Start-up Instructions Peristaltic Pumps with VFD 110 or 220 Volt Single Phase Input Power

Similar documents
GPD 506/P5 Start-up Procedure and Checklist

NX Series Inverters. HVAC Pocket Programming Guide

VLT 6000 HVAC. Contents

A1000 Cheat Sheet (Open Loop Vector)

UNIVERSITY OF WATERLOO ELECTRICAL & COMPUTER ENGINEERING DEPARTMENT ME269 ELECTROMECHANICAL DEVICES AND POWER PROCESSING.

SX460. Generator Automatic Voltage Regulator Operation Manual

1115 4G SERIES GOVERNOR ma ANALOGUE DIGITAL SPEED SETTING

Thermo Top - Troubleshooting Tree

Balzers Sputter Coater SCD 050

Drives 101. Functions of an Adjustable Frequency Drive (AFD) This lesson covers the basic functions of an Adjustable Frequency Drives (AFD).

TOYOTA ELECTRONIC TRANSMISSION CHECKS & DIAGNOSIS

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

SECTION VARIABLE FREQUENCY DRIVES

Royal Digital Rapid steam

Diesel Engine Driven Generators Page 1 of 6

Table of Contents. Introduction. Radio Frequency Control. Initial setup Setting the time. Setting the temperature

Operating Manual Color Changing Fountains

Installation & Operation Manual for Energenics Air-Flow Optimizer

ENGINEERING BULLETIN No. EB 039 Product: Cooling Towers, Closed Circuit Coolers & Evaporative Condensers Date: June 2003

Basic Nameplate Information

Multi Engine Oral Exam Questions

OPL BASIC. Dosing System for Professional Laundry machines. Contents

Sensi TM. Wi-Fi Programmable Thermostat MANUAL OPERATION. Version: March Emerson Electric Co. All rights reserved.

Important: Always perform the Diagnostic System Check - Vehicle prior to using this diagnostic procedure. P0106, P0107 P0107

Electronic Power Control

R438 A.V.R. Installation and maintenance R 438. This manual is to be given to. the end user T10. Armature 6- Field X2 Z1 X1 Z2 E+ E- 0V

RF Etch Monitor. Introduction

Operating Manual. Los Angeles Abrasion Machine HM-70A & HM-70AF

Installation, Operation and Maintenance Manual

Phoenixtech Brushless Motor Speed Controller Programming Guide

MDC Series

EET272 Worksheet Week 9

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

Variable Frequency Drive For use with Block Machines

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

Frequency Converter Fv

FlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3

3753 en /b VE/B - VE/RG Va V riable speed drives

R448 & R448 V50 A.V.R.

LIFT CONTROL SYSTEMS CATALOGUE 2007

SYMETRIX SOLUTIONS: TECH TIP May 2014

LED Security Spotlight User Manual

Contents Installing the ucal Software on your PC/Laptop ucal Programmer Version Connecting the ucal Programmer to your PC/Laptop

LINE POWERED ADA TELEPHONE USER S MANUAL Use With Part Numbers , , , , , and

Automotive Sensor Simulator. Automotive sensor simulator. Operating manual. AutoSim

VLT AutomationDrive for Marine winch applications

The Black Box Push Button Control Box

PEBBLE USER MANUAL. MODEL: GMR1888DAB DAB Digital & FM Radio. Hyper-link ALL text to corresponding sections

Operation Manual. 150 Watt Halogen Light Source for Endoscopy Model # s ESS-150, ESS-150A ESS-220, ESS-220A

Maxi Pressurisation Units (Maxi, Maxi Plus & HP)

PC1130 Electric Air Compressor

Operation Guide 3M-22

EFC Frequency converters

1000 Hz High Frequency Custom Software

Softstarters. Type PSTX Fieldbus communication, Built-in Modbus RTU. 1SFC132089M0201 April SFC132089M0201 1

Operating Manual for Adjustable Height Tables. Contact us at or 1

AirPatrol WiFi Full Manual V1.0

LIFT CONTROL SYSTEMS CATALOGUE 2007

Installation & User Instructions

Additional Benefits of VFDs In addition to energy savings and better process control, VFDs can provide other benefits:

BLWR23MDA Series. 24V, 15A Brushless Controller / Motor. User s Guide. 910 East Orangefair Lane, Anaheim, CA info@anaheimautomation.

Number 1 in efficiency

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

PRODUCTIVITY THROUGH INNOVATION 600 CONTROL DIRECT DRIVE TECHNICAL/OPERATION MANUAL

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

Magnetic Deburring & Polishing Machine

SETTING UP YOUR 6000 SERIES TIME RECORDER

Transmitter Interface Program

The RIDZ 8x2 Audio Switcher

BLY17MDA Series. 24V, 10A Brushless Controller/Motor. User s Guide. 910 East Orangefair Lane, Anaheim, CA info@anaheimautomation.

