THE COMBUSTION BEHAVIOUR OF FORDED-DRAUGHT INDUSTRIAL BURNERS WHEN FIRED WITHIN THE EASEE- GAS RANGE OF WOBBE INDEX

Similar documents
ATMOSPHERIC EMISSIONS FROM GAS FIRED HOME HEATING APPLIANCES

Continuous flow direct water heating for potable hot water

Boiler Tune-up Guide

Utilization of New Gas Supplies Filling Key Information Gaps

Tips for burner modulation, air/fuel cross-limiting, excess-air regulation, oxygen trim and total heat control

The prediction of flue gas emissions from the combustion in the industrial tubular heaters

Module 5: Combustion Technology. Lecture 33: Combustion air calculation

COMBUSTION. In order to operate a heat engine we need a hot source together with a cold sink

Gas Turbine Combustor Technology Contributing to Environmental Conservation

Energy Efficient Operations and Maintenance Strategies for Boilers

CIMAC Position Paper

Improving Steam Methane Reformer Performance with the ZoloSCAN-SMR

Calculate Available Heat for Natural Gas Fuel For Industrial Heating Equipment and Boilers

COKE PRODUCTION FOR BLAST FURNACE IRONMAKING

Gas Burner Technology & Gas Burner Design for Application

STOICHIOMETRY OF COMBUSTION

2nd IEA Oxyfuel Combustion Conference

Texas Commission on Environmental Quality Page 1 Chapter Control of Air Pollution from Nitrogen Compounds

COMBUSTION. By: Michael Biarnes. In collaboration with: Bill Freed and Jason Esteves. E Instruments International LLC -

THE OPTIMISATION OF BIOMASS COMBUSTION IN SMALL BOILERS

NITROGEN OXIDES FORMATION in combustion processes COMBUSTION AND FUELS

This article provides a basic primer on an

Originators of the Flexible Water Tube design

POSSIBILITIES FOR ADMIXING GASIFICATION GASES: COMBUSTION ASPECTS IN DOMESTIC NATURAL GAS APPLIANCES IN THE NETHERLANDS

OXYGEN AND OPACITY STACK EMISSION MONITORING SYSTEMS TO OPTIMIZE COMBUSTION EFFICIENCY AND MEET EPA REQUIREMENTS

Boiler efficiency measurement. Department of Energy Engineering

COMBUSTION STUDIES OF NATURAL GAS AND SYN-GAS WITH HUMID AIR

Offshore Gas Turbines and Dry Low NOx Burners. An analysis of the Performance Improvements (PI) Limited Database

Industrial Gas Turbines utilization with Associated Gases

R&D on Oil-Burning, Environment-Friendly, High-Efficiency Boiler

FINAL REPORT COMBUSTION TESTING OF A BIO-DIESEL FUEL OIL BLEND IN RESIDENTIAL OIL BURNING EQUIPMENT. Prepared for:

Latest Low-NOx Combustion Technology for Pulverized-coal-fired Boilers

Efficiency Options for Thermal & Catalytic Oxidizers

Flame Conductivity VS Flame Rectification Systems

Successfully Integrating Natural Gas from Multiple Origins: The Spanish Case Story

Study on performance and methods to optimize thermal oil boiler efficiency in cement industry

Control Device Requirements Charts For Oil and Gas Handling and Production Facilities

PART 11: START-UP PROCEDURES FOR THE INSTALLER

Advantage of Using Water-Emulsified Fuel on Combustion and Emission Characteristics

ENERGY EFFICIENCY IN POWER PLANTS

The Use of Exhaust Gas Recirculation (EGR) Systems in Stationary Natural Gas Engines. The Engine Manufacturers Association August 2004

INDEX GENERAL

Effects of Ultra-High Turndown in Hydronic Boilers By Sean Lobdell and Brian Huibregtse January 2014

CFD Simulation of Biofuel and Coal Co-Combustion in a Pulverized Coal Fired Furnace

Pulverized Coal Pipe Testing and Balancing

Balancing chemical reaction equations (stoichiometry)

POROUS BURNER - A New Approach to Infrared

Biomass Boiler House Best Practices. Irene Coyle & Fernando Preto CanmetENERGY

MONITORING & MEASURING EQUIPMENT FOR EMISSIONS CONTROL, HAZARD DETECTION & ENERGY OPTIMIZATION

CFD Analysis of a MILD Low-Nox Burner for the Oil and Gas industry


A Review of Biomass Boiler Technologies. Fernando Preto CanmetENERGY, Natural Resources Canada

