Application Techniques. SMC Flex Solid-State Smart Motor Controller Bulletin 150

Similar documents
Bulletin 150 SMC Flex Smart Motor Controller Specifications

WYE-DELTA AND SOLID STATE STARTER APPLICATION GUIDE

USER MANUAL FOR SERIES B. SMC -Flex BULLETIN 150

SMC FLEX QUICK START BULLETIN 150

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

PowerFlex Dynamic Braking Resistor Calculator

XFE. The cost effective starter for all AC induction motors from 4A 2800A The choice for small to medium industrial applications

32VFD Variable Frequency Drives for Centrifugal Chillers

CompactLogix Power Supplies Specifications

BIG SAVINGS FOR A LOT MORE APPLICATIONS

Specifying a Variable Frequency Drive s

Selection Guide. SMC -3 and SMC Flex Smart Motor Controllers

MOTOR CONTROL IS OUR NATURE

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

AuCom s IMS2 soft starters are a total motor starting solution, combining highlevel functionality with ease of use:

Micro800 Programmable Controllers. Bulletin 2080 Selection Guide

Torque control MSF Softstarter

Single Phase Soft Starter

Application Technique. Safety Function: Magnetic Door Switch Monitoring

Number 1 in efficiency

SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade

Panorama. Softstarters The complete range

Altistart. 01 Soft Start The starting solution. For single-phase and three-phase asynchronous motors 3 to 85 Amps 1/4 to 75 HP (0.

NX Series Inverters. HVAC Pocket Programming Guide

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

SMC -3 Specifications

... Electronic Softstarter...

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

FlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

MC Series Drives. Flexible, simple, rugged, robust! Phone: Fax: Web: info@actechdrives.

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

Additional Benefits of VFDs In addition to energy savings and better process control, VFDs can provide other benefits:

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

Phone: Fax: Web: info@clrwtr.com

Stratix 5700 Network Address Translation. Quick Start

PSR The compact range Description

Diesel Engine Driven Generators Page 1 of 6

GPD 506/P5 Start-up Procedure and Checklist

A1000 Cheat Sheet (Open Loop Vector)

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

Motor Protection Principles. Craig Wester GE Multilin

SECTION VARIABLE FREQUENCY DRIVES

Motor Protection Voltage Unbalance and Single-Phasing

GE Industrial Solutions ASTAT BP. User Manual

We will discuss common industrial applications with guides for the proper use of electric motors on these.

Transfer Equipment Controls

Softstarters Type PSR

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

Permissible ambient temperature Operation Storage, transport

What Is Regeneration?

Section 10. Application Manual for NEMA Motors. Special Applications

INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS

Limited Service Fire Pump Controllers Features

VARIABLE FREQUENCY DRIVES Revised 4/30/ Mechanical Systems

AE R6 December Digital Capacity Control for Copeland Scroll Refrigeration Compressors AE R6

Products and solutions for pumping, irrigation and piping

Rotary Phase Converters

Pump Maintenance - Repair

The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

User Manual. DeviceNet Network Configuration

Drives Low Voltage. Adjustable Frequency. Adjustable Frequency Drives Low Voltage Contents

CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING

RVS-DXM Instruction Manual

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

INDUSTRIAL AUTOMATION EQUIPMENT EDITION

Circuit Breakers. Next Generation of Protection Capabilities

ControlNet Standard and High-flex Coax Cable

Brake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module!

(3) Explosion proof. Designed to prevent ignition of any explosive gases or dust and dirt which may surround the motor.

Understanding Variable Speed Drives

Fractional to 2 HP DC Drives for Both Non-Regenerative and Regenerative Applications

Programming Logic controllers

MOTOR PROTECTION AGAINST SINGLE-PHASING

AC Drive Solutions. We Engineer Uptime

TERMINAL MARKINGS AND CONNECTIONS PART WINDING START

Easy to connect - Easy to configure Easy to install

VLT 6000 HVAC. Contents

USB-to-Data Highway Plus Cable

Use your troubleshooting superpowers for good Application Note

Siemens Standard Drives. Application Handbook

Medium Voltage Motor Control Assemblies

*.ppt 11/2/ :48 PM 1

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)

EET272 Worksheet Week 8

Safety Function: Door Monitoring

Unit 33 Three-Phase Motors

MicroLogix 1100 Embedded Web Server

Universal Serial Bus (USB) to DH-485 Interface Converter

Bimetallic Overload Relay Specifications

Commercial Refrigeration Temperature and Defrost Controls

Medium Voltage. Application Guide

THERMAL MANAGEMENT SOLUTIONS

Reduced Voltage Starters Section 2

, User s Manual

ETZGAR CONVEYOR COMPANY Controls Section v12.05

Introduction to Process Control Actuators

Application Note AN-SERV-006

Transcription:

Application Techniques SMC Flex Solid-State Smart Motor Controller Bulletin 150

Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations. WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence. SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present. BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures. IMPORTANT Identifies information that is critical for successful application and understanding of the product. Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. 2 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Table of Contents Important User Information........................................ 2 Chapter 1 Overview Introduction....................................................... 5 SMC Flex Features............................................. 5 Description........................................................ 6 Modes of Operation................................................ 7 Standard:...................................................... 7 Pump Option.................................................. 7 Braking Option................................................ 7 Standard.......................................................... 7 Soft Start with Selectable Kickstart............................... 7 Current Limit Start with Selectable Kickstart................... 10 Dual Ramp Start with Selectable Kickstart...................... 13 Full Voltage Start............................................. 16 Preset Slow Speed............................................ 19 Linear Speed Acceleration with Selectable Kickstart............. 22 Soft Stop..................................................... 25 Pump Control................................................... 27 Pump Control Option with Selectable Kickstart................ 27 Braking Control................................................. 30 SMB Smart Motor Braking Option............................ 30 Accu-Stop................................................... 33 Slow Speed with Braking...................................... 36 Features......................................................... 39 SCR Bypass.................................................. 39 Standard or Wye-Delta Wiring................................ 39 LCD Display................................................. 40 Parameter Programming...................................... 40 Electronic Overload.......................................... 40 Stall Protection and Jam Detection............................ 41 Ground Fault Protection...................................... 42 Thermistor Input............................................. 42 Metering..................................................... 42 Fault Indication.............................................. 42 Parameter Programming.......................................... 43 Communication Capabilities.................................. 43 Auxiliary Contacts............................................ 43 Modular Design.............................................. 44 Control Terminal Description................................. 44 Chapter 2 Overview........................................................ 47 Rockwell Automation Publication 150-AT002C-EN-P - March 2013 1

