Blower Door Testing. Introduction. The blower door system. What can blower door testing do for me? The Pennsylvania Housing Research Center

Similar documents
Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects

Kitchen Ventilation Systems: Part 2 Providing Adequate Makeup Air

Blower Door Testing by David Keefe

FREQUENTLY ASKED QUESTIONS about HERS and CHEERS Provided by the California Energy Commission Consumer Energy Center

Building Energy Codes 101 October 23, Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance

How To Design An Hvac Design For A Stick Built Home

System Interactions in Forced-Air Heating and Cooling Systems, Part II: Continuous Fan Operation

Mario D. Gonçalves, Patenaude-Trempe 1 Pierre Gendron, Patenaude-Trempe 2 Tony Colantonio, PWGSC 3. Abstract

INFORMED MECHANICAL DESIGN THROUGH TESTED AIR LEAKAGE RATES. Jeff Speert, AIA MAIBC LEED AP

Liabilities of Vented Crawl Spaces And Their Impacts on Indoor Air Quality in Southeastern U.S. Homes

Home Energy Evaluation Report

Duct Leakage Testing 101 Frank Spevak The Energy Conservatory Minneapolis, MN

Analysis of Energy Consumption, Rating Score, and House Size

THE IC Y N E N E AD V A N T A G E

Chapter Eight RESNET Standards

Contract for Weatherization Management Address City & State

WHAT IS INFRARED (IR) THERMOGRAPHY

Center for Energy Education Laboratory

Liabilities of Vented Crawl Spaces, Their Impacts on Indoor Air Quality in Southeastern U.S. Homes and One Intervention Strategy

Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen

Key energy-efficient features of your new home

HVAC Code Requirements

Before You Start an Energy Efficiency Retrofit The Building Envelope

Minneapolis Duct Blaster

Evaluating the Field Performance of Windows and Curtain Walls of Large Buildings

BECx& Building Airtightness. Presented by: Eric Amhaus Principal

Airtight ductwork is one of

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

ECHO System for Basements

Impact of Infiltration on Heating and Cooling Loads in U.S. Office Buildings

about your house How to Get the Ventilation That You Need in Your House Figure 1 Infiltration and exfiltration of air in a house

Home Performance with ENERGY STAR. Evaluation Report

DRYER VENTING SPECIFICATIONS DRYER SAFETY

Schedule of Work Experience (OJL) and Training considered necessary to develop a skilled and productive worker.

WHOLE-HOUSE VENTILATION SYSTEMS

Ventilation and Air Leakage

Minneapolis Blower Door. Operation Manual for Model 3 and Model 4 Systems

Chapter 8. Duct Design and Sealing

Problems Related to Air Handler Leakage

RESNET National Rater Test Study Guide Outline

Enclosing Timber Frames. Panels. Frank Baker Founder, Riverbend Timber Framing and Insulspan

Home Energy Evaluation Report for House Three

Heating, Ventilation and Air-Conditioning (HVAC)

EuroPHit. Outlines for training modules For Airtightness Installation and Measurement

Chignecto-Central Regional School Board. Highland Consolidated Middle School. Indoor Air Quality Issues Mechanical Systems

HVAC Checklist - Long Form

HVAC INSTALLATION SUCCESS WITH 2012 IECC DELAWARE. for Builders & Trades. Recommended Practices for Optimized Energy Savings

HVAC INSTALLATION. Success with 2015 IECC Northeast & Mid-Atlantic. Checklist for Builders & Trades

Your Personal Home Energy Action Plan

PERFORMANCE OF SIDE-BY-SIDE SOUTH TEXAS HOMES Isolating the Contribution of Spray Polyurethane Foam Insulation

Preventing Ice Dams on Roofs

BPI Air Conditioning & Heat Pump Professional Training Sample Slides ( ) Agenda

air conditioners how to choose a cooling system

Amendment: Combustion Appliance Testing Standards Removal. Proponent: Brett Dillon, Chair Standards Development Committee

INCORPORATION BY REFERENCE OF INTERNATIONAL. (1) The Department of Labor and Industry adopts and incorporates by

Proposed Amendment: Revisions to Chapter 8 Sections Proponent: RESNET Technical Committee

How To Get A Passive House

IECC Compliance Guide for Homes in Virginia

Building Performance Solutions HVAC Design Guide, 2007

ENERGY STAR QUALIFIED HOMES. Assured Performance in Every Qualified Home

Energy Upgrade California TM Incentive Reservation Form

bout your apartment SOLVING ODOUR TRANSFER PROBLEMS IN YOUR APARTMENT Understanding Air Movement in Your Building

Health Cautions and Opportunities During Energy Audits and Upgrades. Presented by: The National Center for Healthy Housing

Psychrometrics - The Study Of Air-Water Vapor Mixtures

How can insulation contractors expand their service offering? What about weatherization?

