SOLAR PHOTOVOLTAIC (PV) SYSTEMS ELECTRICAL CODE COMPLIANCE AND INSPECTION CHECKLIST

Similar documents
2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

City of Riverside Building & Safety Division Phone: (951)

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

County of Riverside Building and Safety Department

Solar Photovoltaic (PV) Systems

City of San Diego Residential Photovoltaic Systems Inspection Guidelines

How To Plan Out An Array Of Solar Panels

Ontario Electrical Safety Code 25 th Edition/ 2012

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

CITY OF LOS ANGELES CALIFORNIA

Solar Panel Installations

Application Bulletin NEC Reference Guide for SolarBridge-Enabled AC Module Installers

Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

Installation Guide Content for P250xV-240 microinverters

PV and the Electrical Code Page 1 PV and the Electrical Code

AC Module Installation Guide Content

Connecting the Power of the Sun. DC Disconnects for Solar Photovoltaic Installations. DC disconnects for. solar photovoltaic installations

Doe Residence kw DC Roof Mounted Photovoltaic System

DC disconnects for solar photovoltaic installations. Connecting the. power of the sun

Expedited Permit Process for PV Systems AC Module

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes

Electrical Grounding. Appendix C

PERMIT APPLICATION REQUIREMENTS FOR RESIDENTIAL ROOF MOUNTED PHOTOVOLTAIC SYSTEMS

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!

AC Module Installation Guide Content

Request for Proposals for Photovoltaic System Installation

Submittal Requirements for Solar Photovoltaic Installations 10 kw or Less in One and Two Family (Duplex) Dwellings

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST

NEC Code Calculations for Solar Installations. for Inspectors and Building Officials

Photovoltaic System Grounding

Questions and Answers for Heating and A/C Contractors

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

CHAPTER 2 EXAMPLES AND TABLES

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

Top Commercial / Residential Electrical Requirements *

RESIDENTIAL PHOTOVOLTAIC SUBMITTAL REQUIREMENTS

Entrances to and from Electrical Equipment Rooms

Installation Guide of Sunrise Solartech PV Modules. Term Contents. Purpose of this guide. General. Safety precaution for installing a solar

BUILDING CODE MANUAL COUNTY OF LOS ANGELES DEPARTMENT OF PUBLIC WORKS BUILDING AND SAFETY DIVISION Based on the 2014 LACBC

NEC 2014 Code Changes

Solar Inverter Sunny Boy 5000US, 6000US, 7000US

Enphase Microinverter Model M215

Contractors Guide Central Inverter System Installation

Significant Changes in the 2011 NEC Prepared by Bryan Holland City of North Port

Model Number Electrical Compatibility Module Connector Type. M LL-S22 60 cell PV module MC-4 Type 2 Locking

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:

Short Circuit Current Calculations

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

YINGLI SOLAR PV MODULES Installation and User Manual

Solar Water Heating and Photovoltaic Electrical Systems Installed on One or Two Family Dwellings

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL (352) ; FAX: (352)

Title: Grounding and Bonding Rev-01

VLT Series 300 Watt True Sine Wave Inverter

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

Mike Holt s Illustrated Guide to. Rule , Articles 445, 700, 701, and 702. Based on the 2011 NEC

Requirements for Electrical Installations

As we look at the PV array in a PV system, we find that many. by John Wiles

Los Angeles Fire Department Requirement No. 96 SOLAR PHOTOVOLTAIC SYSTEM

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)

YINGLI SOLAR PV MODULES Installation and User Manual

ADDENDUM #1(BID PACKAGE # 3)

ELECTRICAL INSPECTION BULLETIN (Effective )

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23

Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured.

SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide

Checklist Testing and inspection without interconnection

Conext Grid Tie Solar Inverter Conext TX 2800 NA Conext TX 3300 NA Conext TX 3800 NA Conext TX 5000 NA

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

San Diego Area Chapter International Code Council

National Craft Assessment and Certification Program S P E C I F I C A T I O N S

Co-location Interconnect Power Panel (CIPP) Installation Guide

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

Enphase M215 Microinverter

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

AC Unison Installation Guide

PV System Disconnect PV System Discon-

PV-Inverter SunPower SPR-5000m / SPR-6000m / SPR-7000m / SPR-8000m

INSPECTION GUDELINES

Engage Coupler. Engage Coupler Chase

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

TOP 10 CHANGES 2013 CALIFORNIA ELECTRICAL CODE 2013 CALIFORNIA ENERGY CODE (ELECTRICAL)

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS

Solar Home System Kit Quality Standards

1 GENERAL 4 2 DEFINITIONS 4 3 STANDARDS FOR INSTALLATION 4 4 LICENSING Extra Low Voltage (ELV) Low Voltage (LV) 5

Reverse-feed applications for circuit breakers

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

IntelliBrite Controller (For IntelliBrite Pool, Spa and Landscape Lighting Fixtures) Installation and User s Guide

Residential Electrical Inspection Checklist

Solar Integrated Solar Roof Panel System Installation Manual

RAY-MAX Integrated Solar Power Strip

Transcription:

SOLAR PHOTOVOLTAIC (PV) SYSTEMS ELECTRICAL CODE COMPLIANCE AND INSPECTION CHECKLIST This checklist contains common electrical code requirements for PV systems, based on the 2008 National Electrical Code and industry standards, and is intended as a guide for PV system inspectors, designers, and installers. The organization of this checklist is aligned with the major sections of Article 690 on Solar Photovoltaic Systems, including circuit requirements, disconnecting means, wiring methods, grounding, marking, connections to other sources and storage batteries. While the items on this checklist provide an overview of the common electrical system requirements, it should not be considered a complete or exhaustive list of all requirements for documentation or code compliance. In particular, this checklist does not address system performance, manufacturer-specific installation instructions, structural loading issues, special fire codes or other local requirements established by the Authority Having Jurisdiction (AHJ). This checklist is intended for use by qualified persons having a thorough understanding of the building codes and PV systems design and installation practices, and it is not intended as a design guide. System designers and integrators may find this checklist helpful in preparing permit applications and plan review documents, and local officials may also use this as a guide for reviewing plans and issuing building permits. Contractors and installers may use this checklist as part of conducting final checkouts and system commissioning, and field inspectors may use this checklist as part of their final inspection and approval process. SYSTEM INFORMATION Customer Site Address Contact Name Phone Fax Email Permitting Authority Contact Name Phone Fax Email Type of System Module (qty) System Output (kwdc) Inverter (qty) System Output (kwac) Charge Controller Battery GENERAL PRACTICES AND COMPONENTS REFERENCE COMPLIANCE / NOTES 1. Equipment Approval. All equipment is identified and listed for the application (includes UL 1703 listing for modules and UL 1741 listing for inverters and charge controllers). NEC 110.2; 690.4(D); 690.60 2. Manufacturer s Instructions. Equipment is installed and used in accordance with any instructions included in the listing or 110.3(B) labeling. 3. Site Drawings. Site drawings include descriptions and locations of major components. 4. Electrical Diagram. Electrical diagram includes component interconnects, conductor types and sizes, conduit types and sizes, disconnects, and point of interconnection. 5. Array Mounting Information. Mounting detail drawing includes roof type and age, mounting system, fastener spacing, and penetration weather sealing method. 2010 JimDunlopSolar.com 1 P age