Table of Contents Special Application Considerations Product Line Applications Matrix Chapter 3 SMC-Flex Controllers in Drive Applications....................... 57 Use of Protective Modules..................................... 57 Motor Overload Protection....................................... 58 Stall Protection and Jam Detection................................. 58 Built-in Communication.......................................... 58 Power Factor Capacitors.......................................... 59 Multi-motor Applications......................................... 60 Special Motors................................................... 61 Wye-Delta................................................... 61 Part Winding................................................. 62 Wound Rotor................................................ 62 Synchronous................................................. 62 Altitude De-rating................................................ 62 Isolation Contactor............................................... 63 SMC-Flex Controller with Bypass Contactor (BC).................. 63 SMC-Flex Controller with Reversing Contactor.................... 64 SMC-Flex Controller as a Bypass to an AC Drive................... 65 SMC-Flex Controller with a Bulletin 1410 Motor Winding Heater.. 66 Motor Torque Capabilities with SMC Flex Controller Options...... 66 SMB Smart Motor Braking.................................... 66 Preset Slow Speed............................................. 66 Accu-Stop.................................................... 67 Chapter 4 Description.................................................. 69 Mining and Metals............................................... 69 Food Processing.................................................. 70 Pulp and Paper................................................... 70 Petrochemical.................................................... 71 Transportation and Machine Tool................................. 71 OEM Specialty Machine.......................................... 72 Lumber and Wood Products...................................... 72 Water/Wastewater Treatment and Municipalities.................. 72 Chapter 5 Design Philosophy Philosophy....................................................... 73 Line Voltage Conditions.......................................... 73 Current and Thermal Ratings..................................... 73 Mechanical Shock and Vibration................................... 73 Noise and RF Immunity.......................................... 74 Altitude......................................................... 74 Pollution........................................................ 74 Setup............................................................ 74 2 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Table of Contents Chapter 6 Reduced Voltage Starting Introduction to Reduced Voltage Starting.......................... 75 Reduced Voltage................................................. 76 SMC Flex Solid-State............................................. 78 Chapter 7 Solid-State Starters Using SCRs Overview........................................................ 81 Chapter 8 Motor Output Speed/Torque/ Horsepower........................ 83 Torque and Horsepower.......................................... 83 Full-load Torque (FLT)....................................... 85 Locked-Rotor Torque (LRT).................................. 85 Pull-Up Torque (PUT)....................................... 85 Breakdown Torque (BT)...................................... 86 Full-load Current............................................. 86 Locked-rotor Current......................................... 86 Motor Output for NEMA Design Designations Polyphase 1 500 Hp............................................. 89 Calculating Torque (Acceleration Torque Required for Rotating Motion)............... 91 Inertia........................................................... 92 Torque Formulas................................................. 92 AC Motor Formulas.............................................. 93 Torque Characteristics on Common Applications.................. 93 Electrical Formulas............................................... 95 Ohm s Law:.................................................. 95 Power in DC Circuits:........................................ 96 Other Formulas.................................................. 97 Calculating Accelerating Force for Linear Motion:.............. 97 Rockwell Automation Publication 150-AT002C-EN-P - March 2013 3

Table of Contents 4 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Chapter 1 Overview Introduction The Allen-Bradley SMC Controller lines offer a broad range of products for starting or stopping AC induction motors from ½ Hp to 6000 Hp. The innovative features, compact design, and available enclosed controllers meet world-wide industry requirements for controlling motors. Whether you need to control a single motor or an integrated automation system, our range of controllers meet your required needs. This document discusses the SMC Flex. Some of the key features are listed below. SMC Flex Features Soft Start with Selectable Kickstart Current Limit Start with Selectable Kickstart Dual Ramp with Selectable Kickstart Full Voltage Linear Speed Acceleration with Selectable Kickstart Preset Slow Speed Soft Stop Pump Control with Selectable Kickstart SMB Smart Motor Braking Accu-Stop Slow Speed with Braking Built in Bypass Inside the Delta Electronic Motor Overload Protection Stall and Jam Detection Ground Fault Protection Thermistor Input (PTC) Metering Fault Indication Parameter Programming Communication Capabilities Rockwell Automation Publication 150-AT002C-EN-P - March 2013 5

Chapter 1 Overview Description When the Smart Motor Controller (SMC ) was first introduced in 1986, its modular design, digital setup, and microprocessor control set the standard for soft starters. Since its launch in 1996, the SMC Dialog Plus controller has been in a class by itself, providing unmatched performance with innovative starting and stopping options. Now, the SMC-Flex controller achieves a higher level of sophistication with greatly enhanced protection, expanded diagnostics, ability to log the motor s operation (A, kw, and power factor), and flexibility to communicate with various network protocols. The SMC-Flex can also be wired in a standard wiring configuration, or inside-the-delta. This allows the product to operate wye-delta motors with a much smaller device than before. Figure 1 - SMC Flex Controller The SMC-Flex controller is a compact, modular, multi-functional solid-state controller used in both starting three-phase squirrel-cage induction motors or wye-delta motors and controlling resistive loads. The SMC-Flex contains, as standard, a built-in SCR bypass and a built-in overload. The SMC-Flex product line includes current ratings 5 to 480 A, 200 to 600V, 50/60Hz. This covers squirrel-cage induction motor applications up to 400 Hp (wye-delta motors up to 650 Hp). The SMC-Flex controller meets applicable standards and requirements. While the SMC-Flex controller incorporates many new features into its design, it remains easy to set up and operate. You can make use of as few or as many of the features as your application requires. 6 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Overview Chapter 1 Modes of Operation The following modes of operation are standard within a single controller: Standard: Soft Start with Selectable Kickstart Current Limit with Selectable Kickstart Dual Ramp Start with Selectable Kickstart Full Voltage Start Preset Slow Speed Linear Speed Acceleration with Selectable Kickstart Soft Stop Pump Option Pump Control with Selectable Kickstart Braking Option Smart Motor Braking Accu-Stop Slow Speed with Braking Standard Soft Start with Selectable Kickstart This method covers the most general applications. The motor is given an initial torque setting, which is user adjustable from 0 to 90% of locked rotor torque. From the initial torque level, the output voltage to the motor is steplessly increased during the acceleration ramp time, which is user adjustable from 0 to 30 seconds. If, during the voltage ramp operation, the SMC-Flex controller senses that the motor has reached an up-to-speed condition, the output voltage will automatically switch to full voltage, and transition over the SCR Bypass contactors. The kickstart feature provides a boost at startup to break away loads that may require a pulse of high torque to get started. It is intended to provide a current pulse, user adjustable 0-90% locked rotor torque for a selected period of time from 0.0 to 2.0 seconds. Rockwell Automation Publication 150-AT002C-EN-P - March 2013 7

