PV Ground-Fault Detector Interrupter (GFDI) Installation Instructions

Similar documents
FW-X240 AUTO TRANSFORMER Installation Manual

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

RAY-MAX Integrated Solar Power Strip

PV System Disconnect PV System Discon-

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

DC disconnects for solar photovoltaic installations. Connecting the. power of the sun

CITY OF LOS ANGELES CALIFORNIA

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

Connecting the Power of the Sun. DC Disconnects for Solar Photovoltaic Installations. DC disconnects for. solar photovoltaic installations

Troubleshooting Guide, Freedom and Fleet Power Inverter/Chargers

Cooling Fan Replacement September Rev A1 Page 1 of 6

Co-location Interconnect Power Panel (CIPP) Installation Guide

How To Plan Out An Array Of Solar Panels

HUB Communications Manager User s Manual

County of Riverside Building and Safety Department

City of Riverside Building & Safety Division Phone: (951)

LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems

Xantrex XW Hybrid Inverter/Charger

Advantium 2 Plus Alarm

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

Conext Grid Tie Solar Inverter Conext TX 2800 NA Conext TX 3300 NA Conext TX 3800 NA Conext TX 5000 NA

INSTALLATION INSTRUCTIONS

SPR-2800x SPR-3300x SPR-4000x SPR-5000x. Owner s Manual. SunPower Solar Inverter

SP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE

70-Series CAN Power Management System

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

Installation and Operation Guide for PD4000 Series Power Control Center

OWNER'S MANUAL. Model CUL AC Power Inverter/Charger System OM/A96283 REV. A

The power module is Feature Number 8800-F2-901.

Installation Guide of Sunrise Solartech PV Modules. Term Contents. Purpose of this guide. General. Safety precaution for installing a solar

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

How To Install A Sunny Boy

Reverse-feed applications for circuit breakers

Solar Inverter Sunny Boy 5000US, 6000US, 7000US

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

Doe Residence kw DC Roof Mounted Photovoltaic System

CONSERVER CES INSTRUCTIONS. CETTE NOTICE CONTIENT DES INSTRUCTIONS IMPORTANTES CONCERNANT LA SÉCURITÉ. Positive Connection Point Symbol

Solar Photovoltaic (PV) Systems

Owner s Manual. For Automatic Transfer Switch Amp, Service Entrance/Non-Service Entrance

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.

XPower Inverter Installation Guide. This guide for use by qualified installers only.

MidNite Solar E-Panels Explained

VLT Series 300 Watt True Sine Wave Inverter

TC Grounding and Bonding for Telecommunications Systems

HI400. Owner s Guide

Electrical Grounding. Appendix C

PREFACE. The products covered by this Guide are:

MCR1900 Media Converter 19-Slot Chassis

INSTALLATION & SERVICE MANUAL. Display Panel

XW-MPPT Owner s Manual. XW Solar Charge Controller

Parallel Redundant Uninterruptible Power Supply

PV-Inverter SunPower SPR-5000m / SPR-6000m / SPR-7000m / SPR-8000m

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

HMI display Installation Guide

MidNite Solar PV Combiners explained (MNPV)

AUTOMATIC BEST BATTERY SELECTOR INSTALLATION & OPERATION BBS-1600 BBS-1600E

Grounding & Bonding Why it is done And How to Install Properly

HP UPS R1500 Generation 3

PN PN This Inverter/Charger has been factory. programmed to the following settings: Battery Type = LIQUID LEAD ACID

Installation and Operation Guide PD4600 Series Converter Replacement

Application Bulletin NEC Reference Guide for SolarBridge-Enabled AC Module Installers

PHOTOVOLTAIC SYSTEM CONTROLLERS SUNSAVER MODELS INCLUDED IN THIS MANUAL SS-6 / SS-6L SS-10 / SS-10L SS-10-24V / SS-10L-24V SS-20L SS-20L-24V

