FERRO-THERM STEEL PIPING SYSTEM

Similar documents
TEXAS A&M CENTRAL ACADEMIC BUILDIING & PATRIOT S CASA SUBMITTAL Pre-Insulated Piping

NAPCA BULLETIN APPLICATION PROCEDURES FOR CONCRETE WEIGHT COATING APPLIED BY THE COMPRESSION METHOD TO STEEL PIPE

The work of this Section includes furnishing and installing Reinforced Concrete Pressure Pipe as shown on the Drawings and as specified.

SECTION HIGH DENSITY POLYETHYLENE (HDPE) PIPE AND FITTINGS FOR WATER DISTRIBUTION AND TRANSMISSION

SECTION SANITARY SEWER AND STORM DRAIN SYSTEMS

Section 2100-Trenching and Tunneling

SECTION HIGH DENSITY POLYETHYLENE (HDPE) PIPE AND FITTINGS

Specification Guidelines: Allan Block Modular Retaining Wall Systems

SUBDRAINS AND FOOTING DRAIN COLLECTORS. A. Construct subdrains, subdrain cleanouts and outlets, and footing drain collectors.

SECTION POLYVINYL CHLORIDE (PVC) PIPE

SECTION CEMENT-MORTAR LINED AND COATED STEEL PIPE

San Antonio Water System Standard Specifications for Construction ITEM NO SLIP-LINING SANITARY SEWERS

Conduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes

FLEX-WRAP Foam Pipe Wrap

Model Specification 509 DRISCOPLEX 4200 and DRISCOPLEX 4300 Gravity Flow Sanitary Sewer

PTS HELICAL PIERS INSTALLATION SPECIFICATIONS NOTICE

Engineering Specifications

Wastewater Capital Projects Management Standard Construction Specification

DIVISION 4300 STORM DRAINAGE

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, Underground branch circuit feeding a detached garage:

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)

DIVISION 2 - SEWERAGE AND DRAINAGE SECTION STORM DRAIN SYSTEMS PART 1 - GENERAL

SECTION SANITARY SEWER PIPE

Specifications for Residential Property Owners Connection to New Public Sewer

PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification. 96 B. Riutta

SECTION UNDERGROUND ELECTRIC SERVICE

CCU Engineering Specifications. Section PRECAST CONCRETE PRODUCTS

SECTION 36 - CAST-IN-PLACE CONCRETE PIPE (CIPCP) TABLE OF CONTENTS

INDEX. Sec. No. Items Page Nos.

SECTION EARTH MOVING

Green Thread Product Data

SECTION LS 2530 SANITARY SEWERS. A. General: Submit the following in accordance with The General Conditions.

CITY OF SELMA, TEXAS Inspection Checklist: Commercial

53.03 MATERIALS FOR SEWER LINER PIPE AND FITTINGS: The following materials are approved for installation in sanitary sewer lines:

PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT

SECTION 1 GENERAL REQUIREMENTS

State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS

Division 9. SignaFlor Pad and Pour Flooring System

Section SEWER PIPE INSTALLATION AND TESTING

CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements

Series 4000 Fiberglass Pipe and Fittings

B. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation

INSTALLATION RECOMMENDATIONS. Outdoor Rubber Tiles

SECTION 21 REHABILITATION OF SANITARY SEWER MAINS BY THE PIPE BURSTING AND TRENCHLESS PIPE REPLACEMENT METHOD

Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS

The Most Advanced Name in Drainage Systems. Sanitary Sewer Pipe

Chapter 3 Pre-Installation, Foundations and Piers

Suggested Specifications: Steel Pipe for Water Transmission

SECTION PRECAST CONCRETE UTILITY STRUCTURES

Ecoflex Wall Penetration Systems: An efficient, sustainable solution for penetrating concrete or block walls

All work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition.

3. Contractor shall ensure that all permits are obtained prior to any construction. Contractor shall be responsible for all utility fees.