Chapter 1 Overview Figure 2 - Soft Start Current Limit 00% tial que Ramp Time Start Time in Seconds Run Following are the parameters that are specifically used to provide and adjust the voltage ramp supplied to the motor. Table 1 - Soft Start Parameters Parameter SMC Option Starting Mode Ramp Time Initial Torque Kickstart Time Kickstart Level Option 2 Input Stop Mode Stop Time Adjustment Standard, Braking, Pump Soft Start 0 30 s 0 90% LRT 0.0 2.0 s 0 90% LRT Disable Disable 0 s 8 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Overview Chapter 1 Figure 3 - Soft Start Sequence of Operation Selectable Kickstart 100% Coast-to-rest Percent Voltage Soft Stop Start Run Time (seconds) Soft Stop Push Buttons Start Stop Soft Stop Auxiliary Contacts If Soft Stop Selected Normal Up-to-speed If Coast-to-rest Selected Rockwell Automation Publication 150-AT002C-EN-P - March 2013 9

Chapter 1 Overview Figure 4 - Soft Start Wiring Diagram Control Power ➁ Stop Start 11 12 13 14 15 16 17 18 19 20 21 22 SMC-Flex Control Terminals Aux #1 Normal/Up-to-Speed/ Bypass Internal Auxilary Contacts 23 24 25 26 27 28 29 30 31 32 33 34 PTC Input TACH Input Ground Fault Fault Contact Alarm Contact Aux #2 Normal Customer supplied. ➁Refer to the controller nameplate to verify the rating of the control power input rating. Current Limit Start with Selectable Kickstart This method provides a current limit start and is used when it is necessary to limit the maximum starting current. The starting current is user adjustable from 50 to 600% of full load amperes. The current limit ramp time is user adjustable from 0 to 30 seconds. The kickstart feature provides a boost at startup to break away loads that may require a pulse of high torque to get started. It is intended to provide a current pulse, user adjustable 0-90% locked rotor torque for a selected period of time from 0.0 to 2.0 seconds. 10 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Overview Chapter 1 Figure 5 - Current Limit Start 600% Percent Full Load Current 50% Start Time (seconds) To apply a current limit output to the motor, the following parameters are provided for user adjustment. Table 2 - Current Limit Start Parameters Parameter SMC Option Starting Mode Ramp Time Current Limit Level Kickstart Time Kickstart Level Option 2 Input Stop Mode Stop Time Adjustments Standard, Braking, Pump Current Limit 0 30 s 50 600% FLC 0.0 2.0 s 0 90% LRT Disable Disable 0 s Rockwell Automation Publication 150-AT002C-EN-P - March 2013 11

Chapter 1 Overview Figure 6 - Current Limit Sequence of Operation 600% Percent Full Load Current Soft Stop 100% Coast-to-rest 50% Start Run Time (seconds) Soft Stop Push Buttons Start Stop Soft Stop Auxiliary Contacts If Soft Stop Selected Normal Up-to-speed If Coast-to-rest Selected 12 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Overview Chapter 1 Figure 7 - Current Limit Wiring Diagram Control Power ➁ Stop Start 11 12 13 14 15 16 17 18 19 20 21 22 SMC-Flex Control Terminals Aux #1 Normal/Up-to-Speed/ Bypass Internal Auxilary Contacts 23 24 25 26 27 28 29 30 31 32 33 34 PTC Input TACH Input Ground Fault Fault Contact Alarm Contact Aux #2 Normal Customer supplied. ➁Refer to the controller nameplate to verify the rating of the control power input rating. Dual Ramp Start with Selectable Kickstart This starting method is useful on applications with varying loads, starting torque, and start time requirements. Dual Ramp Start offers the user the ability to select between two separate Start profiles with separately adjustable ramp times and initial torque settings. The kickstart feature provides a boost at startup to break away loads that may require a pulse of high torque to get started. It is intended to provide a current pulse, user adjustable 0 90% locked rotor torque for a selected period of time from 0.0 to 2.0 seconds. Rockwell Automation Publication 150-AT002C-EN-P - March 2013 13

Chapter 1 Overview Figure 8 - Dual Ramp Start Current Limit 2 Current Limit 1 100% Ramp #2 Initial que #2 Initial que #1 Ramp #1 Start #1 Start #2 Time in Seconds Run #1 Run #2 To obtain Dual Ramp Start control, the following parameters are available when you select Dual Ramp in the Option 2 Input parameter. Table 3 - Dual Ramp Start Parameters Parameter SMC Option Starting Mode Ramp Time Initial Torque Current Limit Level Torque Limit Kickstart Time Kickstart Level Option 2 Input Starting Mode 2 Start Time 2 Initial Torque 2 Current Limit Level 2 Torque Limit 2 Kickstart Time 2 Kickstart Level 2 Stop Mode Stop Time Adjustments Standard Full Voltage, Current Limit, Soft Start, Linear Speed 0 30 s 0 90% LRT 50 600% FLC 0 100% LRT 0.0 2.0 s 0 90% LRT Dual Ramp Full Voltage, Current Limit, Soft Start, Linear Speed 0 30 s 0 90% LRT 50 600% FLC 0 100% LRT 0.0 2.0 s 0 90% LRT Disable 0 s 14 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Overview Chapter 1 Figure 9 - Dual Ramp Start Sequence of Operation 100% Ramp #2 Coast-to-rest Percent Voltage Ramp #1 Soft Stop Start #1 Start #2 Run #1 Run #2 Soft Stop Push Buttons Time (seconds) Start Stop Soft Stop Auxiliary Contacts If Soft Stop Selected Normal Up-to-speed If Coast-to-rest Selected Rockwell Automation Publication 150-AT002C-EN-P - March 2013 15

