Domestic hot water consumption in apartment buildings

Similar documents
Energy Flexible Buildings proposal for new EBC Annex

Solar Combisystems Changes on the market place since Task beginning

HSQ. Heuston South Quarter Community Heating System User Guide

FIELD TESTS OF FUEL EFFICIENCY MAGNETS J A CRABB JULY 1997 SWEEG REPORT 80

WC flushing cistern single or dual flush to fill in 2 minutes WC trough cistern 0.15 per WC Wash basin tap size 1 2

Measurement of Domestic Hot Water Consumption in Dwellings

Field test of a novel combined solar thermal and heat pump system with an ice store

SOLAR HEATING SYSTEMS.

EXPERIMENTAL STUDY OF A DOMESTIC HOT WATER STORAGE TANK THERMAL BEHAVIOUR

HEAT INTERFACE UNITS (Modular)

Water Volume Calculation in Hydronic Heating & Cooling Systems

Trimming of a ground-source heat-pump system in Saltsjöbaden

ROTEX gas hybrid heat pump. A strong team.

Theta Dual service BFC, SGE, SGS for 20/30/40 kw heating capacity

Daikin Altherma hybrid heat pump. The natural combination

Circulator Fan Performance Testing Standards BY CHRISTIAN TABER, BEMP, HBDP, MEMBER ASHRAE

UV Disinfection Systems A Series. Main Applications: Drinking Water, Process Water, Warm Water / Legionellae. IT T Industries Engineered for life

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2014/07) en

Gas Condensing Boilers

Dienstleistung. Certification as "Quality Approved Passive House" Criteria for Residential-Use Passive Houses

The natural ombination

Tankless Water Heater A Primer for Contractors, Installers, Builders and Homeowners

Hybrid heat pumps. saving energy and reducing carbon emissions

Chelsea s energy saving campaign

High-efficient gas boiler CompactGas

FLUXUS Energy. Manage energy effectively using non-invasive measuring technology. Heat usage, chilled flows and compressed air flow rate

Design of heat exchangers

Range Tribune HE Solar Unvented Direct and Indirect Cylinders

Energy Audits. Good energy management begins with an energy audit

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

Building Performance Optimization Services in the city of Boras, Sweden.

COUNCIL DIRECTIVE 92/42/EEC of 21 May 1992 on efficiency requirements for new hot-water boilers fired with liquid or gaseous fuels

The natural ombination


ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user

30% Safe. DESIGN GUIDE The Danfoss EvoFlat system from A-Z Take lead on your project with an efficient system concept. evoflat.danfoss.

RULES FOR THE SETTING UP OF SUSTAINABLE BRANCHES Summary

Passiv Haus Institut. Certification as "Quality Approved Passive House" Criteria for Residential-Use Passive Houses

CHAPTER 2 HYDRAULICS OF SEWERS

Element D Services Plumbing

Continuous flow direct water heating for potable hot water

WATER STORAGE, TRANSPORT, AND DISTRIBUTION Multi-Dam Systems and their Operation - J.J. Cassidy MULTI-DAM SYSTEMS AND THEIR OPERATION

ITE. Indirect calorifier ITE - 400/500/600/750/1000. Installation, User and Service Manual. Innovation has a name.

Rehabilitation Mas Thibert / Arles

Thermal Mass Availability for Cooling Data Centers during Power Shutdown

Daikin Altherma Hybrid Heat Pump

The natural ombination

PRO-CLEAN. Technical Description. Specifications. Space-saving design with minimum heat loss (melamine resin insulation)

Installation and Operation Instructions Domestic hot water modules: FriwaMidi DN 20 FriwaMaxi DN 25

Stove-boiler for solid fuels KW Directions for use and assembling

Exploitation Tests of Borehole Heat Exchangers in the Laboratory of Renewable Energy Sources in Miekinia Poland

Home comfort: water heating

Saving Heating Costs In Warehouses

ErP made easy! Valves, controls + systems. Guideline Individual packages according to ErP with high energy efficiency and a good benefit/cost ratio

Daikin Altherma. hybrid heat pump. The natural combination

LABELLING OF GAS BOILERS - AN EFFICIENT MARKET REGULATOR

SENSITIVITY STUDY FOR ARCHITECTURAL DESIGN STRATEGIES OF OFFICE BUILDINGS IN CENTRAL CHILE: EFFECTIVENESS OF NOCTURNAL VENTILATION.