Inverter / Charger Installation General Operations and AC and DC Connections

Installation Guide Content for P250xV-240 microinverters

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

Arc Fault Circuit Interrupters Frequently Asked Questions

SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide

WE-350 Series ¼ Turn Electric Actuator

Installation/Operator Manual For use with WFCO ULTRA III Power Center Model WF-8712P and WF-8725P

Installation instructions for Series NRX INCOM communications adapter module

PS4-24 OWNERS MANUAL 24 VAC 90 WATT WALL MOUNTED CCTV POWER SUPPLY

Top Commercial / Residential Electrical Requirements *

Freedom Owner's Manual. Xantrex Freedom 458 Series Inverter/Charger

Xantrex PRO Inverter XM 1000 and XM 1800

Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide

AEROMOTIVE Part # INSTALLATION INSTRUCTIONS

HM-W536 Install Guide

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual

XPower Inverter Owner s Guide

Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters

AMERBRITE UNDERWATER WHITE LED POOL LAMP

4KVA/5KVA Parallel Installation Guide

User Manual. Hybrid 1KW-5KW INVERTER / CHARGER. Version: 1.1

SP 4K/5K Efecto & SP 5K Brilliant Parallel Installation Guide 1. Introduction

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

Zebra RW 420 Mobile Battery Eliminator Kits

IQ SERIES. Industrial Quasi Sine Wave AC Power Inverter. Models IQ IQ IQC IQC IQC

Installation Instructions DTS-HAZ DTS-HAZ-DC. for Use with Self-Regulating & Constant Wattage Heating Cables

Installation Instructions

PV and the Electrical Code Page 1 PV and the Electrical Code

Comfort Control Relay Panel (CCRP)

Solar America Board for Codes and Standards

Mobile Data Power Model: MDP-25

PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS

Contractors Guide Central Inverter System Installation

Solar Panel Installations

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

BX7000 Multi-Access Gateway Getting Started Guide

Transcription:

PV Ground-Fault Detector Interrupter (GFDI) Installation Instructions

About OutBack Power Systems OutBack Power Systems is a leader in advanced energy conversion technology. Our products include true sine wave inverter/chargers, maximum power point charge controllers, system communication components, as well as breaker panels, breakers, accessories, and assembled systems. Notice of Copyright PV Ground-Fault Detector Interrupter Installation Instructions Copyright 2008 All rights reserved. Disclaimer UNLESS SPECIFICALLY AGREED TO IN WRITING, OUTBACK POWER SYSTEMS: (a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION. (b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE, WHETHER DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER S RISK. Date and Revision December 18, 2008 Contact Information OutBack Power Systems 19009 62nd Ave. NE Arlington, WA 98223 Phone (360) 435-6030 Fax (360) 435-6019 www.outbackpower.com 900-0015-01-00 REV A 1

IMPORTANT SAFETY INSTRUCTIONS KEEP THESE INSTRUCTIONS This product is intended to be installed as part of a permanently grounded electrical system as shown in the wiring diagrams. The following important restrictions apply unless superseded by local or national codes: Ground equipment is marked with this symbol: The GFDI is designed for indoor installation or installation inside a weatherproof enclosure. It must not be exposed to rain. Must use a UL approved crimp lug on the cable attached to the breaker stud. NOTE: Outback supplies a #2 AWG ring terminal with the GFDI and recommends a #2 AWG cable when the GFDI is connected to an 80 amp breaker. (#3 AWG is the minimum allowable in this application. See Standards and Requirements, page 3.) Introduction The OutBack Power Systems Ground Fault Detector Interrupter (GFDI) is a safety device for a photovoltaic (PV) array. In the event that the array becomes shorted to ground, it disconnects the PV system from the batteries. The GFDI meets mandatory UL 1741 low-level ground-fault protection requirements for roof-mounted photovoltaic energy systems to prevent fires. The GFDI meets the requirements of the 2008 NEC section 690.5 (A) through (C) to reduce fire hazards when wired according to the wiring diagram contained in these instructions. OutBack GFDI Products OBB-GFDI-80-150VDC-PNL (one 0.5 amp breaker ganged with one 80 amp breaker with common trip) OBB-GFDI-80D-150VDC-PNL (one 0.5 amp breaker ganged with two 80 amp breakers with common trip) OBB-GFDI-80Q-150VDC-PNL (one 0.5 amp breaker ganged with four 80 amp breakers with common trip) 2

