INSTALLATION, OPERATION AND MAINTENANCE MANUAL

Similar documents
Float and Thermostatic Traps Series H, C and X

Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW

TYPE E Main Valve Sizes 3 /8 through 12

PBX Series Quick Fit Connector Bimetallic Steam Traps

Selecting TEMA Type Heat Exchangers

REGULATORS 175/153 Series

FLASH TANK ECONOMIZER PRODUCT GUIDE

Installation, Operation, & Maintenance Instructions For JFD Shell & Tube Heat Exchangers

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap

INSTALLATION, OPERATING, AND MAINTENANCE INSTRUCTIONS PARTS LIST

Fisher 249 Caged Displacer Sensors

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL Purpose:

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)

Product Manual. CVS Type 67AFR Filter Regulator. Introduction. Installation. Description

FT43, FT44, FT46 and FT47 Ball Float Steam Traps

Installation and Commissioning Manual Solar Stations FlowCon Max Evolution II

V47 Series Temperature Actuated Modulating Water Valves

BRAZED PLATE INSTALLATION MANUAL

OWNER S MANUAL FORCE 10 MARINE COMPANY HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) FAX: (604)

James M. Pleasants Company

I N S T A L L A T I O N I N S T R U C T I O N S F O R T H E H i l k o i l Energy S aving Hot Water Kit

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

INSTALLATION INSTRUCTIONS Air Spring Kit Ford F250/F-350 Single Wheel 2WD Ford F350 Dually 2WD IMPORTANT NOTES

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series

WD600 STEAM TRAPS. Thermodynamic Steam Trap

Air Eliminators and Combination Air Eliminators Strainers

OPERATING and MAINTENANCE MANUAL SERIES 2700A CONTROL VALVE CONTENTS. INTRODUCTION...1 Scope...1 Description...1 Valve Identification...

Fisher 1052 Size 20 Diaphragm Rotary Actuator with F and G Mounting Adaptation

ASME Packaged Indirect Fired Water Heater

PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT

PLATE HEAT EXCHANGER. Installation Manual. Customer Name: Serial number: Purchase order number: Project:

BOWIE PUMPS OPERATION - MAINTENANCE

Oil and Coolant Circulating Heating System. Model - OCSM

Select Radiators Installation Guide

CEILING CASSETTE FAN COIL UNIT

SureSite Magnetic Liquid Level Indicator

Installer s Guide 18-AH39D1-13

MANDATORY SERVICE BULLETIN

This instruction is valid for all ACD pump models shown on page 2

INSTALLATION INSTRUCTIONS Air Spring Kit Ford F250 Single Wheel 4WD Ford F350 Dually 4WD (2011 F350 Single Wheel 4WD use p/n 6113)

300 SERIES 331, 332, 333, 344, 356 AND 367 MODELS

L /96. Haldex INSTALLATION INSTRUCTIONS HALDEX PURE AIR PLUS EXTENDED PURGE KIT (DQ6027) HEAVY DUTY CANISTER KIT (DQ6028)

STEAM HEATING SYSTEM TROUBLESHOOTING GUIDE

Important: Please read these instructions carefully and completely before starting the installation. TITAN Fuel Tanks

Submersion/Insertion Toroidal Sensor

NITROUS TRANSFER PUMP INSTRUCTIONS

NFPA31FuelOilPiping 1 Revised

SAMPLE TEST QUESTIONS STEAMFITTER/PIPEFITTER - ITA WEBSITE

Automatic Self-Cleaning Strainers

STORAGE, INSTALLATION AND MAINTENANCE PROCEDURES

Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M (Angle) Schematic. Standard Components

Installation Manual. Thermomax Solar Water Heater ... Installation Procedure for Flatroof and Ground. Revision 8

SINGLE STAGE INLINE FIRE PUMP

Installation Manual DIAPHRAGM WELL TANK

Steam Coil Installation, Operation and Maintenance

STATFlow. Direct-to-Drain System. For use with STATIM 2000 and STATIM 5000 Autoclaves. Installation Guide and Operator s Manual

Fire Hydrant Troubleshooting

Hot Water Boilers and Controls Why Condensing Boilers are Different. Presented Oct. 14, 2008 Long Island Chapter, ASHRAE

Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound.

