Water Source Heat Pumps Field Installed Loop Pump Module

Similar documents
Oil and Coolant Circulating Heating System. Model - OCSM

INSTALLATION INSTRUCTIONS GEO-BOOSTER TM

MAC-120HE-01 Air-Cooled Chiller

Ceiling Mount Air Handler Manual

CTV-1500 Cooling Tower Vacuum Operating & Maintenance Manual

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)

Select Radiators Installation Guide

Packaged Terminal Air Conditioner Wall Sleeve Installation

Model 1210C Battery Powered Pump Shown. Description

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

Rental Services Temporary Cooling - Flexible Water Hose

INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)

! WARNING. Before using product, read and understand instructions.

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)

Miami Heat Pump HP Series Installation Guide

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

FAIRBANKS NIJHUIS FIRE PUMPS.


Standard Hydraulic Piping Flushing Procedure

SunMaxx Solar Filling Station Operating Instructions

INSTRUCTION MANUAL IM042. Slide Rail Systems - Series A10 INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Wilo SP Series Submersible Sump Pumps ECS. ECS ECS ECS Installation and operating instructions

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

Installation and Commissioning Manual Solar Stations FlowCon Max Evolution II

Modulex. Gas Fired Boiler Systems PIPING GUIDE GF-115-P. Modular, Condensing, Hot Water Boilers Models: 303, 454, 606, 757, 909, Instruction No.

Commercial Semi-Instantaneous Water Heaters

Operation & Maintenance Manual

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008

KESSEL KTP 500 Submersible Pump with lateral and vertical outlet connection Order Numbers 28710, 28810, 28850

Float and Thermostatic Traps Series H, C and X

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

IMPORTANT SAFETY NOTICE

Statement of Work. 3.0 Details of Service Pre Start-up Cooling Start-up Service. Installation Service. Table of Contents. 1.0 Executive Summary

BRAZED PLATE INSTALLATION MANUAL

ELECTRIC/DIESEL FIRE PUMP CHECK LIST

AE R6 December Digital Capacity Control for Copeland Scroll Refrigeration Compressors AE R6

Cooling system components, removing and installing

Operators manual Basic water heater

V47 Series Temperature Actuated Modulating Water Valves

Air Eliminators and Combination Air Eliminators Strainers

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060

ENGINE COOLING SYSTEM

CARING FOR YOUR WATER HEATER

REV. REL 1302 WEST BEARDSLEY AVENUE P.O. BOX 1127 ELKHART IN (574) FAX (574) ELKHART BRASS MFG. CO., INC.

ICE AIR. Console Water Source Heat Pump (WSHP) OPERATING & MAINTENANCE MANUAL. Wo r l d C l a s s C o m f o r t.

M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

Test Code: 8297 / Version 1

Your safety and the safety of others are very important.

OWNER S MANUAL FORCE 10 MARINE COMPANY HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) FAX: (604)

Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE

Mini-HYDRO TM Installation Manual

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF (10/2011) LF24 Standard

LOBOY 16 AIR CONDITIONERS

INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL EEMAX ELECTRIC TANKLESS WATER HEATERS IMPORTANT SAFETY INFORMATION

Pre-Fab Easy Installation For Models: 006-CT-USK, 008-CT-USK Installation and Operating Instructions for Existing Homes with Standard Piping

TECHNICAL BROCHURE B5-33GB 5GB, 7GB, 10GB, 18GB, 25GB, 33GB HIGH PRESSURE MULTI-STAGE BOOSTER PUMP

ECOCIAT. Domestic hot water heat recovery unit

HYDROSTATIC TEST PUMPS

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

Single Phase Soft Starter

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS

TABLE OF CONTENTS. SECTION 1 General Information: Pg 2 Description of Operation

FTQ. Daikin Inverter Ducted Heat Pump

MODEL G300 BRAKE BLEEDER

PRESSURE REDUCING CONTROL VALVE

BOWL ASSEMBLY SELECTION Select impeller in exactly the same manner as for lineshaft type pump. Note comments under WELL SIZE.