Native InDesign 2890 SaniTite Brochure 1/8" CMYK April 17, 07

This will also provide you with the knowledge to insure long life for your Investment

4 Installation Requirements

CONTRACT SPECIFICATIONS - SEISMIC ISOLATION BEARINGS

SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701)

STANDARD SPECIFICATIONS FOR PRIVATE BUILDING SEWER LINES IN PUBLIC RIGHT-OF-WAY

Royal Seal Gasketed Sewer Pipe

SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 11/5/13)

B. Types of mechanical insulation specified in this section include the following:

Rental Services Temporary Cooling - Flexible Water Hose

Specification for Pipe Bursting Gravity Sewer Mains with HDPE Pipe

SEPTIC SYSTEM CONSTRUCTION REQUIREMENTS ST. MARY S COUNTY HEALTH DEPARTMENT

SECTION SIGNAL WIRE AND CABLE

SECTION 6 SANITARY SEWER MAIN 6.01 SCOPE

COATING & WRAPPING OF UNDERGROUND PIPING

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

C. Section TESTING LABORATORY SERVICE.

Depend-O-Lok FxE Expansion Coupling. System No. Submitted By Spec Sect Para Location Date Approved Date. DEPEND-O-LOK FxE EXPANSION COUPLING

TECHNICAL NOTE Lining of Casings with SaniTite HP Pipe

For a building with a crawl space, see Figure

Renovating Your Basement

1.02 DESCRIPTION A. This Section specifies furnishing and installing Cast in Place Detectable/Tactile Warning Surface tiles where indicated.

APPLICATION FOR DEMOLITION & RIGHT-OF OF-WAY PERMIT

SECTION 623 CONCRETE BONDING COMPOUND, EPOXY MORTAR AND EPOXY POLYMER CONCRETE OVERLAY SECTION CONCRETE BONDING COMPOUND.

SECTION 603 SANITARY SEWER FORCE MAINS

SANITARY GRAVITY SEWER LINE TESTING. B. Section CCTV Inspection of Gravity Sewer Lines

The minimum reinforcement for the stem wall is the placement of:

SECTION REMOVAL OR ABANDONMENT OF EXISTING UTILITIES AND UNDERGROUND STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

Civil. 2. City of Seattle Supplement to the Specification for Road, Bridge and Municipal Construction, most current addition.

1.3.2 Method of construction and restoration of existing water service connections. This shall include:

Bethel Township Municipal Authority (BTMA) RESIDENTIAL SEWER CONNECTION MANUAL

MS-3/2009 HDPE (High Density Polyethylene) Pipe and Fittings Specification for Buried Potable Water

Caps STANDARD WEIGHT Inches / Pounds

Pipe and Equipment Insulations. Zeston. PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems

Gas Meter Clearances and Service Installation Requirements

GAS INSTALLERS MANUAL CINERGY AND SUBSIDIARY COMPANIES CUSTOMER PROCEDURE FOR INSTALLING 3", 4", 6", AND 8" IPS PLASTIC GAS SERVICE PIPING

Residential Foundations and Basements

High Strain Dynamic Load Testing of Drilled Shafts

Secondary Containment Comparison ATI Ultra COAT vs HDPE

TubeTrace, ThermoTube

SECTION STORM DRAIN SYSTEM

Beacon Hill Sewer District Standard Specifications

SECTION STORM DRAINAGE SYSTEM

CHAPTER 6 - SANITARY SEWER

Ontario Electrical Safety Code - Info Sheet

SECTION POINT REPAIRS TO SANITARY SEWERS. A. Repairs to existing sewer lines by replacing short lengths of failed pipe.

EFFECTIVE FEBRUARY note: drainage permit required to call for a dampproof inspection

San Antonio Water System Standard Specifications for Construction ITEM NO. 854 SANITARY SEWER LATERALS

Transcription:

STEEL PIPING SYSTEM THERMACOR S is a factory-fabricated, preinsulated piping system for below or above ground distribution of hot and chill water, low pressure steam, condensate, or oil and viscous fluids. The system is designed with a steel carrier pipe (type and grade specified, as required), closed cell polyurethane foam insulation, and a High Density Polyethylene (HDPE) jacket. Carrier Pipe d > 2 - A53 ERW Grade B, Std. Wt. Black Steel d < 2 - A106 SML, Std. Wt. Black Steel Seamless & Schedule 80 pipe are available for all sizes. Std. Wt. is the same as Schedule 40 through 10. XS is the same as Schedule 80 through 8 d 6" TYP. 20' or 40' RANDOM LENGTHS Polyurethane Insulation HDPE Jacket Carrier Pipe Polyurethane Insulation Density > 2.0 lbs/ft³ K Factor < 0.16 @ 75 F Compressive Strength > 30 psi Closed Cell Content > 90% @ 75 F Jacket High Density Polyethylene (HDPE) P.O. BOX 79670 1670 HICKS FIELD ROAD EAST FORT WORTH, TEXAS 76179 817 / 847-7300 FAX 817 / 847-7222