In-Line Air Separators

Modulex. Gas Fired Boiler Systems PIPING GUIDE GF-115-P. Modular, Condensing, Hot Water Boilers Models: 303, 454, 606, 757, 909, Instruction No.

Stainless Steel Single and Dual Circulation Kits

RMF Engineering

IF IT FLOWS THE BOWIE PUMP CAN PUMP IT

SunMaxx Solar Filling Station Operating Instructions

Continuous Blowdown Heat Recovery Systems For Boilers Rated 35 to 250 PSIG Installation, Operating & Maintenance Instructions

Toroidal Conductivity Sensor

Installation Manual DIAPHRAGM WELL TANK

Installation, Operation and Maintenance Manual for Pilot Operated Valves

2740 Whitten Rd Bldg 103 Memphis, TN Telephone

Wafer Check Valve ASAHI AV VALVES. Contents. User s Manual. (1) Be sure to read the following description of our product warranty 1

Valves, Automation & Controls. series 84 /99 HIGH PERFORMANCE 3-PIECE BALL VALVE REDUCE & FULL PORT, STANDARD & FIRE SAFE.

INSTALLATION & OPERATING INSTRUCTIONS

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

NUMBER: 08 DD15-10 S.M. REF.: 3.2 ENGINE: DD15 DATE: September 2008

DESIGN STANDARDS SECTION

Pressure Locking & Thermal Binding In Wedge Gate & Parallel Slide Gate Valves

Steam System Best Practices Condensate System Piping

Volkswagen Golf > VW Rabbit GTI 2006->

Zenith Solar thermal 4.5m pump station Installation manual

PREPIPED LIQUID FUEL MANIFOLDS PLPM

PRESSURE REDUCING CONTROL VALVE

Baumann 24000SB Barstock Control Valve

ENGINE FUEL FUEL FILTER... FUEL HEATER... INJECTOR... SUPPLY PUMP... COMMON RAIL... FUEL PRESSURE LIMITTER...

Instruction Manual. Alfa Laval SB Membrane Sample Valve ESE02963-EN

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

Water Tec of Tucson Water Systems

The cylinder head bolts tightening stages have been updated as listed in Table 1.

Owner s Manual. Models: 2S5P & 3S5P OPERATION AND MAINTENANCE OF SELF-PRIMING CENTRIFUGAL TRASH PUMPS PEDESTAL DRIVE

Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters.

Fig B36 Stainless Steel 'T' Type or Basket Type Strainers

3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE

INSTRUCTION MANUAL A REVISION A. Series E1 and E3 Instant Hot Water Recirculating Systems

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

Oregon Fuel Injection

Copper Meter Resetters

Maintenance and Service Instruction

COOLING SYSTEM Section Page

Transcription:

IOM-Heliflow-0507 HELIFLOW INSTALLATION, OPERATION AND MAINTENANCE MANUAL Graham Corporation Corporate and Sales Headquarters: 20 Florence Avenue, Batavia, New York 14020 USA Phone.: 585-343-2216 Fax: 585-343-1097 e-mail: equipment @ graham-mfg.com Web site:www.graham-mfg.com T

TABLE OF CONTENTS SECTION I - INSTALLATION...3 1.1 Mounting...3 1.2 Piping-up (See Figure I)...3 SECTION II - OPERATION...3 2.1 Startup (See Figure I)...3 SECTION III MAINTENANCE / INSPECTION...4 3.1 Disassembly (See Figure I)...4 3.2 Reassembly (See Figure I)...4 3.3 Miscellaneous Notes (See Figure I)...5 SECTION IV - SAFETY CONCERNS / PRECAUTIONS...5 SECTION V SPARE AND REPLACEMENT PARTS...6 FIGURE I...7 HELIFLOW HEAT EXCHANGER SPECIFICATION...8

