Service Bulletin WARNING LIST. MP4000 Warning Descriptions BULLETIN: C 099. DATE: June 19, 2013 WARNING LIST

Similar documents
MP-4000 Alarm List (Software version or later)

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

, User s Manual

Failure code manual. content

Air Conditioning System

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Commercial Refrigeration Temperature and Defrost Controls

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

AIR CONDITIONING SYSTEM 1. FFH SPECIFICATION AIR CONDITIONING SYSTEM RODIUS

Table Z. Troubleshooting Chart for Air Conditioners. Cause

PANASONIC TROUBLE SHOOTING GUIDE

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/

13. Troubleshooting. Indoor unit s LED indication of Corona DC inverter unit. Indoor unit s LED indication of Alfa DC inverter unit

USER S MANUAL HSC-24A

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2

SERVICE MANUAL REFRIGERATION

Panel Mounted Air Conditioners by Dantherm, Inc.

NO-FROST CUSTOMER SUPPORT INFORMATION INFORMATION ON THE NO-FROST TECHNOLOGY WHITE GOODS

A/C-HEATER SYSTEM - AUTOMATIC

SMM. Installation Operation Maintenance

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

Engineering Specifications

14. Troubleshooting Guide

HEAT SIPHON ANSWERBOOK

Troubleshooting Your Refrigerator

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved

Service manual. The voltage in P3 and P4 in outdoor PCB is high voltage about 310V The voltage in P5 and P6 in outdoor PCB is high voltage about 310V

Technical service manual

TSB #: 74 Date: 9/7/2013 HOLDEN VE/WM HVAC & A/C DIAGNOSTIC HINTS

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

Application Engineering

ELECTRIC POSITION for electric heat, then confirm with Fan Test below.

3. AIR CONDITIONER CONTROLLER (UNIT)

Portable Air Conditioner

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Why and How we Use Capacity Control

4 Alarm and info. Alarm. Yes Warning. No Information No Reset alarms > No Current list > Alarm log list > Delete alarm log > No

New Deluxe Wall Mounted Heat Pump Series EXTERIOS

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Electronically Controlled Clutchless or Variable Drive Compressors

Haier Air conditioner

Panasonic/Sanyo A/C Interface Modbus RTU Installation Instructions

*.ppt 11/2/ :48 PM 1

TAS-18MVHN/O TAS-27MVHN/O TAS-36MVHN/O

Split Air Conditioner

SERVICE & MAINTENANCE MANUAL

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

PORTABLE AIR CONDITIONER

Air conditioning, electrical testing

Split units TH with hermetic compressors

BMG/TMG -27, 48, 52, 74, 80 LAE CONTROLLER Installation & Operations Manual

Marine Refrigerator/freezer CR 195 & CR 195 Stainless Steel-INOX

Installation & operating instructions

Regency TAFE, SA. An evaluation of the effects of PermaFrost treatment on a Fujitsu Heat Pump. July Prepared by

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:

Single Zone LCD Thermostat Operating Instructions

HEATER, AIR CONDITIONING AND VENTILATION

AUTOMATIC CONTROL HEATING, VENTILATION AND AIR CONDITIONING SYSTEM

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art A

Technical service manual 2009

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

Instruction manual for Firstline FCS12000CH

USER S MANUAL FH052EAV1 FH070EAV1. System Air Conditioner (Cooling and Heating) ENGLISH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH E HNIKA

WALL MOUNTED SPLIT TYPE AIR CONDITIONER

INSTALLATION MANUAL. Address card EKAC10B

Technical Information

Heater and Air Conditioner, Blend Air System, Troubleshooting 83.06

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM EXPLOSION VIEW 12 6.

TECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR

Hot Water. Heat pump water heaters. Residential and Commercial R410a

Statement of Work. 3.0 Details of Service Pre Start-up Cooling Start-up Service. Installation Service. Table of Contents. 1.0 Executive Summary

LOBOY 16 AIR CONDITIONERS

User Manual for CH-PFC76810

Alerts and Delta T Diagnostics with the Prestige 2.0 IAQ Thermostat

ABNORMAL OPERATION Error code Display. Specifics Error Code. Subsection Error Code. Subsection and Specifics Error code target