6. Owner s Documentation. Documentation includes system warranty, component warranties, owner s manuals, utility interconnection agreement, and instructions for operation and maintenance. 7. AC Modules. AC modules have appropriate markings, overcurrent protection, disconnects, and ground fault protection. 8. Stand-Alone Inverter Output. Inverter output rating is equal to or greater than the largest single load on the system, but is permitted to be less than the sum of every load on the system. 9. Local Building Permit. Permits are obtained and displayed as required. 690.6; 690.52 690.10(A) CIRCUIT VOLTAGE AND CURRENT REQUIREMENTS REFERENCE COMPLIANCE / NOTES 1. Maximum System Voltage. Maximum system voltage is calculated based on module open-circuit voltage at the lowest expected ambient temperature. Module manufacturer s NEC 690.7(A) temperature coefficients are used when available. 2. 600 V Limit. Maximum system voltage is less than 600 V for dwellings. Circuits over 150 V accessible only to qualified 690.7(C); 690.7(D) persons. 3. Maximum PV Current. The maximum PV source- and outputcircuit currents (used for sizing conductors and overcurrent protection devices) are based on 125% of the module shortcircuit 690.8(A)(1); 690.8(A)(2) current. 4. Inverter Current. Maximum inverter input and output circuit currents are based on inverter ratings. 690.8(A)(3); 690.8(A)(4) 5. Equipment Maximum Voltage. Equipment and devices are rated for maximum system voltage at lowest temperature. 690.7; 110.4 CONDUCTORS AND WIRING METHODS REFERENCE COMPLIANCE / NOTES 1. Conductors and Wiring Methods. Standard building-wire conductors and appropriate wiring methods are used. NEC 300; 690.31(A) Conductors are rated for conditions of use. 2. Conduit. PV source- and output-circuit conductors operating at more than 30 V and installed in readily accessible locations 690.31(A) are in conduit. 3. PV Source-Circuit Wiring. Conductors have 90 C, sunlight, and wet service resistances. Single conductor type USE-2 and specifically listed and labeled PV wire is permitted in PV 690.31(B) source circuits. 4. PV Conductors Alone. PV source- and output-circuit conductors are not run together with conductors of other 690.4(B) systems. 5. Ampacity. Conductors are sized for a de-rated ampacity of at least 125% of the maximum currents calculated or 690.8(B); 310.15(B); determined in 690.8(A). De-rating factors include high 310.16 ambient temperatures, location on or above rooftops, and number of conductors run together within a conduit or cable. 6. Flexible Conductors. Tracking or movable array mounts use flexible conductors identified for hard service and outdoor 690.31(C); 400.5 use. Ampacities calculated according to 400.5. 7. Small Conductors. Single-conductor cables in sizes 16 AWG and 18 AWG are permitted for module interconnections 690.31(D); 310.15 if they meet the ampacity requirements of 690.8. 8. PV Source-Circuit Conduit. Where DC PV source circuits are run inside a building, they are in metal conduit from the point of penetration into the building to first accessible 690.31(E) disconnect. 9. Connectors. Connectors are polarized, noninterchangeable, guarded, latching or locking, have first-to-make/last-to-break contact for grounded conductor, and either are rated for 690.33 interrupting current or require a tool to open. 10. Wiring Connectors. Connectors are listed for the intended use and environment. Screw terminals are tightened to recommended torque. Crimp-on terminals are used with 110.14 appropriate crimping tool. 11. Junction Boxes. Junction boxes are of appropriate type and size and allow the conductors within to be accessible. 690.34; 314 2010 JimDunlopSolar.com 2 P age