GENERAL All underground and above ground piping materials transporting chill water, hot water, low-pressure steam (250 F) or condensate shall be as manufactured by THERMACOR PROCESS INC. All straight pipe, fittings, anchors, insulating materials, and technical support shall be provided by the manufacturer. SERVICE PIPE The carrier or service pipe shall be A-53, Grade B, ERW, Standard Weight for pipe sizes 2 and larger and A106/ A53, Grade B, seamless, standard weight for pipe sizes 1.5 and smaller. Condensate piping materials shall be extra strong. Pipe shall be butt-welded for sizes 2 and larger and socket-welded for 1.5 and smaller. Straight sections shall be supplied in 20 or 40 foot random lengths with cutbacks to allow for welding at the field joints. INSULATION Insulation of the service pipe shall be rigid polyurethane foam with a minimum 2.0 lbs/ft³ density, 90% minimum closed cell content, and a K factor not higher than.16 at 75 F per ASTM C518. The polyurethane foam shall be CFC-free. The polyurethane foam shall completely fill the annular space between the service pipe and jacket, and shall be bonded to both. Insulation shall be provided to the minimum insulation thickness specified. JACKET The outer protective jacket shall be high density polyethylene (HDPE). No FRP, HDUP, or tape jacket allowed. SPECIFICATION GUIDE * STEEL PIPING SYSTEM FITTINGS Fittings are Thermacor s SC (standard component) factory pre-fabricated and pre-insulated fittings with polyurethane foam to the thickness specified and jacketed with a one piece seamless molded HDPE fitting cover, a butt fusion welded, or an extrusion welded and mitered HDPE jacket. Carrier pipe fittings shall be butt-welded, except sizes smaller than 2 shall be socket-welded. (At the Engineer s option, fittings can be pre-fabricated/ pre-engineered.) Fittings include expansion loops, elbows, tees, reducers, and anchors. Elbows, loops, offsets, or any other direction changes shall conform to the standards set by ANSI B31.1, Code for Power Piping. FIELD JOINTS Service pipe shall be hydrostatically tested as per the Engineer s specification with a factory recommendation of 1.5 times the specified pressure of the system. Straight joint sections shall be insulated using urethane foam to the thickness specified, jacketed with an HDPE split sleeve, and sealed with a heat shrink sleeve. (At the Engineer s option, joints may be sealed with a pressure testable joint closures.) All joint closures and insulation shall occur at straight sections of pipe. All insulation and jacketing materials shall be furnished by THERMACOR. INSTALLATION Installation of the piping system shall be in accordance with the manufacturer s instructions. Factory trained field technicians shall be provided for critical periods of installation, unloading, field joint instruction, and testing. * For alternate specifications, please contact THERMACOR. THERMACOR PROCESS INC. 1670 Hicks Field Road East Fort Worth, Texas 76179-5248 P.O. Box 79670 Phone (817) 847-7300 Fax (817) 847-7222 www.thermacor.com Your Authorized THERMACOR Representative Is: The information contained in this document is subject to change without notice. THERMACOR PROCESS INC. believes the information contained herein to be reliable, but makes no representations as to its accuracy or completeness. FT-KN (8/11) THERMACOR PROCESS INC. sole and exclusive warranty is as stated in the Standard Terms and Conditions of Sale for these products. In no event will THERMACOR PROCESS INC. be liable for any direct, indirect, or consequential damage.