BROOKFIELD MODEL VTE250 ELECTRIC VISCOSEL PROCESS VISCOMETER. Installation, Operation, and Maintenance Instructions. Manual No.

MAKING MODERN LIVING POSSIBLE. UniLynx Indoor User Manual. ULX 1800i ULX 3000i ULX 3600i ULX 5400i SOLAR INVERTERS

Transfer Equipment Controls

EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board.

Operational Overview and Controls Guide

AVR Pellet Control Board Installation/Service Instructions

Technical Information

USER MANUAL. EZRUN Series Brushless Speed Controller EZRUN-150A-PRO

PC Software for VAV compact and modular controllers

QTRONIX Programmer Pad

Fault codes DM1. Industrial engines DC09, DC13, DC16. Marine engines DI09, DI13, DI16 INSTALLATION MANUAL. 03:10 Issue 5.0 en-gb 1

Speed Control Relays SX2

PC SERIAL INTERFACE FOR LAMBDA GAS CONTROL LGC-700

AD425S Automatic door operator

SED2 Variable Frequency Drives. Operation & Maintenance Manual

Designed for multi-injector endurance testing, the

Specifying a Variable Frequency Drive s

Dear Customer, User Memo: Please visit us on facebook or twitter! Thank you for purchasing this product.

Lab 1: The Digital Oscilloscope

Troubleshooting Salt Generators

We will discuss common industrial applications with guides for the proper use of electric motors on these.

LK Electric Boiler - 4,5

ACS 800. Supplement Traverse Control Application Program 7.x

Phase-Control Alternatives for Single-Phase AC Motors Offer Smart, Low-Cost, Solutions Abstract INTRODUCTION

ACS800. Firmware Manual ACS800 Standard Control Program 7.x

IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER.

Scorpion User Guide for Commander V 59V 160A ESC (OPTO/SBEC)

LDG M-7700 External Meter for Icom IC-7700

PD 100A. Printing data system

TECHNICAL SPECIFICATION TYPE ATESO ALFA

Transcription:

Start-up Instructions Peristaltic Pumps with VFD 110 or 220 Volt Single Phase Input Power Document Version 3

Start-up Instructions for AccuStaltic Peristaltic Pump with VFD 100V or 220V Single Phase Input Power (v3) Pump serial number: Date of manufacture: Motor native speed at 60 Hz: 1725 RPM 3PH 3450 RPM 3PH Gearbox ratio: Pump native operating speed (motor RPM/ gearbox ratio): *Pump operating range: Pump original manifold type: Pump original tubing ID x wall thickness: Approximate flow per channel for this tubing: Original input voltage of VFD at manufacturer: 115V 220V *Going lower than this range for extended periods of time can cause the motor to overheat and is not recommended. The VFD is designed to shut down the motor before catastrophic damage can occur. Start-up Instructions for AccuStaltic Peristaltic Pump with KB VFD 2 of 5

Start-up Instructions Your AccuStaltic pump is equipped with a KBDA-27D Genesis Variable Frequency Drive (VFD) that has been preprogrammed to provide a simple, nearly plug-and-play startup. The VFD has many powerful features which are fully explained in the Installation and Operation Manual. If you are using remote control or interfacing with other machinery, a thorough review of the manual, in addition to this document, is important. For manual operation, the following instructions will explain the pre-programming that has already been done to your VFD. In operation, you can cycle the readout to display amp draw, revolutions or flow per minute (a programmable feature we will explain later), or programming mode. Before operating the pump, please go through the following checklist to verify the preset programming of the VFD. Setup and Verification of VFD Controls: 1. Turn speed control knob counterclockwise to minimum. 2. If your VFD was ordered as 110V, it will come with a US standard 3-prong plug pre-installed. If you ordered it as 220V, it will come bare-wired, ready for the plug of your choosing. Plug in your VFD. Note: The VFD will not auto-switch between voltages, but can easily be converted from 115V to 230V by changing an internal jumper. Failure to change this jumper before attempting to use another voltage can destroy the VFD. If you desire to change the voltage, please call Ledebuhr Industries for assistance. 3. Turn power switch to on. The display should blink 0000. This is the normal startup condition. The display will blink any time the motor is stopped. The PROGRAM/DISPLAY button will cycle through RPM, program settings, and amp draw. If an error code shows, you may have a problem with your input power. Check Table 7 on page 30 of your KBDA Installation and Operation Manual to identify your error code. 4. Check motor preset values: a. Motor Frequency Rating: Press the PROGRAM/DISPLAY button. 00.00 should appear. Press the READ/ENTER button. 0002 should appear. Press READ/ENTER button. "End" should display briefly before returning to 00.00. By choosing the 0002 option, you allow the motor to operate over its native frequency of 60 Hz. Start-up Instructions for AccuStaltic Peristaltic Pump with KB VFD 3 of 5

