Important New Code Requirements for SCCR Labeling of Data Center Equipment



Similar documents
Guidelines on the Short Circuit Current Rating for Industrial Control Panels

Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT

Short-circuit current rating (SCCR) of. industrial control panels. NEC Article 409 and UL 508A

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

UL guidelines, chapter 6.2 / 6.3 Motor Branch Circuits acc. to UL

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

CONDUCTOR SHORT-CIRCUIT PROTECTION

Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

Reverse-feed applications for circuit breakers

UL 508A Industrial Control Panels Power Distribution and Control. Lunch & Learn Training Eaton Corporation. All rights reserved.

misconceptions about arc-flash hazard assessments

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers

Sentron Series Circuit Breakers

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer Electrical Hazards 2/18/2015. Shock.

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION PAGE 1

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST

Vilter motor starter solutions The NEW industry standard in motor starter packages

SECTION VARIABLE FREQUENCY DRIVES

EMERGENCY LIGHTING AND CONTROL

Mike Holt s Illustrated Guide to. Rule , Articles 445, 700, 701, and 702. Based on the 2011 NEC

Owner s Manual. For Automatic Transfer Switch Amp, Service Entrance/Non-Service Entrance

PORTABLE GENERATORS AND OSHA CONSTRUCTION REGULATIONS

Overview of Standards for CO Detection Products

Atlanta Chapter IEEE Industry Applications Society

ELECTRICAL EMERGENCY SYSTEM PLAN REVIEW OVERVIEW OF CODE REQUIREMENTS

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

City of Riverside Building & Safety Division Phone: (951)

Mission Critical Data Center Systems

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

The State Fire Marshal's Office and the VDH/Office of Licensure and Certification. Generator Testing in Nursing Facilities

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A

1. Enforcement Policy Effective Date This policy is effective immediately and applies to all industrial machinery on any project.

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION

Arc Flash Avoidance and its Application to Overhead Traveling Cranes

Using Murrelektronik MICO Modules to Create Low Voltage Limited Energy Circuits in Industrial Control Panels according to UL508A.

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

TECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

County of Riverside Building and Safety Department

Electrical Design TABLE OF CONTENTS FOREWORD BASIC ELEMENTS OF ELECTRICITY... 2 Electricity works much like water Ohm s Law

Choosing the Best Solution for Reducing Arc Energy

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

NEC Class 2 Power Circuits and Power Supplies

ELECTRICAL SAFETY. The standard unit for measuring electrical current.

Dielectric Withstand Testing in a Production Environment

Oil and Coolant Circulating Heating System. Model - OCSM

Circuit Breakers Supplementary Protectors Manual Motor Controllers

Corner-Grounded Delta (Grounded B Phase) Systems

Short Circuit Current Calculations

Fire Alarm Systems Certification

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS

employed to ensure the continuing reliability of critical systems.

Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for

Owner's Manual. Automatic Transfer Switch. This manual should remain with the unit.

What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin?

Electrical Grounding. Appendix C

ARC FLASH HAZARD OVERVIEW. Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc.

Questions and Answers for Heating and A/C Contractors

Low Voltage Disconnect Switches. NFPA79 and UL508A Industrial Machinery Operating Handle Requirements White Paper


CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

Server Technology, Inc.

SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY

Diesel Engine Driven Generators Page 1 of 6

Low Voltage Transformer Through-Fault Protection: A System Approach

Project Name: Nortrax Section Project No: SURGE PROTECTION DEVICES Page 1

Engineering Series Ratings: Is It Practical?