Validated methods for flue gas flow rate calculation with reference to EN

1. Standard conditions are in. Hg (760 mm Hg, psia) and 68 F (20 C).

1.3 Properties of Coal

Case History: Ethanol Facility Retrofit with a Lower Emissions, Improved Fuel Efficiency Thermal Oxidizer and Dryer Burners

Iron and Steel Manufacturing

Beware of Exaggerated Claims and Uncertified Manufacturers Ratings Regarding Commercial Boiler Efficiency

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors

Operating Performance and Latest Technology of DeNOx Plants for Coal-Fired Boilers

Malmö Hydrogen and CNG/Hydrogen filling station and Hythane bus project

3 - Atomic Absorption Spectroscopy

HOW TO SELECT A LOW VOLUME (L.V ) BOILER

Danish stoves - a cosy and eco-friendly heat source

Power-Gen International 2008 Orlando, Florida

Flue Gas Analysis as a Diagnostic Tool for Fired Process Heater Furnaces

COMBUSTION PERFORMANCE SAFETY ACTION LEVELS FOR DOMESTIC GAS APPLIANCES

Natural Gas Energy Efficiency Opportunities for Commercial & Industrial Customers. Michael Pace Lead Engineer C & I Efficiency Programs

Alternative to Fossil Fuel

An Experimental Study on Industrial Boiler Burners Applied Low NOx Combustion Technologies

Basis and Purpose Document on Specifications For Hydrogen-Fueled Flares

Combustion Analysis Basics

A GUIDE TO SELECTING YOUR INDUSTRIAL OVEN

Frequently Asked Questions

Energy Efficient Operations and Maintenance Strategies for Industrial Gas Boilers

Waste Incineration Plants

REPORT. Combustion control in domestic gas appliances. Fuel gases containing hydrogen. Project report April 2014

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard

FIRED HEATER OPTIMIZATION

The Engineer s Guide to Efficiency Requirements for Wood Burning Appliances

1/11 CO2 DOSAGE SYSTEMS. CO2 dosage system consists of following parts;

Air-Free Measurement of Carbon Monoxide Emissions from Gas Ranges: Analysis and Suggested Field Procedure

PROCESS CONTROL SYSTEM DESIGN Process Control System Design. LECTURE 6: SIMO and MISO CONTROL

Application Requirement

Boiler NOx Emissions and Energy Efficiency

WATER WALL BOILER FOR AIR AND OXYGEN FIRED CLAUS SULPHUR RECOVERY UNITS

EMISSIONS OF OXIDES OF NITROGEN FROM INDUSTRIAL, INSTITUTIONAL, AND COMMERCIAL BOILERS, STEAM GENERATORS, AND PROCESS HEATERS

Energy Saving Solutions. Bob Montgomery Technical Solutions Specialist Waterloo Manufacturing

Thermal Mass Flow Meters

TODAY S THERMAL OXIDIZER SOLUTIONS TO MEET TOMORROW S CHALLENGES

PRESSURES GENERATED IN COMBUSTION CHAMBERS BY THE IGNITION OF AIR - GAS MIXTURES

CHAPTER V TOE COMBUSTION EFFICIENCY OF DIFFERENT BOILER SYSTEMS* EXPERIMENTAL OESUX.TS Chapter Preview

MATHESON STACK EMISSION CALIBRATION PROGRAM. Experience the MATHESON Commitment to Supply Chain Excellence

FIELD TESTS OF FUEL EFFICIENCY MAGNETS J A CRABB JULY 1997 SWEEG REPORT 80

6 CONSIDERATION OF ALTERNATIVES

Operating instructions

SUBJECT/TASK (title) CONTRIBUTOR(S) Morten Fossum, Ranveig V. Beyer CLIENT(S) IEA Bioenergy TR NO. DATE CLIENT S REF. PROJECT NO.

Evaluation of portable flue gas analysers for monitoring carbon dioxide in ambient workplace air HSL/2006/42. Project Leader: Peter Walsh.