12. Color Codes. Grounded conductors are marked white or gray and grounding conductors shall be green, green/yellow, or bare. 13. Strain Relief. Strain relief or conduit is used with all conductors. 14. Multiwire Branch Circuits. No multiwire branch circuits are allowed on stand-alone 120 V inverter output circuit or panels. 310.12 300.4 690.10(C) OVERCURRENT PROTECTION REFERENCE COMPLIANCE / NOTES 1. Protected Circuits. PV source circuit, PV output circuit, inverter output circuit, and battery circuit conductors and NEC 690.9(A); 240 equipment are protected in accordance with Article 240. 2. Multiple Power Sources. Circuits connected to multiple power sources are provided overcurrent protection from each source. 690.9(A) 3. Ratings. Overcurrent protection devices are rated for not less than 125% of the maximum currents calculated or determined 690.8(B); 240.4; in 690.8(A). 4. Transformers. Overcurrent protection is provided for power transformers in accordance with Section 450.3. 690.9(B); 450.3 5. Supplementary Overcurrent Protection. Branch-circuit or supplementary-type overcurrent protection devices are 690.9(C) permitted on PV source circuits. 6. Listed for DC. Overcurrent protection devices in DC circuits are listed for such use and have the appropriate voltage, current, and interrupt ratings. 690.9(D) DISCONNECTS REFERENCE COMPLIANCE / NOTES 1. Array Disconnect. A disconnect is provided between the PV power system output and other building conductors. NEC 690.13 2. Accessibility. Array disconnect is installed at a readily accessible location either on the outside of the building or structure or inside nearest the point of entrance of the system 690.14(C)(1); 690.31(E) conductors. 3. Marking. Each PV system disconnect is marked as such, and suitable for the intended use. 690.14(C)(2); 690.14(C)(3) 4. Grouping. There are no more than six disconnects for each source of power. Disconnects for each power source are grouped together. 5. Equipment Disconnects. Disconnects are provided to disconnect equipment (inverters, batteries, charge controllers, etc.) from all ungrounded conductors of all power sources. 6. Fuses. Disconnects are provided to independently disconnect a fuse from all sources of power if the fuse is energized from both directions. 7. Features. Disconnects open all ungrounded conductors, are readily accessible, externally operated, have ON/OFF indication, and have appropriate interrupt rating. Manually operated switches and circuit breakers may fulfill these requirements. 690.14(C)(4); 690.14(C)(5) 690.15 690.16 690.17 GROUNDING REFERENCE COMPLIANCE / NOTES 1. Ungrounded Systems. Ungrounded systems include disconnects, overcurrent protection, and ground-fault protection. Equipment is listed for use with ungrounded 690.35 systems. 2. Module Grounding Continuity. Module connections are such that removal of a module does not interrupt a grounded 690.4(C) conductor to another PV source circuit. 3. Ground-Fault Protection. Ground fault protection is provided for grounded arrays. 690.5 4. PV System Grounding. One DC conductor is grounded for two-wire PV systems operating above 50 V. 690.41; 250.4(A) 5. Single-Point. DC grounding is made at a single point on the PV output circuit. 690.42 6. Equipment Grounding. Non-current-carrying metal components are grounded, including module frames, 690.43 mounting structures, equipment, conduit, and boxes. 7. Equipment Grounding Conductors. Equipment grounding conductors are routed with PV circuit conductors. 690.43 2010 JimDunlopSolar.com 3 P age

8. Equipment Grounding Conductor Size. If array has GFP, the equipment grounding conductor is sized according to 250.122. If array does not have GFP, the equipment grounding conductor is sized for at least twice the de-rated circuit conductor ampacity. 9. Grounding Electrode Systems. The AC system is grounded according to 250.50 through 250.60. The DC system is grounded according to 250.166 or 250.169. 10. Common Grounding. If system includes both AC and DC systems, the grounding electrode systems are bonded together. The bonding conductor is sized for the larger of the AC and DC requirements. Separate DC and AC grounding electrodes are permitted, or both grounding systems may use the premises AC grounding electrode. The grounding electrode conductor is sized to meet both AC and DC grounding requirements. 11. Array Grounding. Array is grounded with separate grounding electrode system, unless it would be within 6 of premises electrode. 690.45; 250.122 690.47(A); 690.47(B); 250 690.47(C); 250 690.47(D) Not Required MARKINGS AND LABELS REFERENCE COMPLIANCE / NOTES 1. Array Ground-Fault Protection. Interactive inverter, groundfault indicator, and/or battery bank label warns of shock 690.5(C) hazard during ground fault. 2. Modules. PV modules are labeled with open-circuit voltage, operating (maximum power) voltage, maximum permissible voltage, operating (maximum power) current, short-circuit 690.51 current, and maximum power. 3. System Info at DC Disconnect. PV power source is labeled with maximum power current, maximum power voltage, maximum system voltage, short-circuit current, and maximum 690.53 rated output current of charge controller (if installed) at the DC disconnect. 4. Inverter Info at AC Disconnect. Point of interconnection is labeled with inverter operating AC voltage and rated AC 690.54 output current at the AC disconnect. 5. Batteries. Battery bank is labeled with maximum operating voltage, equalization voltage, and polarity. 690.55 6. Stand-Alone Systems. Exterior visible notice indicates the structure contains a stand-alone system and identifies the 690.56(A) locations of disconnects. 7. Interactive Systems. Exterior visible notice indicates identifies the locations of array disconnect and utility service 690.56(B) disconnect, if not located together. 8. Single 120 V Supplies. A stand-alone system supplied by a 120 V inverter includes a label warning against connecting 690.10(C) multiwire branch circuits. 9. Ungrounded Systems. Ungrounded systems include a label warning of a shock hazard. 690.35(F) 10. Disconnect Energized While Open. If all terminals of a disconnect are energized when open, a label warns as such. 690.17 11. Marking. Panels containing overcurrent protection devices supplying power to busbar are marked to indicate all sources 690.64(B)(4) of supply. 12. Back-Fed Breakers. Back-fed circuit breakers for load-side connections are labeled as inverter output connections with a warning not to relocate. 690.64(B)(7) CONNECTION TO OTHER SOURCES REFERENCE COMPLIANCE / NOTES 1. Inverters UL Listed. Inverter is listed and identified for interactive operation. 690.60, UL1741 2. Islanding. Interactive inverters will de-energize if utility power is lost. Bimodal inverters may continue to operate if 690.61 disconnected from utility power. 3. Neutral Loading. If two-wire inverter is connected to system with multiple ungrounded conductors, sum of load and inverter s current rating does not exceed ampacity of grounded conductor. 690.62 2010 JimDunlopSolar.com 4 P age

