SMOKE DETECTOR PERFORMANCE FOR LEVEL CEILINGS WITH DEEP BEAMS AND DEEP BEAM POCKET CONFIGURATIONS

Similar documents
Relative Sensitivity based Fire Detection Systems used in High Density Computer Rooms with In-Row Air Conditioning Units

Validation of Modeling Tools for Detection Design in High Airflow Environments

Pollution CO CO 2. Carbonaceo us soot H 2 S, NOX, SO2

The Mission Critical Fire Protection Experts

Influence of fire source locations on the actuation of wet-type sprinklers in an office fire

Single-Ended Reflected Beam Smoke Detector

A P P L I C A T I O N S G U I D E. Single-Ended Reflective Beam Smoke Detector

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective

Empirical Validation of Detection Systems Equivalency for Coincidence Suppression Actuation

RESIDENTIAL SPRINKLER INSTALLATION GUIDE

LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado

Casey C. Grant, P.E., FSFPE Research Director Fire Protection Research Foundation

Integrated CFD Models for Air-sampling Smoke Detection

Sprinkler Protection for Cloud Ceilings

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

FIRERAY 2000 Installation Guide

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases

LESSON PLAN FIRE PREVENTION AND SAFETY

* Any required illumination shall be arranged so that the failure of any single lighting unit shall not leave any area in darkness.

DESIGN OF SLABS. Department of Structures and Materials Engineering Faculty of Civil and Environmental Engineering University Tun Hussein Onn Malaysia

Clark County Fire Prevention

Formwork for Concrete

Technical Article. Sprinkler Protection for High Bay and Automated Storage in Warehouse-Type Storage Facilities

LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.

OHIO BOARD OF BUILDING STANDARDS. Smoke Alarms and Fire Safety

Fire Alarm System Plans Review Checklist Property location Date of Review

RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

Open Channel Flow Measurement Weirs and Flumes

DUCT SMOKE DETECTOR D4120

CH. 2 LOADS ON BUILDINGS

Piotr Tofiło a,*, Marek Konecki b, Jerzy Gałaj c, Waldemar Jaskółowski d, Norbert Tuśnio e, Marcin Cisek f

Flow distribution and turbulent heat transfer in a hexagonal rod bundle experiment

Interfacing Elevators with Fire Alarm and Sprinklers

City of Riverside Building & Safety Division Phone: (951)

BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM

. Address the following issues in your solution:

Enclosure and Airflow Management Solution

Extended Coverage Sprinklers

Approval Standard for Plastic Suspended Ceiling Panels

C I T Y O F S E L M A F I R E D E P A R T M E N T

I.S :2013 Fire Detection & Alarm Systems

Reducing the Annual Cost of a Telecommunications Data Center

Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial

COMPARISON TESTING IN A SIMULATED DATA PROCESSING/ TELECOMMUNICATIONS FACILITY: FM-200 AND AUTOMATIC SPRINKLER SYSTEMS

NUMERICAL SIMULATION OF FLOW FIELDS IN CASE OF FIRE AND FORCED VENTILATION IN A CLOSED CAR PARK

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D

DuPont FM-200 COMPARISON TESTING IN A SIMULATED DATA PROCESSING/TELECOMMUNICATIONS FACILITY

Sharp-Crested Weirs for Open Channel Flow Measurement, Course #506. Presented by:

Development of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling

HEAVY OIL FLOW MEASUREMENT CHALLENGES

Reference numbers following checklist statements represent an NFPA code section unless otherwise specified.

Bath Planning Guidelines With Access Standards

I.S :2013 Fire Detection & Alarm Systems

MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST

HERNANDO COUNTY FIRE ALARM GUIDELINES

Sprinkler Identification Number. Page 1 of 6 MARCH 2014 TFP288. Worldwide Contacts.