ALL IN ONE. Heat Pump Water Heater

Operating Instructions Air Conditioner

Heat Pump Water Heater IOM Manual

Operating Instructions Air Conditioner

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

How To Defrost A Truck

Operating Instructions Split System Air Conditioner

T-Series Air Conditioner T62 Model

FTQ. Daikin Inverter Ducted Heat Pump

Workshop 7 PC Software - Tracker

DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL

Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls

HVAC SYSTEM (AUTO A/C) (DIAGNOSTICS) AC

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

FOXAIR 60/50 ALL MODELS

D SERIES MODULAR AIR-COOLED SCROLL CHILLER. TECHNICAL SALES GUIDE-50Hz CAPACITY RANGE:65~130kW SUPER HIGH AMBIENT OPERATION TO 43

Condensing unit type EPSILON-ECHOS LE Technical information manual

HVAC SYSTEM (HEATER, VENTILATOR, AND A/C)

CGC s Hybrid System Loop Control

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM EXPLOSION VIEW 16 6

Transcription:

Service Bulletin SUBJECT: MP4000 Warning s BULLETIN: C 099 DATE: June 19, 2013 WARNING LIST WARNING LIST Warning id Warning text 1 HIGH PRESS CUT OUT CHECK WATER COOLING 6 HIGH PRESS CUT OUT CHECK COND PROBE 8 HIGH PRESS CUT OUT PLEASE WAIT 13 EVAP HIGH TEMP CHECK HEATER SYSTEM 20 LOW VOLTAGE ON LINE UNIT STOPPED 21 CURRENT TOO HIGH CHECK COMPR AND FANS 22 CURRENT TOO LOW CHECK COMPR AND FANS 23 SUPPLY TEMP TOO HIGH CHECK SENSORS 24 SUPPLY TEMP TOO LOW CHECK EVAP COIL 25 EVAP TEMP TOO HIGH - CHECK EVAP SENSOR 26 EVAP TEMP TOO LOW - CHECK EVAP SENSOR 27 SYSTEM LOW PRESSURE - CHECK REFR CHARGE 28 FROZEN SET POINT - CHECK AIR EXCHANGE 30 HIGH PRESS CUT OUT - PLEASE WAIT 31 HPCO TIMER HOLD - PLEASE WAIT 32 LOW PRESS CUT OUT - PLEASE WAIT 33 LPCO TIMER HOLD - PLEASE WAIT 34 COMP TOO HIGH TEMP TIMER - PLEASE WAIT 35 COMPRESSOR HIGH TEMPERATURE 36 AVL OPEN - CHECK FAE AND CA SETTINGS 37 CO2 READING STUCK FOR >24HOURS 38 HIGH VOLTAGE ON LINE 39 BATTERY CHARGER/HEATER CHECK BATTERY 40 12V SENSOR PSU PROBLEM

WARNING DESCRIPTIONS Each warning is described with the reason / description and the recommended corrective action. Some warnings are special related to specific customer requests and may not be active for standard settings. If the specific warning depends on special customer options it is noticed in the description setting. Warning #0001 HIGH PRESS CUT OUT CHECK WATER COOLING If HPCO is detected and the configuration is set to water cooled condenser: Poor cooling water supply. Controller auto clears message 10 minutes after compressor start-up. Water cooled condensing may be wrongly selected. Warning #0006 HIGH PRESS CUT OUT CHECK COND PROBE Unit stops due to high pressure cutout and the condensing temperature regulation has not activated the condenser fan. Controller auto clears message 10 minutes after compressor start-up. Check location of condenser probe. Wrong location of condenser probe. Warning #0008 HIGH PRESS CUT OUT PLEASE WAIT Unit stops due to high pressure cutout and the condensing temperature regulation has activated the condenser fan. Poor cooling of the refrigerant. Controller auto clears message 10 minutes after compressor start-up. Check for high ambient temperature. Check condenser fan rotation. Check for blocked condenser coil.