Chapter 1 Overview Figure 10 - Dual Ramp Start Wiring Diagram Control Power ➁ Stop Ramp 1 Ramp 2 Start 11 12 13 14 15 16 17 18 19 20 21 22 SMC-Flex Control Terminals Aux #1 Normal/Up-to-Speed/ Bypass Internal Auxilary Contacts 23 24 25 26 27 28 29 30 31 32 33 34 PTC Input TACH Input Ground Fault Fault Contact Alarm Contact Aux #2 Normal Customer supplied. ➁Refer to the controller nameplate to verify the rating of the control power input rating. Full Voltage Start This method is used in applications requiring across-the-line starting. The SMC-Flex controller performs like a solid-state contactor. Full inrush current and locked rotor torque are realized. The SMC-Flex may be programmed to provide full voltage start in which the output voltage to the motor reaches full voltage in ¼ second. 16 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Overview Chapter 1 Figure 11 - Full Voltage Start 100% Percent Voltage Time in Seconds The basic parameter setup for Full Voltage Start follows: Table 4 - Full Voltage Start Parameters Parameter SMC Option Starting Mode Stop Mode Stop Time Adjustments Standard, Braking, Pump Full Voltage Disable 0 s Rockwell Automation Publication 150-AT002C-EN-P - March 2013 17

Chapter 1 Overview Figure 12 - Full Voltage Start Sequence of Operation 100% Coast-to-rest Percent Voltage Soft Stop Start Run Time (seconds) Soft Stop Push Buttons Start Stop Soft Stop Auxiliary Contacts If Soft Stop Selected Normal Up-to-speed If Coast-to-rest Selected 18 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Overview Chapter 1 Figure 13 - Full Voltage Start Wiring Diagram Control Power ➁ Stop Start 11 12 13 14 15 16 17 18 19 20 21 22 SMC-Flex Control Terminals Aux #1 Normal/Up-to-Speed/ Bypass Internal Auxilary Contacts 23 24 25 26 27 28 29 30 31 32 33 34 PTC Input TACH Input Ground Fault Fault Contact Alarm Contact Aux #2 Normal Customer supplied. ➁Refer to the controller nameplate to verify the rating of the control power input rating. Preset Slow Speed This method can be used on applications that require a slow speed for positioning material. The Preset Slow Speed can be set for either Low, 7% of base speed, or High, 15% of base speed. Reversing is also possible through programming. Speeds provided during reverse operation are Low, 10% of base speed, or High, 20% of base speed. Rockwell Automation Publication 150-AT002C-EN-P - March 2013 19

Chapter 1 Overview Figure 14 - Preset Slow Speed 100% Motor Speed Forward 15% - High 7% - Low 10% - Low Time (seconds) Start Run 20% - High Reverse The basic parameter setup for Soft Start selection with Preset Slow Speed Option follows: Table 5 - Preset Slow Speed Parameters Parameter SMC Option Starting Mode Ramp Time Initial Torque Current Limit Level Torque Limit Kickstart Time Kickstart Level Option 2 Input Stop Mode Stop Time Slow Speed Sel Slow Speed Dir Slow Accel Cur Slow Running Cur Adjustments Standard, Braking Full Voltage, Current Limit, Soft Start, Linear Speed 0 30 s 0 90% LRT 50 600% FLC 0 100% LRT 0.0 2.0 s 0 90% LRT Preset SS Disable 0 s SS Low, SS High SS Forward, SS Reverse 0 450% FLC 0 450% FLC 20 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Overview Chapter 1 Figure 15 - Preset Slow Speed Sequence of Operation 100% Motor Speed 7 or 15% Coast-to-rest Soft Stop Slow Speed Start Run Time (seconds) Coast Push Buttons Start Stop Slow Speed Auxiliary Contacts Normal Up-to-speed Rockwell Automation Publication 150-AT002C-EN-P - March 2013 21

Chapter 1 Overview Figure 16 - Preset Slow Speed Wiring Diagram Control Power ➁ Stop Slow Speed Start 11 12 13 14 15 16 17 18 19 20 21 22 SMC-Flex Control Terminals Aux #1 Normal/Up-to-Speed/ Bypass Internal Auxilary Contacts 23 24 25 26 27 28 29 30 31 32 33 34 PTC Input TACH Input Ground Fault Fault Contact Alarm Contact Aux #2 Normal Customer supplied. ➁Refer to the controller nameplate to verify the rating of the control power input rating. Linear Speed Acceleration with Selectable Kickstart This method starts the motor following a linear speed ramp. The ramp time defines the time the motor will ramp from zero speed to full speed. This ramp time is user adjustable from 0 30 seconds. Linear Speed requires a tachometer input (0 5V DC, 4.5 V = 100% speed). The current limit is active during the starting ramp. The kickstart feature provides a boost at startup to break away loads that may require a pulse of high torque to get started. It is intended to provide a current pulse, user adjustable 0 90% locked rotor torque for a selected period of time, 0.0 2.0 seconds. Note that speed ramp begins once the kickstart is completed. 22 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Overview Chapter 1 Figure 17 - Linear Speed Acceleration 100% Start Run Time (seconds) Stop The basic parameter set for Linear Speed follows: Table 6 - Linear Speed Acceleration Parameters Parameter SMC Option Starting Mode Ramp Time Current Limit Level Kickstart Time Kickstart Level Option 2 Stop Mode Stop time Adjustments Standard Linear Speed 0.0 30.0 s 0 600% FLC (Full Load Current) 0.0 2.0 s 0 90% LRT Disable Linear Speed 0.0 120.0 s Rockwell Automation Publication 150-AT002C-EN-P - March 2013 23