b. Max Motor Amps: Press the up arrow to 00.01. Press 04.50 should appear. This is the maximum amperage allowable before the VFD will fault and shut down the motor. Press Because the motor can be operated beyond its rated speed, there is a mandatory power de-rate. 4.5 amps is the maximum input amperage that the motor can sustain at 85 Hz and not overheat, in normal operating conditions. If you only intend to operate the motor at lower than maximum speeds, or intermittently, you may be able to increase the max amps, up to the nameplate amperage rating at 220V. Any increase in this parameter should be followed by a period of monitoring the temperature of the motor using an infrared thermometer. The motor should normalize at 150 Fahrenheit after an hour or so of continuous operation. The motor temperature should never go past 180 F during intermittent operation. If the motor heat continues to climb, decrease the maximum amperage until temperature stabilizes. c. Max Motor Frequency: Press the up arrow to 00.05 and press 85.00 should appear. This is the maximum motor hertz that the VFD will output. Press This parameter should ABSOLUTELY NOT BE INCREASED. If you feel you would like to operate at higher speeds, contact Ledebuhr Industries to discuss your application options. d. Activate the Potentiometer Control: Press the left arrow/reset button twice. Press the up arrow twice. The display should read 02.00. Press It should read 0001. Press This activates the potentiometer dial on the VFD face as the primary speed control. Consult the operation manual for other options. e. Upper Frequency Limit: Press the left arrow/reset button twice. Press the up arrow once. Press the left arrow/reset button twice. Press the up arrow twice. The display should read 03.02. Press The display should read 85.00. Press This is a safety parameter that will disable the motor if it over speeds. Over speeding does not occur during normal operation. This parameter should ABSOLUTELY NOT BE INCREASED. If you feel you would like to operate at higher speeds, contact Ledebuhr Industries to discuss your application options. f. Motor Ramp-up Speed: Press the up arrow once to 03.03, then 010.0 should appear. This is the number of seconds the motor will take to reach full speed after being turned on. Press Setting a motor ramp-up time reduces the current required to accelerate the motor. You may set your ramp to any time range that suits you. At very short ramps you may find the VFD throwing a fault code due to excessive power demand. If this happens, increase your ramp time in.1 second intervals until the VFD no longer faults. g. Motor Ramp-down Speed: Press the up arrow once to 03.04, then 001.0 should appear. This is the number of seconds the motor will have to coast to a stop. Press Ramp-down is similar to ramp-up. A short ramp-down will cause the VFD to act as a brake. At very short ramp intervals, the VFD may throw a fault condition due to high braking current. If this occurs, increase the ramp-down time in.1 second intervals until you no longer get the fault. Start-up Instructions for AccuStaltic Peristaltic Pump with KB VFD 4 of 5

h. Display Mode: Press the left arrow/reset button twice. Press the up arrow once. The display should read 04.00. Press The display should read 0002. Press Setting Display mode parameter 0002 allows you to enter a custom unit. This will allow you to show RPM or flow rate on the readout of the VFD, once you have specified it in 4.01 (next step). i. Set Custom Unit: Press the up arrow once to 04.01, then The display should read the max RPM of the pump head, listed in your pump information at the beginning of this document. Press For displaying any custom units, including flow rate, see page 35 of your manual, or call Ledebuhr Industries for assistance. j. Set Custom Unit Display: Press up to 04.02, and then The display should read 0000. Press This sets custom units to whole numbers. This will need to be modified as well if you want to set Custom Units to flow rate instead of pump RPM. k. Motor Current Display: Press the up arrow twice to 04.04, then press 0001 should appear. Press This enables the motor current display in the rotation when you push the PROGRAM/DISPLAY button. To disable this function and remove it from the display rotation, select 0000. Operate the Pump After all parameters are set correctly, the VFD is ready to operate. Press PROGRAM/DISPLAY and cycle to the Custom Units display. Press the RUN/STOP button, and then twist the control knob clockwise. The motor will accelerate, taking the pre-determined ramp time to reach full speed. You can use the PROGRAM/DISPLAY mode to cycle between program mode, amp draw, and RPM of the motor. All the above presets plus many other options and features are described in the Installation and Operation Manual for the VFD. Care and maintenance Please review the Care and Maintenance of AccuStaltic Pumps manual for instructions on maintaining the pump head and tubes. Also review the Dosing Systems manual if you have purchased a dosing system. Start-up Instructions for AccuStaltic Peristaltic Pump with KB VFD 5 of 5