Home Energy Auditing Standard

Molds and mildew are fungi that grow

EACO DOP / PAO TESTING GUIDELINE 2013

Inspecting to a higher standard.

Energy Efficient Homes: Air Conditioning 1

Thermal Imaging for Home Inspectors

Energy Efficient Homes: Air Conditioning

ENERGY STAR Certified Homes, Version 3 Cost & Savings Estimates

Training Course Catalog

Housing Fact Sheets. Moisture Condensation at the Windows

Centrifugal Fans and Pumps are sized to meet the maximum

Venice Library Humidity Study. for Williams Building Diagnostics, LLC th Street West Bradenton, FL Report April 13, 2015

Residential Duct Systems for New and Retrofit Homes

Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP

Training course catalog

DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1

Introduction. Motor Types

Public Review Draft. ASHRAE Standard

RESNET Interim Guidelines for Combustion Appliance Testing and Writing Work Scope September 1, 2010

Jesse Krivolavek Nebraska Native American Energy Auditors Veterans Dr Ste. 600, Omaha, NE 68022

IT Cost Savings Audit. Information Technology Report. Prepared for XYZ Inc. November 2009

Basic B.S. (building science) insights for. Spray Foam, HVAC and Moisture

Technology Corporation

Because all SPF-insulated homes are very tightly constructed,

BPC Green Builders. Green building for new and existing homes. Health Comfort Energy

The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.

Low Cost. Lower Energy Costs. Higher Efficiency.

FIELD TESTING SERVICES

NREL Job Task Analysis: Crew Leader

ANSI/BPI-1200-S-2015:

Improving Rack Cooling Performance Using Airflow Management Blanking Panels

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program

) SIGNIFICANT CHANGES INCLUDING CODE COMMENTARY

2014 British Columbia Building Code Changes

Transcription:

The Pennsylvania Housing Research Center Blower Door Testing Builder Brief BB0201 Bill Van der Meer Introduction Have you ever had to deal with call-backs from home owners who complain that they aren t comfortable or that their fuel bills are higher than expected? It s a rare builder/remodeler who hasn t. These problems can often be traced directly to air leakage into and out of the conditioned space. Uncontrolled air loss from a building can have a significant impact on comfort, heating and cooling costs, and maintenance; typically, air leakage can account for as much as 25% or more of building heat loss. At the same time, a house should not be made too airtight. Tightening a house too much, in an effort to save energy, can increase the risk of indoor air quality problems. Builders routinely provide controlled openings for ventilation and for the exhaustion of combustion byproducts. Unintentional air leakage, on the other hand, is undesirable. Air leakage may be due to the building technique used or to a simple lack of attention to air sealing during construction. How can air leakage problems be avoided? Fortunately, builders don t have to rely solely on guesswork. A useful, reliable diagnostic tool is available to quantify air leakiness: the blower door sometimes called a door fan. Its application is most practical in single-family residential housing stock, but blower door testing on multiple dwelling units has also been performed. What can blower door testing do for me? Fairly simple to use and understand, the blower door helps the builder/remodeler to find out where the leaks are and how leaky the house is. Tests using the blower door enable the builder/remodeler to assess the tightness of a building, eliminating guesswork regarding leakage and air tightness The test methodology is widely accepted and is used as one of the predictors for energy efficiency in homes. It has been used by energy retrofitters for years to measure the success of their air sealing efforts. Builders who carry out repeated blower door testing on finished houses learn to anticipate where and how air leakage problems are likely to occur and are able to find ways of avoiding them during the construction process. By avoiding air leakage problems in the first place, builders can avoid costly callbacks and increase customer satisfaction with their product. The safety of ventilation levels for occupants can also be assessed. In addition, the knowledge that builders or remodelers gain from the frequent use of this testing leads to a better understanding of the dynamics of airflow in buildings, and thus a better understanding of how their buildings actually perform. The blower door system The system consists of a powerful, variable-speed fan with a speed controller mounted in an adjustable panel that is temporarily fit into an open exterior doorway. A set of manometers or differential pressure gages are used to measure pressure differences generated by the fan. Airflow across a calibrated opening in the fan housing is also measured. Test procedures are fairly straightforward. Detailed instructions are usually provided by the supplier or manufacturer of the blower door kit. After the necessary procedures to set up the house have been performed, the test itself takes about 10 to 15