SECTION I - INSTALLATION 1.1 Mounting Small Heliflow heat exchangers can be supported by their piping; the support bracket shown on the exploded view (Figure I) may not be required. However, larger Heliflows do require mounting brackets, or mounting lugs, to support the extra weight associated with these larger sizes. The unit can usually be mounted on any convenient support; below, above, or to the side - on a base plate, a column or wall, the side of a piece of equipment, or hung from an overhead surface. If a specific orientation is required, a drawing indicating this can be furnished with your Heliflow heat exchanger order. Note that certain condensing or vaporizing applications require that the unit be mounted with the tubeside manifolds in the vertically upward or downward position. 1.2 Piping-up (See Figure I) Normally the fluid with the least fouling tendency (and/or higher operating pressure ) is circulated in the Heliflow coil by connecting its piping to the manifolds (items 6 and 7) that extend through the base plate. The other fluid s piping is connected to the casingside circuit through the threaded openings in the base plate (item 4). To obtain countercurrent flow, which is normally desired, the inlet for one fluid and the outlet for the other must be side by side. Thus, if the coil side fluid enters the lower manifold (item 7), the casing side fluid should exit from the lower base plate opening. Your Graham representative can supply a drawing of any standard Heliflow heat exchanger showing dimensions, pipe sizes, connection specification, etc. 2.1 Startup (See Figure I) SECTION II - OPERATION 1. Open all vents in piping to the Heliflow including removal of the casing vent plug (item 11). Close each vent and/or replace the plug when fluid begins to flow from its opening, indicating that all air has been expelled. If fluid is hot, or other than water, customer may want to consider installing ¼ inch ball valves on the vent and drains for easier and safer start-up. 2. Tighten base plate nuts (item 1) and manifold nuts (item 2) after two or three hours, and check their tightness after 24 hours. These nuts occasionally loosen up during transit and initial start-up. Suggested torque values for compressed fiber type gaskets are as follows: Casing Bolt Torque values Cast Iron Casing: 45 ft-lb Cast Steel Casing: 75 ft-lb Fabricated Casing: 100 ft-lb 3

3. Always start up the cold fluid side prior to the hot side to minimize thermal shock and possibility of water hammer. 4. If equipment is supplied with a pressure relief device, be sure that it is piped or pointed away from personnel or high traffic area in case of discharge. 5. Check nameplate for design pressure and temperature limits so that operation personnel are aware of maximum allowable limits and these are not exceeded during operation of equipment. SECTION III MAINTENANCE / INSPECTION 3.1 Disassembly (See Figure I) If gaskets begin to leak after extended operation or fouling of the tube bundle is suspected, the unit can be disassembled so that inspection of gasket replacement can be accomplished. The Heliflow coil is readily accessible for inspection and cleaning (if necessary) without disturbing piping. The manifold gaskets (item 5) cannot be replaced without disconnecting the tubeside connections. 1. Remove plug (item 11) to drain the casing. 2. Remove all base plate nuts (item 1). 3. Withdraw the casing, being careful not to damage the gasket (item 9). If removal of coil is necessary: 1. Disconnect piping and remove manifold nuts (item 2) and lock rings (item 3). 2. Withdraw the coil-manifold assembly, being careful not to damage the manifold gaskets (item 5). 3.2 Reassembly (See Figure I) 1. When re-assembling, be sure manifold and base plate gaskets are intact and in place. 2. Be sure that tabs on the manifold lock rings (item 3) fit into the base plate slots. These keep the manifold-coil assembly from turning when tightening the manifold nuts and piping to the unit. 3. Be sure the bottom of the manifolds (items 6 and 7) are seated in pockets located at bottom inside of the casing. 4