Fire. The Fire Installers Mate. A guide to fire alarm systems design

MODELING THE PERFORMANCE OF FIRE PROTECTION SYSTEMS IN MODERN DATA CENTERS

Classroom Door Security & Locking Hardware

TEXAS STATE BOARD OF PLUMBING EXAMINERS EXAMINATION AND REGISTRATION Endorsement Training Programs

Current as of 11/10/08 1 of 1

Understanding Shaft Alignment: Thermal Growth. Published in Maintenance Technology 1/2003

Analysis of the Response of Smoke Detectors to Smoldering Fires and Nuisance Sources

Smoke exhaust systems

FIRE DAMPER APPLICATION GUIDE

OPAL TM Detector range

POST AND FRAME STRUCTURES (Pole Barns)

RGB Light Panel Applications. RGB LED Light Panel FEATURES & BENEFITS SPECIFICATION SHEET

Inert Gas Extinguishing System Two Minute Discharge Study. Gene Hill, P.E. Brad Stilwell

EVALUATION OF PHOENICS CFD FIRE MODEL AGAINST ROOM CORNER FIRE EXPERIMENTS

Basic Selection & Proper Application of Overhead Air Distribution Devices

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

CFD STUDY OF TEMPERATURE AND SMOKE DISTRIBUTION IN A RAILWAY TUNNEL WITH NATURAL VENTILATION SYSTEM

By Gene Kitts, Senior Vice President-Mining Services, International Coal Group, Inc.

SPECIAL APPLICATIONS

DSM155 Digital LED Light Meter User s Manual DSM155

THE USE OF AIR ATOMIZING NOZZLES TO PRODUCE SPRAYS WITH FINE DROPLETS

Doppler. Doppler. Doppler shift. Doppler Frequency. Doppler shift. Doppler shift. Chapter 19

An Overview of the International Road Tunnel Fire Detection Research Project

SPEED, VELOCITY, AND ACCELERATION

Cost Estimation for Materials and Installation of Hot Water Piping Insulation

oil liquid water water liquid Answer, Key Homework 2 David McIntyre 1

Practice Tests Answer Keys

D287/D288/D292/D293A/D293E

The Analysis of Open Web Steel Joists in Existing Buildings

GAMBIT Demo Tutorial

rpsa FIRE PROTECTION ENGINEERS

BRUNS-PAK Presents MARK S. EVANKO, Principal

CASE HISTORY #2. APPLICATION: Piping Movement Survey using Permalign Laser Measurement System

Residential Plan Review Emergency Vehicle Access and Water Supply Permit Information Packet

3D SCANNERTM. 3D Scanning Comes Full Circle. s u n. Your Most Valuable QA and Dosimetry Tools A / B / C. The 3D SCANNER Advantage

FLOW CONDITIONER DESIGN FOR IMPROVING OPEN CHANNEL FLOW MEASUREMENT ACCURACY FROM A SONTEK ARGONAUT-SW

Manual for simulation of EB processing. Software ModeRTL

Practice Problems on Boundary Layers. Answer(s): D = 107 N D = 152 N. C. Wassgren, Purdue University Page 1 of 17 Last Updated: 2010 Nov 22

NFPA FAQs. 3. Can plastic pipe be used on a sprinkler system complying with NFPA 13?

SECTION ZONED (DC LOOP) FIREALARM SYSTEM

SMALL SCALE ASTM E 119/UL 263 ONE HOUR FIRE TESTING FOR MARINOWARE ON JOIST-RITE WITH ARMOROC FLOOR VTEC # TESTED: MAY 23, 2008 REVISION

Transcription:

SMOKE DETECTOR PERFORMANCE FOR LEVEL CEILINGS WITH DEEP BEAMS AND DEEP BEAM POCKET CONFIGURATIONS 10th Fire Suppression & Detection Research Application Symposium Daniel J. O Connor P.E. Schirmer Engineering Corporation

Acknowledgements Vision Systems Ltd. (Aus.) Ming He, MIEA Yun Jiang, MIEA John Vythoulkas Tawfeeq Al-Farra Schirmer Engineering Ervin Cui, Ph.D., P.E Matthew J. Klaus Chen Su, P.E. Fire Protection Research Foundation (FPRF) & Supporting Patrons Fire Detection and Alarm Research Council FPRF Appointed Project Technical Panel NFPA 72 Initiating Devices Committee

Current NFPA 72 Spot Smoke Detector Rules for Solid Beams 12 inches 12 feet If Ceiling Ht. >12 or Beam depth > 12 in. Spot smoke detector every beam pocket Detector must be on the ceiling Parallel direction -30 ft. guideline Perpendicular -15 ft spacing

Why Most Questioned Requirement 90 feet 90 ft ft 3 ft by 3 ft Pocket 15 ft 30 ft 30 ft 15 ft Spot smoke detector 15 ft 30 ft 30 ft 15 ft Spot smoke detector

Review of Previous Work NFPRF Sponsored NIST s CFD work in 1993-94 International Fire Detection Research Project, Field Modeling: Effects of Flat Beamed Ceilings on Detector and Sprinkler Response; Technical Report Year 1, October 1993 Significant in identifying flow effects resulting from parallel channels due to beams Scope was limited, CFD modeling was computational intensive in early 1990 s

Scenarios of 1993 Work Majority of Scenarios 11 ft. ceiling Fire to ceiling distance, constant at 8 ft. Beam depths 0, 4, 8, 12, 24 inches Beam spacing varied Few high ceiling scenarios 28 ft. ceiling Beam depth constant at 12 inches 8 ft. 11 ft. 28 ft.