minutes to conduct. window trim, can lights, or heat registers, to name just a few of the possible sources of air leaks. Alternatively, a smoke-generating device can be used to make leakage paths visible. Blower Door System Components include an adjustable door panel, a variable speed fan with speed controller and a set of gages. With software packages and various upgrades, the purchase price of a system varies between $1,300 and $1,800. However, builders and remodelers don t have to purchase the apparatus since the testing can be sub-contracted. Locating air leaks To obtain meaningful data about the tightness of a building shell, blower door tests are performed on finished houses. All exterior openings such as doors and windows are closed, thereby simulating a heating season configuration. When operating, the blower door fan acts as an exhaust fan and vents indoor air to the outside. This sucking action causes the air pressure in the house to drop below the pressure of the air outside. Detecting air leaking into the conditioned space is a simple matter of feeling for leaks around openings such as Baseboard Air Leakage Blower door depressurization in combination with infrared thermography can provide graphic evidence of serious air infiltration sites. The infrared image demonstrates air leakage at the interface of the floor and baseboard molding depicted above. The ability to detect leaks with one s hands or by means of a smoke-generating device works on the principle that what goes out (through the exhaust fan) must come in through the enclosure. An operating blower door turns all of the leaks in the building envelope into leakage paths for infiltrating air. All of the intentional openings (fireplaces with the dampers closed, fan ducts, etc.) as well as all unintended openings contribute to the total measured air leakage. Measuring Air Leakage Blower door testing is usually performed in a depressurization mode. As air is exhausted out of the house (or building envelope), the house becomes depressurized relative to the air pressure outside the

house. Expressed in pascals (a pascal or Pa is a unit of pressure), the magnitude of the difference between these two pressures will depend upon the capacity of the fan because it works against the backpressure created across the building envelope. Measuring air leakage using a blower door system depends on the relationship between pressure, air flow, and the holes. As the airflow generated by the fan is increased across the hole in the blower door, the pressure difference between the inside and outside is also increased. Decrease the airflow and the pressure difference is decreased. It also follows that the size and shape of each of the air leakage holes is important. If the size of the holes is reduced when the same pressure difference is maintained (by keeping the fan speed constant), the airflow will decrease. The actual size of the hole may be physically reduced, or the leakiness of the hole may be reduced by air tightening measures such as caulking for example, around window frames. airflow at a 50 Pa pressure difference is often used to provide a quick estimate of the air leakage rate. Another way to express the results of the blower door test is to use ACH. The expression ACH/50 refers to the number of times in one hour that the inside air volume is replaced with outside air at a house pressure difference of 50 Pa. It is calculated by multiplying the previously obtained CFM/50 value by 60 (minutes) and dividing by the volume of the house, e.g., ACH/50 = CFM/50 * 60 Volume Blower door values Testing can be done for pressure differences ranging between 10 and 60 Pa. Testing done at the higher end of the range (between 40 and 60 Pa) generally produces the most accurate results. Blower door test results are standardized for an air pressure difference of 50 Pa; better consistency and reproducibility occur at higher pressures. Air flow at 50 pascals is the preferred value for blower door testing The amount of airflow measured in cubic feet per minute (cfm) for a pressure difference across the enclosure of 50 Pa is expressed as CFM/50. This value is derived by increasing the fan speed until the pressure difference between the inside and the outside of the house is at the desired level, namely 50 Pa. Airflow readings are taken at numerous pressure differences. These readings, referred to as data sets, are recorded, averaged and corrected for temperature and other variables using a simple computer program. The program then determines the result for an air flow of 50 Pa (or CFM/50). Although multiple data sets are recommended, a simple one-point test performed by recording Blower Door Test Simulation The airflow gage on the left measures airflow through the fan housing. The differential pressure gage on the right measures the pressure difference between inside and outside. In this case the airflow shown is 3,000 CFM at a house pressure difference of 50 Pascals (3,000CFM/50) *(Illustration is reprinted with permission of Saturn Resources Inc.) The term Estimated Natural Infiltration Rate (ENIR) is used in an attempt to reduce a blower-doorderived value such as ACH/50 or CFM/50 to an estimate of the natural infiltration rate, i.e., the rate under typical operating conditions and thus normal air pressure differences, e.g., ACH/Natural = ACH50 / ENIR adjustment factor