CT556 Boiler Efficiency Modern Controls for Package Boiler Operations

EVALUATION OF GEOTHERMAL ENERGY AS HEAT SOURCE OF DISTRICT HEATING SYSTEMS IN TIANJIN, CHINA

Transcription:

THE COMBUSTION BEHAVIOUR OF FORDED-DRAUGHT INDUSTRIAL BURNERS WHEN FIRED WITHIN THE EASEE- GAS RANGE OF WOBBE INDEX B.K. Slim, H.D. Darmeveil, S. Gersen and H.B.Levinsky KEMA Nederland B.V. Groningen, The Netherlands ABSTRACT In Europe, a common business practice for the cross-border exchange of natural gases has been formulated by EASEE-gas. The proposed range of Wobbe Index for this purpose is 48.96-56.92MJ/Nm 3 (25 C/0 C, 1013.25 hpa). However, it is unclear whether the entire range of end-use equipment can accept the suggested range and still function as desired. Research is currently underway tot assess whether this range of gases can be accepted by domestic appliances. To our knowledge, there has been little systematic investigation of the acceptable range of gas quality for large-scale, forced-draught industrial burners. Although natural gas is predominantly methane with lesser amounts of higher hydrocarbons and inerts, the variation in gas composition can have significant effects on burner performance. The vast majority of forced-draught industrial burners features a flow of air independent of the gas composition, therefore the air factor is (inversely) proportional to the Wobbe Index of the gas. In this paper we present the results of experiments on a number of generic large-scale industrial burners for boilers and industrial processes in which the Wobbe Index is varied across the EASEE-gas range. The combustion effects focused mainly on flame stability (burner overheating/blow-off and vibrations) and the pollutant emissions, such as CO, NO x and unburned hydrocarbons over the desired range of turndown ratio. The experimental results showed that, for the burners studied the measured oxygen concentration was the predominant factor governing burner behaviour; between 0.5 and 7% O 2, all burners showed a stable flame while emitting less than 400 ppmv (dry, air free) CO. Outside this O 2 range, the low-no x boiler burners, being the most sensitive, showed decreasing flame stability and increasing CO production. One burner even exhibited blow-off, causing the safety system to shut down burner operation, an undesirable event in practice. In the burners studied, the NO x emission can increase significantly with increasing Wobbe Index. Even a relatively small increase can cause the burner to exceed the locally enforced NO x limit. The visible flame length increased with increasing Wobbe Index, due to the concomitant decrease in air factor and increase in thermal input. This can lead to a higher thermal load on furnaces, which may be unacceptable in some cases. The experimental results indicate that to widen the acceptable range some form of active control is necessary for the burners for boilers. The merits of using a feed-back control system, using oxygen measurement in the flue gas, compared to a feed-forward control using the Wobbe Index of the fuel gas are discussed. In particular, aspects regarding safety in the event of sensor malfunction are seen to be important when choosing a system. In this case, the Wobbe method seems technically preferable.

1. INTRODUCTION In Europe, the common business practice for the cross-border exchange of natural gases has been formulated by EASEE-gas. The proposed range of Wobbe Index for this purpose is 48.96-56.92MJ/Nm 3 with the EASEE-gas references (25 C, 0 C. 1013.25hPa). However, it is unclear whether the entire range of end-use equipment can accept the suggested range and still function as desired. Research is currently underway tot assess whether this range of gases can be accepted by domestic appliances. To our knowledge, there has been little systematic investigation of the acceptable range of gas quality for large-scale, forced-draught industrial burners. Although natural gas is predominantly methane with lesser amounts of higher hydrocarbons and inerts, the variation in gas composition can have significant effects on burner performance. The two main consequences of this variability pertain to the thermal input and the aeration of the burner. As is well known, the thermal input to a burner is directly proportional to the Wobbe Index of the gas. Additionally, the air factor divided by the calorific value is constant to within 0.7% for the major alkanes in natural gas. Taken together with the fact that, without an air-ratio control system, the flow of air is independent of the gas composition, the air factor is (inversely) proportional to the Wobbe Index of the gas as well. In this paper we present the results of experiments on a number of generic large-scale industrial burners in which the Wobbe Index is varied across the EASEE-gas range. The combustion effects focus mainly on flame stability (burner overheating/blow-off and vibrations) and the pollutant emissions, such as CO, NO x and unburned hydrocarbons over the desired range of turndown ratio. The experimental results indicate that to widen the acceptable range some form of active control is necessary for the burners for boilers. Further, the merits of using a feed-back control system based on oxygen measurement in the flue gas, compared to a feed-forward control using the Wobbe Index of the fuel gas, are discussed. 2. EXPERIMENTAL METHOD For this study, one line burner for air heating and four low-no x boiler burners were tested in a water-cooled furnace representing an industrial warm-water boiler. Three high temperature process burners were tested in a test furnace representing a kiln for firing ceramic products. In total 8 burners were tested in 2 different furnaces. The Wobbe Index of the natural gas was varied by adding propane to Groningen gas, a relatively low calorific value natural gas common in the Netherlands. Three different gases, having a Wobbe number of 48.3 MJ/Nm 3 (9% propane), 52.0 MJ/Nm 3 (18% propane) and 57.2 MJ/Nm 3 (29% propane) were blended during the tests, slightly wider than the EASEEgas range. The compositions were monitored using a micro-gaschromatograph. The observed Wobbe Indices remained within +/- 0.2MJ/Nm 3 of the desired value at all times. This relatively high propane content can be considered worst case for CO production and soot formation, since a distribution gas having a Wobbe Index of 57,2 MJ/Nm3 will ordinarily have a smaller fraction of higher hydrocarbons and more methane. However, the large fraction of higher hydrocarbons can be considered favourable for preventing lift-off as

