Operation in explosive environment may cause explosion accident. 2. Don t apply temperature cycle Temperature cycle other than normal temperature change do harm to the internal part of SI unit. 3. Don t use where exposed to surge source Device and instrument which generate big surge (Electromagnetic lifter, High frequency induction furnace, motor etc.) adjacent to the manifold solenoid valve with SI unit lead to cause the deterioration or damage of the switch internal circuit element. Consider the solution against surge and do not to mix lines. 4. Bits of wire and other foreign materials should not enter the product Bits of wire and other foreign materials in SI unit may cause fire, failure or malfunction. 5. Mounting of SI unit on manifold and wiring from the conduit shall be treated as specified Otherwise IP67 rating cannot be attained. Maintenance 1. Periodic maintenance is recommended to avoid unexpected failure and malfunction. 2. Don t touch the terminal and internal board during energization to avoid malfunction, unit damage, and electric shock. - 3 -

Safety instructions for power supply 1. User must supply power to input and solenoid separately single or dual power supplies can be used. 2. Choose UL recognized product for direct current power source to be mounted. (1) Limited voltage current circuit complying with UL508 The power supply circuit made with secondary side coil of isolation transformer which satisfies the following condition Max. voltage (No load applied) : 30Vrms (42.4V peak) or less, and Max. current : 8A or less (Include when short), and restricted by the circuit protecting device (fuse) with rate in the table below Voltage with no load (V peak) Max. current rate 0 to 20 [V] 5.0 Exceeding 20 [V] up to 30 [V] 100 Peak voltage (2) Max. 30Vrms (42.4V peak) or less circuit (Class 2 circuit) which sources class 2 source unit complying with UL1310 or class 2 transformer complying with UL1585. - 4 -

2. Specifications 2-1 General specification Item Operating ambient temp. Operating ambient humidity Storage ambient temp. Vibration proof Impact proof Noise immunity Withstand voltage Insulation resistance Operating environment Specification +5 to +45 C 35 to 85% RH (No dew condensation) -20 to +60 C 10 to 57Hz 0.35mm (Constant amplitude) 57 to 150Hz 50m/s 2 (Constant acceleration) 150m/s 2 (peak), 11ms three times in each direction X, Y and Z. Normal mode : 1500V Pulse duration 1us Common mode : 1500V Pulse duration 1us Radiation : 1000V Pulse duration 1us 500V AC for 1min. 500V DC min10m ohm No corrosive gas and no dust 2-2 Electrical and network Item Specification Applicable system DeviceNet Release 2.0 Power for SI unit 11 to 25V DC Current consumption 100mA or less Power for Input Block Current consumption Power voltage range Current consumption Power for solenoid valve Current consumption - 5-19.2 to 28.8V DC Depending on the number of Input Block stations and sensor specifications. Max 1A or less 22.8 to 26.4V DC Depending on number of Solenoid valve station and specifications Max 2A or less Output type P-ch MOS-FET Open drain type Solenoid valve with protection circuit for 24V Solenoid valve Connection load DC and 1.5W or less surge voltage. connection spec. (made by SMC) Insulation type Opto coupler type Residual voltage 0.3V DC or less 0 to 63 MAC ID setting range (Set by DIP / retain MAC ID information when setting power is shut off via network.) 500kbps,250kbps,125kbps Baud Rate (Transmission speed) (Set by DIP / retain Baud Rate information when setting power is shut off via network.) Slave (branch station) type Group 2 only server Connection type T branch type, Multi drop type Device type 27 Product code 2404 Revision Refer to EDS file Vendor ID 7 Consumed connection size (Receiving bite) 4 (Polled I/O connection : Occupy 4 byte) Produced connection size (Sending bite) 6 (Polled I/O connection : Occupy 6 byte) Correspond message Polled command (I/O message), Explicit message. Network connection spec.