In-Line Air Separators

Seaward Products OWNER S MANUAL WATER HEATERS. Serial Number:

INSTRUCTION MANUAL A REVISION A. Series E1 and E3 Instant Hot Water Recirculating Systems

123 Industrial Loop Road Paynesville, MN Phone: MASTER MANUFACTURING MASTER GARDNER

Customized Assessment Blueprint

DESIGN STANDARDS SECTION

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N

Engineering Specifications

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Installation Manual DIAPHRAGM WELL TANK

Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters.

OASIS-PLUS 120V READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE

Steam System Best Practices Condensate System Piping

300 Series PA Pump and Cooler Assemblies

MACBlower Model Number: MAC40R MAC60R MAC80R MAC100R. MAC120R MAC150R MAC 200R Serial #

Zenith Solar thermal 4.5m pump station Installation manual

Model 800 Residential Steam Humidifier Owner s Manual. Includes Safety & Operating Instructions and Warranty Information

How To Use A Water Source Heat Pump

WALLACE MAXIPUMP 3000, 5000, 6000 and HYDROJET 30P, 30C AND HJ400 INSTALLATION AND MAINTENANCE INSTRUCTIONS

MODEL INSTALLATION INSTRUCTIONS

AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Use & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10)

SINGLE STAGE INLINE FIRE PUMP

VXT. Open Cooling Towers. Open Cooling Towers. Product Detail VXT - B 1. Engineering Data... B2. Structural Support... B6

MUELLER FALLING FILM CHILLERS

SELECTION, APPLICATION AND MAINTENANCE

Transcription:

Installation & Maintenance Data IM 1189 Group: WSHP Part Number: 910144616 Date: October 2013 Water Source Heat Pumps Field Installed Loop Pump Module Single pump module Dual pump module Contents Receiving & Safety...1 Inspection...1 Safety...1 Introduction...2 Loop Circulating Pump Modules...2 Loop Pump Module(s) Hose Kit Parts List...2 Application...2 Installation...3 Mounting The Module...3 Piping The Module...3 Wiring The Module...3 ing And Filling The System...3 Pressurizing The System...4 System Start-Up...5 Maintenance...5 Receiving & Safety Inspection Upon delivery, inspect shipment for visible damage and document on the shipping papers. Remove the module from the carton and inspect for damage. If the module shows signs of transit damage, file a claim with carrier promptly. Safety Prior to installing or servicing this loop pump module, please carefully read all instructions in this manual. Ensure that all installations are in complete accordance with applicable state and local codes. Owner should retain this manual after installation is complete. WARNING The installer must determine and follow all applicable codes and regulations. This equipment presents hazards of electricity, and sharp edges. Failure to read and follow these instructions can result in property damage, severe personal injury or death. This equipment must be installed by experienced, trained personnel only. CAUTION To prevent electrical shock, disconnect electric power to system at main fuse or circuit breaker box until installation is complete. 2013 Daikin Applied www.daikinap.com (800) 432-1342