compared to commonly distributed natural gases. Since the excess oxygen is in principle only dependent on the Wobbe Index and not the composition, we do not anticipate significant effects of the propane content on visible flame length a priori. The burners were tested at three different loads; minimum load (according to the manufacturer 10-20% of maximum load), half-load (50% of maximum load) and maximum load (100%). The effect of the Wobbe Index of the natural gas used when installing or adjusting the burner (particularly the air/fuel ratio) was considered by setting the desired oxygen fraction (usually 3-5%) in the flue gas at each of the three Wobbe Indices mentioned above. This oxygen fraction in the flue gas is required to guarantee safe and reliable combustion at all times. Once the thermal input and air ratio were set using the given "adjustment" gas, the measurement series were performed using the other Wobbe Index gases. This procedure simulates a worst case industrial practice, where this adjustment is done by the service engineer unaware of the Wobbe Index of the supplied gas during burner adjustment. The actual gas quality and its possible variations are not always taken into account during adjustment of the burner. 3. RESULTS AND DISCUSSION 3.1 CO emissions The experimental results showed that, for the burners studied the measured oxygen concentration was the predominant factor governing burner behaviour; between 0.5 and 7% O 2, all burners showed a stable flame while emitting less than 400 ppmv (dry, air free) CO. Outside this O 2 range, the low-no x boiler burners, being the most sensitive, showed decreasing flame stability and increasing CO production, increasing to several thousands ppm (Figure 1). This figure shows the influence of the Wobbe Index used for adjustment and the Wobbe Index variations at each adjustment with varying thermal load. The results also reflect the effects of the air/gas control system intended to maintain the air ratio during turndown. These various effects are a result of our choice to simulate industrial practice. One burner even exhibited blow-off, upon which the safety system shut down burner operation, an undesirable event in practice. With the range of Wobbe Index used, the measured oxygen fraction in the flue gas varied between 0 (Wobbe Index gas 57.2MJ/Nm 3, burner adjusted at 48.3MJ/Nm 3 ) and 9% (Wobbe Index gas 48.3MJ/Nm 3, burner adjusted at 57.2MJ/Nm 3 ), a wider range than that for safe and reliable operation determined above. Variation within the EASEE-gas range, leading to a variation in oxygen fraction between 0.3 and 8.6% is also outside the range for safe and reliable operation. Burners adjusted using the "middle" gas (Wobbe Index 52MJ/Nm 3 ) burners could just perform satisfactorily if the air/fuel controller operated accurately, keeping the O 2 fractions between roughly 1 and 6%,. This range incorporates a margin of safety compared to the 0.5 to 7% range of acceptable boiler burner behaviour mentioned above, to allow for the