4. Unbalanced Interconnections. Loads are balanced on three-phase systems with interconnected single-phase inverters. Three-phase inverter automatically de-energizes if system becomes unbalanced. 5. Point of Connection. The output of interactive inverter is connected to either the supply side or the load side of the utility service disconnect. 6. Load-Side Connection. If load-side connection, the inverter output connection is made at dedicated circuit breaker or fusible disconnect. 7. 120% of Busbar Rating. Sum of ampere ratings of all breakers supplying power to panel does not exceed 120% of the busbar rating. 8. GFCI. Interconnection is on the line side of all ground-fault protection equipment. 9. Suitable for Backfeed. Circuit breakers used for load-side connections are suitable for such operation. 10. Back-Fed Breakers. Back-fed circuit breakers for load-side connections are positioned at the opposite end of the panel as the utility service disconnect. 690.63 690.64 690.64(B)(1) 690.64(B)(2) 690.64(B)(3) 690.64(B)(5) 690.64(B)(7) BATTERIES AND CHARGE CONTROL REFERENCE COMPLIANCE / NOTES 1. General. Battery bank is installed in accordance with Article 480. 690.71(A); 480 2. Voltage Limit for Dwellings. For dwellings, operating voltage is less than 50 V nominal (no more than 24 2 V leadacid cells in series). 690.71(B)(1) 3. Covers/Access. Battery terminals and other live parts are 690.71(B)(2); 480.9 guarded and adequate working space is provided. 4. Fuses. Current-limiting fuses are installed on battery output circuits. 690.71(C) 5. Cases and Racks. Batteries in banks of greater than 48 V nominal are in non-conductive cases. Conductive racks are permissible, if no materials within 6 from top of battery case. 690.71(D) (Requirements do not apply to VRLA batteries.) 6. Series Disconnects. Series disconnects are provided for battery strings over 48 V nominal. 690.71(E) 7. Maintenance Disconnect. A disconnect is provided for the grounded conductor of each string for battery systems over 690.71(F) 48 V. Disconnect is accessible only to qualified persons. 8. Charge Control. Charge control is used if charge rates are greater than 3% of battery capacity (C/33). Adjustment is 690.72(A) accessible only to qualified persons. 9. Diversion Charge Control. Systems using diversion charge controllers have a secondary independent means for charge 690.72(B)(1) control. 10. Diversion Loads. DC diversion load current rating is less than or equal to charge controller rating, load voltage rating is greater than maximum battery bank voltage, and load power 690.72(B)(2) rating is at least 150% of the array power rating. 11. Interactive Systems. Interactive systems with batteries need not comply with diversion load requirements, but must have a 690.72(B)(3) secondary independent means for charge control. 12. Battery Wiring. Battery interconnections are made with #2/0 AWG or larger flexible cables that are listed for hard-service use and identified as moisture-resistant. 690.74; 400 2010 JimDunlopSolar.com 5 P age