Extract from 1993 Technical Report Year 1 Activation 13 C rise only Criteria for detector activation narrowly defined using a threshold fire size Medium growth 100 kw fire Medium growth 1 MW fire No comparison to the expectation of smoke detectors spaced per 30 foot guideline No understanding of how field conditions would change if examined 5, 10, 30 or 60 seconds later No review of gas velocities at smoke detector Most scenarios with parallel channels, no consideration for constraining effects of corridor walls or beam pockets

Objectives - Methodology Identify appropriate spot smoke detector activation thresholds Optical density Temperature rise Flow velocity Best Source for data on thresholds - Recent work by Geiman (Masters thesis) and Geiman & Gottuk (paper in Fire Safety Science) Identify baseline detector performance 30 ft x 30 ft spacing on unconfined flat ceiling Vary performance with increasing height Perform modeling & examine field conditions At postulated smoke detector locations Determine likelihood that field conditions would result in activation Compare postulated detectors with Baseline detector performance Spot detector activation thresholds Reduce the data to usable format results, trends, conclusions

Review of Work by Geiman and Geiman & Gottuk Flaming Fires Only Predicted Alarms Over & under Predictions Alarms within + 60 seconds Evaluation for Beam Study Nominal Sensitivity per UL 217/268 ~ 1-3% Obs/ft ~.014 -.043 OD/m High % predicted 3:2 ratio over : under 30-40 % Not sufficiently conservative Max. Black Smoke OD 10% Obs/ft 0.14 OD/m (closer to 0.15) 30% Almost all overpredictions +1000 % -2000% error <10% Too conservative, unrealistic view of detector performance for flaming fires 20 th percentile Average OD Alarm Threshold 0.007 + OD/m (ion) 0.031 + OD/m (photo) High % predicted Majority underpredicted 63% ion 49% photo Under- prediction not suitable for code requirement study 80 th percentile Average OD Alarm Threshold 0.072 + OD/m (ion) 0.106 + OD/m (photo) Fewer predictions than 20 th percentile Average OD Alarm Threshold More over-predictions than 20 th percentile Average OD Alarm Threshold Tendency for over prediction suitable for code requirement study, but not overly conservative as 0.14 OD/m

Review of Work by Geiman and Geiman & Gottuk Flaming Fires Only Predicted Alarms Over & under Predictions Alarms within + 60 seconds Evaluation for Beam Study 4 degrees C Temperature Rise 100 % predicted 4:1 over/under ion 1: 3 over/under photo 57% ion 30% photo representative of a conservative threshold for ionization detection 13 degrees C Temperature Rise 90% Ion vast majority overpredictions Photo 1:1 Very few representative of the typical photoelectric detector Flow Velocity 0.15 m/s Mean 0.13 + 0.07 m/s (from GG data review) 100% predicted Slight over-predicted ~ 40 % Use mean value to review velocity field conditions to be assured of sufficient velocity at for smoke entry into detector 80 th percentile Average OD Alarm Threshold 0.072 + OD/m (ion) 0.106 + OD/m (photo) Fewer predictions than 20 th percentile Average OD Alarm Threshold More over-predictions than 20 th percentile Average OD Alarm Threshold Tendency for over prediction suitable for code requirement study, but not overly conservative as 0.14 OD/m

Baseline 30 ft. Guideline Spacing 30 ft Spot detector 30 ft Elevation View Plan View

Baseline 30 ft. Guideline Spacing Optical Density Per Meter 0.25 0.2 0.15 0.1 0.05 0 9'ceiling 12'ceiling 18'ceiling 24'ceiling 0 10 20 30 40 50 60 Time (second)

Baseline Ceiling Jet Development 12 ft Ceiling Ht., Red 65 C, Green ~ 40 C

CFD Grid System

Measurment Points

Corridor Scenario 2 In this scenario 12 inch deep beams interrupt the ceiling surface every 3 feet. Temperature rise exceeds the threshold of 13 o C and 4 o C during an early time frame and all locations exceed that of the baseline detector. Optical density exceeds that of the baseline for all detector locations. Detector locations within pocket or on the bottom of the beam experience comparable optical density valu