Although many professionals use CFMs to express the ENIR, the traditional measure of tightness or ventilation rate is expressed in air exchanges per hour. The ACH value is used in many codes and government- and utility-sponsored energy-efficient building programs. Blower door software provides other measures including Equivalent Leakage Area and Leakage ratio. For additional information about blower door values, refer to the manufacturer s instructions and to ASTM E779 87 "Standard Test Method for Determining Air Leakage Rate by Fan Pressurization. Leaky vs. tight At the end of the day, just which numbers define a leaky house or a tight house? What are the acceptable ranges? Although the numbers tend to be somewhat subjective, the chart below provides a reasonable estimate of relative leakiness for a representative, moderate-sized house. Unit Tight Moderate Leaky CFM at Less than Between 1,500 Above 50 Pa 1,500 and 4,000 4,000CFM CFM/50 CFM/50 /50 ACH at Less than Between 5 Above 10 50 Pa 5 ACH/50 and 10 ACH/50 ACH/50 Less than Between 0.35 Above 1 ENIR 0.35 ACH and 1 ACH ACH For the so-called estimated natural infiltration rate (ENIR), air leakage may be considered to be under control when a house comes in at a 0.35 air exchange rate per hour. If the ENIR falls below 0.25 ACH, the house and its occupants may be susceptible to moisture or indoor air quality problems. Remedial measures, including source control or continuous controlled ventilation, may be necessary. Conclusion Disclaimer: The Pennsylvania Housing Research Center (PHRC) exists to be of service to the housing community, especially in Pennsylvania. The PHRC conducts technical projects research, development, demonstration, and technology transfer under the sponsorship and with the support of numerous agencies, associations, companies and individuals. Neither the PHRC, nor any of its sponsors, makes any warranty, expressed or implied, as to the accuracy or validity of the information contained in this report. Similarly, neither the PHRC, nor its sponsors, assumes any liability for the use of the information and procedures provided in this report. Opinions, when expressed, are those of the authors and do not necessarily reflect the views of either the PHRC or any of its sponsors. It would be appreciated, however, if any errors, of fact or interpretation or otherwise, could be promptly brought to our attention. PHRC 219 Sackett Building University Park, PA 16802 www.engr.psu.edu/phrc Telephone: (814) 865-2341 Fax: (814)863-7304 The depressurization method described here produces a result that generally characterizes the airtightness of a building envelope. As ASTM E779-87 states: This test method is intended to produce a measure of the air tightness of a building envelope, but it goes on to caution that because of differences between natural load and test conditions, such measurements cannot be interpreted as direct measurements of air exchange rates under natural conditions. It is extremely difficult to accurately and consistently measure air leakage at natural pressures, which are very low. While a versatile tool, the blower door does have limitations. For instance, the blower door enables the user to measure airtightness and may enable the user to recognize the location of air leaking into the structure, but it can t always help the user to determine the precise source of the leaks. Air leakage may take circuitous pathways through imperfections in the house framing. Such indirect leaks, also referred to as thermal bypasses, can act as conduits for relatively large volumes of air to move through an enclosure. The forces that actually move the air are related to stack, wind and mechanical or fan effects. If air loss occurs across the building enclosure, R values will definitely be degraded. Such hidden bypasses cannot be seen by the blower door. The only practical way of detecting them may be through a combination of infrared scanning and visual inspection.

The results produced by blower door tests can be useful for houses that are too tight as well as those that are leaky. Tight houses may need supplemental ventilation. When used by a builder/remodeler who has a firm grasp of the dynamics of airflow in houses and who understands the importance of paying attention to details, a blower door can be a very effective tool for assuring compliance with the energy code as well as for assuring quality control.