Chapter 1 Overview Figure 18 - Linear Speed Acceleration Sequence of Operation 100% Coast-to-rest Motor Speed Soft Stop or Linear Speed Start Run Time (seconds) Soft Stop Push Buttons Start Stop Soft Stop or Linear Speed Auxiliary Contacts If Soft Stop Selected Normal Up-to-speed If Coast-to-rest Selected 24 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Overview Chapter 1 Figure 19 - Linear Speed Acceleration Wiring Diagram Control Power ➁ Stop Linear Stop Start 11 12 13 14 15 16 17 18 19 20 21 22 SMC-Flex Control Terminals Aux #1 Normal/Up-to-Speed/ Bypass Internal Auxilary Contacts 23 24 25 26 27 28 29 30 31 32 33 34 PTC Input TACH Input Ground Fault Fault Contact Alarm Contact Aux #2 Normal Customer supplied. ➁Refer to the controller nameplate to verify the rating of the control power input rating. Soft Stop The Soft Stop option can be used in applications requiring an extended coast-to-rest. The voltage ramp down time is user adjustable from 0 120 seconds. The Soft Stop time is adjusted independently from the start time. The load will stop when the voltage drops to a point where the load torque is greater than the motor torque. Rockwell Automation Publication 150-AT002C-EN-P - March 2013 25

Chapter 1 Overview Figure 20 - Soft Stop Selectable Kickstart Coast-to-rest Soft Stop Start Run Time (seconds) Soft Stop The basic parameter setup for Soft Stop follows: Table 7 - Soft Stop Parameters Parameter SMC Option Stop Mode Stop Time Adjustments Standard, Braking, Pump Soft Stop 0 120 seconds Figure 21 - Soft Stop Sequence of Operation 100% Coast-to-rest Motor Speed Soft Stop Start Run Time (seconds) Soft Stop Push Buttons Start Stop Soft Stop Auxiliary Contacts If Soft Stop Selected Normal Up-to-speed If Coast-to-rest Selected 26 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Overview Chapter 1 Figure 22 - Soft Stop Wiring Diagram Control Power ➁ Stop Soft Stop Start 11 12 13 14 15 16 17 18 19 20 21 22 SMC-Flex Control Terminals Aux #1 Normal/Up-to-Speed/ Bypass Internal Auxilary Contacts 23 24 25 26 27 28 29 30 31 32 33 34 PTC Input TACH Input Ground Fault Fault Contact Alarm Contact Aux #2 Normal Customer supplied. ➁Refer to the controller nameplate to verify the rating of the control power input rating. Pump Control Pump Control Option with Selectable Kickstart The SMC-Flex controller s unique interactive Pump Control is designed to reduce fluid surges in pumping systems. It provides closed loop acceleration and deceleration control of centrifugal pump motors without the need for feedback devices. The kickstart feature provides a boost at startup to break away loads that may require a pulse of high torque to get started. It is intended to provide a current pulse with user adjustable locked rotor torque from 0-90% and kickstart time from 0.0 to 2.0 seconds. Rockwell Automation Publication 150-AT002C-EN-P - March 2013 27

Chapter 1 Overview Figure 23 - Pump Control Option with Selectable Kickstart 100% Motor Speed Pump Start Ramp Time Run Time in Seconds Pump Stop Stop Time The basic parameter setup for Pump Control follows: Table 8 - Pump Control Option Parameters Parameter SMC Option Starting Mode Start Time Initial Torque Kickstart Time Kickstart Level Stop Time Anti-Backspin Timer Adjustments Pump Pump Start 0 30 s 0 90% LRT 0.0 2.0 s 0 90% LRT 0 120 s 0 999 s 28 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Overview Chapter 1 Figure 24 - Pump Control Option Sequence of Operation Motor Speed 100% Coast-to-Rest Pump Start Run Time in Seconds Pump Stop Push Buttons Start Stop Pump Stop 1 (Stop Option) Auxillary Contacts Normal Up-to-Speed If the Pump Stop is Selected If the Coast-to-Rest is Selected Rockwell Automation Publication 150-AT002C-EN-P - March 2013 29

Chapter 1 Overview Figure 25 - Pump Control Option Wiring Diagram Control Power ➁ Stop Pump Stop Start 11 12 13 14 15 16 17 18 19 20 21 22 SMC-Flex Control Terminals Aux #1 Normal/Up-to-Speed/ Bypass Internal Auxilary Contacts 23 24 25 26 27 28 29 30 31 32 33 34 PTC Input TACH Input Ground Fault Fault Contact Alarm Contact Aux #2 Normal Customer supplied. ➁Refer to the controller nameplate to verify the rating of the control power input rating. Braking Control SMB Smart Motor Braking Option The SMB Smart Motor Braking option provides motor braking for applications, which require the motor to stop quickly. It is a microprocessor based braking system, which applies braking current to a motor. The strength of the braking current is adjustable from 0 400% of full load current. 30 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Overview Chapter 1 Figure 26 - Smart Motor Braking 100% Smart Motor Braking Motor Speed Coast-to-Rest Automatic Zero Speed Shut-Off Time in Seconds Stop Time Start Run Brake The basic parameter setup for Smart Motor Braking follows: Table 9 - Smart Motor Braking Parameters Parameter SMC Option Stop Mode Braking Current Adjustments Braking SMB 0 400% FLC Rockwell Automation Publication 150-AT002C-EN-P - March 2013 31