Time Shift t Relative to Baseline

Corridor Ceiling Jet Development 12 ft Ceiling Ht., Width 5 ft., Beam Depth 12 in. - Red 65 C, Green ~ 40 C

Corridor Scenario 18 : In this scenario 24 inch deep beams interrupt the ceiling surface every 3 feet. Introducing a 24 beam at the 18 ft ceiling height shifts the baseline 15 to 20 seconds before the noted detector locations. However, all detector locations relatively quickly exceed the temperature rise and optical density values observed for the baseline

Trends Shown For a 5 ft wide corridor, the optical density at all locations along corridor reaches into the blue range and exceeds the baseline in 30 seconds. The comparison graph for the 60 second time frame illustrates trends resulting as steady state conditions are reached. At 60 seconds for any given ceiling height grouping the general trend is that optical density values tend to increase as beam depth increases. This is attributable to a reservoir effect that allows soot concentration to build in the deep beam pockets. As ceiling height groupings of data are reviewed left to right (from 9 ft to 18 ft) the trend is that optical density values are reducing in value due to the additional entrainment into the plume that results with increasing ceiling height. In all cases shown it is evident that at 60 seconds all postulate detector locations would be expected to alarm and exceed value for the baseline case

Trends Shown For a 12 ft wide corridor, the optical density at all locations along corridor reaches into the green range and exceeds the base line in most cases in 60 seconds. Some turbulence impacts are observed at early time frame (30 seconds). Also Optical density value shows more entrainment and dilution results in this

Reservoir Effect ncreases OD Top Graph Corridor Smooth Ceiling OD rise earlier than unconfined smooth ceiling baseline Bottom Graph 12 in. beams delay transport 10-15 sec. OD rise readily surpasses baseline

Beam Effect Diminishes at 30 ft. Corridor Width with 18 ft. Height For 100kW fire result is comparable to baseline Expectation for alarm of baseline detector and postulated detectors with 30 ft. corridor width is low

Fire Size Key To Detection for Increasing Ceiling Heights For 100kW fire result is comparable to baseline Circled data is result for 300 kw fire An increased fire size results in relatively fast rise in OD to levels of expected alarm

Optical Density Well Mixed These graphics show the traversal soot density distribution at 15 and 16.5 from fire, at 60 seconds. The results show that the spaces inside the beam pocket and near the bottom of the beam have comparable soot density gradient. No stagnant zone is observed near the sidewall or at the corners

Velocity - (Ceiling Height 12, Corridor Width 5, Beam Depth 12 ) - 1.5 off wall

Velocity - (Ceiling Height 12, Corridor Width 5, Beam Depth 12 ) - 1.5 below ceiling

Velocity - (Ceiling Height 12, Corridor Width 5, Beam Depth 12 ) - 1.5 below beams

Corridor - Basic Findings Linear Spacing of Smoke Detection The data observed in this analysis indicates that for ceilings up to 18 feet in height, that deep beam configurations do not negatively affect expected performance. Reservoir effect contributes to beneficial rise in OD as compared to smooth ceiling scenarios. This means that for these conditions, detector can be effectively used in corridor with deep beams at spaces of 30 to 41 feet as is permitted for smooth ceilings Increasing Ceiling Heights As ceiling height increases the fire size threshold needed for activation of the baseline spot smoke detector must increase. With an increased fire size the smoke detectors on a beam ceiling will be comparable to the performance result for the baseline detector at the same ceiling height. Location Under Beams/On Ceiling Between Beams Where deep beams interrupt the ceiling surface in a corridor, mounting the detector on the ceiling between beams or the bottom of the beam is acceptable, either location providing comparable response to alarm Sidewall Mount or Center of Corridor Keeping smoke detector locations 12 inches below or away from a ceiling-wall corner appears unsubstantiated. No stagnant zone or locations are observed that would preclude smoke detector alarm. Temperature and smoke optical density are relatively uniform and well-mixed throughout the volume of the beam pocket within seconds after the initial ceiling jet passes