SI unit I/O data (Poll command sending / receiving data) Item Occupied byte Sending / receiving data Output (Poll request) Input (Poll response) 4 byte 6 byte (Solenoid valve output) (Sensor input) Address + 0 Output No. 0 to 7 Input No.0 to 7 Address + 1 Output No. 8 to 15 Input No.8 to 15 Address + 2 Output No. 16 to 23 Input No.16 to 23 Address + 3 Output No. 24 to 31 Input No.24 to 31 Address + 4 ------------------ *Note1 Address + 5 ------------------ *Note1 *Note1 Bit(Input) Item 7 6 5 4 3 2 1 0 Address + 4 Reserved Area(state not defined) Sending data Address + 5 Reserved DI_CHK SOLV Reserved SOLV :Solenoid valve power status.(when power is down, to be 0 state. Usually, it is 1 ) DI_CHK :Over current status from Input Block.(When over current is detected, to be 0 state. Usually it is 1 ) *) Mapping method of sending / receiving data is different by PLC. For further information, refer to the manual for PLC master (scanner) 2-3 Applicable solenoid valve series Valve type Valve series VQC series VQC1000, VQC2000 SV series SV1000, SV2000, SV3000-6 -

3. Wiring and Setting 3-1 Connection type DeviceNet can be connected by T branch, Multi branch, Stay branch and Multi drop. Total extension length of trunk and Drop line is different for different Baud rate and thickness of communication cable. Terminal resistance Trunk line Terminal resistance Drop line Multi branch Node Length of wiring Node Node Node Node Drop line Node T branch Drop line Stay branch Node Node Node Communication Total length of Total length of Baud rate Length of stay distance trunk stay 500 kbps 100m or less 39m or less Thick cable 250 kbps 250m or less 6m or less 78m or less 125 kbps 500m or less 156m or less Thin cable Common 100m or less Terminal resistance 121 ohm (1/2W) Cable specification Item Thick cable Thin cable Communication Signal Power supply Communication Signal Power supply Conductor cross section 0.82 mm 2 1.65 mm 2 0.20 mm 2 0.33 mm 2 Colors Blue, White Red, Black Blue, White Red, Black Impedance 120ohm±10%(1MHz) 120ohm±10%(1MHz) Propagation delay 1.36ns / ft(max) 1.36ns / ft(max) 0.13db/100ft@125KHz (max) 0.29db/100ft@125KHz(max) Attenuation rate 0.25db/100ft@500KHz(max) 0.50db100ft@500KHz(max) 0.36db/100ft@1.00MHz(max) 0.70db/100ft@1.00MHz(max) Conductor resistance 6.9ohm / 1000ft(max) 3.6ohm / 1000ft (max) 28ohm / 1000ft(max) Caution on wiring For Multi drop connection, prepare plug connector for T branch separately. Use DeviceNet special cable for communication cable. Be sure to connect DeviceNet special terminal resistor with both ends of trunk. 17.5ohm / 1000ft (max) - 7 -

Example of connection EX250-SDN1-X102 DCA1-5CN[ ][ ]W1 :OMRON RSC RKC 57X-[ ]M :Interlink BT DC PS or terminal WAKW 4.5T-[ ] :TURCK 766-79-4450-[ ][ ]-05 :Franz Binder DCN2-1 :OMRON RSM FKM RKM 57 :Interlink BT DEVICE or Master PLC SMC does not provide the detail of catalog, so contact each manufacture. DEVICE or Terminal resistor DRS2-1:OMRON RSM 57-TR2 (for thick cable) RSE 57-TR2 (for thin cable) :Interlink BT - 8 -