FUNCTION The GFDI consists of a single 0.5 amp breaker, mechanically connected to a combination of 1, 2, or 4 standard OutBack 80 amp breakers (see list on previous page). When a ground fault occurs, the 0.5 amp breaker will trip. Due to the common internal tripping mechanism, all the other breakers connected to the GFDI will also trip and shut power down. All power production from PV array charge controllers ceases when the breakers trip and remove their connection to the batteries. Standards and Requirements Code Requirements All installations must comply with national and local electrical codes; professional installation is recommended. NEC requires ground fault protection for residential PV installations. For more information, see NEC 690.5. DC and Battery-Related Installation Requirements Shut off all DC breakers before connecting any wiring. All wiring must be copper and rated at 75 C or higher. Use a minimum cable size of #3 AWG* for 80 amp breakers and #14 AWG for 0.5 amp breakers (NEC table 310.16). Torque breaker nuts to 35 inch-pounds/4.0nm. For installations above 30 degrees C, follow the correction factors at the bottom of NEC table 310.16 using 100 amps as the baseline. In addition: The GFDI is only to be used with OutBack UL 1741 or UL 508A listed photovoltaic based products. The GFDI shall be the only bonding connection between grounding system and battery negative in the DC system. The GFDI is not intended for use in positive ground installations. *UL174116.1.3 states: A wiring terminal or lead shall be rated and sized for connection to a field wiring conductor having an ampacity, based on Table 310.16 of the NEC, of no less than 125 percent of the RMS or dc current that the circuit carries during rated conditions. 80 amps X 1.25 = 100 amps, which requires #3 AWG wire (in ambient conditions of no more than 30 degrees C). 3

LABELS AND WARNINGS The GFDI comes with a number of warning and identification labels preinstalled by OutBack. The following two labels are installed by the end user or the installer. WARNING! ELECTRIC SHOCK HAZARD IF A GROUND FAULT IS INDICATED, NORMALLY GROUNDED CONDUCTORS MAY BE UNGROUNDED AND ENERGIZED Install this label to the battery enclosure/cabinet. Note: When the photovoltaic system also has batteries, the same warning shall also be applied by the installer in a visible location at the batteries. (NEC 690.5) PV ARRAY GROUND FAULT DETECTOR INTERRUPTER 150 VDC, 80 ADC, 0.5 ADC GROUND FAULT DETECTION OBB-GFDI-80-150VDC-PNL OBB-GFDI-80D-150VDC-PNL OBB-GFDI-80Q-150VDC-PNL CAUTION: RISK OF ELECTRIC SHOCK NORMALLY GROUNDED CONDUCTORS MAY BE UNGROUNDED AND ENERGIZED WHEN A GROUND-FAULT IS INDICATED. Many types of ground-fault detection and interruption equipment break the negative-to-ground bond to interrupt the fault currents, and the now ungrounded PV negative conductor generally is open-circuit voltage below the ground reference 150 volts. USE A MINIMUM OF 3 AWG 75 C COPPER CONDUCTORS Torque 1/4-20 breaker studs to 35 In-lbs (4.0 Nm) Designed and assembled in Arlington, WA USA www.outbackpower.com Install this label on the outside of the panel box location of the GFDI. 4