Three-years operation experience of a ground source heat pump system in Northern Greece

A NEW CONCEPT OF A HYBRID STORAGE SYSTEM FOR SEASONAL THERMAL ENERGY STORAGE IN SOLAR DISTRICT HEATING

Congratulations! Your unique solar monitor ID is located on your monitoring unit as seen on this page.

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY

Overview of Baseboard Heating

HEATING OF DOMESTIC OUTDOOR SWIMMING POOLS

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

Origin s. We ll manage the bulk of your hot water

1 DESCRIPTION OF THE APPLIANCE

Operation manual. Daikin Altherma hybrid heat pump EHYHBH05AA EHYHBH08AA EHYHBX08AA. Operation manual Daikin Altherma hybrid heat pump.

Experimental Evaluation Of The Frost Formation

your water pressure explained

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER

City of Cornwall Social Housing Division Top 10 Energy & Water Saving Tips. in Multi-Unit Residential Buildings

Instructions for designing heating systems.

Session 2: Hot Water Supply

ASPE Seminar Water Heater Piping Strategies. Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International

Seeing by Degrees: Programming Visualization From Sensor Networks

Determination of Thermal Conductivity of Coarse and Fine Sand Soils

ALFEA HYBRID DUO GAZ. New Model 2011

HEAT RECOVERY FROM CHILLED WATER SYSTEMS. Applications for Heat Reclaim Chillers

ACOME. Complete systems for: radiant floor heating/cooling/plumbing.

PELLEXIA COMFORT ENVIRONMENT COMPATIBLE

ELECTRIC INSTANTANEOUS WATER HEATER

Get more from your hot water

Daikin Altherma Hybrid Heat Pump

IMPROVING CALCULATIONS OF BUILDING ENERGY CONSUMPTION BASED ON TEN YEAR MEASURED DATA

CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND?

Case Studies: Infrared Heating in Industrial Applications

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS

Operating instructions

Daikin Altherma Hybrid Heat Pump

Hot water supply, distribution and use

Deliverable A Design guidelines for Solar Cooling of buildings

Drives and motors. A guide to using variable-speed drives and motors in car parks

Laundry Hot Water Systems

REGISTRATION EXAMINATION, JUNE 2009 PLUMBING QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

Natural geothermal energy.

An Assessment of Prices of Natural Gas Futures Contracts As A Predictor of Realized Spot Prices at the Henry Hub

Rainwater Harvesting

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

PERFORMANCE EVALUATION OF WATER-FLOW WINDOW GLAZING

LG Electronics AE Company, Commercial Air Conditioning

Transcription:

Domestic hot water consumption in apartment buildings O. Gerin (1), B. Bleys (2), K. De Cuyper (3), (1) olivier.gerin@bbri.be (2) bart.bleys@bbri.be (3) karel.de.cuyper@bbri.be (1), (2), (3) Belgian Building Research Institute, Belgium Abstract Domestic hot water consumption has been measured in 12 apartment buildings of different sizes (11 to 378 apartments) in Belgium. Each building was monitored for a period of 1 or 2 months with a measurement interval of 1 second. Peak flow rates were deduced from these data for each building. The measured peak flow rates were converted to reference conditions in order to obtain flow rates which can be compared and be used for dimensioning purposes. In this article, a new conversion method is suggested and the different steps are discussed. These standardised peak flow rates are then compared to the peak flows as calculated in accordance with existing guidelines in order to determine the relevance of these guidelines for Belgium. DIN 1988-300:2012 [1] was found to be most appropriate. Keywords water consumption, peak flow rate, domestic hot water, domestic cold water, pipe sizing. 1 Introduction As the energy-use for space heating continues to diminish in the European Union, due to better performances of the building envelope and the use of high performance heating appliances, the energy use for hot water production becomes increasingly relevant. Since the recast of the Energy Performance of Buildings Directive [4] stipulates that by 2020 all new buildings in the European Union should be almost near zero energy buildings, reducing the energy use for hot water production, whilst maintaining the desired comfort level for the buildings occupants, will become one of the challenges for the future. Therefore it becomes ever more important to design hot water production and distribution installations inside our buildings -of which apartment buildings are an important part- in a more efficient way. Also an optimal design of the drinking water system (hot and cold) is an even more important necessity in order to guarantee the hygienic quality of the water at the taps: avoiding