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

National Craft Assessment and Certification Program S P E C I F I C A T I O N S

INSPECTION AND TESTING OF EMERGENCY GENERATORS

Significant Changes in the 2011 NEC Prepared by Bryan Holland City of North Port

Rack-mount Power Distribution Units and UL

INSTALLATION & SERVICE MANUAL. Display Panel

ELECTRICAL SAFETY RISK ASSESSMENT

Understanding Emergency Power Off (EPO)

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23

Motor Protection Voltage Unbalance and Single-Phasing

SINGLE FAMILY DWELLING ELECTRICAL SERVICES RATED 225 TO 600 AMPS

Electrical Plan Design

2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes

City of San Diego Residential Photovoltaic Systems Inspection Guidelines

Circuit Breakers. Next Generation of Protection Capabilities

HERNANDO COUNTY FIRE ALARM GUIDELINES

N.J.A.C. 14:8-4 NET METERING FOR CLASS I RENEWABLE ENERGY SYSTEMS

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

Evaluating Water-Damaged Electrical Equipment

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE

Transcription:

Important New Code Requirements for SCCR Labeling of Data Center Equipment Michael P. Murphy D V L G r o u p 1 1 5 S i n c l a i r R o a d B r i s t o l, P A 1 8 9 6 3 Short Circuit Current Ratings (SCCR) are required by Code on all types of data center power and cooling equipment. Owners, Specifying Engineers and Contractors need to understand these requirements to prevent Authorities Having Jurisdiction (AHJ s) from shutting down projects due to the presence of equipment with missing labeling. This document reviews the applicable codes and standards and provides examples of appropriate labels and submittal documentation. 215-8 2 6-1111 215-7 8 5-6800 1 1 / 9 / 2 0 1 2

EXECUTIVE SUMMARY Beginning with the 2005 version of the Nation Electric Code (NEC), also known as NFPA-70, changes to the NEC impose some significant new requirements for Short Circuit Current Rating (SCCR) of electrical machinery including UPS, Air Conditioners and practically every other large power consuming or conversion device in today s Data Center. This code, along with OSHA and UL standards for Data Center Equipment require clear marking of SCCR on each piece of data center power and cooling equipment. Many specifiers and end users are unaware of these new requirements and are shocked when Inspectors (Authority Having Jurisdiction or AHJ ) halt projects or deny the use of the facility until questions regarding equipment not supplied with SCCR ratings are answered. This document is intended to show how the codes and standards are interpreted regarding this requirement, and provide some examples for labels and revised submittal requirements. 1

National Electric Code Requirements The National Electric Code (NEC) specifies general requirements for all electrical installations in Section 100 of the code. Beginning with the code revisions of 2005 and continuing thorough subsequent revisions, dramatic and substantial changes that effect owners, engineers, contractors and manufacturers have been implemented. To begin with, Article 110.3-Examination, Identification, Installation, and Use of Equipment specifies that A) Examination. In judging equipment, considerations such as the following shall be evaluated: (1) Suitability for installation and use in conformity with the provisions of this Code. Informational Note: Suitability of equipment use may be identified by a description marked on or provided with a product to identify the suitability of the product for a specific purpose, environment, or application. Special conditions of use or other limitations and other pertinent information may be marked on the equipment, included in the product instructions, or included in the appropriate listing and labeling information. Suitability of equipment may be evidenced by listing or labeling. Based on this section of the code, most Authorities Having Jurisdiction (AHJ s) will require that equipment be listed and labeled in accordance with Underwriter Laboratories (UL) published standards. Equipment either improperly labeled or not labeled will most often not be allowed to be put into service by the AHJ, imposing costly delays on a project. Further discussion on UL will occur later in this article. See Appendix A for further information on listed and labeled products. Article 110.9-Interrupting Rating specifies that protective devices such as fuses and circuit breakers be specified and installed with in accordance with the following requirement: Equipment intended to interrupt current at other than fault levels shall have an interrupting rating at nominal circuit voltage not less than the current that must be interrupted. This requirement insures that short circuits will be definitively interrupted without a failure of the interrupting device. It does not require that downstream equipment survive without damage. This requirement is commonly interpreted to mean it is acceptable for equipment damage to occur so long as it does not create a shock or other hazard to personnel, and does not create a fire hazard. In fact, the equipment can be non-repairable and meet this requirement! If this requirement is not properly met severe injury or death can occur. Under Article 100 Definitions, Short-Circuit Current Rating was introduced in the 2008 code and is defined as follows: 2