Warning #0013 EVAP HIGH TEMP CHECK HEATER SYSTEM If the state Hot Evaporator Section is active and the control calls for heat the warning is set. The state Hot Evaporator Section is defined either by: RA probe error and Defrost probe error. RA, SA or defrost probe is above 50C. The warning is held by a 60 second timer after the conditions disappear. Enter Manual Function Test menu and test (operate) heating element. Check volts and amps to determine problem. Use DATA menu to evaluate evaporator section sensors. Evaporator section temperatures are high. Supply Air, Return Air and Defrost, indicates high temperature. Warning #0020 LOW VOLTAGE ON LINE UNIT STOPPED Low voltage observed, voltage has been below 330 VAC and has not risen above 340VAC yet. After 30 minutes this warning will set the low voltage alarm. Enter Manual Function Test menu and test (operate) components to load the power source. Check volts and amps to help determine the problem. Poor quality of power source. Warning #0021 CURRENT TOO HIGH CHECK COMPRESSOR AND FANS When the component current draw exceeds expected. 50% above expected for 4 minutes. Digital Control valve malfunction. Compressor, evaporator fans motor, condenser fan motor or heater current too high. Defective volt or amp meter on power module. Power supply voltage too low. Enter Manual Function Test menu and test (operate) each component. Check volts and amps to determine which component has high amp draw. Check power supply volts. Check volt and ampere meter. When the warning is set the current power consumption is logged in the event log.

Warning #0022 CURRENT TOO LOW CHECK COMPRESSOR AND FANS When the component current draw exceeds expected. 50% below expected for 4 minutes. Defective or open high pressure cutout switch. Defective or open motor internal high temperature protection switch. Unit on water-cooled condensing with no water flow. Defective condenser coil sensor or sensor location. Check Display for High Pressure Cutout message. Enter Manual Function Test menu and test (operate) each component. Check volts and amps to determine which component has low amp draw. Check volt and ampere meter. Warning #0023 SUPPLY TEMP TOO HIGH CHECK SENSORS During Chill or Frozen Mode: Supply air temperature is too high compared to return air temperature under operating conditions. The state will by time request defrost or/and probe test. Using DATA menu inspect readings. Enter Manual Function Test menu and operate evaporator fan at high speed to evaluate probe spread. Low refrigerant charge. Incorrect connection or location of supply or return air sensor. Air leakage at supply air sensor cable. Ice or frost on evaporator coil. Incorrect evaporator fan operation.

Warning #0024 SUPPLY TEMP TOO LOW CHECK EVAP COIL During Chill or Frozen Mode: Supply air temperature is too low compared to return air temperature under operating conditions. The state will by time request extended defrost, defrost or/and probe test. Using DATA menu inspect readings. Enter Manual Function Test menu and operate evaporator fan at high speed to evaluate probe spread. Incorrect connection or location of supply or return air sensor. Air leakage at supply air sensor cable. Incorrect evaporator fan operation. Warning #0025 EVAP TEMP TOO HIGH - CHECK EVAP SENSOR During Chill or Frozen Mode: Evaporator coil temperature is too high compared to return air temperature under operating conditions. Probe spread, misplaced probes. Using DATA menu inspect readings. Enter Manual Function Test menu and operate evaporator fan at high speed to evaluate probe spread. Warning #0026 EVAP TEMP TOO LOW - CHECK EVAP SENSOR During Chill or Frozen Mode: Evaporator coil temperature is too low compared to return air temperature under operating conditions. The state will by time request extended defrost, defrost or/and probe test. Using DATA menu inspect readings. Enter Manual Function Test menu and operate evaporator fan at high speed to evaluate probe spread. Ice on the evaporator coil, need for defrost. Probe error.

Warning #0027 SYSTEM LOW PRESSURE - CHECK REFR CHARGE - The warning is related to the capacity surveillance system which observes the reefer machine capability to create a temperature drop between return air and supply air when expected to be running at high capacity. Check Refrigerant level. Check for refrigerant flow through the system, look for restrictions. Action: - If the expected delta temperature is not reached the warning are set and the evaporator fans stopped to prevent heating the cargo. Lack of refrigerant. Warning #0028 FROZEN SET POINT - CHECK AIR EXCHANGE If AVL door is open in frozen set point mode. Check air ventilation door position Air ventilation ought to be in position closed when running within frozen mode.