significant changes observed during turndown (see below). Two burners exhibited hysteresis in the control system during turndown, leading to larger variations in O 2 fraction, with ensuing instabilities and excessive CO formation in some cases. This range is equivalent to a range of Wobbe Index of roughly ± 5%, significantly more narrow than the EASEE-gas proposal. The line burner and the 3 process burners considered here exhibited a more robust behaviour; in all experiments the flame stability and the emissions were within values deemed acceptable. 3000 CO ppmv, n=1 2500 2000 1500 1000 500 0 BB1-48.3 BB1-52 BB1-57.2 BB2-48.3 BB2-52 BB2-57.2 BB3-48.3 BB3-52 BB3-57.2 BB4-48.3 BB4-52 BB4-57.2 0 1 2 3 4 5 6 7 8 9 10 O2, vol.% Figure 1 Boiler burners BB1-4: CO vs O 2 at different Wobbe Indices (48.3, 52 and 57.2) of the natural gas, at different themal loads In Figure 1 the oxygen concentration varies almost continuously from 0 to 9% and is not grouped in distinct clusters as one would expect with three different fuels and three different Wobbe adjustments of the burners. This is mainly caused by hysteresis in the burner control systems with turndown, as described above. Generally, after a few changes in burner load the fuel/air ratio (and thus the oxygen fraction in the flue gas) has changed noticeably. 3.2 NO x emissions In the burners studied, the effect of the Wobbe Index of the fuel gas on the NO x emission of the burner varied significantly as can be seen in Figures 2 and 3. In two of the cases illustrated below the NO x emissions decreased with increasing Wobbe Index of the fuel (Boiler Burner 4 and Oven Burner 1). In two cases (Oven Burner 2 and Boiler Burner 3) the NO x emission approximately doubled with an increasing Wobbe Index of the fuel gas. In the other cases the NO x increased between 10% and 50%. The dependence of the NO x emission on the Wobbe Index of the fuel gas varies widely among the burners investigated here. While clear that this variation arises from the details of the combustion process created by each burner design, it is not clear how burner design causes these differences.

In industrial practice, burners often barely meet the locally enforced NO x limit. In those cases, even a relatively small increase can cause the burner to exceed this local NO x limit. 120 100 NOx, mg/m3 (3%) 80 60 40 20 BB3 BB1 BB2 BB4 0 48 50 52 54 56 58 Wobbe Index natural gas, MJ/Nm3 Figure 2 Boiler burners BB1-4: NO x vs Wobbe Index of the natural gas NOx, mg/m3 (3%) 200 180 160 140 120 100 80 60 40 20 0 48 50 52 54 56 58 Wobbe Index natural gas, MJ/Nm3 OB2 OB3 OB1 Figure 3 - Oven burners OB1-3: NO x vs Wobbe Index of the natural gas 3.3 Visible flame length The visible flame length of the 4 boiler burners investigated was measured. The flames of the 3 oven burners could not be measured due to the visible radiation of the hot (approximately 1000ºC) furnace walls. Figure 4 shows an increase in visible flame length with increasing Wobbe Index of the fuel gas, mainly due to the decrease in air factor. As discussed above, the air factor is inversely proportional to the Wobbe Index of the fuel gas, in principle independent of the

detailed composition of the fuel. The flame length of boiler burners 3 and 4 in particular increased dramatically at flue gas oxygen levels lower than 1%. This can lead to a higher thermal load on furnaces, especially on the rear wall of the first flue, which may be unacceptable in some cases. Flame length, cm 600 500 400 300 200 100 0 0 1 2 3 4 5 6 7 8 9 10 O2, vol.% BB1-48.3 BB1-52 BB1-57.2 BB2-48.3 BB2-52 BB2-57.2 BB3-48.3 BB3-52 BB3-57.2 BB4-48.3 BB4-52 BB4-57.2 Figure 4 - Boiler burners BB1-4: Flame length vs O 2 at different Wobbe Indices of the natural gas 3.4 Discussion The experimental results indicate that to widen the acceptable range of performance some form of active control is necessary for the burners for boilers. If the O 2 fraction in the flue gas can be kept at a desired level, regardless of the Wobbe Index of the fuel, the burner will perform satisfactorily at all times. Oxygen trim is a closed loop control system available as an option on some electronic fuel/air ratio controls. Oxygen trim was employed on industrial installations for the first time in the late seventies, about the same time that Lambda control came into use in cars. But, the oxygen probes on several early systems suffered from short operating lifetimes, giving the oxygen trim a bad reputation. More robust probes are available now. When oxygen trim is included the oxygen levels can be set at their optimum level. If the oxygen level is set at about 2%, allowing for a small margin of safety, it will contribute energy savings of approximately 0,5% for every percent of oxygen fraction reduction at the common boiler flue gas temperature of 150ºC. A reduction of oxygen fraction from the usual 5% to 2% improves the boiler efficiency by 1.5%. For a boiler of about 4M th an oxygen trim system will typically be paid back between one and two years, depending on the load duration curve of the boiler. However, oxygen trim is a feed-back control system; the oxygen is measured after combustion and it takes typically 20-30 seconds after a change in measured oxygen faction before the control systems starts acting. After a sudden change ( step ) in the Wobbe Index of