Installation Instructions Insert the GFDI into the breaker mounting bracket. Insert and hand-tighten the GFDI s mounting screws. CAUTION overtightening can damage the GFDI. With all system power off, attach the ground and negative wires to their respective bus bars and to the back of the GFDI. The ground wire goes to the top of the 0.5 amp breaker. The negative wire goes to the bottom of the same breaker. (See Figures 1 and 2.) GFDI 0.5 Amp Breaker Figure 1. Placement of Ground and Negative Wires With all system power off, make the connections to the individual 80-amp breakers. The specifics will vary with the GFDI model and installation type. Attach the Battery + wire from one charge controller to the top of one 80-amp breaker. (See Figure 2.) Attach a wire from your battery positive breaker or battery positive bus bar to the bottom of the same 80-amp breaker. (See Figure 2.) Repeat these steps for additional charge controllers. The GFDI should have one 80-amp breaker for each controller. Torque all GFDI wires to 35 inch-pounds/4.0 Nm. 5

Once all breakers are turned on, the 0.5 amp breaker of the GFDI connects the grounding system to the battery negative, while the 80 amp breaker(s) connect the battery to the charge controllers (see Figure 2). Normal operation of the GFDI is indicated by the green breaker lever in the up/on position. In normal operation, grounding system is bonded directly to battery negative through the 0.5 amp breaker, and the charge controllers receive battery voltage. The 0.5 breaker detects a ground fault by detecting current flow between chassis ground and battery negative. In the event of a ground fault, flow of fault current is interrupted and indicated by the green breaker lever in the down/off/tripped position. When the 0.5 amp breaker opens, the other GFDI poles mechanically connected to it will open at the same time. This disconnects voltage between all charge controllers and the batteries. If the breakers trip, the negative-to-ground bond remains established through the 43 kilohm, 5 Watt resistor in parallel to the GFDI breaker. Note: The GFDI shall not be installed as a PV disconnect. The 80 amp breakers of the GFDI are intended only for connecting the battery positive to the charge controllers. 6

TO CC #3 BAT+ TO CC #1 BAT+ TO CC #2 BAT+ TO CC #4 BAT+ GREEN WIRE GROUND BUS 43K OHM 5 WATT WHITE WIRE TO NEGATIVE BUS TO BATTERY POSITIVE TO BATTERY POSITIVE Figure 2. Wiring Diagram, Rear View 7

PV ARRAY TERMINAL BUS BAR SHUNT CONTROLLER #1 BATTERY + GND WHITE GFDI 1/2 AMP GROUND FAULT GREEN 43K OHM RESISTOR GROUND BUS BAR DC POSITIVE BUS BAR BATTERY BANK Figure 3. OBB-GFDI-80-150VDC-PNL Two-Position Installation 8

PV ARRAY #2 PV ARRAY #1 GND CONTROLLER #2 BATTERY + TERMINAL BUS BAR SHUNT CONTROLLER #1 BATTERY + GND WHITE GFDI 1/2 AMP GROUND FAULT GREEN 43K OHM RESISTOR GROUND BUS BAR DC POSITIVE BUS BAR BATTERY BANK Figure 4. OBB-GFDI-80D-150VDC-PNL Three-Position Installation 9

PV ARRAY #4 PV ARRAY #2 PV ARRAY #1 PV ARRAY #3 CONTROLLER #4 BATTERY + GND CONTROLLER #2 BATTERY + TERMINAL BUS BAR SHUNT DC NEGATIVE 43K OHM RESISTOR WHITE GREEN 1/2 AMP GROUND FAULT CONTROLLER #1 BATTERY + GFDI GND CONTROLLER #3 BATTERY + GROUND BUS BAR DC POSITIVE BUS BAR BATTERY BANK Figure 5. OBB-GFDI-80Q-150VDC-PNL Four-Position Installation 10

Corporate Office 19009 62nd Avenue NE Arlington, WA USA (+1) 360-435-6030 www.outbackpower.com European Sales Office C/ Castelló, 17 08830 - Sant Boi de Llobregat BARCELONA, España Phone: +34.93.654.9568 900-0015-01-00 REV A