Specification Guide STANDARD SPECIFICATION FTSG 7.101 8.10.11 Pre-insulated HDPE-Jacketed Steel Piping Systems suitable for Chilled Water, Heating Water, Domestic Hot Water, Process Fluids, Low Pressure Steam (15 PSIG Max.), Condensate Return, and Cryogenic services. Part 1 - General 1.1 Pre-insulated Piping - Furnish a complete HDPE jacketed system of factory pre-insulated steel piping for the specified service. All pre-insulated pipe, fittings, insulating materials, and technical support shall be provided by the Pre-insulated Piping System manufacturer. 1.2 The system shall be as manufactured by Thermacor Process Inc. of Fort Worth, Texas. Part 2 - Products 2.1 Carrier pipe shall be steel ASTM A-53, Grade B., ERW (Type E) or seamless (Type S), standard weight for sizes 2 and larger, and shall be ASTM A-106/ A-53, seamless, standard weight for sizes 1-1/2 and smaller (Std. Wt. is the same as Sch. 40 through 10 ). Condensate return piping shall be Extra Strong (XS is the same as Sch. 80 through 8 ). When practical, piping shall be provided in 40-foot double-random lengths. All carbon steel pipe shall have ends cut square and beveled for butt-welding. Straight sections of factory insulated pipe shall have 6 of exposed pipe at each end for field joint fabrication. 2.2 Insulation shall be polyurethane foam either spray applied or injected with one shot into the annular space between carrier pipe and jacket. Insulation shall be rigid, 90% minimum closed cell polyurethane with a minimum 2.0 lbs per cubic foot density, compressive strength of 30 psi, and coefficient of thermal conductivity (K-Factor) of not higher than 0.16 @ 75 F per ASTM C-518. Maximum operating temperature shall not exceed 250 F. Insulation thickness shall be specified by calling out appropriate carrier pipe and jacket size combinations as listed on drawing FTSG 7.103. 2.3 Jacketing material shall be extruded, black, high density polyethylene (HDPE), having a wall thickness not less than 100 mils for jacket sizes less than or equal to 12, 125 mils for jacket sizes larger than 12 to 24, and 150 mils for jacket sizes greater than 24. No tape jacket allowed. The inner surface of the HDPE jacket shall be oxidized by means of corona treatment, flame treatment (patent pending), or other approved methods. This will ensure a secure bond between the jacket and foam insulation preventing any ingression of water at the jacket/ foam interface. 2.4 Straight run joints shall be field-insulated per the manufacturer s instructions, using polyurethane foam poured in an HDPE sleeve and sealed with heat shrink tape. (At the Engineer s option, a pressure testable joint closure may be specified.) All joint closures and insulation shall occur at straight sections of pipe. All insulation and jacketing materials shall be furnished by THERMACOR. 2.5 Fittings are Thermacor s SC (standard component) factory pre-fabricated and pre-insulated fittings with polyurethane foam to the thickness specified and jacketed with a one-piece seamless molded HDPE fitting cover, a butt fusion welded, or an extrusion welded and mitered HDPE jacket. Carrier pipe fittings shall be butt-welded, except sizes smaller than 2 shall be socket-welded. (At the Engineer s option, fittings can be pre-fabricated/ pre-engineered.) Fittings include expansion loops, elbows, tees, reducers, and anchors. Elbows, loops, offsets, or any other direction changes shall conform to the standards set by ASME B31.1, Code for Power Piping. 2.6 Expansion/ contraction compensation will be accomplished utilizing factory pre-fabricated and pre-insulated expansion elbows, Z-bends, expansion loops, and anchors specifically designed for the intended application. External expansion compensation utilizing flexible expansion pads (minimum one inch thickness), extending on either side, both inside and outside the radius of the fittings are used with all fittings having expansion in excess of 3/4. (Continued)

Specification Guide STANDARD SPECIFICATION FTSG 7.102 Part 3 - Execution 3.1 Pre-fabricated systems shall be provided as SC (standard components) fittings and factory insulated straight pipe sections for field engineering per the contract drawings. (At the Engineer s option, system can be pre-fabricated/ pre-engineered.) 3.2 Underground systems shall be buried in a trench not less than two feet deeper than the top of the pipe and not less than eighteen inches wider than the combined O.D. of all piping systems. A minimum thickness of 24 inches of compacted backfill placed over the top of the pipe will meet H-20 highway loading. 3.3 Trench bottom shall have a minimum of 6 of sand, pea gravel, or specified backfill material as a cushion for the piping. All field cutting of the pipe shall be performed in accordance with the manufacturer s installation instructions. 3.4 A hydrostatic pressure test of the carrier pipe shall be performed per the engineer s specification with a factory recommendation of one and one-half times the normal system operating pressure for not less than two hours. Care shall be taken to insure all trapped air is removed from the system prior to the test. Appropriate safety precautions shall be taken to guard against possible injury to personnel in the event of a failure. 3.5 Field Service, if required, shall be provided by a certified manufacturer s representative or company field service technician. The technician will be available at the job a minimum of one day (or more if required by job size) to check unloading, storing, and handling of pipe, pipe installation, pressure testing, field joint insulation, and backfilling techniques.