Legionella-problems means, between others, no stagnation of the water in oversized hot water vessels and avoiding too low velocities due to the oversized pipes. This concern requires also a better knowledge of the water consumption in our buildings. Given the fact that Belgium has no national standard, complementing the simplified pipe sizing method of NBN EN 806-3:20016 [5], foreign methods are since long commonly used. As these methods were in general issued already many years ago -the most commonly used methods for sizing hot water distribution systems rely on methods based on consumption data of the seventies of the past century [6], [7]-, while as well the equipment level, the sanitary comfort as the technology greatly evolved since then, it is evident that there is an urgent need to get actual and reliable data on water consumption in buildings. This need was also recognized in other countries, which led them to review already their guidelines, leading -in general- to smaller peak flows and thus smaller pipe sizes, eg: Germany in 2012 [1] and The Netherlands in 2013 [8]. In previous articles we have described the first results of our domestic hot water (DHW) and domestic cold water (DWC) measurement campaigns [2] and we reported, last year in Brazil, on the fact that the hot water consumption depends significantly on the season, mainly due the seasonal variation the cold water temperature, as a result of our the latitude (about 50 N). This seasonal variation was shown to affect as well the mean daily DHW consumption as the peak flow [3]. In this paper, we will discuss the latest results of our measurement campaign on the DHW peak flow. First we propose a method for the conversion of the measured data ( raw data ) into reference peak flow, ie. the corresponding peak flow at 60 C, given a cold water temperature of 10 C, called DHW6010 peak flow. It is this reference value which normally is used for the sizing of the supply pipes. Besides taking into account a conversion for correcting the measurements with temperatures differing from 60 C (hot) and 10 C (cold), correction is also made for the above mentioned seasonal variation. But a correction is also made for the fact that the temperature measured at the outlet of the heating device, is not in the mean- the temperature of the hot water just before the taps. We also discuss some of the limitations of our conversion method and hypothesis and hope hereby to contribute to a better understanding of our measurements for other research teams and maybe open a debate to deduce a uniform method, since it seems probable to us that other teams would be confronted with some of the same challenges. 2 The BBRI measurement campaign Since 2011 domestic hot water consumption was measured in 12 apartment buildings of different sizes (7 to 378 apartments) with centralised hot water production. Each building was monitored for a period of about 1 to 2 months. For the measure of the water consumption, ultrasonic flow meters were used, measuring the flow rate of the water qdwh at the entrance of the heating appliance. Since these meters have sensors which are fixed on the pipes outer wall, no modification of the installation in the building was needed [2]. The cold (Tc) and hot water temperatures were measured as well, using thermocouples. For DHW systems with a circulation system, both departure (Tdepart) and return temperatures (Treturn) were measured at the level of the heating appliance. The data

were stored on a data logger with a measurement interval of one second. All measurements points are located in the central boiler room as shown in figure 1. Figure 1 Identification of measuring points in the boiler room Table 1 gives for the different buildings the total number of apartments, as well as the length of the measurement period and the average hot (T DHW) and cold (T DCW) water temperatures. Table 1 Measured apartment buildings and characteristics Measuring average Number of period T DHW apartments (days) ( C) Building number average T DCW ( C) 1 11 30 45 17 2 36 22 70 18 3 57 32 55 20 4 62 58 65 20 5 93 86 52 14 6 96 81 50 13 7 113 58 53 16 8 124 78 68 13 9 277 70 50 11 10 312 64 52 12 11 320 64 57 17 12 378 36 49 13 Table 1 shows a rather large variation in both average DHW and DCW temperatures, which confirms the need of a data conversion to reference conditions in order to be able to compare the results for different buildings.