Chapter 1 Overview Figure 27 - Smart Motor Braking Sequence of Operation Motor Speed 100% Smart Motor Braking Coast-to-Rest Automatic Zero Speed Shut-Off Start Run Time in Seconds Brake Push Buttons Start Stop Smart Motor Braking (Stop Option 1 ) Auxillary Contacts Normal Up-to-Speed If Coast-to-Rest Selected If Brake Selected 32 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Overview Chapter 1 Figure 28 - Smart Motor Braking Wiring Diagram Control Power ➁ Stop Brake Start 11 12 13 14 15 16 17 18 19 20 21 22 SMC-Flex Control Terminals Aux #1 Normal/Up-to-Speed/ Bypass Internal Auxilary Contacts 23 24 25 26 27 28 29 30 31 32 33 34 PTC Input TACH Input Ground Fault Fault Contact Alarm Contact Aux #2 Normal Customer supplied. ➁Refer to the controller nameplate to verify the rating of the control power input rating. Accu-Stop The Accu-Stop option provides rapid braking to a slow speed, and then braking to stop, facilitating cost-effective general positioning control. Rockwell Automation Publication 150-AT002C-EN-P - March 2013 33

Chapter 1 Overview Figure 29 - Accu-Stop The basic parameter setup for Accu-Stop follows: Table 10 - Accu-Stop Parameters Parameter SMC Option Stop Mode Slow Speed Sel Slow Accel Cur Slow Running Cur Braking Current Stopping Current Adjustments Braking Accu Stop SS Low, SS High 0 450% FLC 0 450% FLC 0 400% FLC 0 400% FLC 34 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Overview Chapter 1 Figure 30 - Accu-Stop Sequence of Operation 100 % Motor Speed Braking Slow Speed Braking Coast-to-rest Slow Speed Slow Speed Start Run Time (seconds) Accu-Stop Push Buttons Start Stop Accu-Stop Auxiliary Contacts Normal Up-to-speed If Coast-to-rest Selected Slow Speed Braking Rockwell Automation Publication 150-AT002C-EN-P - March 2013 35

Chapter 1 Overview Figure 31 - Accu-Stop Wiring Diagram Control Power ➁ Stop Accu-Stop Start 11 12 13 14 15 16 17 18 19 20 21 22 SMC-Flex Control Terminals Aux #1 Normal/Up-to-Speed/ Bypass Internal Auxilary Contacts 23 24 25 26 27 28 29 30 31 32 33 34 PTC Input TACH Input Ground Fault Fault Contact Alarm Contact Aux #2 Normal Customer supplied. ➁Refer to the controller nameplate to verify the rating of the control power input rating. Slow Speed with Braking The Slow Speed with Braking option combines the benefits of the SMB Smart Motor Braking and Preset Slow Speed options for applications that require slow setup speeds and braking to a stop. 36 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Overview Chapter 1 Figure 32 - Slow Speed with Braking The basic parameter setup for Slow Speed with Braking follows: Figure 33 - Slow Speed with Braking Parameters Parameter SMC Option Option 2 Input Slow Speed Sel Slow Speed Dir Slow Accel Cur Slow Running Cur Stop Mode Braking Current Adjustments Braking Preset SS SS Low, SS High SS Forward, SS Reverse 0 450% FLC 0 450% FLC SMB 0 400% FLC Rockwell Automation Publication 150-AT002C-EN-P - March 2013 37

Chapter 1 Overview Figure 34 - Slow Speed with Braking Sequence of Operation 100% Coast-to-Stop Motor Speed Braking Slow Speed Start Run Brake Time (seconds) Push Buttons Start Stop Slow Speed Brake Auxiliary Contacts Normal Up-to-speed Brake If Coast-to-rest selectede 38 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Overview Chapter 1 Figure 35 - Slow Speed with Braking Wiring Diagram Control Power ➁ Stop Brake Slow Speed Start 11 12 13 14 15 16 17 18 19 20 21 22 SMC-Flex Control Terminals Aux #1 Normal/Up-to-Speed/ Bypass Internal Auxilary Contacts 23 24 25 26 27 28 29 30 31 32 33 34 PTC Input TACH Input Ground Fault Fault Contact Alarm Contact Aux #2 Normal Customer supplied. ➁Refer to the controller nameplate to verify the rating of the control power input rating. Features SCR Bypass The SMC-Flex has a built-in bypass contactor that is automatically pulled in when the motor reaches full speed. An external bypass contactor may be used. When an external bypass contactor is enabled (by setting the parameter Aux1 Config to Bypass ) the internal bypass contactor will not be used, and a separate overload is required. Standard or Wye-Delta Wiring The SMC-Flex can operate either a standard squirrel-cage induction motor or a wye-delta motor. The user must program the selected configuration into the unit using the Motor Connection parameter. The wye-delta motor is connected in an inside-the-delta wiring configuration, and the Motor Connection is det to Delta. Rockwell Automation Publication 150-AT002C-EN-P - March 2013 39

Chapter 1 Overview LCD Display A graphical backlit LCD display provides parameter definition with straightforward text so that controller setup may be accomplished without a reference manual. Parameters are arranged in an organized three-level menu structure for ease of programming and fast access to parameters. The displayed language can also be changed to meet global customer needs. Parameter Programming Programming of parameters is accomplished through a five-button keypad on the front of the SMC-Flex controller. The five buttons include up and down arrows, an Enter button, a Select button, and an Escape button. The user needs only to enter the correct sequence of keystrokes for programming the SMC-Flex controller. Figure 36 - LCD Display with Keypad LCD Display Keypad Electronic Overload The SMC-Flex controller meets applicable requirements as a motor overload protective device. Overload protection is accomplished electronically through current sensors and an I 2 t algorithm. The overload trip class is selectable for OFF, 10, 15, 20, or 30 protection. The trip current is set by entering the motor s full load current rating and the service factor. 40 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Overview Chapter 1 Thermal memory is included to model motor operating and cooling temperatures. Ambient insensitivity is inherent in the electronic design of the overload. Stall Protection and Jam Detection Motors can experience locked rotor currents and develop maximum torque in the event of a stall (during start) or a jam (after full speed is reached). These conditions can result in winding insulation breakdown or mechanical damage to the connected load. The SMC-Flex controller provides both stall and jam detection for enhanced motor and system protection. Stall protection allows the user to program a maximum stall time of up to 10 seconds. Jam detection allows the user to determine the jam level as a percentage of the motor s full load current rating, and a trip delay time of up to 99 seconds. The stall trip delay time is in addition to the programmed start time. Figure 37 - Stall Protection Sequence of Operation 600% Percent Full Load Current Programmed Start Time Time (seconds) Stall Figure 38 - Jam Detection Sequence of Operation Percent Full Load Current User Programmed Trip Level 100% Running Time (seconds) Jam Rockwell Automation Publication 150-AT002C-EN-P - March 2013 41