3-2 Wiring of power supply Power supply line inside the unit has individual power supplies for solenoid valve actuation (SV power supply) and for Sensor (SW power supply). Supply 24V DC for each of them. Either single or dual power supply is available. Wiring is not necessary for SW power supply when Input Block is not used. SV power 24V DC Power supply cable with shield 3 2 5 SW power 24V DC 4 1 Power supply connector E A. Separate power supply Power supply cable with shield SV/SW power 24V DC 3 2 5 *In case of single power supply, pay 4 1 Power supply connector attention to the range of each supply voltage. E B. Single power supply Power for sensor is supplied to sensor connected with Input Block. Select sensor concerning voltage drop up to approx. 1V inside the unit at this moment. If sensor requires 24V, it is necessary to lower power supply voltage for sensor slightly or secure power supply for sensor separately without going through SI unit so that sensor input voltage can be 24V with actual loading (allowable voltage of sensor power supply : 19.2V to 28.8V). Voltage reduction of approx. 1V 24V DC 23V DC Sensor SI unit Input Block - 9 -

Power supply connector M12 5pin (Plug) Example of connector on cable side : Ex.TURCK WAKW 4.5T-[ ] etc. 4 3 5 2 1 No. Description Function 1 SV 24V For solenoid valve +24V 2 SV 0V For solenoid valve 0V 3 SW 24V For input block +24V 4 SW 0V For input block 0V 5 E Earth Communication connector M12 5pin (Plug) [Special for DeviceNet] Example of connector on cable side : Ex.OMRON DCA1-5CN[ ][ ]F1 KARL LUMBERG RKT5-56 Interlink BT RSC RKC 57X-[ ]M etc. 3 4 5 2 1 No. Description Function 1 Drain Drain / Shield 2 V + Power supply + for circuit 3 V - Power supply - for circuit 4 CAN_H Signal wire H 5 CAN_L Signal wire L Applicable to Micro Style connector with DeviceNet specification - 10 -

3-3 Installation and maintenance Installation size SI unit does not have mounting holes. The unit can not be installed by itself. Solenoid valve manifold must be attached with SI unit. If no Input Block is required,then them End Plate must be attached with SI unit. Example of installation The number of solenoids = n (pieces) The number of Input Blocks = m (pieces) M4 6 Thickness:13.2(mm) 0 PWR(V) PWRMOD/NET 0 1 2 1 0 SETTINGS 66 (mm) 1 3 EX250 EX250 EX250 L2 = 21m + 89.8 (mm) L1 = 10.5n + 45 (mm) n_m L 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 L1 45.0 55.5 66.0 76.5 87.0 97.5 108.0 118.5 129.0 139.5 150.0 160.5 171.0 181.5 192.0 202.5 213.0 L2 89.8 110.8 131.8 152.8 173.8 194.8 215.8 236.8 257.8 278.8 299.8 320.8 341.8 362.8 383.8 404.8 425.8 Note : Dimensions of L1 are shown for VQC1000 solenoid valve series. (mm) Refer to SMC catalogue for valve series. Wiring (for power supply, communication and input) and piping are done on only one side. On the side, make a space for wiring and piping. - 11 -

Maintenance Addition of Input Block 1.Remove screws from End Plate. 2.Mount attached tie rod. 3.Connect additional Input Block. 4.Connect End Plate and tighten removed screws by specified tightening torque. (0.6N m) Exchange of SI unit 1.Remove screws from End Plate and release connection of each unit. 2.Replace old SI unit with new one. (Tie rod does not need to be removed.) 3.Connect End Plate and tighten removed screws by specified tightening torque. (0.6N m) Caution for maintenance (1) Be sure to turn-off all power supplies. (2) Be sure that there is no foreign object in any of units. (3) Be sure that gasket is lined properly. (4) Be sure that tightening torque is according to specification. If these items are not kept, it may lead to the breakage of substrate or intrusion of liquid or dust into the units. Assembly and disconnection of unit M3 hexagon screw Tightening torque : 0.6N m Tie rod BUS X102 PWR End Plate SI unit Valve unit - 12 -