Specification Guide POLYURETHANE FOAM IN HDPE JACKET FTSG 7.103 10.07.11 Carrier Pipe: d > 2 - A53 ERW Grade B, Std. Wt. Black Steel d < 2 - A106 SML, Std. Wt. Black Steel - Seamless and Schedule 80 pipe available for all sizes - Std. Wt. is the same as Schedule 40 for all sizes thru 10 - XS is the same as Schedule 80 for all sizes thru 8 Jacketing Material: High Density Polyethylene (HDPE) Insulation: Polyurethane Foam d t L D Pipe Size Jacket Size Standard Length L Insulation Thickness t Weight Per Foot (lbs.) 1/2 5.4 20 2.2 1.9 3/4 5.4 20 2.1 2.2 1 5.4 20 1.9 3.2 1-1/4 5.4 20 1.8 3.8 1-1/2 5.4 20 1.7 4.2 2 5.4 40 1.4 5.1 2-1/2 6.7 40 1.8 7.7 3 5.7 40 1.0 9.1 6.7 40 1.5 9.5 4 6.7 40 1.0 12.5 7.7 40 1.5 13.0 8.7 40 2.0 13.5 5 7.7 40 1.0 16.7 8.7 40 1.5 17.1 6 8.9 40 1.0 21.5 9.9 40 1.5 22.0 10.9 40 2.0 22.4 8 10.9 40 1.0 31.5 11.9 40 1.5 32.2 12.9 40 2.0 32.9 10 13.0 40 1.0 44.3 14.1 40 1.6 46.3 12 15.0 40 1.0 55.4 16.1 40 1.6 56.2 14 16.2 40 1.0 60.8 17.2 40 1.5 61.9 18.2 40 2.0 63.0 Pipe Size Jacket Size Standard Length L Insulation Thickness t Weight Per Foot (lbs.) 16 18.3 40 1.0 69.7 19.3 40 1.5 71.2 20.3 40 2.0 72.7 18 20.3 40 1.0 79.6 21.3 40 1.5 80.7 22.3 40 2.0 81.8 20 22.4 40 1.0 88.6 23.4 40 1.5 87.8 24.4 40 2.0 90.9 24 26.3 40 1.0 106.3 27.3 40 1.5 108.1 28.3 40 2.0 109.9 28 30.3 40 1.0 126.0 31.3 40 1.5 127.5 32.3 40 2.0 129.0 30 32.3 40 1.0 140.0 33.3 40 1.5 141.5 36.6 40 3.2 143.0 Pipe/ Jacket combination available on sticks & kits only. * Other pipe sizes and pipe and jacket combinations are available. ** Insulation thickness is calculated using minimum wall thickness. Actual wall thickness may be greater than stated, thereby minimally decreasing actual foam thickness.

Specification Guide HEAT LOSS DIAGRAM (1-8 PIPE) FTSG 7.104 HEAT LOSS FOR 1 OF POLYURETHANE FOAM* 70 8 60 6 50 4 40 Q loss (Btu/ft/hr) 30 3 2 20 1 10 0 100 120 140 160 180 200 220 240 260 - Burial depth: 36 - Soil conductivity: 12 (Btu/h.ft 2. F/ft) - Soil temperature: 50 F Service Temperature ( F) HEAT LOSS FOR 2 OF POLYURETHANE FOAM* 50 45 8 40 35 6 Q loss (Btu/ft/hr) 30 25 20 15 10 4 3 2 1 5 0 100 120 140 160 180 200 220 240 260 - Burial depth: 36 - Soil conductivity: 12 (Btu/h.ft 2. F/ft) - Soil temperature: 50 F Service Temperature ( F) * Values are calculated using 3E Plus in accordance with ASTM C680 and are subject to the terms and limitations stated in the software. Actual heat loss may vary.

Specification Guide HEAT LOSS DIAGRAM (10-30 PIPE) FTSG 7.105 HEAT LOSS FOR 2 OF POLYURETHANE FOAM* 140 30 120 24 Q loss (Btu/ft/hr) 100 80 60 20 18 16 12 10 40 20 0 100 120 140 160 180 200 220 240 260 - Burial depth: 36 - Soil conductivity: 12 (Btu/h.ft 2. F/ft) - Soil temperature: 50 F Service Temperature ( F) 140 HEAT LOSS FOR 3 OF POLYURETHANE FOAM* 120 100 30 Q loss (Btu/ft/hr) 80 60 40 24 20 18 16 12 10 20 0 100 120 140 160 180 200 220 240 260 - Burial depth: 36 - Soil conductivity: 12 (Btu/h.ft 2. F/ft) - Soil temperature: 50 F Service Temperature ( F) * Values are calculated using 3E Plus in accordance with ASTM C680 and are subject to the terms and limitations stated in the software. Actual heat loss may vary.