Chapter 1 Overview Ground Fault Protection The SMC-Flex Controller can sense ground faults before they become short circuits. Ground faults generally start at low levels (amps), but can rapidly increase to hundreds or thousands of amperes. This feature is not intended as a ground fault circuit-interrupter for personnel protection. The Ground Fault protection settings are user-adjustable. A separate Cat. No. 825-CBCT core balance current transformer is required for setup of this feature. Thermistor Input The SMC-Flex controller offers enhanced motor protection with additional circuitry to monitor motor stator-embedded positive temperature coefficient (PTC) thermistors. The PTC acts as a thermally sensitive resistor. It exhibits a large sudden increase in resistance at its activation temperature rating. Excessive motor heating can still occur without the motor being overloaded. Such over-heating can result from blocked motor ventilation or high ambient temperatures, and the PTC will help identify this. The thermistor input settings are user adjustable. See the User Manual for more details. Metering The SMC-Flex controller contains several power monitoring parameters as standard. These parameters include: Three-phase current Three-phase voltage Power in kw Power usage in kwh Power factor Elapsed time Motor thermal capacity usage Fault Indication The SMC-Flex controller monitors both the pre-start and running modes. If the controller senses a fault, the SMC-Flex controller shuts down the motor and displays the appropriate fault condition in the LCD display. The controller monitors the following conditions: Line Loss Shorted SCR SCR Gate Thermistor (PTC) 42 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Overview Chapter 1 Overtemperature (Power Pole, SCR, Motor) Bypass Failure No Load Overvoltage Undervoltage Overload Underload Jam Stall Phase Reversal Phase Unbalance Current Unbalance Voltage Unbalance Loss of Communication Power Loss Excessive Starts/Hour Ground Fault Motor Lead Loss Line Fault Communication Fault Any fault condition will cause the auxiliary contacts to change state and the hold-in circuit to release. Parameter Programming Communication Capabilities A serial interface port is furnished as standard with the SMC-Flex controller. This communication port allows connection to a Bulletin 20 Human Interface Module, and a variety of 20-COMM modules. These include Allen-Bradley Remote I/O, DeviceNet, ControlNet, Ethernet, ProfiBUS, Interbus, and RS485. Auxiliary Contacts Four hard contacts are provided as standard with the SMC-Flex controller. The first contact is programmable for Normal/Up-to-speed/Bypass. The second, third and fourth contact are configured to N.O/N.C. Rockwell Automation Publication 150-AT002C-EN-P - March 2013 43

Chapter 1 Overview Modular Design The SMC-Flex controller packaging is designed for industrial environments. The modularity of control and power modules feature plug-in functionality. There are no gate wires to remove and no soldering is required. Common control modules reduce inventory requirements. Figure 39 - Exploded View Control Terminal Description The SMC-Flex controller contains 24 control terminals on the front of the controller. These control terminals are described below. See Figure 40 44 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Overview Chapter 1 Table 11 - Control Terminal Designation. Terminal Number Description 11 Control Power Input 12 Control Power Common 13 Controller Enable Input 14 Ground 15 Option Input #2 16 Option Input #1 17 Start Input 18 Stop Input 19 20 N.O. Aux. Contact #1 (Normal/Up-to-Speed/External Bypass) ➁ N.O. Aux. Contact #1 (Normal/Up-to-Speed/External Bypass) ➁ 21 Not Used 22 Not Used 23 PTC Input 24 PTC Input 25 Tach Input 26 Tach Input 27 Ground Fault Transformer Input 28 Ground Fault Transformer Input 29 Fault Contact (N.O./N.C.) 30 Fault Contact (N.O./N.C.) 31 Alarm Contact (N.O./N.C.) 32 Alarm Contact (N.O./N.C.) 33 Aux Contact #2 Normal (N.O./N.C.) 34 Aux Contact #2 Normal (N.O./N.C.) Do not connect any additional loads to these terminals. These parasitic loads may cause problems with operation, which may result in false starting and stopping. ➁ External Bypass operates an external contactor and overload once the meter reaches full speed. The SMC-Flex overload functionality is disabled when the external bypass is activated. Proper sizing of the contactor and overload is required. Rockwell Automation Publication 150-AT002C-EN-P - March 2013 45

Chapter 1 Overview Figure 40 - SMC-Flex Controller Control Terminals 11 12 13 14 15 16 17 18 19 20 21 22 SMC-Flex Control Terminals Opt Input #2 Opt Input #1 Start Input Stop Input Aux #1 23 24 25 26 27 28 29 30 31 32 33 34 PTC Input TACH Input Ground Fault Aux #2 Aux #3 Aux #4 46 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Chapter 2 Application Profiles for the SMC Flex Controller Overview In this chapter, a few of the many possible applications for the SMC Flex controller are described. The basis for selecting a particular control method is also detailed. Illustrations are included to help identify the application. Motor ratings are specified, but the ratings may vary in other typical applications. For example, a tumbler drum is described as requiring the Soft Start feature. The application is examined further to determine how the SMC Flex controller options can be used to improve the tumbler drum performance and productivity. Figure 41 - Compressor with Soft Start AirFilter InletValve TurnValve Ports 208...480 Volts 50...250Hp 50/60 Hz Problem: A compressor OEM shipped its equipment into overseas markets, where wye-delta motors are common. There were many different voltage and frequency requirements to meet because of the compressor s final destination. Due to power company requirements and mechanical stress on the compressor, a reduced voltage starter was required. This made ordering and stocking spare parts difficult. Solution: The SMC Flex controller was installed and wired to a wye-delta motor. The unit was set for an 18-second Soft Start, which reduced the voltage to the motor during starting and met the power company requirements. By reducing the voltage, the starting torque was also reduced, minimizing the shock to the compressor. Panel space was saved because the SMC Flex controller has a built-in overload and SCR bypass feature. Rockwell Automation Publication 150-AT002C-EN-P - March 2013 47