Beam Pocket Scenarios Small rooms: - Pocket size 3x3, 6x6, 12x12 ft, and - Beam depth of 0 (as baseline), 12, 24 inches, with - Ceiling heights of 12, 18, and 24 feet Large rooms: - Pocket size 3x3, 6x6, 12x12 ft, and - Beam depth of 0 (as baseline), 12 inches, with - Ceiling heights of 36 feet Fire sizes: Ceiling height (ft) Constant Flaming Fire (kw) 12 100 18 200 24 300 36 feet 600kW

Beam Pocket Model

Case CH 18 ft., BD 24 in., PS 6x6 ft. slice in-pocket under ceiling

Case CH 18 ft., BD 24 in., PS 6x6 ft. slice just under beams

Optical Density Profile for 3 x 3 ft. Pockets OD, H18D24P3, 15 to 30 seconds, 10cm below the ceiling

Optical Density Profile for 12 x 12 ft. Pockets Near Beam Centerline of pocket OD, H18D24P12 at 30 seconds Far Beam

Temperature Profile for 12 x 12 Pockets Near Beam Centerline of pocket Temperature, H18D24P12 at 30 seconds Far Beam

Case CH 18 ft., BD 24 in., PS 3x3 ft. -5 seconds from baseline for detectors at 15 and 18 foot spacing -22 seconds from baseline for detectors at 30 ft. spacing

Case CH 12 ft., BD 24 in., PS 6x6 ft. -30 seconds from baseline for detectors at 24 foot spacing -18 seconds from baseline for detectors at 18 foot spacing -40 to 50 seconds from baseline for detectors at 30 foot spacing

Optical Density (OD/m) 0.40 0.35 0.30 0.25 0.20 0.15 0.10 0.05 Scenario H12D24P06 In the Pocket Baseline 6ft (1st pocket) 18ft (2nd pocket) 30ft 0.00 0 5 10 15 20 25 30 35 40 45 50 Time (s)

0.30 Scenario H12D24P06 Under the Beam Optical Density (OD/m) 0.25 0.20 0.15 0.10 Baseline 12ft (1st beam) 24ft (2nd beam) 0.05 0.00 0 5 10 15 20 25 30 35 40 45 50 Time (s)

Case CH 12 ft., BD 24 in., PS 6x6 ft. -8 seconds from baseline for detectors at 24 foot spacing -13 seconds from baseline for detectors at 30 foot spacing

0.5 0.4 0.3 0.2 0.1 0.0 OD (1/m) D12P03 D12P06 D12P12 D24P03 D24P06 D24P12 D12P03 D12P06 D12P12 D24P03 D24P06 D24P12 D12P03 D12P06 D12P12 D24P03 Beam Pockets Data Summary ODs at various points at 10s 1st pocket 2nd pocket 3rd pocket 1st beam 2nd beam 3rd beam H12 H18 H24 D24P06 D24P12

0.4 0.3 0.2 0.1 0 OD (1/m) D12P03 D12P06 D12P12 D24P03 D24P06 D24P12 D12P03 D12P06 D12P12 D24P03 D24P06 D24P12 D12P03 D12P06 D12P12 D24P03 Beam Pockets Data Summary ODs at various points at 30s 1st pocket 2nd pocket 3rd pocket 1st beam 2nd beam 3rd beam H12 H18 H24 D24P06 D24P12

Waffle or Pan Type Ceilings Basic Findings Linear Spacing of Smoke Detection The data observed in this analysis indicates that for pan type ceilings with beams or solid joists no greater than 24 in. deep, and beam spacing no greater than 12 ft. center -to-center configurations do not negatively affect expected performance. Reservoir effect contributes to beneficial rise in OD as compared to smooth ceiling scenarios. This means that for these conditions, detector can be effectively used in waffle or pan type at a spacing of 3o ft. Increasing Ceiling Heights As ceiling height increases the fire size threshold needed for activation of the baseline spot smoke detector must increase. With an increased fire size the smoke detectors on a beam ceiling will be comparable to the performance result for the baseline detector at the same ceiling height. Location Under Beams/On Ceiling Between Beams Where deep beams interrupt the ceiling surface in a room, mounting the detector on the ceiling in beam pockets or the bottom of the beams is acceptable, either location providing comparable response to alarm for flaming fires Sidewall Mount or Center of Corridor Keeping smoke detector locations 12 inches below or away from a beam-ceiling corner appears unsubstantiated. No stagnant zone or locations are observed that would preclude smoke detector alarm. Temperature and smoke optical density are relatively uniform and well-mixed throughout the volume of the beam pocket within seconds after the initial ceiling jet passes.

Thanks for Your Attention Questions?