the fuel gas the burner can operate outside its safe limit for a certain period of time, producing considerable CO emissions and/or flame instability, even to the point of blow-off or flame extinction. A feed-forward control system, using an input signal ( Wobbe signal ) reflecting the oxygen required for a safe and reliable combustion, ahead of time, will be able to maintain safe and reliable combustion under all circumstances, including sudden changes in Wobbe Index of the fuel gas. For very large installations, such as power plants and refineries, such feed-forward Wobbe control systems are common practice. For medium-sized installations, these systems are still too expensive. However, there are a few promising developments towards a more affordable Wobbe sensor. We have performed a numerical simulation, using MATLAB /Simulink software, to assess the feasibility of a feed-forward Wobbe control system. Using a typical first-order response time t 63 of the Wobbe sensor of 6 seconds, as measured in our lab, a delay time of 2 seconds before the fuel gas sample enters the sensor, and a fuel gas valve servo behaviour given by the manufacturer, the results show the feasibility of the system. The relationship between Wobbe Index and flue gas O 2 was modeled using the relations described in Physical Properties of Natural Gases, june 1988, N.V. Nederlandse Gasunie, the Netherlands; the relations are based on simple arguments of stoichiometry. The results of the simulation are depicted in Figures 5 and 6. At t = 10 seconds the Wobbe Index increases suddenly by about 5MJ/Nm 3. At t = 30 seconds the Wobbe Index decreases suddenly by the same amount (Figure 6). This is a substantially unfavourable situation. The corresponding oxygen fraction in the flue gas, as predicted by the model is shown in Figure 6. At a setting of 2.2% the control system keeps the oxygen fraction in the flue gas between 0.8% and 3.4%, an acceptable range for safe and reliable operation of the burner. Figure 5 Wobbe Index vs time Figure 6 O 2 vs time In particular, aspects regarding safety in the event of sensor malfunction are seen to be important when choosing a system. If a sensor, e.g. an oxygen, carbon monoxide or Wobbe sensor fails, a back-up control mode assuming a Wobbe Index of the fuel gas in the centre of

the Wobbe range automatically takes over the burner control. This setting must be known by the control system. This is impossible with an oxygen trim control not knowing the Wobbe Index of the fuel gas. In industrial practice this problem can be addressed by setting the burner at a very high oxygen fraction in the flue gas to fall back on. This oxygen fraction can exceed the upper level (7% for LowNO x boiler burners) for safe and reliable combustion at the lower Wobbe Indices of the fuel gas in the Wobbe range. Another solution is a limitation in the allowable reduction in oxygen fraction by the control system, rendering it less efficient. In this case, the Wobbe method seems technically preferable to the oxygen trim. 4. CONCLUSIONS 1. For the burners studied the measured oxygen concentration was the predominant factor governing burner behaviour Between 0.5 and 7% O 2, all burners showed a stable flame while emitting less than 400 ppmv (dry, air free) CO. Outside this O 2 range, the low-no x boiler burners being the most sensitive, showed decreasing flame stability and increasing CO production. 2. The EASEE-gas range) is a wider range than that for safe and reliable operation of LowNO x boiler burners. 3. In the burners studied, the effect of the Wobbe Index of the fuel gas on the NO x emission of the burner varied significantly. In two cases the NO x decreased with an increasing Wobbe Index of the fuel gas. In two cases the NO x emission approximately doubled with an increasing Wobbe Index of the fuel gas. In the other cases the NO x increased between 10% and 30%. In industrial practice burners often barely meet the locally enforced NO x limit. In those cases, even a relatively small increase can cause the burner to exceed this local NO x limit. 4. The visible flame length increases with increasing Wobbe Index of the fuel gas, mainly due to the decrease in air factor. This longer visible flame can lead to a higher thermal load on furnaces, especially on the rear wall of the first flue, which may be unacceptable in some cases. 5. The experimental results indicate that to widen the acceptable range some form of active control is necessary for the burners for boilers. If the O 2 fraction in the flue gas can be kept at a desired level, regardless of the Wobbe Index of the fuel gas the burner will perform satisfactorily at all times.

TABLE OF CONTENTS 1. Abstract 2. Paper