The prospective symmetrical fault current at a nominal voltage to which an apparatus or system is able to be connected without sustaining damage exceeding defined acceptance criteria. Article 110.10 Circuit Impedance; Short-Circuit Current Ratings, and Other Characteristics further clarifies required system performance and the importance of using listed and presumably labeled equipment in all installations: The overcurrent protective devices, the total impedance, the equipment short-circuit current ratings, and other characteristics of the circuit to be protected shall be selected and coordinated to permit the circuit protective devices used to clear a fault to do so without extensive damage to the electrical equipment of the circuit. This fault shall be assumed to be either between two or more of the circuit conductors or between any circuit conductor and the equipment grounding conductor(s) permitted in 250.118. Listed equipment applied in accordance with their listing shall be considered to meet the requirements of this section. 3

OSHA Requirements OSHA is becoming a significant player in the data center. OSHA1910.303 (b)(4) and 1910.303 (b)(5) impose very similar requirements to the above referenced NEC Articles 110.09 and 110.10. 1910.303(b)(4): Interrupting rating. Equipment intended to interrupt current at fault levels shall have an interrupting rating sufficient for the nominal circuit voltage and the current that is available at the line terminals of the equipment. Equipment intended to interrupt current at other than fault levels shall have an interrupting rating at nominal circuit voltage sufficient for the current that must be interrupted. 1910.303(b)(5): Circuit impedance and other characteristics. The overcurrent protective devices, the total impedance, the component short-circuit current ratings, and other characteristics of the circuit to be protected shall be selected and coordinated to permit the circuit protective devices used to clear a fault to do so without the occurrence of extensive damage to the electrical components of the circuit. This fault shall be assumed to be either between two or more of the circuit conductors, or between any circuit conductor and the grounding conductor or enclosing metal raceway. Further, OSHA Article 1910.303(e)(1)(ii) requires electrical equipment without definition to be marked by the manufacturer with specific data including: Other markings giving voltage, current, wattage, or other ratings as necessary. The author would postulate that OSHA would consider whatever marking requirements specified by the NEC or a Listing agency to be necessary. Personal injury or property damage resulting from non-compliance with the requirements of OSHA and NEC in applying the above articles will put equipment suppliers, contractors, engineers and owners at risk of substantial and potentially severe financial penalties. 4

UL Standards The NEC includes an informative annex (Annex A) providing a list of product safety standards used for product listing where that listing is required by this Code. Under Annex A the following computer room products are required to be listed as follows, including the Product Standard Name and Number: Product Standard Name Product Standard Number Heating and Cooling Equipment UL 1995 Industrial Control Equipment UL 508 Industrial Control Panels UL 508A Information Technology Equipment Safety UL 60950-21 Part 21: Remote Power Feeding Power Conversion Equipment UL 508C Uninterruptible Power Systems UL 1778 5

Computer Room Air Conditioner unit Labeling Requirements Computer Room Air Conditioning units (CRAC s) are clearly covered by both the NEC and UL, and required to be marked for SCCR. The applicable NEC section is Article 440.4-Marking on Hermetic Refrigerant Motor-Compressors and Equipment, paragraph (B) Multi-motor and Combination-Load Equipment, and specifies the following: Multi-motor and combination-load equipment shall be provided with a visible nameplate marked with the maker s name,., and the short-circuit current rating of the motor controllers or industrial control panel. In addition, NEC Section 430 - Motors, Motor Circuits, and Controllers, Article 430.8 Marking on Controllers, specifies the following: A controller shall be marked with the manufacturer s name or identification, the voltage, the current or horsepower rating, the short-circuit current rating,.. Since virtually all packaged HVAC equipment includes multiple motors, minimally a fan and compressor, this section will apply. With regard to listing requirements, per Annex A, UL 1995 (CSA C22.2 No 236) is the NEC requirement for HVAC/R equipment, covering most packaged HVAC equipment, including Computer Room Air Conditioning units (CRAC s). As of July 30, 2012, adoption of the 3rd edition of UL 1995 requires compliance with the National Electrical Code (NEC), Article 440-4(B). The standard mandates that CRAC s have a marked Short Circuit Current Rating (SCCR) on their label. The following is an example of a properly constructed UL approved label for a CRAC with the short circuit current ratings clearly indicated: All AHJ s will be actively enforcing the SCCR requirement in accordance with the NEC. Design Professionals and Contractors should be familiar with this new requirement and insure their documents and specifications reflect the new requirements. 6