Warning #0030 HIGH PRESS CUT OUT - PLEASE WAIT Unit stop due to high pressure cutout signal from the HPCO switch. The warning will go away when the input signal indicates normal condition. Poor or missing cooling of the refrigerant. Action The state will stop / remove the compressor run signal. The state will overrule regulation of the condenser fan and starts the fan. This state will activate and hold warning #31 as long as the input signal indicates HPCO. Controller clears message on compressor start-up. No direct alarm action based on this situation. If the state continues: Checkup for airflow through the condenser coil, air flow might be blocked. Checkup for condenser fan rotation and direction, must such air through the coil and blow air out through the grill. Warning #0031 HPCO TIMER HOLD - PLEASE WAIT The warning is a timer based warning to protect the compressor from starting at high pressure. The warning will go away when the holding time after HPCO gets normal has run out. HPCO present or has just been present. Action The state will stop / remove the compressor run signal. The state will overrule regulation of the condenser fan and starts the fan. This state will activate and hold warning #31 as long as the input signal indicates HPCO. Controller clears message on compressor start-up. No direct alarm action based on this situation. If the state continues: Checkup for airflow through the condenser coil, air flow might be blocked. Checkup for condenser fan rotation and direction, must such air through the coil and blow air out through the grill.

Warning #0032 LOW PRESS CUT OUT - PLEASE WAIT Unit stops due to low pressure cutout signal from the HPCO switch or the suction pressure reading (if present). If suction pressure sensor is mounted the signal level for LPCO is below -0,27BarR to activate LPCO state and above +0.38BarR to clear the state. The warning will go away when the input signal indicates normal condition. Controller activates Alarm Code 31 after 5 minutes. Controller clears message after compressor start-up. Possible causes include low refrigerant charge, defective low pressure cutout switch or open circuit, block TXV or suction line restriction etc. Action The state will stop / remove the compressor run signal. This state will activate and hold warning #33 as long as the input signal indicates LPCO. Warning #0033 LPCO TIMER HOLD - PLEASE WAIT The warning is a timer based warning to protect the compressor from starting before the pressure has risen from low pressure. The warning will go away when the holding time after LPCO gets normal has run out. Controller clears message on compressor start-up. No direct alarm action based on this situation. LPCO present or has just been present.

Warning #0034 COMP TOO HIGH TEMP TIMER - PLEASE WAIT If the compressor temperature gets above 148C, the warning is set. The warning will go away when the compressor temperature has been below 137C for 60 seconds. The warning will (also) go away when the compressor temperature gets below 132C. The warning clears itself when the compressor temperature gets normal. Compressor stops because discharge temperature is above 148 C (300 F). Message remains in display until discharge temperature decreases to normal. Action The state will stop / remove the compressor run signal. The state will overrule regulation of the condenser fan and starts the fan. Warning #0035 COMPRESSOR HIGH TEMPERATURE If the compressor temperature gets above 138C, the warning is set. The warning will go away when the compressor temperature gets below 132C. The warning clears itself when the compressor temperature gets normal. Action: Compressor running at high discharge temperature results in economizer/vapor injection will be active until discharge temperature decreases to normal. In temperature log the state will be represented by the char c (small c)

Warning #0036 AVL OPEN - CHECK FAE AND CA SETTINGS If configuration is AVL, the setting is below 125CMH and the AVL sensor indicates full open / dismounted door, the warning is set. Check air exchange position vs. setting. Wrongly dismounted air ventilation door. Warning #0037 CO2 READING STUCK FOR >24HOURS With AFAM+ option the Co2 level is constantly monitored. If the reading does not change / fluctuates minimum 0.1% within 24 hour the warning is set. The warning will clear itself 10 minutes after a change has been observed. Check gas analyzer readings. Problems with the gas analyzer. Action: When the warning is set the event Gas reading surveillance - Co2 reading stuck for 24H at: x.x% is made in the event log. Warning #0038 HIGH VOLTAGE ON LINE - High voltage observed, voltage has been above 515 VAC. The Warning will clear when voltage gets below 500 VAC. Action: - When the warning is set a power line value log is made in the event log. Ie: CURR: 0.2A PH1: 0.2A PH2: 0.2A PH3: 0.3A VOLT: 529V FREQ: 63Hz Enter Manual Function Test menu and test (operate) components to load the power source. Check volts and amps to help determine the problem. Possible cause for the problem is a wild running generator set.

Warning #0039 BATTERY CHARGER/HEATER CHECK BATTERY The data logger battery charger reports battery charging suspended due to low temperature and the battery internal heater has been on for 2 hours the warning is set. Check for battery position, placement and wiring. Fault in the data logger battery circuit. Warning #0040 12V SENSOR PSU PROBLEM If the sensor supply ( + 12VDC ) for the humidity or pressure transducers is not able of supplying the 12VDC. Check humidity sensor or transducer Too high load on the sensor supply.