3 Results 3.1 Measurement data Table 2 gives the measured DHW peak flow rates, the peak flow converted to standardized DHW6010 peak flow rates standardized for DHW at 60 C for DCW at 10 C [3] and the reference DHW6010 peak flow rates, in which further data conversions are integrated. We would suggest using these latter values for dimensioning purposes. Building number Table 2 Measured and converted DHW peak flow rates Raw DHW peak flow rate (1s) (L/min) DHW 6010 peak flow rate (2 s) (L/min) "Reference" DHW 6010 peak flow rate (L/min) 1 28,2 31,2 34,4 2 42,4 47,4 54,5 3 36,7 45,2 54,8 4 69,7 60,7 73,5 5 80,5 74,4 80,8 6 82,2 79,0 90,8 7 60,5 58,3 82,2 8 77,6 86,1 118,0 9 134,7 110,9 116,4 10 143,0 66,6 72,3 11 196,0 136,8 148,4 12 100,2 84,2 84,2 The different steps of our conversion method are discussed in paragraph 3.2. 3.2 Conversion method The conversion method we applied to the measurement data contains different steps. 1) Step 1: visual check of the measured data (flow rates and temperatures) through daily graphs. In case of potentially abnormal data, and if the technical reason can be discovered (for instance: refilling of space heating circuit, maintenance intervention on DHW system, leakages, etc.), the data for day where the abnormal event occurred are supressed. 2) Step 2: conversion to standardized DHW6010 peak flow rates A frequently used formula of conversion into standardized DHW6010 is given in equation 1: (T DHW 10) q DHW 6010 = q DHW (eq. 1) (60 10)

In this equation, the actual cold water temperature is totally ignored. However, if cold water temperature is 25 C, the hot water flow will be less than the flow in the same building if the cold water is around 10 C. Each building facility had his own DHW production temperature and his own cold water temperature. The conversion of their DHW flows into standardized DHW6010 flows should therefore take into account both the measured cold and hot water temperatures. This formula also ignores the fact that the temperature measured at the outlet of the heating appliance, decreases in the installation due to the heat losses of the pipes, so that a tap near the heating appliance will have a lower consumption, than an the same tap with an identical use, at the end of the piping system. The measured DHW flows were therefore converted into standardized DHW6010 flows according the equation (2): qq DDDDDD 6010 = qq DDDDDD (TT DDDDDD TTTT) (TTTT 10) (TTTT TTTT) (60 10) (eq. 2) Where: q DHW6010: the standardized flow of DHW6010 (l/min) q DHW : the measured flow of the domestic hot water (l/min). T DWH: the average temperature of the hot water at the taps -see remark below- ( C) Tc: the average temperature of the cold water at the taps -see remark below- ( C) Tu: the mean temperature of the mixed water at the taps -see also remark below ( C). Remarks: Due to the practical difficulty of measuring the flows and the temperature of both cold and hot water at each tap in larger apartment buildings, the following assumptions and evaluations were made, with respect to the following parameters of the above formula - Tc: we assumed no warming up of the cold water while flowing through the pipes at moments of peak consumption. So the temperature value measured on the main domestic water pipe inlet, was used without correction. - Tu: For the average temperature of the mixed water at the taps a value of 38 C was considered. This value is more secure than 40 C when used in the formule (2), because Tc is often greater than 10 C. - T DWH : the average temperature of the domestic hot water at the taps was estimated from the measurements of DHW temperature departure and the return of the circulation system. This T DWH was estimated by using equation (3). TT dddddddddddd TT rrrrrrrrrrrr T DWH = TT dddddddddddd (eq. 3) 4 Where: T depart: the temperature of the domestic hot water at the outlet pipe of the hot water heat exchanger or the storage tank ( C) T return: the temperature of the domestic hot water at the inlet of the return pipe in the heat exchanger or storage tank 3) Step 3: averaging DHW6010 peak flow rates to 2 second time step - this step results in the DHW6010 peak flow rate (2s) in Table 2