Introduction Loop Circulating Pump Modules Single pump module Dual pump module Features Fully insulated cabinet eliminates condensation No assembly required All pump modules are leak tested Full flow 1-1/8" brass valves Standard 1" NPT connections Compatible with all industry components Functions smoothly and quietly Easy access to valves and circulators for ease of service 14-3/4" 13-1/4" 7" unit size makes for a compact unit Five year parts & labor warranty Loop Pump Modules Specifications: Single Pump Geothermal Loop Modules Module Dimensions:...14 ¾" 13 ¼" 7⅛" All Circulators...1 Phase 60 Hz Cast Iron 230 VAC Load:...Low 0.6A /Med 0.8A /High 1.2A Bronze 230 VAC Load:...Low 0.6A /Med 0.8A /High 1.2A Approved Liquid Solutions: Methanol, Exoendosol, Propylene Glycol Additional Information: Minimum Valve Bore:... 1-1/8" External Piping Connections...1" NPT Maximum Operating Pressure:...150 PSI Minimum Operating Temperature:...0 F Maximum Operating Temperature:...225 F Weight:...34 lbs. Dual Pump Geothermal Loop Modules Module Dimensions:... 14¾" 13¼" 7⅛" All Circulators... 1 Phase 60 Hz Cast Iron 230 VAC...(2 pumps) Load:....Low 1.2A /Med 1.6A / High 2.4A Bronze 230 VAC...(2 pumps) Load:... Low 1.2A /Med 1.6A /High 2.4A Approved Liquid Solutions: Methanol, Exoendosol, Propylene Glycol Additional Information: Minimum Valve Bore:...1-1/8" External Piping Connections... 1" NPT Maximum Operating Pressure:... 150 PSI Minimum Operating Temperature:... 0 F Maximum Operating Temperature:... 225 F Weight:... 44 lbs. *Loop Pump Module(s) Hose Kit Parts List 12 feet of 1" ID Reinforced Flexible Hose (1) Tapped Brass Heat Pump Adaptors (2) Brass Module Adaptors (2) Stainless Steel Hose Clamps (4) Pressure-Temperature Plugs Permit pressure drop and temperature measurements (2) * Hose kit not included with Loop Pump Module Application The circulator pumps in a geothermal loop circulate the liquid through a geothermal heat pump and the earth loop. This results in the transfer of heat. The loop pump modules are designed to satisfy the fluid circulation requirements for most residential and light commercial closed-loop geothermal heating and cooling systems. Consult your Daikin Sales Representative to determine which Loop Pump Module is required for a particular installation. Page 2 of 6 Loop Pump Module for Water Source Heat Pumps Catalog 1189

Installation Mounting The Module Using the mounting holes provided, mount the module to a vertical surface as close to the heat pump as possible. The module can be mounted with the flow paths either vertical or horizontal. Figure 1: Pump Module Mounting Options Motor electrical always located at top Pump Module as provided from the factory Pump Module rotated 180º Piping The Module Note: 1. The following instructions illustrate the pump module mounted in the 180 degree rotated position. 2. Always pipe the module so that the circulator(s) is (are) located between the module valves and the heat pump, never on the earth loop side of the valves. ing the earth loop through the circulator(s) could introduce unwanted debris into the pump. Piping connections from the module to the heat pump are best made with a hose kit. Be sure to insulate the flexible hose where water condensation could be a problem. Standard 1" NPT external water connections are provided to make connections with the earth loop piping. Follow the recommendations of the earth loop pipe manufacturer or IGSPHA (International Ground Source Heat Pump Association) when making these transition connections. Again, insulate the earth loop pipe indoors where water condensation could be a problem. See Figure 2. Figure 2: Typical Ground Loop (Reverse Return) Application Water In from Loop Field Water Out to Loop Field Wiring The Module Single pump or dual pump modules are available with 230VAC single phase circulator pump(s). Always check the circulator nameplate to confirm the correct voltage. Never make an assumption. Wire the module according to the instructions in IM 1186. Follow all applicable electrical codes. Generally, the module should operate whenever the heat pump compressor operates. ing And Filling The System Step 1 Use water and a high-volume, high head circulator pump to flush all air and debris and fill earth loop system. Do not introduce antifreeze into the system until both the ground loop and the unit have been purged of air. Refer to recommendations provided by IGSPHA when choosing a pump for the flushing process 1. The pump must be capable of providing a water flow velocity of at least two feet per second. It is recommended that pump suction should be from the bottom of a large volume container. Use a suction line strainer to prevent debris discharged into the container from being recycled to the system. 1 http://www.igshpa.okstate.edu/pdf_files/publications/igshpa2011standardssec.pdf Page 3 of 6 Loop Pump Module for Water Source Heat Pumps Catalog 1189