3-4 Address setting When DIP switch is set, turn power supply of SI unit to OFF. SW1 ON 1 1 2 3 4 5 6 7 8 9 10 0 Setting of MAC ID MAC ID SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 2 0 (1) 2 1 (2) 2 2 (4) 2 3 (8) 2 4 (16) 2 5 (32) 0 0 0 0 0 0 0 1 1 0 0 0 0 0 2 0 1 0 0 0 0 : 62 0 1 1 1 1 1 63 1 1 1 1 1 1 Setting of Baud rate Baud rate SW1-7 SW1-8 125 kbps 0 0 250 kbps 1 0 500 kbps 0 1 Not used 1 1 Setting of solenoid output state in communication fault Solenoid output state : Communication stops (IO connection time out) or fault message is received. SW1-9 Solenoid output state 1 HOLD All solenoid valve outputs are hold before communication fault. (Fault state=1 Fault value=0) 0 CLEAR All solenoid outputs are reset to zero. (Fault state=0 Fault value=0) Mode setting SW1-10 Mode H/W mode 0 Set MAC ID and Baud rate by SW1-1 to 8 S/W mode 1 Set MAC ID and Baud rate by network. SW1-1 to 8 are invalid. - 13 -

Position of DIP switch DIP switch SW1 M3 pan head screw Tightening torque : 0.6N m Caution 1.Default value of MAC ID and baud rate. MAC ID and baud rate are preset to 63, 125kbps respectively at the shipment in H/W mode. 2.In S/W mode, setting value of MAC ID and baud rate are retained even after power supply is off. 3.In H/W mode, once power supply is turned off and turned on again, then setting value of MAC ID and baud rate in S/W mode are erased. MAC ID and baud rate can be newly set by setting switch SW1. Example S/W mode H/W mode S/W mode MAC ID : 63 MAC ID: 0 MAC ID : 0 Baud rate : 125kbps Baud rate : 500kbps Baud rate : 500kbps 4.Output with communication stopped is set to 0 (full output clear mode) at shipment from factory. It is possible to change setting of single output when communication stopped. In this case,setting of SW1-9 gets invalid. - 14 -

4.LED indicator and Physical dimensions 4-1 LED indication SI unit (EX250-SDN1-X102) Indication PWR (V) PWR MOD / NET Contents Lights up when power for solenoid valve is supplied. Lights up when power for DeviceNet line is supplied. Lights off Power off,off line or Duplicate MAC ID. Green flashing Waiting for I/O connection (ON line) Green lights up I/O Connection completed (ON line) Red flashing I/O Connection time out (Minor communication error) Red MAC ID duplication error or BUS OFF error lights up (Major communication error) - 15 -

4-2 Physical dimensions SI unit (EX250-SDN1-X102) - 16 -

5. Trouble Shooting MOD/NET LED Lights off Green flashing Red flashing Red lights up Cause & Countermeasure PWR LED lights off <Countermeasure> Confirm that power for SI unit circuit is supplied. Confirm correct wiring for circuit. If above countermeasures do not improve status, please exchange SI unit. PWR LED lights up <Countermeasure> Confirm that baud rate is set correctly. If MOD/NET LED lights off in spite of baud rate is set correctly, change SI unit. I/O Connection waiting Shows communication waiting status between SI unit and master. <Countermeasure> Confirm master operate correctly. If using scan list, ensure slave is recorded to scan list correctly. I/O Communication wire disconnected error Warning for SV supply voltage drop <Countermeasure> Confirm communication wire is not disconnected. Confirm SV power supply voltage is according to specification. (22.8 to 26.4V) <Remark> Red flashing if master power source is turned off during communication. MAC ID overlapping error <Countermeasure> Confirm there is no overlapping on the MAC ID. BUS OFF error Detects communication error. <Countermeasure> Case 1 Communication error due to noise. Confirm there is no component or high voltage cable that generate noise around communication wire. Make some distances between communication wire and noise source. Case2 Communication cable problem Confirm terminal resistance (121ohm) connects to the both ends of communication wire that is main wire of communication wire. If red MOD/NET LED is still lights up in spite of above countermeasures, change SI unit. Caution When red MOD/NET LED is lit, even if cause is solved, SI unit do not do auto-recovery. In this case, please reset the power to SI unit circuit (Communication/Internal power supply). - 17 -