4) Step 4: correction for the seasonal variation in DHW consumption, by applying the previously determined monthly correction factors [3] - this step results in the "Reference" DHW6010 peak flow rate in Table 2 3.3 Limitations and need of future improvements During our measuring campaign we have encountered several difficulties and limitations, linked to either the measuring method or the conversion method. With regard to the measuring method Because we only measured in the central boiler room, we needed to make assumptions concerning the average tap temperature, in order to be able to take into account the cold water temperature (eq. 2 and 3).. Also the pressure at the taps could influence the peak flow. This aspect wasn t covered in our measuring campaign. Furthermore, our ultrasonic flow meters were not compatible with certain types of multilayer pipes. With regard to the conversion method Short-term fluctuations in the DHW temperatures in the circulation system may have a significant impact on the standardized DHW6010 peak flow rates. We found it very useful to verify visually the impact of each data correction. Furthermore, if the temperature of the cold water rises above 38 C, the conversion equation (eq. 2) should not be used. Another important need for future improvement is to take into account the time lag due to the circulation of the hot water in the circulation system. The conversion would be more correct if based on T depart at time t, in combination with T return at time t + time lag. 3.4 Comparison with existing guidelines Figure 2 represents, for the building in the measuring campaign, the reference DHW peak flow rates compared to the calculated peak flow rates following the different guidelines.

Figure 2 Reference and calculated peak flow rate in apartment buildings of different sizes The calculated DHW peak flow rates according to the different guidelines are systematically higher than the reference DHW6010flow rate. The European standard (EN 806-3) even results in a peak flow rate which is 4 times the reference peak flow rate. Most existing guidelines overestimate the peak flow rate, especially EN 806-3 [5] and DTU 60.11 [7]. Calculations following DIN 1988-300 [1] are closest to the reference peak flow rates, followed by ISSO 55 [8]. The difference between calculated and reference peak flow rates becomes more important for larger buildings. 4 Conclusions Most existing guidelines over-estimate the DHW peak flow rate, especially in larger apartment buildings. Overestimations up to a factor of 4 and more are no exeption. DIN 1988-300:2012 was found to be most relevant for the Belgian situation. In most buildings this standard seems still to contain a (to?)high safety margin.

6 References 1. DIN 1988-300, Codes of practice for drinking water installations - Part 300: Pipe sizing; (DVGW code of practice), Deutsches Institut für Normung e. V., Berlin, 2012. 2. Bleys et al, Measurements of water consumption in apartment buildings, Proceedings of the 38th International Symposium CIB W062 on Water supply and drainage for buildings in Edinburgh, Scotland, 2012. 3. Gerin et al, Seasonal variation of hot and cold water consumption in apartment buildings, Proceedings of the 40th International Symposium CIB W062 on Water supply and drainage for buildings in Brazil, 2014. 4. DIRECTIVE 2010/31of the European Parliament and the Council of 19 May 2010 on the energy performance of buildings. 5. NBN EN 806-3, Specifications for installations inside buildings conveying water for human consumption. Pipe sizing. Simplified method,. European Committee for standardisation, Brussels, Belgium, 2006. 6. DIN 1988-3, Drinking water supply systems; pipe sizing (DVGW code of practice), Deutsches Institut für Normung e. V., Berlin, 1988. 7. DTU 60.11, Règles de calcul des installations de plomberie sanitaire et des installations d'évacuation des eaux pluviales, Commission Générale de Normalisation du Bâtiment/DTU, Paris, France, 1988. 8. Anonymous, Leidingwaterinstallaties in woon- en utiliteitsgebouwen, ISSO publicatie 55, Rotterdam, The Netherlands, 2013.