3.3 Miscellaneous Notes (See Figure I) 1. Please note that if the Heliflow has flanged, socket weld, or buttweld connections on the tubeside, unit will have the manifolds welded to the base plate, thus eliminating the manifold nuts, lock rings and manifold ring gaskets, (items 2,3, and 5) from the heat exchanger. 2. If upon initial visual inspection of unit, an external leak is evident, a gasket leak may be the cause. First, try to tighten the nuts slightly to see if the leak stops. If the leak does not stop and unit has been in operation for an extended period, a new replacement set of gaskets may be required. 3. If installing a new tube bundle, note that it may be necessary to drill a new hole in the front side of base plate to line up the tab in the lock ring. The location of the manifold keyway in relation to the existing predrilled lock ring hole may be different from the original tube bundle. SECTION IV - SAFETY CONCERNS / PRECAUTIONS 1. Before installing equipment, be sure to read the equipment nameplate for maximum allowable working pressures and design temperatures. Do not exceed these values during operation of the equipment. 2. Be sure unit is not over-pressurized. A safety relief device or over-pressure protection must be provided and installed (by others), prior to placing equipment into service. 3. Adequate support should be provided for entrance and exit piping of the heat exchanger so that loads are minimized. 4. Always start up equipment one side at a time. Typically, first the cold side and then the hot side. The exception to this rule would be for low temperature cryogenic applications. Cryogenic applications require the warmer heat transfer fluid to be circulated first, and then the cold liquid (usually liquid O 2 or N 2 ) to be introduced slowly. 5. Unit should be properly vented to remove any trapped air. 6. Possible high temperature: Unit may be hot to the touch. Consider insulation of unit. 7. Do not exceed manufacturer s recommended flowrates. If no performance data sheet accompanies equipment, consult manufacturer for maximum recommended values for your specific application. 8. If pulsating pumps are used, adequate dampeners must be in place (by others). 9. Never try to open heat exchangers during operation. 5

SECTION V SPARE AND REPLACEMENT PARTS Order through your nearest Graham representative or address orders directly to Graham Corporation: GRAHAM CORPORATION 20 Florence Avenue Batavia, NY 14020 Telephone: 585 / 343-2216 Spare Parts: 800 / 828-8150 Fax: 585 / 343-1097 E-MAIL: spares@graham-mfg.com WEBSITE: http://www.graham-mfg.com While Graham ships parts promptly from an extensive stock, when even a brief delay in restoring a Heliflow heat exchanger to service cannot be accepted, it is advisable to keep spare gaskets on hand. Many users also stock spare coil-manifold assemblies or one or more complete Heliflow units. When ordering spare or replacement parts, please specify: 1. Serial number of the Heliflow unit. This is important. 2. Part number(s) and name(s) from the exploded view. 3. Material of construction for each component. 4. Method of shipment desired (freight, express, air express, etc.) Graham Corporation presents the information in this manual as good engineering practice. We cannot be held responsible for any damage to equipment that may result from maloperation nor for any personal injuries should they occur during normal or abnormal operation. 6

7

HELIFLOW HEAT EXCHANGER SPECIFICATION Contact Company Street Address City State, Zip Phone Fax Email Cust Ref Due Date Performance of One Unit Tubeside Fluid Shell Side Fluid Fluid Name Total Flow Rate Inlet Temperature Outlet Temperature * Physical Properties Operating Pressure Design Pressure Design Temperature Code Of Construction (lb/hr or gpm) Vapor (lb/hr) Liquid (lb/hr) Steam (lb/hr) Water (lb/hr) Non-condensable (lb/hr) (ºF) (ºF) specific gravity specific heat (Btu/lb F) thermal conductivity (Btu/hr ft F) viscosity (cp) at two temperatures cp@ ºF cp@ ºF cp@ ºF cp@ ºF (psig) (psig) ( F) Graham Std ASME Materials Tubeside Shellside Copper (Std) Cast Iron (Std) 304 SS Steel 316 SS 304 SS 70/30 Cu. Ni 316 SS 90/10 Cu. Ni. Other: Admiralty Other: Connection Type NPT (Std) NPT (Std) Flg Flg BW BW Other: Other: (*) Physical properties required for uncommon fluids only REMARKS: Return this completed form via: Email: applicationengineering@graham-mfg.com or fax or mail to: Graham Corporation Corporate and Sales Headquarters: 20 Florence Avenue, Batavia, New York 14020 USA Phone.: 585-343-2216 Fax: 585-343-1097 e-mail: equipment @ graham-mfg.com Web site:www.graham-mfg.com 8