Chapter 2 Figure 42 - Tumbler with Soft Start and Accu-Stop 480 Volts 150 Hp Loading Door Tumbler Drum Drive Chain Motor Problem: A tumbler drum used in the de-burring process was breaking the drive chain because of the uncontrolled acceleration from the across-the-line starter. To increase production on the drum, the coasting time on stop had to be reduced. Previous solutions were a separate soft start package plus a motor brake, which required additional panel space and power wiring. A small enclosure size and simplified power wiring were needed to reduce the cost of the controls. Because a PLC was controlling several other processes in the facility, communication capabilities were desired. Solution: The SMC Flex controller with the braking option configured as Accu-Stop was installed on the process. The Soft Start provided a smooth acceleration of the drive chain, which reduced downtime. The controlled acceleration made positioning for loading/unloading easier. The drum was positioned for loading using the Preset Slow Speed. For unloading, the drum was rotated at Preset Slow Speed and then accurately stopped. This increased the productivity of the loading/unloading cycle. Further, the Accu-Stop option did not require additional panel space or wiring. The SMC Flex controller s built-in overload eliminated the need to mount an external overload relay in the enclosure. The built-in SCR Bypass eliminated the need for an external bypass contact in the enclosure. Both features saved further panel space. The communication feature of the SMC Flex controller allowed remote starting and stopping of the process from a PLC. 48 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Chapter 2 Figure 43 - Pump with Soft Start Ground Level 480V 150 Hp Check Valve Pump Motor Problem: A municipal water company was experiencing problems with pump impellers being damaged. The damage occurred during frequent motor starting while the load below the check valve was draining from the system. A timing relay was installed to prevent restart underload, but need to be adjusted frequently.the pumping station motor was over 100 feet below ground, making repair costly. For maintenance scheduling purposes, an elapsed time meter measuring motor running time had to be installed in the enclosure. Solution: The SMC Flex controller with Pump control was installed, providing a controlled acceleration of the motor. By decreasing the torque during start up, the shock to the impeller was reduced. The SMC Flex Anti-backspin timer feature was implemented to prevent the motor from starting while turning in a reverse direction. Panel space was saved by employing the built-in elapsed time meter. The SMC Flex controller s line diagnostics detected the pre-start and running single-phase condition and shut off the motor, protecting against motor damage. Rockwell Automation Publication 150-AT002C-EN-P - March 2013 49

Chapter 2 Figure 44 - Bandsaw with Soft Start and Slow Speed with Braking 480 Volts 300 Hp Saw Blade Log Carriage Motor High Inertia Problem: Because of the remote location of the facility and power distribution limitations, a reduced voltage starter was needed on a bandsaw application. When the saw blade became dull, the current drawn by the motor increased. Therefore, an ammeter was required. The saw was turned off only during shift changes or routinely to change the saw blade. This application required 25 minutes to coast to stop, and braking devices were unacceptable due to their high complexity and panel space requirements. After a blade was replaced, it was dangerous to bring the saw up to full speed because of alignment problems. Metering the application for jam conditions was a necessity. In addition, single phasing of the motor was a problem because of distribution limitations. Solution: The SMC Flex controller was installed to provide a reduced voltage start. This minimized the starting torque shock to the system. With the braking option configured as Slow Speed with Braking, it provided a preset slow speed, allowing the saw blade tracking to be inspected before the motor was brought to full speed. The current monitoring and jam detection features of the SMC Flex controller were implemented, saving valuable panel space and the cost of purchasing dedicated monitoring devices. The controller s built-in programmable overload protection was used. The SMC Flex controller s diagnostic capabilities would detect single phasing and shut the motor off accordingly. Starting and stopping control was furnished in a single modular unit, providing ease of installation. 50 Rockwell Automation Publication 150-AT002C-EN-P - March 2013

Chapter 2 Figure 45 - Rock Crusher with Soft Start 250 HP 480 Volts Starts: Unloaded Gearbox Motor Discharge Problem: Because of the remote location of a rock quarry, the power company required a reduced voltage start on all motors over 150 Hp. The starting current on these large motors strained the capacity of the power system, causing severe voltage dips. When the rock crusher became overloaded, the current draw by the Wye-Delta motor increased. Therefore, current monitoring capabilities within the soft starter were required. Because the conveyor feeding the rock crusher was controlled by a PLC, communications between the soft starter and a PLC was necessary. When the rock crusher ran, occasionally a stall or jam would occur. Solution: The SMC Flex controller was installed, meeting the power company requirements. The motor was wired inside-the-delta, which saves valuable panel space. The metering capabilities of the SMC Flex controller allowed the current drawn by the motor to be monitored. With the built-in communications capabilities, the motor current was communicated to the PLC. When the motor current reached a specified limit, the conveyor feeding the rock crusher could be slowed. By slowing the conveyor, a jam condition in the rock crusher was avoided. The stall and jam detection capabilities of the SMC Flex controller would shut off the motor when a stall or jam condition occurred. Rockwell Automation Publication 150-AT002C-EN-P - March 2013 51

Chapter 2 Figure 46 - Hammermill with Current Limit Start and SMB Smart Motor Braking 480 Volts 350 Hp Belts Hammer Feed Motor Problem: A hammermill required a reduced voltage start because of power company restrictions. A stopping time less than the present 5 minute coast-to-rest was desired. To save panel space, the customer wanted to incorporate both starting and stopping control in the same device. Solution: The SMC Flex controller with the braking option configured as SMB Smart Motor Braking was installed. A 23-second, 450% current limit acceleration was programmed, meeting the power company requirements and reducing the mechanical stress on the belts during start-up. The braking function was accomplished without additional power wiring, panel space, or contactors. Zero speed was detected without additional sensors or timers. The current limit start, braking, and overload protection were accomplished within the same modular package. 52 Rockwell Automation Publication 150-AT002C-EN-P - March 2013