Installation Manual GENERAL INSTALLATION INSTRUCTIONS FTIM 7.201 UNLOADING & HANDLING Lift joints from trucks. DO NOT DROP SHARP OR HEAVY OBJECTS ON INSULATED UNITS. DO NOT use chains or other devices which might puncture insulation jacket. STORAGE Pipe is stockpiled off the ground. Do not exceed a stacking height of 6. Prevent dirt and debris from entering pipe. Fittings, joining materials, etc. must be stored indoors to protect them from freezing, overheating, moisture, or loss. LAYING OF PIPE UNITS TRENCHING All sharp rocks, roots, and other abrasive material must be removed from the trench. The trench bed should be 6 of sand or backfill as specified by the engineer, providing a smooth and uniform stabilizing surface (sandbags may be used as a means to keep the pipe off the ground until backfilling is started). The trench width should provide a minimum of 6 from trench wall to jacket O.D. and a minimum of 6 between pipe units. Trench depths will be indicated on the contract drawing and in line with good construction practices. Trench depth should allow for a minimum cover of 24 on top of the insulated unit. FIELD JOINING METHODS Ferro-Therm piping and fittings shall be joined in the field using approved methods of welding for appropriate pipe. FIELD ALTERATIONS Pipe will be cut in the field, based on the appropriate field measurements for fabrication of loops, fittings, and/ or making manhole or wall entries unless the system is pre-engineered with piece mark sections and/ or with pre-fabricated/ pre-insulated fittings. If special short pieces are required, measure distance needed for field alteration and cut through unit with saw. Using factory insulated pipe as guide, cut back insulation and bevel pipe (simultaneously removing burrs, cuts, nicks, and scratches). Apply end seal to the clean, dry, exposed insulation surface, if required. HYDROSTATIC TESTING Anchor blocks shall be poured and cured, prior to testing. Bleed all air from lines to eliminate possible incorrect readings. The hydrostatic pressure test shall be performed per the engineer s specification with a factory recommendation of one and one-half times the normal operating pressure for not less than two hours. Inspect all fittings, valves, and couplings at this time. Appropriate safety precautions shall be taken to guard against possible injury to personnel in the event of a failure. FIELD JOINT & FITTING INSULATION See Drawings furnished with job material. INSTALLATION INSTRUCTIONS BACKFILL FINAL Before backfilling is started, the trench should be cleaned of any trench wall cave-ins and general trash, especially metal. Backfilling should be done with sand or other engineer-approved material 6 below the casing to 1 above. Engineer-approved backfill may be used to fill the rest of the trench. This material should be free of rocks, roots, large clods, or anything that could cause damage to the jacket. Jacket should have a minimum of 2 cover. WHEELED OR TRACKED VEHICLES SHALL NOT BE USED FOR TAMPING!