7

Uninterruptible Power System Labeling Requirements NEC Article 409-Industrial Control Panels governs the safe installation and inspection of Industrial Control Panels less than or equal to 600V. Article 409.2-Definitions establish a methodology to determine if equipment qualifies as an industrial control panel with the following two descriptions: Control Circuit. The circuit of a control apparatus or system that carries the electric signals directing the performance of the controller, but does not carry the main power current. Industrial Control Panel. An assembly of two or more components consisting of one of the following: (1) Power circuit components only, such as motor controllers, overload relays, fused disconnect switches, and circuit breakers (2) Control circuit components only, such as pushbuttons, pilot lights, selector switches, timers, switches, control relays (3) A combination of power and control circuit components. These components, with associated wiring and terminals, are mounted on or contained within an enclosure or mounted on a subpanel. The industrial control panel does not include the controlled equipment. Clearly, equipment such as UPS qualifies as an Industrial Control Panel under section (3) and must be marked in accordance with the code. Marking requirements are defined later in the article. NEC Article 409.110 Marking requires Industrial Control Panels to be visibly labeled with each component s SCCR or with the complete assembly SCCR, as follows: An industrial control panel shall be marked with the following information that is plainly visible after installation.. : (4) Short-circuit current rating of the industrial control panel based on one of the following: a. Short-circuit current rating of a listed and labeled assembly b. Short-circuit current rating established utilizing an approved method Informational Note: UL 508A-2001, Standard for Industrial Control Panels, Supplement SB, is an example of an approved method. Exception to (4): Short-circuit current rating markings are not required for industrial control panels containing only control circuit components. 8

With regard to listing requirements, per NEC Annex A, UL 1778 is the NEC requirement for UPS designed to ensure continuity of an alternating power source. This standard further indicates that the equipment is intended to be installed in accordance with ANSI/NFPA 70, otherwise known as the NEC. While UL 1778 does not specifically require SCCR labeling from the writers review of the standard, Annex II (normative) Standards for components incorporates the requirements of Industrial Control Equipment UL 508 into the scope of the standard. The following is an example of a properly constructed UL approved label for a UPS with the short circuit current ratings 9

Labeling Requirements for other Data Center Equipment NEC articles can potentially justify an AHJ requiring SCCR labels on many other types of equipment. For instance, NEC Article 670-Industrial Machinery governs the safe installation and inspection of Industrial machines less than or equal to 600V. Article 670.2-Definitions establish a methodology to determine if equipment qualifies as an industrial machine: A power-driven machine (or a group of machines working together in a coordinated manner), not portable by hand while working, that is used to process material. [The associated electrical equipment, including the logic controller(s) and associated software or logic together with the machine actuators and sensors, are considered as part of the industrial machine.] NEC Article 670.3-Machine Nameplate Data requires Industrial Machines to be visibly labeled with each component s SCCR or with the complete assembly SCCR, as follows (A) Permanent Nameplate. A permanent nameplate shall be attached to the control equipment enclosure or machine and shall be plainly visible after installation. The nameplate shall include the following information: (1) Supply voltage, number of phases, frequency, and full load current (2) Maximum ampere rating of the short-circuit and ground-fault protective device (3) Ampere rating of largest motor, from the motor nameplate, or load (4) Short-circuit current rating of the machine industrial control panel based on one of the following: a. Short-circuit current rating of a listed and labeled machine control enclosure or assembly b. Short-circuit current rating established utilizing an approved method Informational Note: UL 508A-2001, Supplement SB, is an example of an approved method. 10