Installation Step 2 Pump water into the system by connecting the pump discharge hose to one (not both) of the 1" NPT water connections located on the front of the module. Connect a return hose to the opposite side of the the module to discharge debris, air and water as the loop is flushed. Check for air leaving the system by placing the return hose below the container water level (Figure 3). Figure 3: ing The Loop Module Valves Step 5 the heat pump. To do so, simply rotate valves as shown below while pump is running. the heat pump using the same procedure as used to flush the earth loop. Figure 5: Step 5 Valves Positions To To Heat Pump From Heat Pump From Pump Pressurizing The System Step 6 After flushing and filling the system, rotate the module valve discharging into the flush container as shown below, right. Figure 6: Step 6 Valves Positions Pump To Heat Pump From Heat Pump Step 3 Rotate the module valves as shown below: Figure 4: Rotate Valves as Shown To From Pump To From Pump From Earth Loop To Earth Loop From Earth Loop To Earth Loop Step 4 Start the pump. Add anti-freeze and water to the container as needed so that no air enters the system (at first only air will come out of return hose, then air mixed with water, and finally nothing but water). If flushing pump assembly is equipped with valves to reverse flow direction through earth loop during flushing, do so occasionally to help remove trapped air. When air bubbles cease in the return hose container, the earth loop has been completely flushed. System pressure should increase rapidly as the flush pump works to force more water into the system. Flow into the container should cease. Additional purging is necessary if the water level in the container falls. This is evidence of air in the system that is being compressed. If purging has been successful, rotate the other module valve as illustrated in Figure 7. Figure 7: To Heat Pump From Heat Pump WARNING Do NOT use calcium as anti-freeze. This causes corrosion and voids pump warranty if used. Follow recommendations of IG- SPHA for the appropriate type and amount of anti-freeze. From Earth Loop To Earth Loop Page 4 of 6 Loop Pump Module for Water Source Heat Pumps Catalog 1189

System Start-Up Step 7 Turn off the flush pump. System should maintain pressure. Release excess pressure by rotating either module valve to allow a small amount of water to pass through and out of the system and into the container. Some initial loss of pressure can be expected and is due to the expansion of the earth loop pipe under pressure. This pressure will stabilize if the system has no leaks. Note: System operating pressures are 10 to 40 PSI. Protect circulators by maintaining positive pressure at all times. Step 8 If your module has a cabinet, put the module cover back in place. Step 9 ing, filling and pressurizing should be complete. Now, start the loop pump module circulators. Step 10 If for some reason the circulators are not operating, power off and diagnose the problem. Step 11 Using a single water pressure gauge, measure the pressure drop at the pressure/temperature plugs across the heat pump heat exchanger. Compare this measurement with the flow versus pressure drop data shown in Figure 3 on page 4 of IM 1160, to determine the actual flow rate. If the flow rate is low, recheck the selection of the loop pump module model for sufficient capacity. If the module selection is correct, there is likely trapped air or a restriction in the flow circuit. Figure 8: Single pump performance curve Total Head - feet 35 30 25 20 15 10 5 0 0 5 10 15 20 25 30 35 Flow - gpm Figure 9: Dual pump performance curve Total Head - feet 70 60 50 40 Speed 1 Speed 2 Speed 3 30 20 10 0 0 5 10 15 20 25 30 35 Flow - gpm Speed 1 Speed 2 Speed 3 Maintenance Loop pump modules do not require routine maintenance. Page 5 of 6 Loop Pump Module for Water Source Heat Pumps Catalog 1189

Daikin Training and Development Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high priority. For training information on all Daikin HVAC products, please visit us at www.daikinap.com and click on training, or call 540-248-9646 and ask for the Training Department. Warranty All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local Daikin Representative for warranty details. Refer to Form 933-430285Y. To find your local Daikin Representative, go to www.daikinap.com. Aftermarket Services To find your local parts office, visit www.daikinap.com or call 800-37PARTS (800-377-2787). To find your local service office, visit www.daikinapcom or call 800-432-1342. This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.daikinap.com. Products manufactured in an ISO Certified Facility. 2013 Daikin Applied www.daikinap.com (800) 432 1342 IM 1189 / Page 6 of 6 (10/13)