Installation Manual SHIPPING & HANDLING FTIM 7.202 SHIPPING & HANDLING INSTRUCTIONS HANDLE COATED PIPE WITH EXTRA CARE! THIS PIPE CAN DAMAGE WHEN HANDLED, MOVED, OR STORED IMPROPERLY! UPON RECEIPT OF MATERIALS Make an overall inspection of the load, checking all bands and braces to see if they are intact. Also, check the load for shifting. If the load has shifted, or if the braces and bands are broken, examine each pipe for damage. HAVE THE TRUCK DRIVER MAKE AN ITEMIZED NOTATION OF ANY DAMAGE ON THE DELIVERY RECEIPT AND HAVE IT SIGNED BY THE DRIVER. CHECK PACKING LIST Compare materials received with those listed on the packing list. Count all pipe and boxes. NOTE ANY SHORTAGES ON DRIVER S DELIVERY RECEIPT. CHECK BOXES Open all boxes and inspect for damages, shortages, and correct size. REPORT ANY DISCREPANCIES WITHIN 30 DAYS AFTER RECEIPT. CLAIMS FOR DAMAGES Claims for damages in transit or lost goods must be made within 30 days. The filing of any claim is the Purchaser s Responsibility. Thermacor will file any claim on Purchaser s behalf upon receipt of the following: 1. Written authority to file such a claim. 2. Written notice of loss or damage (signed and noted Bill of Lading) by truck driver or carrier freight agent. UNLOADING PIPE Pipe may be unloaded by hand or with fork lifts*, cherry pickers, or cranes. DO NOT HOOK pipe ends. Minimum 4 wide straps or slings should be used. * Fork Lift When using Fork Lift, wide tines or a large surface covering the fork tines must be used to prevent coating damage. Fork Lift must be able to handle the weight of the insulated pipe length. PIPE STOCKPILING Pipe should be stored on level ground, elevated to be as dry as possible, and in such a way that the pipe ends do not lie in water or on the ground. To prevent deformation of the jacket and insulation due to the weight of the pipe, place a series of supports (3 for 20 or 5 for 40 ) of ample size generally constructed from 2 x 4 s under the pipe as shown below. Supports should increase in width as weight load increases so that the top supports of a fully loaded stockpile should be approximately 10 wide, gradually increasing to the bottom level, approximately 18 wide. Pipe can be pyramided (within reasonable and safe limits) approximately 6 high after a properly braced or chocked base is formed. Pipe stored outside for long periods of time can be covered with blue mesh tarpaulin (plywood can also be used). Do not prevent airflow as jacket can be deformed from heat buildup. 6' 20' 6' 20' 6' 20' BE VERY CAREFUL NOT TO DROP THE PIPE! NOTE: Thermacor does not approve of the practice of installing pipe and fittings, and backfilling the pipe before testing. Thermacor will not allow or pay claims for charges which arise in locating and digging up leaks regardless of cause.

Details RISER DETAIL FTAD 7.301 5'-0" CARRIER PIPE CARRIER PIPE PIPE SLEEVE & SEAL (BY INSTALLING CONTR.) FIN. FLR. 1'-0" EXTERIOR WALL FLOOR SLEEVE AND SEAL (BY INSTALLING CONTR.) 1'-0" GRADE FIN. FLR. ANCHOR PLATE 5'-0" C-E 5'-0" C-E HDPE JACKET ANCHOR PLATE HDPE JACKET CONCRETE ANCHOR BLOCK (BY OTHERS) 5'-0" CONCRETE ANCHOR BLOCK (BY OTHERS) 90 ELBOW WALL SLEEVE AND SEAL (BY INSTALLING CONTR.) FOUNDATION ELEVATION ELEVATION PIPING RISER DETAIL SCALE: NONE BUILDING RISER DETAIL SCALE: NONE FLOOR SLEEVE AND LINKSEAL (BY INSTALLING CONTRACTOR) CARRIER PIPE FLOOR SLEEVE AND LINKSEAL (BY INSTALLING CONTRACTOR) CARRIER PIPE GRADE OUTSIDE FACE OF WALL FIN. FLR. 1'-0" GRADE OUTSIDE FACE OF WALL FIN. FLR. 5'-0" 1'-0" 5'-0" CARRIER PIPE CARRIER PIPE INSULATION 90 ELBOW INSULATION HDPE JACKET 90 ELBOW HDPE JACKET ANCHOR BLOCK SHALL BE LOCATED MINIMUM OF 3'-0" FROM WALL BUILDING RISER DETAIL SCALE: NONE ELEVATION BUILDING RISER DETAIL SCALE: NONE

Details WALL PENETRATION DETAIL FTAD 7.302 SITE PLAN DIMENSIONS END HERE 9" 3" OUTSIDE FACE OF WALL WALL SLEEVE AND SEAL (BY INSTALLING CONTR.) CARRIER PIPE INSULATION HDPE JACKET WALL PENETRATION DETAIL SCALE: NONE

Details EXPANSION BOLSTER DETAIL FTAD 7.303 1.09.08

Details EXPANSION LOOP DETAIL FTAD 7.304 1.10.08

Details ANCHOR DETAIL FTAD 7.305

Details 4 PIPE TRENCH DETAIL FTAD 7.306 HDPE JACKET (TYP) 24" MIN. OF SELECT BACKFILL GRADE CARRIER PIPE (TYP) A MINIMUM TRENCH WALL SAND OR SELECT BACKFILL 6" OVER TOP OF JACKET UNDISTURBED EARTH 6" B MIN. C D 6" MIN. 6" SAND OR SELECT BACKFILL BED IN BOTTOM OF TRENCH E MINIMUM 4-PIPE TRENCH SECTION SCALE: NONE