Determining SCCR SCCR for individual components is determined during product testing by the manufacturing company. Assembly SCCR may be determined by the manufacturer, if the assembly is a UL listed product, or by an NEC approved method. UL508A Supplement SB Industrial Control Panels is the only method listed in the NEC for determining an assembly SCCR, being mentioned in the Fine Print Notes (FPN) under various articles mentioned in the above text. However, other related standards such as UL 508C-Power Conversion Devices would almost certainly be acceptable. Per this standard, after the SCCR has been determined, the equipment label must be marked with multiple data, including the following: Short Circuit Current: ka rms symmetrical, V maximum Also included would be the following information: Short Circuit Rating of the main overcurrent protective device if provided (NFPA 79, UL508A 67.1.2) If the overcurrent protective device associated to a high fault control panel SCCR is not provided, and is to be installed locally, a marking on the nameplate must show the type of overcurrent protective device necessary for the high fault rating An SCCR value is considered High Fault when the assigned SCCR is greater than the Standard SCCR for the given component or assembly as defined in UL 508A Table SB 4.1. With the exception of motor controllers with much higher required ratings, all other devices are 10,000 Amps or less. This includes circuit breakers, terminal blocks, fuse holders, and other miscellaneous devices. SCCR is normally calculated by the weakest link method, whereby the lowest rated component SCCR of an assembly determines the overall rating of the assembly. If the assigned SCCR value is based on a High Fault Rating, the label must include the following warning: Risk of Fire or Electric Shock The opening of the branch-circuit protective device may be an indication that a fault current has been interrupted. All current-carrying parts and other components protected by this device should be examined and replaced if damaged. If burnout of a current element of an overload relay occurs, the complete overload relay must be replaced. If an SCCR is not marked on the assembly, the assumed SCCR is 5,000 Amps. In most power circuits greater than 60 Amps, this rating will be insufficient to meet the requirements of the NEC. 11

Recommendations for Specifiers The new SCCR requirements of the NEC represent a liability to specifiers of Data Center Equipment if not addressed at the design phase of a project. To prevent potential liability specifications should be specifically modified to insure suppliers meet the following labeling requirements: NEC Article 409.110 Marking (Industrial Control Panels) NEC Article 440.4-Marking on Hermetic Refrigerant Motor-Compressors and Equipment NEC Article 430.8 Marking on Controllers (Motors, Motor Circuits, and Controllers) NEC Article 670.3-Machine Nameplate Data (Industrial Machinery) It is suggested that electrical one-lines be clearly marked with both the available fault current at each point in the system, as well as the SCCR required on any equipment at that location in the circuit. Specifications should clearly require the submission of data to substantiate compliance with plans and specifications prior to approval of the submitted equipment by the specifier. Failure to comply with this requirement should provide for automatic rejection of the equipment submittals. If the AHJ prevents equipment from being energized due to inadequate SCCR after it is already installed, the expense to correct the problems can be costly and disruptive. The best way to prevent this from happening is to clearly specify the required SCCR levels before the project is bid. On the following page a representative drawing for a typical UPS submittal is attached. 12

Appendix A NEC Definitions of Listed and Labeled Equipment Under Article 100 Definitions, Identified is defined as follows: Identified-Recognizable as suitable for the specific purpose, function, use, environment, application, and so forth, where described in a particular Code requirement. Informational Note: Some examples of ways to determine suitability of equipment for a specific purpose, environment, or application include investigations by a qualified testing laboratory (listing and labeling), an inspection agency, or other organizations concerned with product evaluation. Labeled. Equipment or materials to which has been attached a label, symbol, or other identifying mark of an organization that is acceptable to the authority having jurisdiction and concerned with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the manufacturer indicates compliance with appropriate standards or performance in a specified manner. Listed. Equipment, materials, or services included in a list published by an organization that is acceptable to the authority having jurisdiction and concerned with evaluation of products or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing states that either the equipment, material, or service meets appropriate designated standards or has been tested and found suitable for a specified purpose. Informational Note: The means for identifying listed equipment may vary for each organization concerned with product evaluation, some of which do not recognize equipment as listed unless it is also labeled. Use of the system employed by the listing organization allows the authority having jurisdiction to identify a listed product. 13